Plan Review Details - Permit 06010881
Plan Review Stops For Permit 06010881
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-02-08 Cont ID  
Sent By mperson Date 2006-02-08 Time 12:52 Rev Time 1.00
Received By mperson Date 2006-02-08 Time 12:52 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-01-30 Cont ID  
Sent By mperson Date 2006-01-30 Time 07:46 Rev Time 1.25
Received By mperson Date 2006-01-30 Time 07:46 Sent To PC
Notes
2006-01-30 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1. IF TANK IS BELOW GROUND THE CONTAINER
 SHALL BE SECURELY ANCHORED PER NFPA 58.
 (DETAIL REQUIRED)
 2. INDICATE SHUT OFF VALVES, AND
 REGULATORS ON ISOMETRIC DRAWINGS ALSO
 INDCATE THE MAKE AND MODEL NUMBER OF
 REGULATORS (ADD TO DRAWINGS)
 3. NOTE AS OF OCT. 1ST 2005 FBC-2004
 FUEL GAS CODES IN EFFECT.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-06 Cont ID  
Sent By adarroug Date 2006-02-06 Time 15:48 Rev Time 0.00
Received By adarroug Date 2006-02-06 Time 15:48 Sent To G
Notes
2006-02-06 00:00:00TO "G" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-08 Cont ID  
Sent By mperson Date 2006-02-08 Time 12:53 Rev Time 0.00
Received By mperson Date 2006-01-24 Time 11:30 Sent To  
Notes
2006-01-24 00:00:00TO "G" BOX