Plan Review Details - Permit 06010702
Plan Review Stops For Permit 06010702
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-21 Cont ID  
Sent By amorse Date 2006-02-21 Time 11:26 Rev Time 0.75
Received By amorse Date 2006-02-21 Time 11:26 Sent To PC
Notes
2006-02-21 00:00:00 
  
 DENIED
  
 1) CONTRACTOR NAME DOES NOT APPEAR ON
 LICENCE NUMBER CGCA25810 WITH DBPR
  
 2) A SCHEDULE PER ATTACHED MEMO SHALL BE
 SUBMITTED WITH PERMIT APPLICATION C/W
 OPENING SIZES,UNIT#'S, SHUTTER SPANS,
 FASTENER CENTERS AND TYPE, ETC. ENCLOSED
 IS A SAMPLE OF SCUEDULE
  
 3) SHOW THE OPENING SIZES AND WINDOWS ON
 THE KEY PLAN THAT REQUIRE DETAIL 2 ON
 SHEET 1 AND DETAIL 2A ON SHEET 1
  
 4) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO A
 PERMIT BEING ISSUED
  
 5) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
  
 IS RELEVANT. THESE SHOULD INCLUDE THE
 FLORIDA STATE APPROVAL COVER PAGES, AND
 THE PRODUCT NOA THAT LISTS THE SYSTEM
 COMPONENTS/ FASTENER LIST PAGES, THE
 PAGES WITH THE CHOSEN ASSEMBLY/ SYSTEM
 TO BE USED AND THE GENERAL LIMITATIONS
 PAGE. ALL CAN BE FOUND ON
 WWW.FLORIDABUILDING.ORG
  
  
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-21 Cont ID  
Sent By amorse Date 2006-02-21 Time 11:26 Rev Time 0.00
Received By amorse Date 2006-01-22 Time 11:11 Sent To  
Notes
2006-01-22 00:00:00TO "MISC" BOX#1