Plan Review Details - Permit 06010581
Plan Review Stops For Permit 06010581
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-03-29 Cont ID  
Sent By alange Date 2006-03-29 Time 13:46 Rev Time 2.25
Received By alange Date 2006-03-29 Time 13:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-07 Cont ID  
Sent By alange Date 2006-03-07 Time 08:31 Rev Time 3.50
Received By alange Date 2006-03-07 Time 08:31 Sent To  
Notes
2006-03-07 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.CONSTRUCTION
 TYPE SHOWN IS TYPE SHOWN IS TYPE IV
 HEAVY TIMBER.BUILDING HEIGHT
 REFERENCES TABLE 500.TABLE 500 IS NOW
 TABLE 503 2004 FBC.
  
 4.K D WINOW MULLIONS ARE SUBMITTED
 WITH A PGT STATE PRODUCT APPROVAL.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 LINTELS ALL WINDOWS AND STORE FRONTS,
 AND TRANSOM WINDOWS, NO PRODUCT
 APPROVALS SUBMITTED FOR ANY WINDOWS..
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.SUBMIT TWO SETS OF TRUSS DRAWINGS
 FOR REVIEW PER 2004 FBC R-802.10.1
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-11-04 Cont ID  
Sent By dpalmer Date 2006-11-04 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2006-11-04 Time 15:43 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-22 Cont ID  
Sent By dpalmer Date 2006-10-22 Time 17:20 Rev Time 0.00
Received By dpalmer Date 2006-10-22 Time 17:11 Sent To PC
Notes
2006-10-22 17:14:58******* UNSAT **********
  
 1) NOTE: PLEASE CORRELATE RISER AND PANEL(S) SCHEDULE
 SUBMITTED. PLEASE SEE PANEL "A" IS SHOWN FEEDING PANEL
 "C", YET PANEL "C" IS SHOWN FROM PANEL ""B" ON
 SCHEDULE.??
  
 2) NOTE: PLEASE SEE LOAD CALCULATIONS FOR BOTH PANELS
 FOR A/C LOADS DO NOT CORRELATE. PLEASE ADJUST AND
 REVISE. PLEASE CORRELATE.
 220.31
  
 PLEASE SUBMIT TEH ABOVE INFORMATION FOR REVIEW.
 IF THERE ARE NAY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-18 Cont ID  
Sent By dpalmer Date 2006-03-18 Time 16:32 Rev Time 0.00
Received By dpalmer Date 2006-03-18 Time 15:55 Sent To M
Notes
2006-03-18 00:00:00************ PROVISO ***************
  
 1)NOTE: PLEASE CORRELATE ELECTRICAL AND
 MACHANICAL PLANS AND INSTALLATION.
 PLEASE SEE MECH PLANS INDICATE 5KW FOR
 AHU#1 AND 10KW FOR AHU#2, YET ELECTRICAL
 PLANS INDICATE 7.5 KW FOR EACH OF THESE.
 PLEASE KNOW, EVEN IF UNITS ARE 7.5 KW,
 THE 60A OCP IS TOO HIGH.
 PLEASE KNOW, THESE HAVE CHANGED SINCE
 PREVIOUS REVIEW.
 PLEASE VERIFY AND CORRELATE OCP, AWG AND
 KW RATINGS AND REVISE.
  
 **************************************
 PLEASE SUBMIT THE ABOVE ALONG WITH ANY
 OTHER REVISIONS BEFORE ROUGH ELETRICAL
 INSPECTION.
 PLEASE KNOW, IF PLANS COME BACK FOR ANY
 OTHER COMMENTS, PLEASE REVISE AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 REDLINED 210.70 FOR FOYER LT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-24 Cont ID  
Sent By dpalmer Date 2006-01-24 Time 08:56 Rev Time 0.00
Received By dpalmer Date 2006-01-24 Time 07:45 Sent To M
Notes
2006-01-24 00:00:00********* UNSAT **********
  
 1)NOTE: PLEASE CORRELATE RISER DIAGRAM
 FOR POOL PANEL WITH POOL PANEL SCHEDULE.
 PLEASE SEE RISER INDICATES 100A OCP, AND
 FEEDERS FOR 100A ALSO, HOWEVER PLEASE
 SEE PANEL "B" SHOWS FEED AT 60A'S, AND
 POOL PANEL IS SHOWN AS 60A'S?
 215.5
  
 2)NOTE: PLEASE SEE POOL PANEL SHOWS A
 "GAS" POOL HEATER, AND SHOWS A 4KW
 LOAD AND SHOWN AT 125% WHICH IS SHOWN TO
 5KW? IF THIS A "GAS " POOL HEATER THEN
 LOADS WOULD NOT BE AS SHOWN.
 PLEASE KNOW, ONLY ELECTRICAL TYPE POOL
 HEATERS (HEAT PUMPS) ARE REQUIRED TO
 HAVE OCPAND LOADS FIGURED AT125%. IF
 THIS IS GAS THEN THE LOADSSHOULD BE
 ADJUSTED. THIS WOULD ALSO AFFECT HOW
 LARGE THE POOL PANEL WOULD NEED TO BE.
 PLEASE SEE NOTE #1
 215.5
  
 3)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PLEASE SEE 2002 NEC 210.12
 WHICH REQUIRES ARC FAULT PROTECTION FOR
 ALL "OUTLETS" IN BEDRMS. LTS, SD'S,
 RECEPTS, FANS ETC.
  
 4)NOTE: PLEASE SEE RISER INDICATES
 OUTDOOR MCB PANELS , HOWEVER NO PANEL
 SCHEDULES FOR THESE WERE SUBMITTED.??
 PLEASE SUBMIT.
  
 5)NOTE: PLEASE SEE RISER DIAGRAM WHICH
 SHOWS POOL PANEL BEING FED FROM THE NEW
 OUTDOOR MCB PANELS, HOWEVER PLEASE SEE
 PANEL "B" FOR INDOOR GARAGE PANEL WHICH
 SHOWS POOL PANEL BEING FED FROM THIS
 LOCATION??PLEASE CORRELATE.
  
 6)NOTE: PLEASE SEE PLANS ONLY INDICATE
 ONE DISCONECT LCOATED OUTSIDE NEXT TO
 METER, WHEREAS RISER SHOWS TWO PANELS.
 PLEASE ADJUST AND CORRELATE.
  
 7)NOTE: PLEASE VERIFY THE ATTACHMENT
 LOCATION OF THE GROUNDING ELECTRODE
 CONDUCTOR. THIS IS SHOWN COMING FROM THE
 ONE MAIN BRKR PANEL. PLEASE CLARIFY HOW
 THIS IS CONNECTED FOR THE GROUNDING
 ELECTRODE SYSTEM AS THERE ARE TWO MCB
 PANELS? PLEASE SEE 250.24,250.6 ETC.
 PLEASE SEE METER IS THE TYPICAL
 ATTACHMENT POINT.
  
 8)NOTE: PLEASE SEE MISSING RECEPT FOR 2'
 OF WALL IN KITCHEN.210.52
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO SETS
 FOR REVIEW AND STAMPING. ONE COPY OF OLD
 SHEETS SHOULD BE SUBMITTED FOR REFERENCE
 ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW .IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-06 Cont ID  
Sent By adarroug Date 2007-03-06 Time 16:42 Rev Time 0.00
Received By adarroug Date 2007-03-06 Time 16:42 Sent To P
Notes
2007-03-06 16:43:09TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-02 Cont ID  
Sent By adarroug Date 2006-11-02 Time 10:01 Rev Time 0.00
Received By adarroug Date 2006-11-02 Time 10:01 Sent To E
Notes
2006-11-02 10:02:09TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-20 Cont ID  
Sent By adarroug Date 2006-10-20 Time 15:42 Rev Time 0.00
Received By adarroug Date 2006-10-20 Time 15:42 Sent To E
Notes
2006-10-20 15:43:29TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 15:29 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 15:29 Sent To E
Notes
2006-03-17 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-07 Cont ID  
Sent By alange Date 2006-03-07 Time 08:48 Rev Time 0.00
Received By alange Date 2006-01-17 Time 18:45 Sent To  
Notes
2006-01-17 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-03-20 Cont ID  
Sent By tgordon Date 2006-03-20 Time 12:15 Rev Time 0.30
Received By tgordon Date 2006-03-20 Time 12:15 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-25 Cont ID  
Sent By tgordon Date 2006-01-25 Time 12:10 Rev Time 0.30
Received By tgordon Date 2006-01-25 Time 12:10 Sent To P
Notes
2006-01-25 00:00:00 
 *** DENIED ***
 1) THE MECHANICAL PLANS NEED THE
 MECHANICAL COMPANY'S NAME, ADDRESS,
 PHONE NO.,LICENES NUMBER, NAME OF PERSON
 WHO DID THE A/C DESIGN AND THEIR
 SIGNATURE ON THEM.
 2) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2007-03-21 Cont ID  
Sent By jleech Date 2007-03-21 Time 10:07 Rev Time 0.00
Received By jleech Date 2007-03-21 Time 10:07 Sent To  
Notes
2007-03-21 10:07:51REVISED RISER DIAGRAM OK

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-01-26 Cont ID  
Sent By jleech Date 2006-01-26 Time 07:28 Rev Time 0.33
Received By jleech Date 2006-01-26 Time 07:27 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By mmclean Date 2006-01-20 Time 19:34 Rev Time 0.00
Received By mmclean Date 2006-01-20 Time 19:34 Sent To E
Notes
***NONE***