Plan Review Details - Permit 06010504
Plan Review Stops For Permit 06010504
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-05-11 Cont ID  
Sent By amorse Date 2006-05-11 Time 15:26 Rev Time 0.00
Received By amorse Date 2006-05-11 Time 15:26 Sent To  
Notes
2006-05-11 00:00:00 
  
 DENIED
  
 1) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC* PERMIT VALUE WILL BE ADJUSTED
 ACCORDINGLY
  
 2) WIND DESIGN INFORMATION SHT A3 SHALL
 USE ASCE 7-02 STANDARD FROM 2004 FBC
 ALSO DRAWING SPECIFIES EXP. C AND THE
 COMPONENT AND CLADDING SHT IS USING 2001
 CODE WITH EXP. B PLEASE CLARIFY
  
 3) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 4) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
  
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 5) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 6) PRODUCT APPROVAL FOR SINGLE HUNG
 WINDOWS DO NOT STATE DESIGN PRESSURES.
 THESE ARE REQUIRED FOR PRODUCT
 COMPLIANCE, PLEASE PROVIDE MANUFACTURERS
  
 SPECIFICATIONS FOR DESIGN PRESSURES ON
 THIS PRODUCT. ALSO SUPPLY THE SIZE OF
 THE MANUFACTURERS SH DESIGNATIONS (SH23,
 SH24, SH25, AND SH35)
  
 7) MIN. FOOTING DEPTH BELOW GRADE IS 12"
 PER 1805.2 FBC, DETAIL K/8 ON A8 SHOW
 10" ALSO FOUNDATION SCHEDULE FOR TYPE 1
 FOUNDATION DOES NOT MATCH SIZE ON DETAIL
 K/8 ON A8 PLEASE CLARIFY
  
 8) SECTION L/8 ON A8 HAS TWO DIFFERENT
 CEILING HEIGHTS PLEASE CLARIFY
  
 9) SEE PLACEMENT OF ATTIC ACCESS ON A5
 THIS LOCATION WILL NOT PROVIDEREQUIRED
 30" CLEARANCE ABOVE
  
 10) ATTIC ACCESS DETAIL D/3 ONA3 DOES
 NOT MEET THE MIN. WIDTH REQUIREMENT OF
 20"
  
 11) PROVIDE BEAM/LINTEL SCHEDULE WITH
 LENGTHS THAT MEET THE 4" MIN. BEARING
 PER 2104.1.5
  
 12) PROVIDE DRAINAGE PLAN (SHOW DRAINAGE
 ON SITE OR LANDSCAPE PLAN)
  
 13) ENERGY CALC'S SHALL BE SIGNED BY
 OWNER/AGENT
  
 14) FEE SIMPLE TOWNHOUSES REQUIRE
 SEPERATE PROPERTY CONTROL NUMBERS
  
 15) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-17 Cont ID  
Sent By dpalmer Date 2006-03-17 Time 13:09 Rev Time 0.00
Received By dpalmer Date 2006-03-17 Time 12:14 Sent To  
Notes
2006-03-17 00:00:00***********UNSAT ***********
  
 1)NOTE: PLEASE SEE ALL CURRENT CODES
 SHALL BE REFERENCED.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72 AT A MIN.
  
 2)NOTE: PLEASE SEE VALUATION FOR THIS
 PROJECT IS WAY TOO LOW. THE $210K ON
 APPLICAION IF NOT ADJUSTED CORRECTLY BY
 THE CONTRACTOR, SHALL BE ADJUSTED BY
 THIS OFFICE BASED ON THE TABLES ADOTED
 INTO THE 2004 FBC.
 108.3
  
 3)NOTE: PLEASE SEE PLANS AND ELECTRICAL
 SERVICES ARE INDICATING THESE AS
 "TOWNHOMES" , WHICH AS DEFINED UNDER THE
 FBC , NEC THESE ARE NOT. PLEASE KNOW, IF
 INDEED FEE SIMPLE TH, EACH UNIT WOULD
 HAVETHEIR OWN PCN, EACH UNIT WOULD
 HAVE ITS OWN PERMIT APPLICATION ETC.
 PLEASE SEE BLDG REVIEW NOTES.
 PLEASE ALSO SEE FURTHER ELECTRICAL
 COMMENTS FOR SERVICE.
  
 4)NOTE: PLEASE INDICATE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE
 SUBMITTED PANEL SCHEDULE.(S) UNIT PANEL
 SCHEDULE(S) CNA BE TYPICAL AS EACH FLOOR
 LAYOUT APPEARS TO BE THE SAME.
 215.5
  
 5)NOTE: PLEASE SEE SOME MISSING RECEPTS
 PER 210.52
  
 6)NOTE: PLEASE SEE THERE CAN ONLY BE ONE
 ELECTRICAL SERVICE. 230.2, ALL MAINS TO
 BE GROUPED. 230.72, SIZING OF SEC'S, GE
 SYSTEMS ETC SHALL BE BASED ON
 240.4,250.66,310.16 ETC.
  
 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW SERVICE. 110.9, 215.5
  
 8)NOTE: PLEASE SEE BEDRMS WHICH INDICATE
 THE EGRESS LIGHTING AS A FUTURE FAN/LT.
 PLEASE KNOW, EITHER A SWITCHED RECEPT
 MUST BE INSTALLED, OR A LIGHTING FIXTURE
 OF SOME SORT WILL BE REQUIRED.
 LS101 7.8, 210.70
  
 9)NOTE: PLEASE CORRELATE KW RATING OF
 CU'S ON ELECTRICAL PLANS WITH MECHANICAL
 PLANS. ONE SHOWS 4.5 AND THE OTHER 7.5.
 PLEASE ALSO VERIFY THE 60A OCP FOR AHU
 AS SHOWN, THIS SEEMS A LITTLE HIGHER
 THAN NORMAL.
 424.3,215.5 ETC
  
 10)NOTE: PLEASE SEE 210.11C, 220.16 FOR
 MIN VA FOR WASHER/AND LAUNDRY CIRCUIT
 REQUIRED. 210.52F
  
 PLEASE BE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE BE SURE TO SEE ANY COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELETCRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2006-05-23 Cont ID  
Sent By   Date 2006-05-23 Time   Rev Time 0.50
Received By   Date 2006-05-23 Time   Sent To  
Notes
2006-05-23 00:00:00DRAINAGE PLANS, PRE-AND POST DEVELOPMENT
 DRAINAGE CALCULATIONS REQUIRED.CIVIL
 PLANS NOT SUBMITTED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-05-10 Cont ID  
Sent By mwennerg Date 2006-05-10 Time 15:20 Rev Time 0.00
Received By mwennerg Date 2006-05-10 Time 15:20 Sent To  
Notes
2006-05-10 00:00:00******DENIED******
  
 1) STAIRS SHALL COMPLY WITH APPLICABLE
 BUILDING CODES AND NFPA 101, 2003
 EDITION SECTION 7.2.2.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED FOR EACH UNIT, AND MUST BE
 MOUNTED AT TIME OF FIRE FINAL
 INSPECTION.
  
 3) ADDRESSES ARE REQUIRED FOR BUILDING,
 AND SHALL MEET THE RESIDENTIAL
 REQUIREMENT OF MINIMUM 3" IN HEIGHT AND
 CONTRASTING TO BACKGROUND.
  
 4) SMOKE DETECTORS TO BE PLACED A
 MINIMUM OF (3)' FROM HVAC DIFFUSERS.
  
 5) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-23 Cont ID  
Sent By lmartine Date 2006-05-23 Time 13:05 Rev Time 0.00
Received By lmartine Date 2006-02-07 Time 16:14 Sent To  
Notes
2006-03-06 00:00:00TO "COMM" BD#64
2006-02-07 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-03-28 Cont ID  
Sent By hmoser Date 2006-03-28 Time 07:50 Rev Time 0.00
Received By hmoser Date 2006-03-28 Time 07:50 Sent To  
Notes
2006-03-28 00:00:00PLAN DENIED
 1)PLEASE REFER TO SECTION 501.4EXHAUST
 DUCTS AND SECTION 504.6 DRYER DUCT 2004
 FBC(M).
 2) PLEASE REFER TO SECTION 602.2.1
 METERIALS EXPOSED WITHIN PLENUMS.A/C
 CLOSIT DOOR MUST BE NONCOMBUSTIBLE.
 3) PLEASE REFER TO SECTION 307.2.3
 AUXILIARY AND SECONDARY DDAIN SYSTEM
 2004 FBC(M)
 4) PLEASE PROVIDE MORE INFORMATION ON
 PLANS.WHAT WALLS ARE RATEDNO WALL TAGS,
 ARE FLOOR RATED IF SO WHAT IS UL
 LISTING.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-01 Cont ID  
Sent By pschmitz Date 2006-04-01 Time 09:22 Rev Time 0.00
Received By pschmitz Date 2006-04-01 Time 09:22 Sent To  
Notes
2006-04-01 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
 1) SHT A2
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED
 PRESSURE CAUSED BY THERMAL EXPANSION
 SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND
 607.3.2.
 2) SHT A2
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICIAL. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE BUILDING OFFICIAL
 (SEE ALSO SECTION 106.3.5).
 PROVIDE A DETAIL OF THE SHELF FOR THE
 WATER HEATER OVER THE CLOTHES DRYER.
  
 3) SEC 608 PROTECTION OF WATER SUPPLY.
 PROVIDE INFORMATION: WATER SUPPLY TO
 EACH UNIT, ONE METER FOR ALL UNITS,
 REQUIRE A BACK FLOW PREVENTER AT THE
 METER. LOCAL ORDINANCE #2853-95
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-13 Cont ID  
Sent By mmclean Date 2006-04-06 Time 15:22 Rev Time 0.00
Received By mmclean Date 2006-04-06 Time 15:22 Sent To  
Notes
2006-04-12 00:00:004/12/06 FEE SIMPLE.
  
 DENIED,
 1. MUST PROVIDE TWO SETS OF LANDSCAPE
 PLANS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
2006-04-07 00:00:004/7/06 PLANS ARE LOCATED ON THE 5TH
 FLOOR WITH SHIRLEY & GRACE, CRA FOR A
 MEETING WITH OWNER/CONTRACTOR 4/10/06 AT
 8:30AM.
 4/12/06 PLANS RETURNED TO COMM BOARD #
 64