Plan Review Details - Permit 06010859
Plan Review Stops For Permit 06010859
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-02-09 Cont ID  
Sent By btrobaug Date 2006-02-09 Time 07:40 Rev Time 0.33
Received By btrobaug Date 2006-02-09 Time 07:35 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-26 Cont ID  
Sent By btrobaug Date 2006-01-24 Time 17:37 Rev Time 0.50
Received By btrobaug Date 2006-01-24 Time 17:28 Sent To PC
Notes
2006-01-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE LOAD CALCULATIION FOR ONE UNIT IS
 120 AMPS AND THE RISER WIRE IS ONLY
 RATED FOR 200 AMPS. SEE 310.15(B)(6).
  
 2} INDICATE THE SIZE OF THE GROUNDING
 ELECTRODE CONDUCTOR PER 250.66.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN MUST PRINT NAME AND SIGN SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-03 Cont ID  
Sent By adarroug Date 2006-02-03 Time 08:51 Rev Time 0.00
Received By adarroug Date 2006-02-03 Time 08:51 Sent To E
Notes
2006-02-03 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-24 Cont ID  
Sent By btrobaug Date 2006-01-24 Time 17:28 Rev Time 0.00
Received By btrobaug Date 2006-01-23 Time 15:59 Sent To E
Notes
2006-01-23 00:00:00TO "E" BOX