Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-02-14 Cont ID  
Sent By mwennerg Date 2006-02-14 Time 13:39 Rev Time 0.00
Received By mwennerg Date 2006-02-14 Time 13:39 Sent To  
Notes
2006-02-14 00:00:00******PROVISO******
  
 1) PLANS HAVE BEEN RED LINED IN
 REFERENCE TO SUPPLY PIPE SERVING (2)
 HYDRANTS.
  
 2) MONITORING SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE.
  
 3) ELECTRONIC SUPERVISION REQUIRED ON
 ALL CONTROL VALVES INCLUDING OS&Y VALVES
 AT THE WATER TANK.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722