Plan Review Details - Permit 06010914
Plan Review Stops For Permit 06010914
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-07-19 Cont ID  
Sent By mperson Date 2006-07-19 Time 10:28 Rev Time 0.33
Received By mperson Date 2006-07-19 Time 10:28 Sent To PC
Notes
2006-07-19 00:00:00REVISION: GENERATOR RELOCATED FROM ONE
 SIDE OF PROPERTY TO THE OTHER. NEW SITE
 SURVEY PLAN INDICATING CHANGE

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-02-23 Cont ID  
Sent By mperson Date 2006-02-23 Time 16:26 Rev Time 1.00
Received By mperson Date 2006-02-23 Time 16:26 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-01-31 Cont ID  
Sent By mperson Date 2006-01-31 Time 07:44 Rev Time 1.25
Received By mperson Date 2006-01-31 Time 07:44 Sent To PC
Notes
2006-01-31 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR A GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.(NOTE: YOUR DRAWING SHOWS
 ONLY 16' OF 1" POLY BEING USED U/G WHAT
 ARE THE LENGTHS OF THE RISERS)
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 (NOTE: YOUR DRAWING SHOWS ONLY 1" POLY
 BEING USED. IS THIS YOUR INTENT?)
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).(NOTE: HOUSE HAS EXISTING GAS,
 THE TOTAL BTU LOAD ON SYSTEM NEEDS TO BE
 NOTED ON DRAWING)
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).(NOTE: THE
 LONGEST LENGTH ON SYSTEM NEEDS TO BE
 NOTED ON DRAWING IN ORDER TO CHECK
 SIZING WITH TABLES)
  
 END OF COMMENTS
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVSNS
 (561)805-6721
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-14 Cont ID  
Sent By adarroug Date 2006-07-14 Time 17:59 Rev Time 0.00
Received By adarroug Date 2006-07-14 Time 17:58 Sent To G
Notes
2006-07-14 00:00:00TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-22 Cont ID  
Sent By adarroug Date 2006-02-22 Time 15:19 Rev Time 0.00
Received By adarroug Date 2006-02-22 Time 15:19 Sent To G
Notes
2006-02-22 00:00:00TO "G" BOX/RES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-24 Cont ID  
Sent By mperson Date 2006-02-24 Time 09:29 Rev Time 0.00
Received By mperson Date 2006-01-24 Time 11:17 Sent To  
Notes
2006-01-24 00:00:00TO "G" BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved