Plan Review Details - Permit 06010742
Plan Review Stops For Permit 06010742
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-10 Cont ID  
Sent By lmartine Date 2006-05-10 Time 11:16 Rev Time 0.00
Received By lmartine Date 2006-05-10 Time 11:16 Sent To  
Notes
2006-04-26 00:00:00NEW DETAIL FOR SLAB, NEEDS BLDG REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-02-12 Cont ID  
Sent By lmartine Date 2006-02-12 Time 13:22 Rev Time 0.00
Received By lmartine Date 2006-02-12 Time 13:21 Sent To P
Notes
2006-02-12 00:00:00 
  
 COMPLY WITH MECHANICAL NOTES FOR
 LOCATION AND FOUNDATION REQUIREMENTS FOR
 UNIT.
  
  
 L.MARTINEZ
 805-6710

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-18 Cont ID  
Sent By dpalmer Date 2006-05-18 Time 12:46 Rev Time 0.00
Received By dpalmer Date 2006-05-18 Time 12:46 Sent To PC
Notes
2006-05-18 00:00:00***** PROVSIO ********
  
  
 ** NOTES REDLINED, THE SERVICE ENT RATED
 ATS, MUST MEET 230.76,230.76,
 225.31-225.39
 THIS WILL BE VEERIFIED BY THIS OFFICE.
  
 ** NEUTRAL CALCULATIONS STILL PENDING,
 MUST VERIFIED BEFORE FINAL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-26 Cont ID  
Sent By dpalmer Date 2006-04-26 Time 19:10 Rev Time 0.00
Received By dpalmer Date 2006-04-26 Time 18:35 Sent To  
Notes
2006-04-26 00:00:00PLACED CALL AND E-MAIL TO
 JEFF HALVERSON,
 ELECTRICAL PLANS SUBMITTED FOR FIRE
 STATION #5 ARE ON HOLD AS PLANS NEED TO
 BE SUBMITTED FOR ELECTRICAL CODE
 COMPLIANCE.
 THERE ARE NUMEROUS ITEMS WHICH NEED TO
 BE ADDRESSED.
 **********UNSAT 2ND REVIEW **********
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS
 REVIEW, PLEASE SEE NOW TWO DIFFERENT
 ELECTRICAL RISERS ARE BEING SUBMITTED
 FOR REVIEW.
 PLEASE SEE RISERS SUBMITTED DO NOT MEET
 MIN NEC CODE COMPLIANCE FOR
 INSTALLATIONS.
 PLEASE SEE MOST COMMENTS FROM PREVIOUS
 REVIEW STILL REMAIN.
 215.5
  
 2) NOTE: PLEASE SEE PLANS SUBMITTED DO
 NOT CONTAIN THE PRINTED NAME AND THE
 SIGNATURE OF THE "DESIGN
 PROFESSIONAL"/CONTRACTOR WHO IS TAKING
 RESPONSIBILITY FOR PLANS AND DESIGN.
 FBC 104.2.1 ADMINISTRATIVE SECTION AS
 ADMENDED BY THE CITY OF WEST PALM BEACH.
  
 3) NOTE: PLEASE SEE RESPONSE LETTER
 MENTIONS GEN WILL BE SEPARATELY DERIVED
 , HOWEVER PLANS HAVE NOT BEEN REVISED TO
 MEET CODE COMPLIANCE FOR THIS AND THE
 SPECS FOR THE ATS DO NOT MENTION BEING
 4-POLE.
 250.30,215.5
  
 4) NOTE: PLEASE SEE FLORIDA STATUES
 553.80(2)(B) WITH RESPECT TO THE "DESIGN
 PROFESSIONAL" AND REPEAT COMMENTS FOR
 CODE COMPLIANCE.
 PLEASE KNOW, DUE TO THE EXTREME TIME
 SENSATIVE NATURE OF THIS PROJECT IT IS
 STRONGLY RECOMMENDED A MEETING BE HELD
 WITH CITY'S PROJECT REPRESENTATIVE, AND
 PLANS EXAMINER TO GO OVER NOTES AND
 COMMENTS IN ORDER TO HELP ALLEAVIATE ANY
 FURTHER DELAYS.
  
 PLEASE CALL TO SET UP A TIME TO GO OVER
 PLANS AND FOR NEW PLANS TO BE SUBMITTED
 ONCE ALL REVIEWS ARE COMPLETE.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-06 Cont ID  
Sent By dpalmer Date 2006-02-06 Time 15:52 Rev Time 0.00
Received By dpalmer Date 2006-02-03 Time 21:53 Sent To  
Notes
2006-02-06 00:00:00********* UNSAT ***********
  
  
 1)NOTE: PLEASE PROVIDE NEUTRAL LOAD
 CALCULATIONS FOR DOWN SIZING OF NEUTRAL.
 215.5
  
 2)NOTE: PLEASE PROVIDE PLANS TO BE DONE
 MINIMUM BY AN ARCHITETC AS REQUIRED
 UNDER FS 481.229. PLANS MAY ALSO BE DONE
 BY AND PE AS LISTED UNDER FS
 471.003(2)H).
 PLEASE SEE THE FOLLOWING COMMENT AS
 PLANS MAY BE REQUIRED TO BE DONE BY A PE
 AS VALUE MAY BE ADJUSTED. (IF $50K OR
 MORE, THEN A PE WILL BE REQUIRED FOR
 PLANS.
  
 3)NOTE: PLEASE SEE FBC ADMINISTRATIVE
 SECTION 108.3 WHICH REQUIRES VALUE BASED
 ON COMPLETE SCOPE WORK TO INCLUDE ALL
 LABOR AND MATERIALS, EVEN IF EQUIPMENT
 IS OWNER SUPPLIED.
 PLEASE SEE VALUE IS SHOWN AS THE SAME
 FOR ALL THREE PERMITTED JOBS.
  
 4)NOTE: PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR THE NEW GENERATOR,
 ATS AND FUEL TANK.
 215.5
  
 5)NOTE: PLEASE PROVIDE MIN FUEL FOR ALL
 LIFE SAFETY DEVICES.
 PLEASE ALSO SEE FIRE REVIEW COMMENTS.
 LS 101 7.8,7.9 ETC
  
 6)NOTE: PLEASE SEE AN EQUIPMENT
 GROUNDING CONDUCTOR IS BEING SHOWN
 BETWEEN THE ATS AND THE MDP?
 PLEASE SEE 20.6,250.24 AS "EQUIPMENT
 GROUNDING CONDUCTORS" ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 7)NOTE: PLEASE DECLARE WHETHER OR NOT
 THE GENERATOR WILL OR WILL NOT BE A
 SEPARATEY DERVIED SYSTEM. PLEASE ADJUST
 AS NEEDED.
 215.5
  
 8)NOTE: PLEASE SEE 445.13 FOR MIN SIZING
 OF CONDUCTORS FROM GENERATOR TO ATS,
 FIRST MEANS OF OCP.
 215.5, 240.4,310.16
  
 9)NOTE: PLEASE SEE NO OCP IS SHOWN AT
 GENERATOR.?
 215.5
  
 10)NOTE: PLEASE SUBMIT PLANS INDICATION
 LOCATION OF GENERATOR AT SITE.
 PLEASW SHOW DETAIL OF WHERE BOLLARDS MAY
 BE REQUIRED DEPENDING ON THE LOCATION OF
 GENERATOR ETC.
  
 11)NOTE: PLEASE SEE BLDG REVIEW ,AS NO
 SLAB/FOOTER DETAILS WERE SUBMITTED.
  
 12)NOTE: PLEASE SEE , RISER AS SHOWN MAY
 REQUIRE A MAIN DISC ON THE LINE SIDE OF
 ATS.
  
  
 13)NOTE: PLEASE SEE NO OCP IS INDICATED
 FOR NEW FEED TO PANEL EM?
 CAN NOT VERIFY FEEDERS ETC AT THIS TIME.
 215.5,310.16
  
 ** PLEASE SEE COMMENTS FROM OTHER
 REVIEWER(S) WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY
 QUESTIONS,PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
  
 PLANS SENT TO LUIS M.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-02 Cont ID  
Sent By mwennerg Date 2006-05-02 Time 13:57 Rev Time 0.00
Received By mwennerg Date 2006-05-02 Time 13:57 Sent To  
Notes
2006-05-02 00:00:00******APPROVED******
  
 1) WORK SHALL COMPLY WITH NFPA 110,
 STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-08 Cont ID  
Sent By mwennerg Date 2006-02-08 Time 09:16 Rev Time 0.00
Received By mwennerg Date 2006-02-08 Time 09:16 Sent To  
Notes
2006-02-08 00:00:00******DENIED******
  
 1) PLEASE PROVIDE MANUFACTURER SPEC
 SHEETS FOR GENERATOR AND ASSOCIATED FUEL
 EQUIPMENT.
  
 2) WORK TO COMPLY WITH NFPA 110.
  
 3) PLEASE ILLUSTRATE LOCATION OF
 GENERATOR IN RELATION TO BUILDING AND
 PROPERTY LINES.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-04-29 Cont ID  
Sent By pschmitz Date 2006-04-29 Time 12:56 Rev Time 0.00
Received By pschmitz Date 2006-04-29 Time 13:06 Sent To  
Notes
2006-04-29 00:00:00UNSAT
 NO PLANS, CONTRACTOR TO SUBMITT PLANS AT
 TIME OF PERMIT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-02-13 Cont ID  
Sent By jleech Date 2006-02-13 Time 07:21 Rev Time 0.50
Received By jleech Date 2006-02-13 Time 07:21 Sent To  
Notes
2006-02-13 00:00:00DENIED;
 1. PERMIT APPLICATION WITH PLANS IS
 REQUIRED FROM A LICENSED L.P.
 CONTRACTOR.
 2. LOCATION OF TANK AND GENERATOR IS
 REQUIRED.
 3. PLEASE PROVIDE MANUFACTURE'S SPEC.
 SHEETS.
 GAS PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-26 Cont ID  
Sent By adarroug Date 2006-04-26 Time 12:54 Rev Time 0.00
Received By adarroug Date 2006-04-26 Time 12:54 Sent To  
Notes
2006-04-26 00:00:00WAITING FOR "COMM" BD
 TO "COMM" BD#45

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-28 Cont ID  
Sent By adarroug Date 2006-01-28 Time 15:05 Rev Time 0.00
Received By adarroug Date 2006-01-28 Time 15:05 Sent To  
Notes
2006-01-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-01-22 Time   Rev Time 0.00
Received By adarroug Date 2006-01-22 Time 12:22 Sent To  
Notes
2006-01-22 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-01 Cont ID  
Sent By pkrauss Date 2006-05-01 Time 14:57 Rev Time 0.00
Received By pkrauss Date 2006-05-01 Time 14:57 Sent To  
Notes
2006-05-01 00:00:00PROVISO:
 ADDITIONAL PERMIT REQUIED FOR GAS.
 PLEASE PROVIDE PIPE SIZING AND MATERIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-07 Cont ID  
Sent By pkrauss Date 2006-02-07 Time 09:54 Rev Time 0.00
Received By pkrauss Date 2006-02-07 Time 09:54 Sent To  
Notes
2006-02-07 00:00:00DENIED:
 1.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE GENERATOR.
  
 2.PLEASE PROVIDE SITE PLANS INDICATING
 LOCATION OF THE GENERATOR.SHOW
 DISTANCE FROM BUILDING STRUCTURE,
 WINDOWS, DOORS, LOUVERS, ETC.PLEASE
 INDICATE DISTANCE FROM PROPERTY LINES.
  
 3.PERMIT APPLICATION INDICATES NATURAL
 GAS BUT A SUBMITTAL FOR AN LP TANK IS
 ALSO PROVIDED.WILL THIS BE A "DUEL
 TYPE OF FUEL SORCE"?PLEASE CLARIFY.
  
 4.ADDITIONAL PERMIT REQUIRED FOR GAS
 INSTALLATION.
  
 5.PLEASE PROVIDE DETAIL FOR THE
 GENERATOR SLAB & ANCHORING OF THE
 GENERATOR.SHOW COMPLIANCE WITH 2004
 FMC 301.13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-04-29 Cont ID  
Sent By pschmitz Date 2006-04-29 Time 13:07 Rev Time 0.00
Received By pschmitz Date 2006-04-29 Time 13:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-02-13 Cont ID  
Sent By jleech Date 2006-02-13 Time 07:20 Rev Time  
Received By jleech Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-03 Cont ID  
Sent By mmclean Date 2006-05-03 Time 14:15 Rev Time 0.00
Received By mmclean Date 2006-05-03 Time 14:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-01-28 Cont ID  
Sent By mmclean Date 2006-01-28 Time 13:52 Rev Time 0.00
Received By mmclean Date 2006-01-28 Time 13:52 Sent To I
Notes
2006-01-28 00:00:00DENIED,
 1. NEED TO SHOW THE LOCATION OF
 GENERATOR ON TWO COPY OF SITEPLAN WITH
 SETBACKS FROM PROPERTY LINE.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720