Plan Review Details - Permit 06010876
Plan Review Stops For Permit 06010876
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-02-13 Cont ID  
Sent By btrobaug Date 2006-02-13 Time 08:45 Rev Time 0.33
Received By btrobaug Date 2006-02-13 Time 08:27 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-03 Cont ID  
Sent By btrobaug Date 2006-02-03 Time 17:51 Rev Time 0.33
Received By btrobaug Date 2006-02-03 Time 17:42 Sent To PC
Notes
2006-02-03 00:00:00 
 THE ARCHITECT OF RECORD MUST MAKE
 CHANGES TO HIS DRAWING PER 481 FS. THE
 SCOPE OF THIS WORK DOES NOT REQUIRE AN
 ARCHITECT AND THE CONTRACTOR COULD DRAW
 THEM.
  
 THE VALUE GIVEN ON THE APPLICATION MUST
 REFLECT ALL LABOR AND MATERIAL PER FBC.
  
 CORRECT THE ABOVE AND RESUBMIT FOR
 REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-10 Cont ID  
Sent By adarroug Date 2006-02-10 Time 16:21 Rev Time 0.00
Received By adarroug Date 2006-02-10 Time 16:21 Sent To E
Notes
2006-02-10 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-03 Cont ID  
Sent By btrobaug Date 2006-02-03 Time 17:42 Rev Time 0.00
Received By btrobaug Date 2006-01-24 Time 11:15 Sent To E
Notes
2006-01-24 00:00:00TO "E" BOX