Plan Review Details - Permit 06010448
Plan Review Stops For Permit 06010448
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-06-15 Cont ID  
Sent By alange Date 2006-06-15 Time 11:48 Rev Time 2.00
Received By alange Date 2006-06-15 Time 11:48 Sent To  
Notes
2006-06-15 00:00:00REVIEWED AND STAMPED AND ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-05-16 Cont ID  
Sent By alange Date 2006-05-16 Time 13:34 Rev Time 0.75
Received By alange Date 2006-05-16 Time 13:34 Sent To  
Notes
2006-05-16 00:00:00DENIED
  
 2.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-03-30 Cont ID  
Sent By alange Date 2006-03-30 Time 13:53 Rev Time 1.50
Received By alange Date 2006-03-30 Time 13:53 Sent To  
Notes
2006-03-30 00:00:00DENIED
  
 2.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 5.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
 SHOW BUILDING CONSTRUCTION TYPE AND
 CHANGE CODE SECTIONS TO REFLECT THE 2004
 FBC.SEE S-3
  
 NEW COMMENT:BE SURE TO SEE NEW
 ELECTRICAL NOTE #2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-13 Cont ID  
Sent By alange Date 2006-02-13 Time 09:55 Rev Time 3.00
Received By alange Date 2006-02-13 Time 08:47 Sent To  
Notes
2006-02-13 00:00:00DENIED
  
 1.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUATION HAS BEEN REVISED TO
 $142,651.00.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 2.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 3.SUBMIT PRODUCT APPROVALS FOR LINTELS
 AND STRAPS AND TIE-DOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 ** PLEASE DO NOT ATTACH PRODUCT
 APPROVALS TO PLANS**
  
 4.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
 SHOW BUILDING CONSTRUCTION TYPE AND
 CHANGE CODE SECTIONS TO REFLECT THE 2004
 FBC.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 17:17 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 17:10 Sent To M
Notes
2006-05-14 00:00:00PLANS REDLINED,
  
 SD'S ARE BEING SHOWN ON CIRCUIT A-2, IF
 ON THIS CIRCUIT THEN AFCI PROTECTION
 WILL BE REQUIRED.2002 210.12B
 PANEL SCHEDULE DOES NOT INDICATE AFCI
 PROTECTION FOR A-2
 ** THE SD'S SHOULD BE ON ONE OF THE
 BEDRM CIRCUITS, MAY REVISE LATER.
 PLANS STAMPED AND PASSED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-03-17 Cont ID  
Sent By dpalmer Date 2006-03-17 Time 19:42 Rev Time 0.00
Received By dpalmer Date 2006-03-17 Time 19:38 Sent To M
Notes
2006-03-17 00:00:00******* UNSAT 2ND REVIEW ********
  
 ** PLEASE SEE SOME NOTES FROM FIRST
 REVIEW AND SOME NEW NOTES DUE TO PLANS
 SUBMITTED.
 NOTE BELOW ARE TAKEN DIRACTLY FROM FIRST
 REVIEW NOTES.
  
  
 1)NOTE:NOTE #1 OK.
  
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE:NOTE #3 OK, SEE NEW NOTES.
  
 4)NOTE:NOTE #4 OK, HOWEVER SEE NEW
 NOTE.
  
  
 5)NOTE: NOTE # 5 OK. HOWEVER SEE NEW
 NOTE.
  
 6)NOTE: NOTE #6 OK, HOWEVER SEE NEW
 NOTE.
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE SD'S ARE NOW BEING
 SHOWN ON MORE THAN ONE CIRCUIT WHICH IS
 NOT POSSIBLE SINCE ALL SD'S ARE REQUIRED
 TO BE WIRED "INLINE" PER NFPA-72
 11.5.1.1. PLEASE ADJUST.
  
 2)NOTE: PLEASE SEE ALL HAND DRAWN
 CHANGES ON SIGNED, DATED AND SEALED
 PLANS BY AN ENGINEER IS NOT PERMITTED
 PER FS 471.025. PLEASE KNOW IT IS
 PERMITTED FOR THE ENGINEER TO MAKE
 CHNAGES, HOWEVER EACH INDIVIDUAL CHANGE
 WOULD REQUIRE EACH AND EVERY ITEM TO BE
 SIGNED, AND DATED. PLEASE KNOW, WITH AS
 MANY CHANGES AS NOTED, THIS WOULD LEAVE
 PLANS WITH THE GREAT POSSIBILITY OF WHAT
 IS NEW OR OLD, CLEAR OR UNCLEAR ETC
 PLEASE SEE FBC ADMINISTRATIVE SECTION AS
 ADOPTED BY THE CITY OF WEST PALM BEACH
 106.1.3 WHICH REQUIRES PLANS TO BE CLEAR
 AND CONCISE, CLARITY ETC. PLEASE MAKE
 ALL NEEDED PLANS IN COMPUTER, RE-PRINT
 AND , SIGN, DATE AND SEAL PLANS.
  
 3)NOTE: PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONLY ONE COPY OF THE
 REMOVED OLD/VOIDED SHEET S FOR
 REFERENCE.
  
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE ON CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 22:51 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 22:51 Sent To M
Notes
2006-01-20 00:00:00******** UNSAT ************
  
 1)NOTE: PLEASE SEE MISSING FIRM LICENSE
 NUMBER ON TITLE BLOCK FOR ARCHITECTUAL
 FIRM. FAC 61G1-16.004, FS 481.219
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEEELECTRICAL PLANS ARE
 SIGNED , DATED AND SEALED BY AN
 ELECTRICAL ENGINEER, HOWEVER PLANS DO
 NOT CONTAIN ANY TITLE BLOCK FOR SAID
 ENGINEER OF RECORD AS REQUIRED PER FAC
 61G15-23.002, FS 471.023
  
 3)NOTE: PLEASE VERIFY THE 1/2" CONDUIT
 SHOWN FOR FUTURE PHONE. IT IS KNOWN TO
 THIS OFFICE THE TELEPHONE COMPANY AND
 CABLE COMPANY REQUIRES A MIN OF 3/4"
 CONDUIT FOR UNDERGROUND INSTALLATIONS.
 THIS IS FOR INFORMATIONAL PURPOSE ONLY
 AS THIS IS NOT AN NEC REQUIREMENT.
  
 4)NOTE: PLEASE CORRELATE LOAD FOR RANGE
 IN LOAD CALCS WITH LOAD ON PANEL
 SCHEDULE.
 PLEASE VERIFY IF INDEED A 40A BRKR WILL
 BE USED AS MOST RANGES REQUIRE A MIN OF
 50A. (RANGE RECEPT IS 50A)
 PLEASE ALSO VERIFY WIRING METHODS TO BE
 USED. PLANS INDICATE CONDUIT AND WIRING,
 HOWEVER IF ROMEX IS USED, THE #8 SHOWN
 WOULD BE REQUIRED TO BE INCREASED TO #6.
 SEE 310.16, 60 DEGREE COL.
 215.5
  
 5)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS IN THE PANEL
 SCHEDULE PROVIDE. IT IS KNOWN THAT NOTE
 #7 ON PLANS MENTIONS TO PROVIDE ARC
 FAULT BRKRS FOR ALL BEDRMS, HOWEVER
 PLEASE SEE 2002 NEC 210.12 WHICH
 REQUIRES ALL "OUTLETS" IN BEDRMS TO BE
 AFCI PROTECTED. THIS INCLUDES SD'S,
 HOWEVER SD'S ARE SHOWN BEING WIRED TO
 FAMILY RM RECEPTS. THIS IS OK, HOWEVER
 THEN THIS CIRCUIT WOULD ALSO BE REQUIRED
 TO BE ARC FAULT, THUS NOTE #7 WOULD NOT
 REFERENCE.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES LANSCAPE LTS, HOWEVER PLANS DO
 NOT SHOW ANY. PLEASE KNOW, IF NONE SHOWN
 ON PLANS, THEN LANDSCAPE LIGHTING WILL
 BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT, WHICH WILL INCLUDE PERMIT, PLANS
 AND FEE.
  
 ** PLEASE VERIFY WIRING METHOD, AS PLANS
 INDICATE CONDUIT AND WIRING FOR ALL
 CIRCUITS. IF SHOWN , ROMEX WOULD NOT BE
 PERMITTED.
 THIS IS ONLY A NOTE.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE ON CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-05 Cont ID  
Sent By adarroug Date 2006-06-05 Time 08:55 Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 08:55 Sent To B
Notes
2006-06-05 00:00:00TO "ALANGE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 16:35 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 16:35 Sent To E
Notes
2006-05-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-04 Cont ID  
Sent By adarroug Date 2006-05-04 Time 14:19 Rev Time 0.00
Received By adarroug Date 2006-05-04 Time 14:19 Sent To Z
Notes
2006-05-04 00:00:00TO "Z" BOX/RESUB-NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-13 Cont ID  
Sent By adarroug Date 2006-03-13 Time 16:22 Rev Time 0.00
Received By adarroug Date 2006-03-13 Time 16:22 Sent To E
Notes
2006-03-13 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-13 Cont ID  
Sent By alange Date 2006-02-13 Time 09:55 Rev Time 0.00
Received By alange Date 2006-01-13 Time 14:29 Sent To  
Notes
2006-01-13 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-05-15 Cont ID  
Sent By tgordon Date 2006-05-15 Time 10:59 Rev Time 0.20
Received By tgordon Date 2006-05-15 Time 10:59 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-03-20 Cont ID  
Sent By tgordon Date 2006-03-20 Time 08:49 Rev Time 0.30
Received By tgordon Date 2006-03-20 Time 08:49 Sent To P
Notes
2006-03-20 00:00:00*** DENIED **
 1) ENERGY CALCULATIONS ARE CALLING FOR
 22,600 TOTAL BTU'S. MECHANICAL PLANS ARE
 CALLING FOR 2 1/2 TON A/C SYSTEM
 ESTIMATED 30,000 TOTAL BTU'S. THE PLANS
 CAN NOT CALL FOR MORE BTU'S. THAN THAN
 THE ENERGY CAL'S.
  
 2) PLEASE SHOW THE TOTAL BTU'S. ON THE
 MECHANICAL PLANS.
  
 3) PLEASE SHOW THE COPPER LINE SIZES ON
 THE MECHANICAL PLANS.
  
 4) PLEAS SHOW THE LOCATION OF THE
 CONDENSATE DRAIN LINE ON THE MECHANICAL
 PLANS.
  
 5) PLEASE SHOW THE LOCATION OF THE
 CONDENSER UNIT ON THE MECH. PLANS.
  
 6) PLEASE SHOW THE CLOTHES DRIER VENT
 LOCATION ON THE MECH. PLANS.
  
 7) PLEASE SHOW THE SIZE OF THE SUPPLY
 AIR DUCT (FLEX) FROM THE AHU TO THE
 MIXING BOX IN THE LIVING ROOM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-25 Cont ID  
Sent By tgordon Date 2006-01-25 Time 11:43 Rev Time 0.15
Received By tgordon Date 2006-01-25 Time 11:43 Sent To B
Notes
2006-01-25 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) NEED A/C CONTRACTOR'S LICENCE NUMBER,
 NAME, AND SIGNATURE ON MECHANICAL PLANS.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3)NEED JOB SITE ADDRESS ON MECHANICAL
 PLANS.
  
 4) SUPPLY AIR DUCTS FROM AHU TO MIXING
 BOXES ARE NOT SIZED.
  
 5) BEDROOM #1 RETURN AIR TRANSFER DUCT
 IS TO SMALL,SEE NOTE #6.
  
 6)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 7) MECHANICAL PLANS HAVE TO MUCH FLOOR
 PLAN INFOMATION ON THEM AND ARE
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-05-16 Cont ID  
Sent By jleech Date 2006-05-16 Time 07:02 Rev Time 0.00
Received By jleech Date 2006-05-16 Time 07:02 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-03-29 Cont ID  
Sent By jleech Date 2006-03-29 Time 14:18 Rev Time 0.00
Received By jleech Date 2006-03-29 Time 14:18 Sent To B
Notes
2006-03-29 00:00:00DENIED;
 SEE ELECTRICAL PLAN REVIEW "NEW NOTES
 #2".
 I RED LINED THE PLUMBING DRAWINGS TO
 HELP MAKE CORRECTIONS CLEAR. PLEASE MAKE
 CHANGES AND PRINT OUT A NEW "P" PAGE
 THANK YOU.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status   Date 2006-01-23 Cont ID  
Sent By jleech Date 2006-01-23 Time 12:51 Rev Time 0.33
Received By jleech Date 2006-01-23 Time 12:51 Sent To M
Notes
2006-01-23 00:00:00DENIED;
 1. SEE ELECTRICAL PLAN REVIEW COMMENT #
 1.
 2. WATER HAMMER ARRESTORS REQUIRED AT
 KITCHEN SINK.
 3. HOUSE VALVE REQUIRED ON WATER SEVICE.
 4. W/M REQUIRES A 3" DRAIN PER 2004
 PLUMBING CODE
 5. CODE BOOKS USED FBC-2004.
 6. REMOVE NOTE 26 FROM PLUMBING
 SPECIFICATIONS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-11 Cont ID  
Sent By mmclean Date 2006-05-11 Time 15:10 Rev Time 0.00
Received By mmclean Date 2006-05-11 Time 15:10 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By mmclean Date 2006-01-20 Time 19:32 Rev Time 0.00
Received By mmclean Date 2006-01-20 Time 19:32 Sent To E
Notes
2006-01-20 00:00:00NOTE:
 1.THE PORCH MUST SIT 25FT FROM THE FRONT
 SETBACK.
 2.ROOF OVERHANG PROJECTIONS SHALL NOT
 EXTEND FARTHER THAN THREE FEET INTO ANY
 SETBACK.