Plan Review Details - Permit 06010952
Plan Review Stops For Permit 06010952
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-07-01 Cont ID  
Sent By mjacobs Date 2006-07-01 Time 09:48 Rev Time 0.00
Received By mjacobs Date 2006-07-01 Time 08:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-02 Cont ID  
Sent By mjacobs Date 2006-05-24 Time 07:58 Rev Time 0.00
Received By mjacobs Date 2006-05-24 Time 06:27 Sent To  
Notes
2006-06-02 00:00:00 
 1) 11-4.1.3 (10) DRINKING FOUNTAINS .
 (A) WHERE ONLY ONE DRINKING FOUNTAIN
 IS PROVIDED ON A FLOOR, THERE SHALL BE A
 DRINKING FOUNTAIN WHICH IS ACCESSIBLE TO
 INDIVIDUALS WHO USE WHEELCHAIRS IN
 ACCORDANCE WITH SECTION 11-4.15 AND ONE
 ACCESSIBLE TO THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING. (THIS CAN BE
 ACCOMMODATED BY THE USE OF A ?HI-LO?
 FOUNTAIN; BY PROVIDING ONE FOUNTAIN
 ACCESSIBLE TO THOSE WHO USE WHEELCHAIRS
 AND ONE FOUNTAIN AT A STANDARD HEIGHT
 CONVENIENT FOR THOSE WHO HAVE DIFFICULTY
 BENDING; BY PROVIDING A FOUNTAIN
 ACCESSIBLE UNDER SECTION 11-4.15 AND A
 WATER COOLER; OR BY SUCH OTHER MEANS AS
 WOULD ACHIEVE THE REQUIRED ACCESSIBILITY
 FOR EACH GROUP ON EACH FLOOR.)
  
 2) 11-4.1.6 ACCESSIBLE BUILDINGS:
 ALTERATIONS
 (B) IF EXISTING ELEMENTS, SPACES, OR
 COMMON AREAS ARE ALTERED, THEN EACH SUCH
 ALTERED ELEMENT, SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO
 SECTION 11-4.1.3 , MINIMUM REQUIREMENTS
 FOR NEW CONSTRUCTION.
 NOTE: A MINIMUM OF 60" IS REQUIRED FORM
 THE TOILET STALL WALL TO THE EDGE OF THE
 LAVATORY. SEE FIG.30E FOR MORE
 INFORMATION. ALSO INDICATE THE CLEAR
 FLOOR SPACE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-28 Cont ID  
Sent By mjacobs Date 2006-04-28 Time 14:44 Rev Time 0.00
Received By mjacobs Date 2006-04-28 Time 10:55 Sent To  
Notes
2006-04-28 00:00:001) THE BATHROOMS ON SHEET 2.1 AND SHEET
 4.1 HAVE DIFFERENT LAY-OUTS. PLEASE SHOW
 THE CHANGES ON EACH PAGE TO SHOW THAT
 THE BATHROOMS WILL MEET THE
 ACCESSIBILITY CODE.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) WILL THE HOLDING TANK AREA HAVE A
 WALL BUILT AROUND IT OR WILL THE OXYGEN
 TANKS BE STORED IN THE CART WHICH HAS A
 MODEL#CB50-4. AS ASKED PREVIOUSLY, SHOW
 A DETAIL DRAWING INCLUDING ELEVATIONS OF
 THE HOLDING AREA FOR THE OXYGEN TANKS.
 EACH PAGE WHICH SHOWS THE FLOOR PLAN
 NEEDS TO REFLECT THE SAME IMAGE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-23 Cont ID  
Sent By mjacobs Date 2006-03-23 Time 16:28 Rev Time 0.00
Received By mjacobs Date 2006-03-22 Time 14:42 Sent To PC
Notes
2006-03-22 00:00:001) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) NOTE:105.9 ASBESTOS. THE ENFORCING
 AGENCY SHALL REQUIRE EACH BUILDING
 PERMIT FOR THE DEMOLITION OR RENOVATION
 OF AN EXISTING STRUCTURE TO CONTAIN AN
 ASBESTOS NOTIFICATION STATEMENT WHICH
 INDICATES THE OWNER?S OR OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE
 PROVISIONS OF SECTION 469.003, FLORIDA
 STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF ENVIRONMENTAL PROTECTION OF HIS OR
 HER INTENTIONS TO REMOVE ASBESTOS, WHEN
 APPLICABLE, IN ACCORDANCE WITH STATE AND
 FEDERAL LAW.
  
 4)(2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 5) INDICATE CLEARLY ON THE DRAWINGS WHAT
 TYPE OF BUSINESS WILL BE AT THIS
 LOCATION AND THE SQUARE-FOOTAGE OF
 WAREHOUSE AND THE PATIENT/OFFICE AREA.
  
 6) WHAT TYPE OF MATERIALS WILL BE STORED
 IN THE WAREHOUSE AND WHAT AMOUNT WILL BE
 STORED. WILL THE BE FORK-LIFTS BE
 DRIVING AROUND IN THE WAREHOUSE?
  
 7) A MORE DETAIL DRAWING FOR THE HOLDING
 AREA FOR THE OXYGEN TANK IS REQUIRED
 SHOWING HOW THE TANKS WILL BE PREVENTED
 FROM TIPPING OVER. ALSO THE SIZE AND
 TYPE OF TANKS SHALL BE INDICATED ON THE
 PLANS.
  
 8) WHAT IS THE REASON FOR HAVING A
 PATIENT SERVICE TECH OUT IN THE
 WAREHOUSE AREA.
  
 9) THE PLANS INDICATE THE OCCUPANCY AS :
 SMALL ASSEMBLY HOWEVER, LOOKING AT THE
 DRAWINGS AND READING THE DEFINITION OF
 ASSEMBLY, THESE PLANS DO NOT FALL UNDER
 THAT TYPE OF OCCUPANCY. SEE FBC SECTION
 "303 AND 304" FOR THE CORRECT TYPE OF
 OCCUPANCY.
  
 10) SEE FBC.SEC 311 FOR THE TYPE OF
 STORAGE WHICH IS REQUIRED FOR THE
 BUILDING. STATE CLEARLY THE OCCUPANT
 LOAD OF THE BUILDING.
  
 11) SHEET 2.1 MENTION "STUDIO" WHERE IS
 THE STUDIO ON THE PLANS?
  
 12) THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG. THE
 NEW ROLL UP DOOR NEEDS PRODUCT APPROVAL.
  
 13) 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-22 Cont ID  
Sent By btrobaug Date 2006-05-22 Time 18:49 Rev Time 0.75
Received By btrobaug Date 2006-05-22 Time 18:41 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-02 Cont ID  
Sent By dpalmer Date 2006-05-02 Time 10:00 Rev Time 0.00
Received By dpalmer Date 2006-05-02 Time 07:03 Sent To  
Notes
2006-05-02 00:00:00********* UNSAT 2ND REVIEW *********
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO PLANS
 AND INFORMATION NOW SHOWN.
  
  
 1) NOTE: PLEASE SEE 700.12E FOR
 CIRCUITING OF EM/ EXT LTS. PLEASE SEE
 PLANS SEEM TO BE CIRCUITED CORRECTLY,
 HOWEVER PLEASE SEE PANEL SCHEDULE WHICH
 INDICATE THESE ONLY CIRCUITED TO ONE
 CIRCUIT.
 PLEASE CORRELATE CIRCUITING WITH PLANS
 AND PANEL SCHEDULE,
  
 2) NOTE: PLEASE INDICATE A NEW OR
 EXISTING SIGN CIRCUIT AS REQUIRED PER
 600.5.
 A RESPONSE NOTE ON PLANS INDICATES
 "FASCIA SIGNS DO NOT REQUIRE ELECTRIC."
 HOWEVER PLEASE SEE CODE AS REFERENCE AS
 IS DOES NOT MATTER WHETHER OR NOT AN
 ELECTRICAL SIGN IS INSTALLED, THE MEANS
 OF AN ELECTRICAL CIRCUIT IS REQUIRED FOR
 USE AT THIS TIME OR FUTURE USE.
  
 3) NOTE: PLEASE SEE PLANS ARE NOW COMING
 IN WITH OUT ANY SIGNATURE, SEAL, TITLE
 BLOCK OR THE PRINTED NAME AND SIGNATURE
 OF A DESIGN PROFESSIONAL.
 PLEASE SEE ORIGINAL PLANS AND ALL OTHER
 SHEETS CONTAINED THIS AND NOW PLANS ARE
 REVISED TO INDICATE AN "ELECTRICAL
 CONTRACTOR".
 PLEASE KNOW, DUE TO THE SCOPE OF WORK ,
 PLANS SHALL BE SIGNED AND SEALED BY A
 MIN OF AN ARCHITECT OR PE.
  
 4) NOTE: PLEASE SPECIFY ANY
 CLASS/DIVISION LOCATIONS ON PLANS WHERE
 APPLICABLE AT OYGEN STORAGE.
 WILL ANY TREATMENTS BE ADMINISTERED AT
 THIS LOCATION? IF NOT, PLEASE NOTE ON
 PLANS.
 PLEASE SEE OCCUPANCY WAS DECCLARED ON
 PLANS AND THESE PLANS INDICATE
 "BUSINESS", HOWEVER THERE IS SOME
 CONFUSION OVER "PATIENT SETUP ROOM" AND
 "RESPITORY OFFICE" IS THIS A SALES
 OFFICE OR A TREATMENT ROOM?
  
 5)NOTE: PLEASE SEE EXISTING PANELS ARE
 NOW BEING SHOWN, HOWEVER LOCATION OF
 THESE COULD NOT BE LOCATED ON PLANS.
 PLEASE SHOW AND VERIFY PER 240.24,110.26
  
 6) NOTE: PLEASE VERIFY SIZES OF
 CONDUCTORS TO THE AHU'S AS THEY ARE
 SHOWN AS 10KW, 60A OCP ON #8?
 IT IS NOTED THAT THESE ARE EXISTING,
 HOWEVER PLEASE VERIFY.
 240.4,310.16
  
 7) NOTE: PLEASE SEE FBC CHAPTER 13 ,
 13-415.1.ABC.1.1 AND .2.
 13-415.1.ABC.3
  
 **PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS
 BEFORE RESUBMITTING PLANS.
 PLEASE BE SURE TO ATTACHED ONE COPY OF
 ANY OF THE OLD/VOIDED SHEETS .
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-27 Cont ID  
Sent By dpalmer Date 2006-02-27 Time 11:53 Rev Time 0.00
Received By dpalmer Date 2006-02-27 Time 10:53 Sent To  
Notes
2006-02-27 00:00:00*********UNSAT **********
  
 1)NOTE: PLEASE SEE THE PLANS REFERENCE
 THE 2005 NEC , WHEN WE ARE CURRENTLY
 UNDER THE 2002 NFPA-70.
 PLEASE ALSO KNOW, WE ARE UNDER THE 2003
 NFPA-101, AND 2002 NFPA-72
  
 2)NOTE: PLEASE SEE FIXTURE LEGEND DOES
 NOT INDICATE ANY BATTERY BACK UP FOR EM
 LTS.
 PLEASE SEE LS 101 7.8, 7.9 WHICH
 REQUIRES A MIN. PLEASE ALSO SEE FIRE
 REVIEW COMMENTS.
  
 3)NOTE: PLEASE SEE ADDRESS ON PLANS
 MENTIONS "OLD " OKEECHOBEE RD. PLEASE
 SEE AND KNOW, THERE IS ONLY A
 "OKEECHEOBEE RD" IN CITY OF WEST PALM
 BEACH.
 PLEASE ADJUST PLANS AND PERMIT
 APPLICATION.
  
 4)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS WITH PANEL SCHEDULE(S). PLEASE SEE
 EM/EXT LTS, SW RECEPTS?
 215.5
  
 5)NOTE: PLEASE CLARIFY IF THERE IS A NEW
 OR EXISTING SIGN CIRCUIT(S). 600.5
  
 6)NOTE: PLEASESEE ITEMS ON PANEL
 SCHEDULE WHICH SHOWS AWG AND OCP,
 HOWEVER DOES NOT INDICATE WHAT THESE
 ARE.
 215.5
  
 7)NOTE: PLEASE SUBMIT LOADS AND CALCS
 FOR USE. 220.3,220.10,220.11,220.13 ETC
 215.3, 230.42 FOR CONTINUOUS LAODS.
  
 8)NOTE:
  
 9)NOTE: PLEASE SEE NUMEROUS ELECTRICAL
 NOTES ON PLANS WHICH REFLECT ELECTRICAL
 WORK FOR WHAT APPEARS TO BE A
 RESIDENTIAL USE? RECEPT SPACING,,ETC .
 PLEASE SEE NOTES SHOULD REFLECT COMM
 SCOPE OF WORK.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE COPY OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2006-02-24 Cont ID  
Sent By mamini Date 2006-02-24 Time 09:49 Rev Time 0.50
Received By mamini Date 2006-02-24 Time 09:49 Sent To  
Notes
2006-02-24 00:00:00PASSED:
  
 1. N/A

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-07-06 Cont ID  
Sent By mwennerg Date 2006-07-06 Time 15:56 Rev Time 0.00
Received By mwennerg Date 2006-07-06 Time 15:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-05-24 Cont ID  
Sent By nmccray Date 2006-05-24 Time 10:44 Rev Time 0.00
Received By nmccray Date 2006-05-24 Time 10:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-05 Cont ID  
Sent By mwennerg Date 2006-05-05 Time 15:48 Rev Time 0.00
Received By mwennerg Date 2006-05-05 Time 15:48 Sent To  
Notes
2006-05-05 00:00:00PLANS WERE PASSED ON 3/20/06 BY N
 MCCRAY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-03-20 Cont ID  
Sent By nmccray Date 2006-03-20 Time 14:59 Rev Time 0.00
Received By nmccray Date 2006-03-20 Time 14:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 11:33 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 11:33 Sent To  
Notes
2006-06-19 00:00:00TO "BOB"#7
2006-06-14 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-22 Cont ID  
Sent By adarroug Date 2006-05-22 Time 14:31 Rev Time 0.00
Received By adarroug Date 2006-05-22 Time 14:31 Sent To  
Notes
2006-05-22 00:00:00TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-25 Cont ID  
Sent By adarroug Date 2006-04-14 Time 12:57 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 13:23 Sent To  
Notes
2006-04-25 00:00:00TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-24 Cont ID  
Sent By adarroug Date 2006-04-14 Time 15:01 Rev Time 0.00
Received By adarroug Date 2006-04-14 Time 15:01 Sent To FIRE
Notes
2006-04-24 00:00:00TO "F" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-03-23 Time   Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 11:52 Sent To  
Notes
2006-03-15 00:00:00TO "COMM" BD#52
2006-01-27 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-03-20 Cont ID  
Sent By pkrauss Date 2006-03-20 Time 12:46 Rev Time 0.00
Received By pkrauss Date 2006-03-20 Time 12:46 Sent To  
Notes
2006-03-20 00:00:00NO MECHANICAL PLANS OR CONTRACTOR
 INDICATED WITH PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-06-23 Cont ID  
Sent By jleech Date 2006-06-23 Time 07:43 Rev Time 0.00
Received By jleech Date 2006-06-23 Time 07:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-06-02 Cont ID  
Sent By jleech Date 2006-06-02 Time 07:13 Rev Time 0.00
Received By jleech Date 2006-06-02 Time 07:13 Sent To  
Notes
2006-06-02 00:00:00DENIED;
 1.REVISE RISER DIAGRAM TO INCLUDE
 ADDITIONAL HANDICAP LAVS.
 2.SHOW CLEAR FLOOR SPACE AND HIGHT OF
 URINAL.
 3.HANDICAP BATHROOM STALLS MUST COMPLY
 WITH FBC-2004 CHAPTER 11
 SEC.11-4.1.6(1)(B). FIGURE 30E 60" MIN
 IS REQUIRED FROM TOILET STALL WALL TO
 EDGE OF LAVATORY.
 4.DRINKING FOUNTAIN IS REQUIRED TO BE A
 HI-LOW OR A CUP DISPENSOR IS REQUIRED
 FOR PEOPLE WITH BAD BACKS SEE
 SEC.11-4.1.3(10).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-04-27 Cont ID  
Sent By jleech Date 2006-04-27 Time 07:01 Rev Time 0.00
Received By jleech Date 2006-04-27 Time 07:00 Sent To  
Notes
2006-04-27 00:00:00DENIED;
 1.DRINKING FOUNTAIN REQUIRED TO MEET THE
 MINIMUM NUMBER OF PLUMBING FIXTURES
 REQUIRED. SEE FBC-2004 PLUMBING TABLE
 403.1 OCCUPANCY B. (2ND REQUEST)
 2.WOMAN'S ROOM HANDICAP STALL DOOR SHALL
 BE LOCATED IN THE CORNER DIAGONAL TO THE
 WATER CLOSET. SEE FOOT NOTES AT FIRURE
 30E ACCESSIBILITY CODE. (SECOND REQUEST)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-18 Cont ID  
Sent By pschmitz Date 2006-03-18 Time 06:55 Rev Time 0.00
Received By pschmitz Date 2006-03-18 Time 06:55 Sent To  
Notes
2006-03-18 00:00:00 
 PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 DENIED
 1) SHT 2.1 PROJECT DATA ( ASSEMBLY)
 PLEASE CLARIFI, PLANS SHOW, BUSINESS AND
 WARE HOUSE OCCUPANCY.
 SHOW LOCATION OF STUDIO AND SEATING.
 THE USE OF OXYGEN TANK HOLDING AREA,
 AND RESPITORY THERAPIST ROOM.
 2) SHT C.1 DESIGN SYMBOLS.
 SHOW THE SYMBOL FOR WALLS TO BE REMOVED
 OR RELOCATED IN THE KITCHEN.
  
 3) SEC 403 MINIMUM FACILITIES
 ONE DRINKING FOUNTAIN REQUIRED.
  
 4)SHT 2.1 MEN AND WOMENS REST RM
 SEC 11-4.17.3 SIZE AND ARRANGEMENT
 EXCEPTION: NEW CONSTRUCTION.
 (1) THE STANDARD ACCESSIBLE RESTROOM
 STALL SHALL CONTAIN AN ACCESSIBLE
 LAVATORY WITHIN IT, THE SIZE OF SUCH
 LAVATORY TO BE NOT LESS THAN 19 INCHES
 WIDE BY 17 INCHES (483 MM BY 432 MM)
 DEEP, NOMINAL SIZE, AND WALL MOUNTED.
 THE LAVATORY SHALL BE MOUNTED SO AS NOT
 TO OVERLAP THE CLEAR FLOOR SPACE AREAS
 REQUIRED BY SECTION 11-4.17 [SEE FIGURE
 11-30(A) AND FIGURE 11-30(E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE.
 SUCH LAVATORIES SHALL BE COUNTED AS PART
 OF THE REQUIRED FIXTURE COUNT FOR THE
 BUILDING.
 (5) THE ACCESSIBLE WATER CLOSET SHALL BE
 LOCATED IN THE CORNER, DIAGONAL TO THE
 DOOR.
  
 END OF COMMENTS, QUESTIONS 561-805-6692