| Plan Review Stops For Permit 06010759 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-01-24 |
|
|
Cont ID |
|
| Sent By |
kconrad |
Date |
2006-01-24 |
Time |
12:31 |
Rev Time |
0.30 |
| Received By |
kconrad |
Date |
2006-01-24 |
Time |
12:31 |
Sent To |
I |
|
| Notes |
| 2006-01-24 00:00:00 | 1)THE GAF STRATOVENT BASE SHEET IS | | | REQUIRED TO BE MECHANICALLY ATTACHED DUE | | | TO THE EXISTING ROOF CONDITIONS.THIS WAS | | | DETERMINED AFTER THE PREINSPECTION OF | | | THE SAME.THIS ENSURES THAT THE EXISTING | | | ISOBOARD WILL BE PROPERLY ATTACHED AS | | | PER THE RAS 117. | | | | | | 2)THE EXISTING ROOFING BALLAST MUST BE | | | STRIPPED AND THE EXISTING MEMBRANE | | | CLEANED PRIOR TO THE RECOVER | | | APPLICATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-01-24 |
|
|
Cont ID |
|
| Sent By |
amorse |
Date |
2006-01-23 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
kconrad |
Date |
2006-01-24 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2006-01-23 00:00:00 | | | | | | | DENIED | | | | | | SENT TO KEN CONRAD FOR SITE INSPECTION |
|
|
|