Plan Review Details - Permit 06010861
Plan Review Stops For Permit 06010861
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-01-24 Cont ID  
Sent By lursu Date 2007-01-24 Time 13:35 Rev Time 0.00
Received By lursu Date 2007-01-24 Time 13:35 Sent To  
Notes
2007-01-24 13:35:58PERMIT APPLIED TO THE CORRECT ADDRESS 3230 COMMERCE
 PL.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-10-02 Cont ID  
Sent By lursu Date 2006-10-02 Time 16:49 Rev Time 0.00
Received By lursu Date 2006-10-02 Time 16:49 Sent To  
Notes
2006-10-02 00:00:00IF THE PERMIT IS NEEDED FOR THE PCN =
 74424301170000030 THEN THIS ADDRESS
 :3230 COMMERCE PL WITH THE ABOVE PCN
 MUST BE SPECIFIED ON THE APPLICATION.
2006-09-28 00:00:00NEEDS, AS OUR SYSTEM SHOWS 3222, YET
 ARCHITECT'S RESPONSE MENTION ADDRESS
 SHOULD BE 3230 AND THE ADDRESS ON PLANS
 IS ALSO 3220.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-08-21 Cont ID  
Sent By kconrad Date 2007-08-21 Time 19:11 Rev Time 0.00
Received By kconrad Date 2007-08-21 Time 18:52 Sent To I
Notes
2007-08-21 19:12:11REVISIONS FOR SHEETS T1.1 AND A1.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2007-04-26 Cont ID  
Sent By lmartine Date 2007-04-26 Time 12:43 Rev Time 0.00
Received By lmartine Date 2007-04-26 Time 12:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-04-13 Cont ID  
Sent By lmartine Date 2007-04-13 Time 16:55 Rev Time 0.00
Received By lmartine Date 2007-04-13 Time 16:39 Sent To  
Notes
2007-04-13 16:54:28 
 BUILDING COMMENTS
  
  
 PLEASE SEE ELECTRICAL COMMENTS , ENERGY EFFICIENCY
 REPORT SHALL BE CORRECTED BEFORE ISSUANCE OF BUILDING
 PERMIT.
  
  
  
  
  
  
  
 L.MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-01-26 Cont ID  
Sent By lmartine Date 2007-01-26 Time 16:26 Rev Time 0.00
Received By lmartine Date 2007-01-26 Time 16:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-11-17 Cont ID  
Sent By alange Date 2006-11-17 Time 14:12 Rev Time 0.00
Received By alange Date 2006-11-17 Time 14:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-16 Cont ID  
Sent By alange Date 2006-10-16 Time 14:29 Rev Time 0.00
Received By alange Date 2006-10-16 Time 14:29 Sent To  
Notes
2006-10-16 14:32:50DENIED
  
 THE SIGNATURE SEAL AND DATE OF THE ARCHITECT SHALL
 APPEAR ON ALL PAGES OF ARCHITECTURAL DOCUMENTS FILED
 FOR PUBLIC RECORD.FAC 61G1-16.003,FS 481.2055
  
 ART LANGE
 BUILING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-18 Cont ID  
Sent By alange Date 2006-07-18 Time 09:45 Rev Time 0.00
Received By alange Date 2006-07-18 Time 09:45 Sent To  
Notes
2006-07-18 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.SEE GENERAL
 NOTES #3.
  
 4.SHOW CONSTRUCTION TYPE ON PLANS.
 FBC 106.3.5IT APPEARS THE WRONG TYPE
 HAS BEEN SELECTED, TYPE IV IS HEAVY
 TIMBER CONSTRUCTION UNDER THE 2004 FBC.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-19 Cont ID  
Sent By alange Date 2006-04-19 Time 08:29 Rev Time 0.00
Received By alange Date 2006-04-19 Time 08:28 Sent To  
Notes
2006-04-19 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2005 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 3.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 4.SHOW CONSTRUCTION TYPE ON PLANS.
 FBC 106.3.5
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2007-04-20 Cont ID  
Sent By dpalmer Date 2007-04-20 Time 11:44 Rev Time 0.00
Received By dpalmer Date 2007-04-20 Time 11:44 Sent To  
Notes
2007-04-20 11:46:29*NEW PLANS SUBMITTED VIA FED-EX, REMOVED OLD SHEETS,
 INSERTED NEW SHEETS. STAMPED ELECTRICAL SHEETS OK.
 THE THIRD SET OF ELECTRICAL SHEETS SUBMITTED ARE
 STAMPED FOR CONTRACTOR TO HAVE AN EXTRA COPY OF
 ELECTRICAL SHEETS TO USE AT DISCRETION.

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2007-04-18 Cont ID  
Sent By dpalmer Date 2007-04-18 Time 10:41 Rev Time 0.00
Received By dpalmer Date 2007-04-18 Time 07:58 Sent To  
Notes
2007-04-18 10:41:53** UNSAT **
  
 ** TEMPORARY FAILED STATUS
  
  
 1) NOTE: PLEASE SEE THE TWO NEW SETS SUBMITTED ARE NOT
 COMPLETE WITH NEW SHEETS. ONE SET WHICH IS OK CONTAINS
 SHEETS E1.0 DATED 3/6/07, 2.0 DATED 12/11/06 AND 2.1
 DATED 3/30/07, WHERE THE SECOND SET CONTAINS ONLY THE
 FOLLOWING ELECTRICAL SHEETS, E1.0 DATED 12/11/06, AND
 2.1 DATED 3/30/07.
 THE SECOND SET IS NOT COMPLETE WITH ALL THREE
 ELECTRICAL SHEETS AND IT DOES NOT CONTAIN THE MOST
 CURRENT SHEETS.
  
 ** PLEASE OVER-NIGHT ALL THREE NEW SIGNED, DATED SEALED
 SHEETS FOR EACH SET. THESE MAY BE SENT TO THIS OFFICE
 DIRECTLY. THIS REVIEWER WILL INSERT NEW SHEETS INTO
 BOTH SETS FOR STAMPING.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 200 2ND ST. #RD FLOOR.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2007-03-15 Cont ID  
Sent By dpalmer Date 2007-03-15 Time 08:40 Rev Time 0.00
Received By dpalmer Date 2007-03-14 Time 16:49 Sent To  
Notes
2007-03-15 08:52:02** UNSAT 7TH REVIEW **
  
 1) NOTE: PLEASE SEE AS NOTED IN THE PREVIOUS REVIEW,
 THE ENERGY CALCULATIONS DO NOT CORRELATE WITH PLANS.
 PLEASE SEE THE SQ FT ON THE CALCULATIONS DO NOT
 CORRELATE WITH THE SQ FT AS SHOWN ON PLANS.
 PLEASE SEE THAT THE SHEET CONTAINING THE LIGHTING HAS
 NOW BEEN REVISED HOWEVER NO REVISION TO THE ENERGY
 CALCULATIONS WAS DONE TO COORDINATE WITH PLANS AND
 FIXTURE LEGEND FOR THE NUMBER OF FIXTURES AND THE
 TOTALS ON THE POWER.
 PLEASE SEE THE ENERGY CALCULATIONS ON ONE SHEET ARE
 DIFFERENT THAN THAT OF THE SAME TOTAL ON ANOTHER
 SHEET.
 PLEASE SEE THE LIGHTING PLANS MENTIONS NOW THE 4-LAMP
 FIXTURES ARE OMITTED, HOWEVER NOTE #3 ON PLANS STILL
 INDICATES 4-LAMP FIXTURES ARE TO BE INSTALLED.
 PLEASE SEE THE FIXTURE LEGEND WHICH STATES FOR FIXTURE
 *L3*,3- 32WATT LAMPS= 85WATTS AS A TOTAL FOR EACH
 FIXTURE. THE SAME FOR IS SAID FOR FIXTURE *L2* AND
 FIXTURE *L1* WHICH DOES NOT STATE ANY WATTAGE OR
 TYPE??
 PLEASE CLARIFY HOW THE FIXTURES CAN CONTAIN 3-32W LAMPS
 AND IT ONLY ADDS UP TO 85WATTS OR THE 2-32W AMPS, WHICH
 ARE SHOWN @60WATTS? (EFFICIENCY?)
  
 2) NOTE: PLEASE KNOW AS PLANS WERE ORIGINALLY SUBMITTED
 FOR PLAN REVIEW ONLY, THE FS 553.80(2)(B) DID NOT
 APPLY. PLEASE KNOW IF PLANS ARE REJECT FOR THE SAME
 COMMENT ON THE FOLLOWING REVIEW, A FEE FOR THE PLAN
 REVIEW PORTION OF THE PERMIT FEE WILL BE ASSESSED.
 PLEASE ALSO KNOW AT THIS TIME ONE SET OF PLANS AND
 ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE
 FOR POSSIBLE REVIEW BY THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS.
  
 3) NOTE: PLEASE SEE NEW SHEET A1.2 WAS NOT DATED BY THE
 ARCHITECT ALONG WITH SHEET T1.1. THIS IS REQUIRED
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADES. SHEET
 A1.2 IS NEW IN SET.
 FS 481.221
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2007-03-01 Cont ID  
Sent By dpalmer Date 2007-03-01 Time 11:49 Rev Time 0.00
Received By dpalmer Date 2007-03-01 Time 11:11 Sent To PC
Notes
2007-03-02 15:33:49** NOTE ADDED.
  
  
 REPLACED SHEET A1.2 THAT WAS REVISED FOR THE REFLECTED
 CEILING PLAN NOW CONTAINS A "RUBBER STAMP" FOR THE
 REQUIRED ORIGINAL SIGNTURE BY THE ARCHITECT PER FS
 481.221. INFORMED MR. IAN GUNTHER OF ARCHITECT'S OFFICE
 THAT WE NEED NEW SIGNED, DATED AND SEALED SHEETS FOR
 THIS.
2007-03-01 11:50:00*** UNSAT ***
  
 1) NOTE:PLEASE SEE ENERGY CALCULATIONS HAVE NOW
 CHANGED WITH THE LIGHTING LOADS. PLEASE SEE THE
 PREVIOUS DESIGN WAS HIGHER, YET NO CHANGES TO LIGHTING
 ON PLANS COULD BE FOUND TO DECREASE THIS NUMBER.
 PLEASE SEE THE NUMBER FOR THE LIGHTING DESIGN NOW
 EXCEEDS THAT OF THE ALLOWANCE PER 13-415.2.C AND THE
 TABLES.
 PLEASE SEE THE ALLOWANCE FOR LIGHTING DENSITIES IS
 STATED IN THE FBC AS 1.0 PER SQ FT AND YET DESIGN IS
 NOW SHOWN ABOVE.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-01-10 Cont ID  
Sent By dpalmer Date 2007-01-10 Time 07:35 Rev Time 0.00
Received By dpalmer Date 2007-01-09 Time 18:14 Sent To  
Notes
2007-01-10 07:37:15 
 ** UNSAT ***
  
  
 ** PLEASE SEE PROJECT HAS NOW BEEN CONVERTED TO A
 PERMIT.
 APIIED DATE FOR PERMIT IS NOW DECEMBER 19TH, 2006.
 PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW STILL NEEDS
 TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW.
 PLEASE SEE THAT THE TIMES FOR MAXIMUM OVER RIDES TIMES
 WERE GIVEN WHICH COME DIRECTLY FROM THE CODE SECTIONS
 GIVEN; HOWEVER PLEASE SEE A TIME OF 1HR IS BEING STATED
 FOR OCCUPANCY SENSOR TYPES OF DEVICES.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2 AND .1.3. (30MINS MAX
 FOR OC SENSOR TYPES AND 4HRS MAXIMUM FOR TIMER TYPE
 OVER RIDES.
 PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED STILL DO
 NOT INDICATE THE INFORMATION AS NEEDED TO COMPLY WITH
 13-415.1.AB.1, 13-415.2.
  
 ** PLEASE SEE THESE NOW INDICATE LIGHTING FOR OPERATING
 ROOMS WHICH IF THIS FACILITY HAS "OPERATING ROOM", THEN
 THIS ENTIRE PROJECT WOULD FALL UNDER DIFFERENT
 REQUIREMENTS IN THE CODE AND WOULD NEED TO RE-DESIGN
 ALL ELECTRICAL AS SHOWN FOR SUCH.
  
 ** PLEASE SEE ENERGY CALCULATIONS NOW DO NOT CONTAIN
 ANY WATER HEATING SYSTEMS, WHICH ARE SHOWN ON PLANS,
 DOES NOT INCLUDE ANY MECHANICAL A/C SYSTEMS WHICH ARE
 SHOWN ON PLANS.
 PLEASE SEE OTHER INFORMATION FOR ELECTRICAL SYSTEMS
 WHICH ARE ON PLANS NOW ARE REMOVED FROM THE ENERGY
 CALCULATIONS.
  
  
 ** PLEASE SEE THE LIGHTING TIMES FOR MAXIMUM PERMITTED
 OVER RIDES COULD HAVE BEEN REDLINED ON PLANS, HOWEVER
 STATING THIS FACILITY CONTAINS "OPERATING ROOM" ON THE
 ENERGY CALCULATIONS WHEN THIS DOES NOT HAVE THIS
 OCCUPANCY AS A HOSPITAL.
  
  
 ** PLEASE KNOW ONE COPY OF ENERGY CALCULATIONS
 SUBMITTED AND PLANS ARE NOW BEING RETAINED BY THIS
 OFFICE.
  
  
  
 2) NOTE: PLEASE SEE PERMIT APPLICATION NOW CONTAINS A
 PARCEL CONTROL NUMBER WHICH IS FOR THE ADDRESS OF 3230,
 THIS WILL BE CHANGED BY THE ADDRESSING REVIEWER OR THIS
 OFFICE BEFORE PERMIT ISSUANCE.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-09 18:27:13IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-11-04 Cont ID  
Sent By dpalmer Date 2006-11-04 Time 18:36 Rev Time 0.00
Received By dpalmer Date 2006-11-04 Time 17:55 Sent To  
Notes
2006-11-04 18:36:28*** UNSAT 4TH REVIEW***
  
  
 ** PLEASE KNOW THIS IS STILL UNDER "PLAN REVIEW" ONLY.
 NO APPLICATION FOR PERMIT HAS YET BEEN MADE TO DATE.
 PLEASE KNOW A CODE CHANGE FOR NFPA-70 IS COMING AND IF
 PERMIT IS NOT APPLIED FOR BEFORE STATE ADOPTS NEW CODE,
 THEN THE PLANS WILL BE REQUIRED TO CHANGE AS NEEDED.
 THE TENTATIVE DATE IS DEC 1ST, 2006
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS AND
 ENERGY CALCULATIONS IN AND NEAT AND ORDERLY FASHION.
 PLEASE SEE ONLY PARTS OF WHAT SEEMS TO BE A PARTIAL SET
 OF REVISED ENERGY CALCULATIONS WERE SUBMITTED. PLEASE
 SEE IN EITHER CASE THE PARTIAL ENERGY CALCULATIONS ARE
 NOT SIGNED, DATED OR SEALED BY THE DESIGNER OF
 RECORD??? THEY ARESIGNED AND DATED10/23/06, BUT NOT
 SEALED AND NOT IN ANY ORDER OF ANY KIND??
 PLEASE SUBMIT AS REQUIRED AND REQUESTED.
 FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH 106.1.2, 106.1.3. , 106.3.5.1 ETC.
  
  
 2) NOTE: PLEASE SEE OUR SYSTEM STILL INDICATES PLANS
 BEING REVIEWED UNDER THE ADDRESS OF 3222 COMMERCE PL,
 THE "PLAN REVIEW" SUBMITTAL SHEET WHEN PLANS WERE
 SUBMITTED ALSO INDICATE "3222"
 PLEASE CORRELATE, AND ONCE AN ADDRESS IS FINALIZED,
 PLEASE ADJUST PLANS AS NEEDED OR IF NEEDED.
  
 3) NOTE: PLEASE SEE COMPLIANCE WITH FBC CHAPTER 13,
 13-415.1.ABC.1.1, .1.2 HAS NOT YET BEEN MET. PLEASE SEE
 NEW OC SENSOR TYPE SWITCHES WERE ADDED TO SOME ROOMS
 AND SOME AREAS INDICATE A NOTE #7 IN AN OCTAGONAL SHAPE
 WHICH MENTIONS TO ADD AN OVER RIDE SWITCH, WITH A MAX
 OF 1HR, HOWEVER PLEASE SEE THIS NOTE IS ADDED AT FRONT
 DOOR, YET NO "S" IS SHOWN? PLEASE SEE OTHER AREAS WHICH
 DO INDICATE AN OC, YET NO TIME LIMITS ARE INDICATED ON
 SYMBOL LEGEND?
 PLEASE SEE OTHER AREAS WHICH CONTAIN SWITCHES, BUT THEY
 WERE NOT CHANGED???
 PLEASE SEE MAX TIMES PERMITTED ON OC SENSOR DEVICES AS
 PERVIOUSLY NOTED PER SECTIONS GIVEN. (30MINS MAX ON OC
 TYPE AND 4HR MAX ON TIMER TYPE)
 PLEASE SEE NOTES #1 , AS ENERGU
 CALCULATIONS/PERFORMANCE CALCUALTIONS SUBMITTED DO NOT
 PROVIDE THE INFORMATION AS REQUIRED. PLEASE SEE
 13-415.2.ABC.1, TABLE(S) 415.2.C.1
  
 4) NOTE: PLEASE SEE A SIGN CIRCUIT HAS NOW BEEN ADDED,
 YET PLEASE SEE 600.5, WHICH REFERENCES THE
 220.3(B)(6). PLEASE SEE THE MINIMUM VA SHALL BE
 INDICATED. (SHOWN AS 600VA)
  
  
 ** PLEASE KNOW, AS PLANS HAVE ONLY BEEN SUBMITTED FOR A
 "PLAN REVIEW "SERVICE AND NOT FOR PERMIT, THIS DOES NOT
 FALL UNDER THE SAME ENFORCEMENT AS REQUIRED FOR REPEAT
 CODE COMPLAINT COMMENTS 3 OR MORE TIMES AS REQUIRED IN
 FS 553.80(2)(B).
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-09-28 Cont ID  
Sent By dpalmer Date 2006-09-28 Time 20:55 Rev Time 0.00
Received By dpalmer Date 2006-09-28 Time 18:52 Sent To  
Notes
2006-09-28 00:00:00***** UNSAT3RD REVIEW ******
  
 ** PLANS STILL ONLY SUBMITTED FOR "PLAN
 REVIEW>
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES .
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED AT THE BOTTOM.
  
  
  
 *** NEW NOTE ***
 ** IMPORTANT***
  
 1)A)NOTE; PLEASE KNOW, TO WHOM IT MAY
 CONCERN:. WHEN PLANS ARE SUBMITTED TO
 THE CONSTRUCTION SERVICES DEPARTMENT,
 THE "DATE STAMP" MAY NOT BE BORROWED
 FROM ANY FRONT COUNTER PERSONEL AND USED
 TO STAMP EACH PAGE OF SAID PLANS BEING
 SUBMITTED. THIS DATE STAMP ON EACH SHEET
 IS ONLY DONE WHEN PLANS ARE READY FOR
 ISSUANCE AND THIS IS DONE BY THEPLAN
 REVIEW STAFF ONLY.
  
 1)B) NOTE: PLEASE SEE NONE OF THE
 ARCHITECTURAL SHEETS ARE SIGNED, DATED
 OR SEALED BY THE ARCHITECT OF RECORD.
 PLEASE SEE FS 481.221
 THIS COMMENT IS REQUIRED WHETHER OR NOT
 MADE BY OTHER REVIEWERS.
  
 1)C) NOTE: PLEASE SEE ADDDRESS APPLIED
 FOR"PLAN REVIEW" WAS UNDER "3222" AND
 NOW ARE BEING SHOWN IN TITLE BLOCKS
 UNDER THE ADDRESS OF "3230". PLEASE
 KNOW, THE PAPERWORK HAS BEEN ROUTED TO
 "ADRESSING" AND THE APPLIED FOR "PERMIT"
 OR "PLAN REVIEW" WILL NEED TO CORRELATE
 AND BE CORRECTED.
  
 ** PREVIUOUS REVIEW NOTES BELOW WHICH
 ARE NOT ADDRESSED.
  
  
 1)NOTE: OK.
  
 2)NOTE: OK.
  
  
 3)NOTE: OK.
  
 4)NOTE: OK.
  
 5)NOTE: NO, SAME NOTE, IF ONE IS NOT
 EXISTING , ONE WILL BE REQUIRED. THE
 CODE DOES NOT SAY AN ELECTRICAL SIGN
 MUST BE INSTALLED, HOWEVER ELECTRIC AT A
 J-BOX LOCATED AT THE FRONT ENTRANCE IS
 REQUIRED.
 600.5.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE RESPONSE MENTIONS
 TO VERIFY, HOWEVER THIS IS REQUIRED AT
 THIS TIME TO EITHER SHOW NEW OR EXISTING
 PER 600.5, 1500VA MIN.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE INDICATE EITHER NEW OR
 EXISTING SIGN CIRCUIT PER 600.5
  
 6)NOTE:NO, WHERE IS LARGEST MOTOR
 LOAD BEING SHOWN AT 125%.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE LOADS FOR ALL
 EXISTING AND NEW LOADS SHALL BE SHOWN
 FOR EXISTING AND NEW.
 PLEASE SEE IT WAS NOT STATED WHETHER OR
 LOADS ARE DONE AT 125% FOR CONTINUOUS
 AND LOAD FOR LARGEST MOTOR LOADS.
 PLEASE SEE PREVIOUS NOTE ABOVE WITH
 RESPECT TO THE 4TH TENANT SERVICE WHICH
 DOES NOT SEEM TO BE INCLUDED IN RISER
 AND CALCULATIONS.
 215.3,230.42,220.3,220.10,220.11,220.13
 ,ETC
  
 ** PREVIOUS NOTE REVIEW #1 **
 PLEASE VERIFY ALL LOADS FOR
 EXISTING WIREWAY. PLEASE INDICATE THESE
 LOADS AND THE ADDED NEW LOADS.
 215.5,220
 PLEASE SEE IT APPEARS A CONTINUOUS LOAD
 FACTOR OF 125% IS BEING DONE FOR
 LIGHTING, HOWEVER UNABLE TO VERIFY AS
 THIS IS NOT SHOWN?
 215.3,230.42 ETC.
  
 7)NOTE: OK.
  
 8)NOTE: NO, PLEASE SEE SAME NOTE, NO
 CONTROLS SHOWN OR SUBMITTED. PLEASE SEE
 RESPONSE ONLY MENTIONS, ENERGY
 CALCULATIONS?
 PLEASE ASLSO SEE ONLY ONE COPY OF THE
 ENERGY CALCUALTIONS ARE SIGNED , DATED
 AND SEALED WITH TEH RAISED SEAL AS
 REQUIRED UNDER FS 471.025. ETC
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE COMPLIANCE FOR
 THIS COULD NOT BE LOCATED. PLEASE SEE NO
 LIGHTING CONTROLS, AUTOMATIC SHUTT OFF,
 SCHEDULING ETC WAS SHOWN. PLEASE SEE
 SEPARATE SPACES AND DEVICES REQUIRED FOR
 OVER RIDES. PLEASE LSIT THE DEVICES
 BEING CHOSEN AND THE TIME LIMITS AS SET
 FORTH IN CHAPTER 13.
 PLEASE SEE ENERGY CALCULATIONS SHALL BE
 SIGNED, DATED AND SEALED. PLEASE SEE EN
 CALCS CONTAIN A "RUBBER STAMP" WHICH IS
 NOT PERMITTED UNDER FS 471.025
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE FBC 2004, CHAPTER 13
 FOR COMMERCIAL BLGS.
 PLEASE SEE 13-413.1.ABC.1.1&.2
 PLEASE SEE 13-415.1.ABC.1.1 &.2&.3
 13-415.1.ABC.3, 13-415.1.AB.1
 SCHEDULING, SPACE LAYOUT, DEVICE
 LOCATIONS ETC WILL BE REQUIRED AT A MIN.
  
 **** NEW NOTES 2ND REVIEW *****
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
  
  
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-07 Cont ID  
Sent By dpalmer Date 2006-07-07 Time 07:59 Rev Time 0.00
Received By dpalmer Date 2006-07-06 Time 20:45 Sent To  
Notes
2006-07-07 00:00:00***** UNSAT ******
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES .
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW AND NEW
 NOTES ARE ADDED AT THE BOTTOM.
  
 ** PLEASE STILL KNOW, PLANS ARE ONLY
 BEING SUBMITTED FOR "PLAN REVIEW" AND
 ARE BEING SUBMITTED FOR PERMIT.
  
  
  
 1)NOTE: NO, PLEASE SEE AREAS OF PLANS
 WHICH STILL INDICATE THE 2001 FBC.
 PLEASE SEE ARCH WHICH NOW INDICATES THE
 2004 FBC, WHICH SHOULD BE THE 2002
 NFPA-70
 PLEASE SEE THE FOLLOWING CODES ARE
 REQUIRED FOR THIS REVIEWER. OTHERS MAY
 BE REQUIRED FOR OTHER TRADES.
 2004 FBC, 2002 NFPA-70 (NEC), 2002
 NFPA-72, 2003 LS, NFPA-101. AT A MIN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, AS OF OCT 1ST,2005 THE
 STATE OF FLORIDA ADOPTED THE 2004 FBC.
 PLEASE SEE MANY LOCATIONS ON PLANS WHICH
 INDICATE 2001 ETC.
 PLEASE ADJUST.
  
 2)NOTE: NO, PLEASE STILL SEE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER
 REQUIRED FOR ENGINEERING COMPANY.
 OTHER ITEMS WERE OK. SEE NE NOTE FOR EN
 CALCS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION
 ON BOTH TITLE BLOCKS FOR ARCHITECT AND
 ENGINEERING FIRM.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 FOR ARCHITECT'S, MISSING THE
 PRINTED LICENSE # ON ALL TITLE BLOCKS
 AND SHEETS.
 PLEASE SEE FAC 61G15-23.002 FOR MISSING
 INFORMATION ON ENGINEER'S TITLE BLOCK,
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
 FLORIDA STATUES 471.023
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT(S) ARE MAADE BY OTHER
 REVIEWER(S).
  
 3)NOTE:OK/NO, PLEASE SEE LETTER WAS
 SUBMITTED HOWEVER IT WAS SHOULD BE
 SEALED WHEN DATED AND NOTORIZED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FS 471.025 WHICH
 REQUIRES A LEGAL SIGNATURE FROM THE
 ENGINEER. PLANS SEEM TO CONTAIN
 "INITIALS"?, IF INDEED THIS IS THE
 "LEGAL SIGNATURE" OF SAID ENGINEER ,
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALED LETTER FOR VERIFICATION OF LEGAL
 SIGNATURE. PLEASE KNOW, LETTER SHOULD BE
 PROPERLY NOTORIZED UNDER THE STATE
 STATUES IN WHICH THE NOTORIZATION IS
 TAKING PLACE. FS 117.05
  
 4)NOTE: NO, PLEASE SEE THE FOLLOWING AS
 THERE ARE STILL DIFFERENCES IN PLANS,
 RISER ETC.
 A) PLEASE SEE RISER SHOWS 250MCM TO
 PANEL "D" AND PANEL "D" SHOWS FEEDERS AS
 3/0'S?
 PLEASE SEE FEEEDERS FOR PANEL "C" ARE
 BEING SHOWN AS THE SAME ON 100A BRKR
 FEED. PLEASE KNOW, THE 100A BRKR WILL NO
 ACCEPT THE 3/0 CONDUCTORS.
 PLEASE SEE RISER IS NOW SHOWING A THIRD
 TENANT BUT STILL DOES NOT SEEM TO BE
 COMPLETE. PLEASE SEE THAT THIS BUILDING
 CONTAIN FOUR TENANTS. SEE COMMENT WITH
 RESPECT TO LOADS.
 PLEASE SEE CIRCUITING FOR AN EM LT IS
 SHOWN TO A CIRCUIT 13, YET THIS SPACE IN
 THE ELECTRICAL PANEL IS A "SPARE"??
 PLEASE SEE PLANS MENTIONS TO "RELOCATE"
 THE EXISTING PANEL "C" , HOWEVER DOES
 NOT SHOW THE NEW LOCATION.
 PLEASE CORRELATE THESE AND PLEASE GO
 OVER PLANS.
  
 ** PREVIOUS NOTE **
 PLEASE CORRELATE ALL EQUIPMENT,
 LOADS, SIZES ETC ON EQUIPMENT SCHEDULE
 AND PANEL SCHEDULE/ LOAD CALCS.
 PLEASE ADJUST PLANS AS NEEDED AS SOME DO
 NOT MATCH.
 215.5
  
 5)NOTE: NO, PLEASE SEE RESPONSE MENTIONS
 TO VERIFY, HOWEVER THIS IS REQUIRED AT
 THIS TIME TO EITHER SHOW NEW OR EXISTING
 PER 600.5, 1500VA MIN.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE INDICAET EITHER NEW OR
 EXISTING SIGN CIRCUIT PER 600.5
  
 6)NOTE: NO, PLEASE SEE LOADS FOR ALL
 EXISTING AND NEW LOADS SHALL BE SHOWN
 FOR EXISTING AND NEW.
 PLEASE SEE IT WAS NOT STATED WHETHER OR
 LOADS ARE DONE AT 125% FOR CONTINUOUS
 AND LOAD FOR LARGEST MOTOR LOADS.
 PLEASE SEE PREVIOUS NOTE ABOVE WITH
 RESPECT TO THE 4TH TENANT SERVICE WHICH
 DOES NOT SEEM TO BE INCLUDED IN RISER
 AND CALCULATIONS.
 215.3,230.42,220.3,220.10,220.11,220.13
 ,ETC
  
 ** PREVIOUS NOTE **
 PLEASE VERIFY ALL LOADS FOR
 EXISTING WIREWAY. PLEASE INDICATE THESE
 LOADS AND THE ADDED NEW LOADS.
 215.5,220
 PLEASE SEE IT APPEARS A CONTINUOUS LOAD
 FACTOR OF 125% IS BEING DONE FOR
 LIGHTING, HOWEVER UNABLE TO VERIFY AS
 THIS IS NOT SHOWN?
 215.3,230.42 ETC.
  
 7)NOTE: NO, PLEASE SEE SOME EM LTS NOT
 TO LOCAL LTS. SEE PREVIOUS NOTE ABOVE
 FOR CIRCUIT #13
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.
 PLEASE SEE ONE NOTE ON PLANS MENTIONS TO
 SEE PANEL SCHEDULE FOR CIRCUITING , ONE
 NOTE MENTIONS TO CIRCUIT TO LOCAL
 LIGHTING CIRCUIT.
 PLEASE KNOW, 700.12E REQUIRES TE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
 PLEASE ADJUST NOTES ON PLANS, PLEASE
 SHOW AND ADJUST PLANS FOR CIRCUITING.
  
 8)NOTE: NO, PLEASE SEE COMPLIANCE FOR
 THIS COULD NOT BE LOCATED. PLEASE SEE NO
 LIGHTING CONTROLS, AUTOMATIC SHUTT OFF,
 SCHEDULING ETC WAS SHOWN. PLEASE SEE
 SEPARATE SPACES AND DEVICES REQUIRED FOR
 OVER RIDES. PLEASE LSIT THE DEVICES
 BEING CHOSEN AND THE TIME LIMITS AS SET
 FORTH IN CHAPTER 13.
 PLEASE SEE ENERGY CALCULATIONS SHALL BE
 SIGNED, DATED AND SEALED. PLEASE SEE EN
 CALCS CONTAIN A "RUBBER STAMP" WHICH IS
 NOT PERMITTED UNDER FS 471.025
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 2004, CHAPTER 13
 FOR COMMERCIAL BLGS.
 PLEASE SEE 13-413.1.ABC.1.1&.2
 PLEASE SEE 13-415.1.ABC.1.1 &.2&.3
 13-415.1.ABC.3, 13-415.1.AB.1
 SCHEDULING, SPACE LAYOUT, DEVICE
 LOCATIONS ETC WILL BE REQUIRED AT A MIN.
  
 **** NEW NOTES *****
  
 9) NOTE: PLEASE CLARIFY IF THERE IS A
 NER OR EXISTING ROOFTOP GFI RECEPT.
 210.63, 210.8
  
 10) NOTE: PLEASE SPECIFY ALL CIRCUITS ON
 SCHEDULE TO THE AREA(S) AND RM IN WHICH
 THEY ARE FEEDING. IE: BATH LTS, OFFICE
 #3 RECEPTS , ETC.
 PLEASE ALSO INCLUDE ALL CONDUCTOR SIZES
 ON PANEL SCHEDULE AND CORRELATE WITH THE
 OCP AS SHOWN.
 240.4,310.16,408.4.
  
  
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-07-06 00:00:00NOTES TO FOLLOW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-28 Cont ID  
Sent By dpalmer Date 2006-02-28 Time 17:49 Rev Time 0.00
Received By dpalmer Date 2006-02-28 Time 07:58 Sent To  
Notes
2006-02-28 00:00:00************ UNSAT **********
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
  
 1)NOTE: PLEASE KNOW, AS OF OCT 1ST,2005
 THE STATE OF FLORIDA ADOPTED THE 2004
 FBC.
 PLEASE SEE MANY LOCATIONS ON PLANS WHICH
 INDICATE 2001 ETC.
 PLEASE ADJUST.
  
 2)NOTE: PLEASE SEE MISSING INFORMATION
 ON BOTH TITLE BLOCKS FOR ARCHITECT AND
 ENGINEERING FIRM.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 FOR ARCHITECT'S, MISSING THE
 PRINTED LICENSE # ON ALL TITLE BLOCKS
 AND SHEETS.
 PLEASE SEE FAC 61G15-23.002 FOR MISSING
 INFORMATION ON ENGINEER'S TITLE BLOCK,
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER.
 FLORIDA STATUES 471.023
 PLEASE KNOW, THIS IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT(S) ARE MAADE BY OTHER
 REVIEWER(S).
  
 3)NOTE: PLEASE SEE FS 471.025 WHICH
 REQUIRES A LEGAL SIGNATURE FROM THE
 ENGINEER. PLANS SEEM TO CONTAIN
 "INITIALS"?, IF INDEED THIS IS THE
 "LEGAL SIGNATURE" OF SAID ENGINEER ,
 PLEASE PROVIDE A SIGNED, DATED AND
 SEALED LETTER FOR VERIFICATION OF LEGAL
 SIGNATURE. PLEASE KNOW, LETTER SHOULD BE
 PROPERLY NOTORIZED UNDER THE STATE
 STATUES IN WHICH THE NOTORIZATION IS
 TAKING PLACE. FS 117.05
  
 4)NOTE: PLEASE CORRELATE ALL EQUIPMENT,
 LOADS, SIZES ETC ON EQUIPMENT SCHEDULE
 AND PANEL SCHEDULE/ LOAD CALCS.
 PLEASE ADJUST PLANS AS NEEDED AS SOME DO
 NOT MATCH.
 215.5
  
 5)NOTE: PLEASE INDICAT EITHER NEW OR
 EXISTING SIGN CIRCUIT PER 600.5
  
 6)NOTE: PLEASE VERIFY ALL LOADS FOR
 EXISTING WIREWAY. PLEASE INDICATE THESE
 LOADS AND THE ADDED NEW LOADS.
 215.5,220
 PLEASE SEE IT APPEARS A CONTINUOUS LOAD
 FACTOR OF 125% IS BEING DONE FOR
 LIGHTING, HOWEVER UNABLE TO VERIFY AS
 THIS IS NOT SHOWN?
 215.3,230.42 ETC.
  
 7)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULES.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM/
 EXT LTS.
 PLEASE SEE ONE NOTE ON PLANS MENTIONS TO
 SEE PANEL SCHEDULE FOR CIRCUITING , ONE
 NOTE MENTIONS TO CIRCUIT TO LOCAL
 LIGHTING CIRCUIT.
 PLEASE KNOW, 700.12E REQUIRES TE BRANCH
 CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL
 BE THE SAME BRANCH CIRCUIT AS THAT
 SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL
 SWITCHES.
 PLEASE ADJUST NOTES ON PLANS, PLEASE
 SHOW AND ADJUST PLANS FOR CIRCUITING.
  
 8)NOTE: PLEASE SEE FBC 2004, CHAPTER 13
 FOR COMMERCIAL BLGS.
 PLEASE SEE 13-413.1.ABC.1.1&.2
 PLEASE SEE 13-415.1.ABC.1.1 &.2
 13-415.1.ABC.3, 13-415.1.AB.1
 SCHEDULING, SPACE LAYOUT, DEVICE
 LOCATIONS ETC WILL BE REQUIRED AT A MIN.
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICLA
 PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF OLD/VOIDED
 SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2007-04-25 Cont ID  
Sent By mawillia Date 2007-04-25 Time 14:27 Rev Time 0.00
Received By mawillia Date 2007-04-25 Time 14:24 Sent To  
Notes
2007-04-25 14:27:24*****APPROVED*****
  
  
 PLAN SHEETS A1.2 AND E2.1 (ROUTED BY LUIS MARTINEZ)
 WERE STAMPED, INITIALED, AND DATED

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2007-04-11 Cont ID  
Sent By mawillia Date 2007-04-11 Time 15:48 Rev Time 0.00
Received By mawillia Date 2007-04-11 Time 15:29 Sent To  
Notes
2007-04-11 15:35:36*****APPROVED*****
  
  
  
 SHEETS A1.2 AND E2.1 WERE STAMPED, INITIALED, AND
 DATED ON 02/14/07 BUT WERE "VOIDED" BY OTHER PLAN
 REVIEWERS.THE NEW RESUBMITTED SHEETS WERE RESTAMPED
 WITH THE CURRENT DATE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-02-14 Cont ID  
Sent By mawillia Date 2007-02-14 Time 16:56 Rev Time 0.00
Received By mawillia Date 2007-02-14 Time 16:56 Sent To  
Notes
2007-02-14 17:08:46*****APPROVED*****
  
  
  
 ALL COMMENTS FROM PREVIOUS FIRE PLAN REVIEWS HAVE BEEN
 ADDRESSED.SHEETS A1.2 AND E2.1 WERE STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2006-11-22 Cont ID  
Sent By mwennerg Date 2006-11-22 Time 14:01 Rev Time 0.00
Received By mwennerg Date 2006-11-22 Time 14:01 Sent To  
Notes
2006-11-22 14:06:11***APPROVED***
  
 1) PLEASE NOTE THAT ADDRESS ON APPLICATION DOESN'T
 CORRULATE WITH PLANS. PLEASE MAKE CORRECTION.
  
 2) SHEET T1.1 INDICATES SPRINKLERED BUILDING. SEPARATE
 SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE SPRINKLER
 REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-25 Cont ID  
Sent By mcarsill Date 2006-10-25 Time 07:54 Rev Time 0.00
Received By mcarsill Date 2006-10-25 Time 07:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-07-10 Cont ID  
Sent By mcarsill Date 2006-07-10 Time 14:57 Rev Time 0.00
Received By mcarsill Date 2006-07-10 Time 14:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-03-23 Cont ID  
Sent By mwennerg Date 2006-03-23 Time 11:08 Rev Time 0.00
Received By mwennerg Date 2006-03-23 Time 11:08 Sent To  
Notes
2006-03-23 00:00:00******DENIED******
 **PLAN REVIEW ONLY**
  
 1) PLEASE NOTE THAT FLORIDA FIRE
 PREVENTION CODE, 2004 EDITION SHALL BE
 REFERENCED. SHT T1.1.
  
 2) DUCT SMOKE DETECTOR SHALL BE LOCATED
 IN SUPPLY AIR SYSTEM, NOT RETURN DUCT.
 SHT M1.0.
  
 3) 2A-10B,C RATED FIRE EXTINGUISHERS TO
 BE MOUNTED AND ACCESSIBLE NOT TO EXCEED
 75' TRAVEL DISTANCE REQUIREMENT.
  
 4) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-08-06 Cont ID  
Sent By adarroug Date 2007-08-06 Time 13:20 Rev Time 0.00
Received By adarroug Date 2007-08-06 Time 13:20 Sent To M
Notes
2007-08-06 13:21:09TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-07-30 Cont ID  
Sent By adarroug Date 2007-07-30 Time 16:52 Rev Time 0.00
Received By adarroug Date 2007-07-30 Time 16:52 Sent To M
Notes
2007-07-30 16:53:20TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-07-16 Cont ID  
Sent By adarroug Date 2007-07-16 Time 08:56 Rev Time 0.00
Received By adarroug Date 2007-07-16 Time 08:56 Sent To M
Notes
2007-07-16 08:56:54TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-04-17 Cont ID  
Sent By adarroug Date 2007-04-17 Time 13:22 Rev Time 0.00
Received By adarroug Date 2007-04-17 Time 13:20 Sent To  
Notes
2007-04-17 13:25:17TO "COMM" BD#54

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-03-13 Cont ID  
Sent By adarroug Date 2007-03-13 Time 09:56 Rev Time 0.00
Received By adarroug Date 2007-03-13 Time 09:56 Sent To  
Notes
2007-03-13 09:57:06TO "COMM" BD#47

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 15:05 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 15:05 Sent To E
Notes
2007-02-22 15:06:16TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 13:20 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 13:19 Sent To  
Notes
2007-01-08 09:13:48TO "COMM" BD#3
2006-12-17 13:20:16WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-03 Cont ID  
Sent By adarroug Date 2006-11-03 Time 11:12 Rev Time 0.00
Received By adarroug Date 2006-11-03 Time 11:12 Sent To  
Notes
2006-11-03 11:15:42TO "COMM" BD#7

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 12:19 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 12:19 Sent To  
Notes
2006-09-25 00:00:00TO "COMM' BD#44
2006-09-12 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-25 Cont ID  
Sent By adarroug Date 2006-06-25 Time 16:18 Rev Time 0.00
Received By adarroug Date 2006-06-25 Time 16:42 Sent To  
Notes
2006-07-05 00:00:00TO "COMM" BD#17
2006-06-25 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-19 Cont ID  
Sent By alange Date 2006-04-19 Time 08:32 Rev Time 0.00
Received By alange Date 2006-01-23 Time 15:08 Sent To  
Notes
2006-02-22 00:00:00TO "COMM" BD#23
2006-02-07 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2007-08-14 Cont ID  
Sent By tgordon Date 2007-08-14 Time 13:53 Rev Time 0.25
Received By tgordon Date 2007-08-14 Time 13:53 Sent To  
Notes
2007-08-14 13:54:09REVISION TO MECHANICAL PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2007-08-08 Cont ID  
Sent By tgordon Date 2007-08-08 Time 09:22 Rev Time 0.20
Received By tgordon Date 2007-08-08 Time 09:22 Sent To  
Notes
2007-08-08 09:35:00** MECHANICAL REVISION **
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 7-31-07 MECHANICAL PLANS ON
 FILE ARE SEALED BY AN ARCHITECT ("KERRY PICKETT") SO
 ONLY THIS ARCHITECT CAN MAKE REVISIONS TO THEM.
 REVISION SUBMITTED HAS BEEN SEALED BY GEORGE SARFATTY.
 PLEASE CORRECT.
  
 2)INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT
 SEE FAC 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2007-07-31 Cont ID  
Sent By tgordon Date 2007-07-31 Time 08:25 Rev Time 0.25
Received By tgordon Date 2007-07-31 Time 08:25 Sent To  
Notes
2007-07-31 09:00:13** MECHANICAL REVISION DENIED **
 1) MECHANICAL PLANS ON FILE ARE SEALED BY AN ARCHITECT
 (KERRY PICKETT) SO ONLY THE ARCHITECT CAN MAKE
 REVISIONS TO THEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 6 Status N Date 2007-07-17 Cont ID  
Sent By tgordon Date 2007-07-17 Time 11:52 Rev Time 0.20
Received By tgordon Date 2007-07-17 Time 11:52 Sent To B
Notes
2007-07-17 11:54:03REVISION TO PLANS PAGE A1.1, BUILDING REV. NOT MECH.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-02-09 Cont ID  
Sent By rregueir Date 2007-02-09 Time 09:34 Rev Time 0.00
Received By rregueir Date 2007-02-09 Time 09:34 Sent To  
Notes
2007-02-09 09:41:31-------------PROVISO---------------
  
 DUCT MOUNTED SMOKE DETECTORS ARE TO BE LOCATED IN
 SUPPLY DUCT PER FBC,M 606.2.1

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-02-08 Cont ID  
Sent By hmoser Date 2007-02-08 Time 08:44 Rev Time 0.00
Received By hmoser Date 2007-02-08 Time 08:44 Sent To  
Notes
2007-02-08 08:54:30PLAN DENIED.
 1) PLEASE PROVIDE A DETAIL ON HOW TO ANCHOR AIR
 CONDITIONING CURB TO ROOF, AND RTU' S TO CURB.
 2) PLEASE REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM.
 3) PLEASE REFER TO CECTION 601.4 BALANCED RETURN AIR.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-16 Cont ID  
Sent By hmoser Date 2006-10-16 Time 09:35 Rev Time 0.00
Received By hmoser Date 2006-10-16 Time 09:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-18 Cont ID  
Sent By tgordon Date 2006-08-18 Time 09:54 Rev Time 0.30
Received By tgordon Date 2006-08-18 Time 09:54 Sent To  
Notes
2006-08-18 00:00:00*** DENIED ***
 1) SEE MECHANICAL PLAN PAGE M1.0
 BUILDING CODE NOTES #1 REFERS TO 2000
 INTERNATIONAL MECH. CODE. MECHANICAL
 CODE IN USE IS 2004 FLORIDA BUILDING
 CODE MECHANICAL, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-13 Cont ID  
Sent By hmoser Date 2006-03-13 Time 17:44 Rev Time 0.00
Received By hmoser Date 2006-03-13 Time 17:44 Sent To  
Notes
2006-03-13 00:00:00PLAN DENIED
 1) ROOM 110 MISSING SUPPLY DUCT SIZE
 2) ROOM 116 MISSING RETURN AIR DUCT SIZE
 3) ROOM 171 MISSING SUPPLY DUCT SIZE
 4) PLEASE PROVIDE BATHROOM EXHAUST ON
 PLANS.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-02-01 Cont ID  
Sent By kstevens Date 2007-02-01 Time 12:20 Rev Time 0.00
Received By kstevens Date 2007-02-01 Time 12:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2006-12-02 Cont ID  
Sent By pschmitz Date 2006-12-02 Time 09:35 Rev Time 0.00
Received By pschmitz Date 2006-12-02 Time 09:35 Sent To  
Notes
2006-12-02 09:48:13RE-SUB

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-11 Cont ID  
Sent By kstevens Date 2006-10-11 Time 17:05 Rev Time 0.00
Received By kstevens Date 2006-10-11 Time 17:05 Sent To  
Notes
2006-10-11 17:12:02DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 7. OK
  
 **************NEW COMMENT**************
  
 REFERENCE FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FBC-2004 CHAPTER 1
  
 1B. THE PERSONAL SEAL, SIGNATURE AND
 DATE OF THE ARCHITECT SHALL APPEAR
 ON ALL ARCHITECTURAL DOCUMENTS TO
 BE FILED FOR PUBLIC RECORD.
 FAC 61G1-16.003, FS 481.2055 AND
 SECTION 106.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-05 Cont ID  
Sent By kstevens Date 2006-08-05 Time 14:15 Rev Time 0.00
Received By kstevens Date 2006-08-05 Time 14:15 Sent To  
Notes
2006-08-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT T1.1 CODE INDICATED IS FBC-2001,
 CODE ADOPTED IS FBC-2004. PLEASE CHANGE
 REFERENCE TO PROPER CODE.
 ****RESPONSE NOTED, BUT SOME REFERENCES
 TO FBC-2001 STILL ON PLANS.
  
 2. OK
  
 3. SHT A1.2 DETAIL #4 BREAK ELEVATION:
 SINK SHALL BE ACCESSIBLE. SUBMIT
 INFORMATION SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 CLEAR FLOOR SPACE SHALL BE FORWARD
 APPROACH AND NO CABINET DOORS ALLOWED IN
 THE CLEAR FLOOR SPACE.
 ****RESPONSE NOTED, BUT DETAIL SHOW
 120'-0" OPENING. PLEASE CLARIFY. - ALSO
 SHOW THE FOLLING INFORMATION:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
 D. 11-4.24.7 FAUCETS
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
  
 7. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM SHOWING ALL PIPE SIZES,
 VALVES, WATER HAMMER ARRESTORS REQUIRED
 BY SECTION 604.9. IF INSTALLED ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT FULL OPEN VALVES
 ARE REQUIRED AT THE TOP OF EVERY WATER
 DOWN-FEED PIPE PER SECTION 606.1(4).
 PLEASE SHOW ON RISER DIAGRAM.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-04-13 Cont ID  
Sent By kstevens Date 2006-03-17 Time 15:48 Rev Time 0.00
Received By kstevens Date 2006-03-16 Time 16:54 Sent To  
Notes
2006-03-17 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT T1.1 CODE INDICATED IS FBC-2001,
 CODE ADOPTED IS FBC-2004. PLEASE CHANGE
 REFERENCE TO PROPER CODE.
 2. SHT A DRINKING FOUNTAIN IS REQUIRED
 PER TABLE 403.1. SHOW LOCATION ON THE
 FLOOR PLAN. SUBMIT A DETAIL SHOWING
 COMPLIANCE WITH 11-4.15 AND ALL
 SUBSECTIONS AS WELL AS 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
 3. SHT A1.2 DETAIL #4 BREAK ELEVATION:
 SINK SHALL BE ACCESSIBLE. SUBMIT
 INFORMATION SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 CLEAR FLOOR SPACE SHALL BE FORWARD
 APPROACH AND NO CABINET DOORS ALLOWED IN
 THE CLEAR FLOOR SPACE.
 4. SHT A1.3 DETAIL #3 SHOW THE
 FOLLOWING:
 A. FOR W/C'S
 11-4.16.3 HEIGHT
 B. FOR LAVS
 11-4.19.2 HEIGHT & CLEARANCES
 11-4.19.4 EXPOSED PIPES AND SURFACES
 11-4.19.5 FAUCETS
 5. SHT A1.3 FIXTURE KEY D TO READ 19"
 "MINIMUM" SECTION 11-4.19.6.
 6. P1.0 PLUMBING SPECIFICATION
 (CONDENSATE DRAINAGE PIPING) 50/50
 SOLDER NOT APPROVED. SECTION 705.9.3.
 SOLDER SHALL COMFORM TO ASTM B32.
 7. SHT P1.0 BUILDING CODE NOTES #15: AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 REFERENCE. SECTION 604.9.
 8. SHT P2.0 DWV DRAINAGE RISER DIAGRAM,
 TRAPS SHOWN FOR WATER CLOSETS NOT
 APPROVED. SECTION 1002.1(1).
 7. SUBMIT A WATER RISER DIAGRAM IN
 ISOMETRIC FORM SHOWING ALL PIPE SIZES,
 VALVES, WATER HAMMER ARRESTORS REQUIRED
 BY SECTION 604.9. IF INSTALLED ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING.
 SECTION 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]