| Plan Review Stops For Permit 06010742 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-05-10 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-05-10 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-05-10 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2006-04-26 00:00:00 | NEW DETAIL FOR SLAB, NEEDS BLDG REVIEW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2006-02-12 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2006-02-12 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2006-02-12 |
Time |
13:21 |
Sent To |
P |
|
| Notes |
| 2006-02-12 00:00:00 | | | | | | | COMPLY WITH MECHANICAL NOTES FOR | | | LOCATION AND FOUNDATION REQUIREMENTS FOR | | | UNIT. | | | | | | | | | L.MARTINEZ | | | 805-6710 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2006-05-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-05-18 |
Time |
12:46 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-05-18 |
Time |
12:46 |
Sent To |
PC |
|
| Notes |
| 2006-05-18 00:00:00 | ***** PROVSIO ******** | | | | | | | | | ** NOTES REDLINED, THE SERVICE ENT RATED | | | ATS, MUST MEET 230.76,230.76, | | | 225.31-225.39 | | | THIS WILL BE VEERIFIED BY THIS OFFICE. | | | | | | ** NEUTRAL CALCULATIONS STILL PENDING, | | | MUST VERIFIED BEFORE FINAL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2006-04-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-04-26 |
Time |
19:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-04-26 |
Time |
18:35 |
Sent To |
|
|
| Notes |
| 2006-04-26 00:00:00 | PLACED CALL AND E-MAIL TO | | | JEFF HALVERSON, | | | ELECTRICAL PLANS SUBMITTED FOR FIRE | | | STATION #5 ARE ON HOLD AS PLANS NEED TO | | | BE SUBMITTED FOR ELECTRICAL CODE | | | COMPLIANCE. | | | THERE ARE NUMEROUS ITEMS WHICH NEED TO | | | BE ADDRESSED. | | | **********UNSAT 2ND REVIEW ********** | | | | | | 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS | | | REVIEW, PLEASE SEE NOW TWO DIFFERENT | | | ELECTRICAL RISERS ARE BEING SUBMITTED | | | FOR REVIEW. | | | PLEASE SEE RISERS SUBMITTED DO NOT MEET | | | MIN NEC CODE COMPLIANCE FOR | | | INSTALLATIONS. | | | PLEASE SEE MOST COMMENTS FROM PREVIOUS | | | REVIEW STILL REMAIN. | | | 215.5 | | | | | | 2) NOTE: PLEASE SEE PLANS SUBMITTED DO | | | NOT CONTAIN THE PRINTED NAME AND THE | | | SIGNATURE OF THE "DESIGN | | | PROFESSIONAL"/CONTRACTOR WHO IS TAKING | | | RESPONSIBILITY FOR PLANS AND DESIGN. | | | FBC 104.2.1 ADMINISTRATIVE SECTION AS | | | ADMENDED BY THE CITY OF WEST PALM BEACH. | | | | | | 3) NOTE: PLEASE SEE RESPONSE LETTER | | | MENTIONS GEN WILL BE SEPARATELY DERIVED | | | , HOWEVER PLANS HAVE NOT BEEN REVISED TO | | | MEET CODE COMPLIANCE FOR THIS AND THE | | | SPECS FOR THE ATS DO NOT MENTION BEING | | | 4-POLE. | | | 250.30,215.5 | | | | | | 4) NOTE: PLEASE SEE FLORIDA STATUES | | | 553.80(2)(B) WITH RESPECT TO THE "DESIGN | | | PROFESSIONAL" AND REPEAT COMMENTS FOR | | | CODE COMPLIANCE. | | | PLEASE KNOW, DUE TO THE EXTREME TIME | | | SENSATIVE NATURE OF THIS PROJECT IT IS | | | STRONGLY RECOMMENDED A MEETING BE HELD | | | WITH CITY'S PROJECT REPRESENTATIVE, AND | | | PLANS EXAMINER TO GO OVER NOTES AND | | | COMMENTS IN ORDER TO HELP ALLEAVIATE ANY | | | FURTHER DELAYS. | | | | | | PLEASE CALL TO SET UP A TIME TO GO OVER | | | PLANS AND FOR NEW PLANS TO BE SUBMITTED | | | ONCE ALL REVIEWS ARE COMPLETE. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-02-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-02-06 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-02-03 |
Time |
21:53 |
Sent To |
|
|
| Notes |
| 2006-02-06 00:00:00 | ********* UNSAT *********** | | | | | | | | | 1)NOTE: PLEASE PROVIDE NEUTRAL LOAD | | | CALCULATIONS FOR DOWN SIZING OF NEUTRAL. | | | 215.5 | | | | | | 2)NOTE: PLEASE PROVIDE PLANS TO BE DONE | | | MINIMUM BY AN ARCHITETC AS REQUIRED | | | UNDER FS 481.229. PLANS MAY ALSO BE DONE | | | BY AND PE AS LISTED UNDER FS | | | 471.003(2)H). | | | PLEASE SEE THE FOLLOWING COMMENT AS | | | PLANS MAY BE REQUIRED TO BE DONE BY A PE | | | AS VALUE MAY BE ADJUSTED. (IF $50K OR | | | MORE, THEN A PE WILL BE REQUIRED FOR | | | PLANS. | | | | | | 3)NOTE: PLEASE SEE FBC ADMINISTRATIVE | | | SECTION 108.3 WHICH REQUIRES VALUE BASED | | | ON COMPLETE SCOPE WORK TO INCLUDE ALL | | | LABOR AND MATERIALS, EVEN IF EQUIPMENT | | | IS OWNER SUPPLIED. | | | PLEASE SEE VALUE IS SHOWN AS THE SAME | | | FOR ALL THREE PERMITTED JOBS. | | | | | | 4)NOTE: PLEASE SUBMIT ALL MANUFACTURES | | | CUT/SPEC SHEETS FOR THE NEW GENERATOR, | | | ATS AND FUEL TANK. | | | 215.5 | | | | | | 5)NOTE: PLEASE PROVIDE MIN FUEL FOR ALL | | | LIFE SAFETY DEVICES. | | | PLEASE ALSO SEE FIRE REVIEW COMMENTS. | | | LS 101 7.8,7.9 ETC | | | | | | 6)NOTE: PLEASE SEE AN EQUIPMENT | | | GROUNDING CONDUCTOR IS BEING SHOWN | | | BETWEEN THE ATS AND THE MDP? | | | PLEASE SEE 20.6,250.24 AS "EQUIPMENT | | | GROUNDING CONDUCTORS" ARE ONLY INSTALLED | | | AFTER THE FIRST MEANS OF DISCONNECT. | | | | | | 7)NOTE: PLEASE DECLARE WHETHER OR NOT | | | THE GENERATOR WILL OR WILL NOT BE A | | | SEPARATEY DERVIED SYSTEM. PLEASE ADJUST | | | AS NEEDED. | | | 215.5 | | | | | | 8)NOTE: PLEASE SEE 445.13 FOR MIN SIZING | | | OF CONDUCTORS FROM GENERATOR TO ATS, | | | FIRST MEANS OF OCP. | | | 215.5, 240.4,310.16 | | | | | | 9)NOTE: PLEASE SEE NO OCP IS SHOWN AT | | | GENERATOR.? | | | 215.5 | | | | | | 10)NOTE: PLEASE SUBMIT PLANS INDICATION | | | LOCATION OF GENERATOR AT SITE. | | | PLEASW SHOW DETAIL OF WHERE BOLLARDS MAY | | | BE REQUIRED DEPENDING ON THE LOCATION OF | | | GENERATOR ETC. | | | | | | 11)NOTE: PLEASE SEE BLDG REVIEW ,AS NO | | | SLAB/FOOTER DETAILS WERE SUBMITTED. | | | | | | 12)NOTE: PLEASE SEE , RISER AS SHOWN MAY | | | REQUIRE A MAIN DISC ON THE LINE SIDE OF | | | ATS. | | | | | | | | | 13)NOTE: PLEASE SEE NO OCP IS INDICATED | | | FOR NEW FEED TO PANEL EM? | | | CAN NOT VERIFY FEEDERS ETC AT THIS TIME. | | | 215.5,310.16 | | | | | | ** PLEASE SEE COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION | | | FOR REVIEW. IF THERE ARE ANY | | | QUESTIONS,PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | PLANS SENT TO LUIS M. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2006-05-02 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-05-02 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-05-02 |
Time |
13:57 |
Sent To |
|
|
| Notes |
| 2006-05-02 00:00:00 | ******APPROVED****** | | | | | | 1) WORK SHALL COMPLY WITH NFPA 110, | | | STANDARD FOR EMERGENCY AND STANDBY POWER | | | SYSTEMS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-02-08 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-02-08 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-02-08 |
Time |
09:16 |
Sent To |
|
|
| Notes |
| 2006-02-08 00:00:00 | ******DENIED****** | | | | | | 1) PLEASE PROVIDE MANUFACTURER SPEC | | | SHEETS FOR GENERATOR AND ASSOCIATED FUEL | | | EQUIPMENT. | | | | | | 2) WORK TO COMPLY WITH NFPA 110. | | | | | | 3) PLEASE ILLUSTRATE LOCATION OF | | | GENERATOR IN RELATION TO BUILDING AND | | | PROPERTY LINES. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-04-29 |
Time |
12:56 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-04-29 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2006-04-29 00:00:00 | UNSAT | | | NO PLANS, CONTRACTOR TO SUBMITT PLANS AT | | | TIME OF PERMIT. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2006-02-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-02-13 |
Time |
07:21 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2006-02-13 |
Time |
07:21 |
Sent To |
|
|
| Notes |
| 2006-02-13 00:00:00 | DENIED; | | | 1. PERMIT APPLICATION WITH PLANS IS | | | REQUIRED FROM A LICENSED L.P. | | | CONTRACTOR. | | | 2. LOCATION OF TANK AND GENERATOR IS | | | REQUIRED. | | | 3. PLEASE PROVIDE MANUFACTURE'S SPEC. | | | SHEETS. | | | GAS PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-04-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-26 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-04-26 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2006-04-26 00:00:00 | WAITING FOR "COMM" BD | | | TO "COMM" BD#45 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-01-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-01-28 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-28 |
Time |
15:05 |
Sent To |
|
|
| Notes |
| 2006-01-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2006-01-22 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-01-22 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2006-01-22 00:00:00 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2006-05-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-05-01 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-05-01 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2006-05-01 00:00:00 | PROVISO: | | | ADDITIONAL PERMIT REQUIED FOR GAS. | | | PLEASE PROVIDE PIPE SIZING AND MATERIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-02-07 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-02-07 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2006-02-07 00:00:00 | DENIED: | | | 1.PLEASE PROVIDE MANUFACTURER | | | SUBMITTAL DATA FOR THE GENERATOR. | | | | | | 2.PLEASE PROVIDE SITE PLANS INDICATING | | | LOCATION OF THE GENERATOR.SHOW | | | DISTANCE FROM BUILDING STRUCTURE, | | | WINDOWS, DOORS, LOUVERS, ETC.PLEASE | | | INDICATE DISTANCE FROM PROPERTY LINES. | | | | | | 3.PERMIT APPLICATION INDICATES NATURAL | | | GAS BUT A SUBMITTAL FOR AN LP TANK IS | | | ALSO PROVIDED.WILL THIS BE A "DUEL | | | TYPE OF FUEL SORCE"?PLEASE CLARIFY. | | | | | | 4.ADDITIONAL PERMIT REQUIRED FOR GAS | | | INSTALLATION. | | | | | | 5.PLEASE PROVIDE DETAIL FOR THE | | | GENERATOR SLAB & ANCHORING OF THE | | | GENERATOR.SHOW COMPLIANCE WITH 2004 | | | FMC 301.13. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2006-04-29 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2006-04-29 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2006-04-29 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2006-02-13 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2006-02-13 |
Time |
07:20 |
Rev Time |
|
| Received By |
jleech |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2006-05-03 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-05-03 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-05-03 |
Time |
14:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-01-28 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2006-01-28 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2006-01-28 |
Time |
13:52 |
Sent To |
I |
|
| Notes |
| 2006-01-28 00:00:00 | DENIED, | | | 1. NEED TO SHOW THE LOCATION OF | | | GENERATOR ON TWO COPY OF SITEPLAN WITH | | | SETBACKS FROM PROPERTY LINE. | | | | | | MICHELLE MCLEAN | | | ZONING TECHNICIAN | | | 805-6720 |
|
|