Plan Review Details - Permit 06010445
Plan Review Stops For Permit 06010445
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-06 Cont ID  
Sent By jgomez Date 2006-09-06 Time 18:00 Rev Time 2.00
Received By jgomez Date 2006-09-06 Time 17:45 Sent To  
Notes
2006-09-06 00:00:00BUILDING REVIEW PROVISO:
 1- PROVIDE COMPLETE AND CORRECT
 INFORMATION FOR STORM SHUTTERS UNDER A
 SEPARATE PERMIT AS AGREED ON WITH
 CONTRACTOR OVER THE PHONE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-28 Cont ID  
Sent By jgomez Date 2006-06-28 Time 10:52 Rev Time 2.50
Received By jgomez Date 2006-06-28 Time 10:52 Sent To  
Notes
2006-06-28 00:00:00PLAN BUILDING REVIEW 2ND CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK COPY OF PAID RECEIPT AND
 STAMPED PLANS.
  
 2- NOC IS EXPIRED AFTER 90 DAYS OF BEEN
 RECORDED IF WORK IS NOT COMMENCED. NEED
 RE-RECORDED NOC. SEE SEC. 713.13. 9(2)
 OF FLORIDA STATUTES.
  
 3- PROVIDE SPECS/SECTION/DETAILS FOR
 INSTALLATION OF DECORATIVE STORM
 SHUTTERS. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 4- PROVIDE PRODUCT APPROVAL FOR:
 A) SINGLE HUNG WINDOWS. DADE COUNTY NOA
 SUBMITTED IS EXPIRED AND IT DOESN'T
 MATCH THE NOA SUBMITTED TO OBTAIN THE
 FLORIDA PRODUCT APPROVAL. RESUBMIT.
 B) CONCRETE LINTELS. DADE COUNTY NOA
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL
 WAS NOT SUBMITTED IN THIS PACKAGE. BUT,
 NEED TO GET ANOTHER PRODUCT APPROVAL
 BECAUSE DADE COUNTY NOA IS EXPIRED
 ANYWAY.
 C) ALUMINUM SIDING. PRODUCT APPROVAL
 SUBMITTED IS FOR CEMENTITIOUS SIDING
 PRODUCTS, NOT ALUMINUM AS SPECIFIED ON
 PLANS. NEED SPECIFIED PRODUCT APPROVAL.
 D) ALL SIMPSON STRUCTURAL CONNECTORS
 AS SPECIFIED ON PLANS. PRODUCT APPROVALS
 SUBMITTED ARE FOR USP AND ONLY ONE WAS
 GOOD FOR THE USP HLPTA75 CONNECTOR. THE
 REST OF THE PRODUCT APPROVALS SUBMITTED
 WERE NOT SPECIFIED ON PLANS.
 E) ALUMINUM VENTS.
  
 5- DESIGNER OF RECORD TO APPROVE IN
 WRITTING ALL PRODUCT APPROVALS,
 INCLUDING THE STORM SHUTTERS AS REQUIRED
 BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
 TYPICALLY THIS IS DONE USING THE
 STANDARD REVIEW STAMP USED FOR SHOP
 DRAWINGS REVIEW.
  
 6- STORM SHUTTERS:
 A) PRODUCT APPROVAL SUBMITTED IS
 INCOMPLETE. IT DIDN'T INCLUDE THE DWGS.
 B) INSTALLATION SCHEDULE:
 * WHY THE DESIGN PRESSURES ARE N/A?.
 THIS IS THE MOST IMPORTANT INFORMATION
 TO VERIFY COMPLIANCE OF PRODUCT BASED ON
 THE CALCULATED DESIGN PRESSURES. NEED
 THIS INFORMATION. SEE PLANS.
 C) VERIFY SIZES FOR PANEL SPAN. EG:
 OPENINGS 12 AND 13. IF THE OPENINGS ARE
 5'X6'-8" HOW COME THE PANEL SPAN IS
 88"?. ALSO, THIS APPLIES TO 4' HIGH
 OPENINGS. WHY USING 68" LONG PANELS?.
  
 D) VERIFY STRUCTURE TO BE ATTACHED TO.
 THIS IS A CONCRETE BLOCK STRUCTURE, NOT
 POURED CONCRETE. REVISE AS REQUIRED.
  
 7- DRAWING A-1: A) PROVIDE COMPLETE
 DETAILS/SPECS FOR WOOD DECK OUTSIDE
 MASTER BEDROOM AND FOR WOOD STEPS AT
 REAR COVERED PORCH. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 AND R11.5.3.2.
 B) UPDATE CODE REFERENCE SPECIFIED FOR
 ATTIC ACCESS, FIREBLOCKING AND
 WINDOW/DOOR GLAZING PROTECTION. THIS
 IS A RESIDENCE THE CORRECT CODE THAT
 REGULATES DWELLINGS IS THE RESIDENTIAL
 2004 CODE, NOT THE FBC 2004. REVISE AS
 REQ'D AND CITE CORRECT CODE REFERENCE
 SECTIONS FROM THE RESIDENTIAL CODE.
  
 8- DRAWING SP-1: A) SURVEY DOESN'T MATCH
 PLANS. SEE PLANS FOR PORCH DIMENSIONS
 AND LOCATION.
 B) NORTH ARROW ORIENTATION ON SITE PLAN
 IS INCORRECT. SEE SURVEY FOR CORRECT
 ORIENTATION AND REVISE AS REQUIRED.
  
 9- DRAWING A-2: A) BEDROOM #1 WINDOW
 DOESN'T COMPLY WITH EGRESS SECTIONS
 R310.1.1 AND R310.1.2.BOTH WINDOWS IN
 FRONT ELEVATION ARE SHOWN AS 3'X4'
 WINDOWS. ACCORDING TO FLOOR PLAN WINDOW
 IS 3'X5'. CLARIFY/REVISE AS REQUIRED.
 B) LETTERS IDENTIFYING THE OPENINGS
 DON'T MATCH FLOOR PLAN. REVISE AS REQ'D.
 C) SPECIFY SIZE FOR MANUFACTURED
 ALUMINUM LOUVERS AT FRONT AND BACK
 ELEVATIONS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004 AND SECTION R806.
  
 10- DRAWING A-3: A) SECTION "A":
 * THERE IS NOT POURED CONCRETE ARCH.
 SEE ELEVATIONS STRUCTURAL DWGS. REVISE.
 ** WHERE IS DETAIL SHT 5?
  
 11- DRAWING A-4: A) WALL SECTION "A".
 SPECIFY FIREBLOCKING MATERIAL AND
 REVISE REFERENCE FOR FIREBLOCKING. SEE
 RESIDENTIAL 2004 FOR CORRECT CODE
 SECTION.
 B) WALL SECTION "B" DOESN'T MATCH
 STRUCTURAL DRAWINGS AND ELEVATIONS. SEE
 ROOF PORCH BEAM AND REVISE AS REQUIRED.
  
 12- DRAWING S-2: A) TYP. ONE STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. PROVIDE SPECIFIC
 INFORMATION. SECTION R806 2004.
 B) DETAIL H: USP RT24 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
  
 13- DRAWING S-3: A) REVISE TRUSS ANCHOR
 SCHEDULE. UPLIFT CAPACITY DOESN'T MATCH
 UPLIFT CAPACITY SHOWN ON CURRENT USP
 CATALOGUE. REVISE AS REQUIRED OR PROVIDE
 COMPLETE ENGINEERING PACKAGE SHOWING WHY
 CHANGING THE VALUES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 14- ENERGY CALCULATIONS:
 A) IF THIS IS A MODEL HOUSE. ENERGY
 CALCULATIONS NEED TO BE DONE FOR WORST
 CASE SCENARIO OR MUST BE SITE SPECIFIC
 WITH CORRECT HOUSE ORIENTATION.
 CALCULATIONS SUBMITTED ARE NOT FOR WORST
 CASE SCENARIO AND THEY DON'T MATCH THE
 ACTUAL ORIENTATION OF THE HOUSE. SEE
 SURVEY FOR CORRECT ORIENTATION. PROVIDE
 CALCULATIONS THAT COMPLY WITH EITHER
 WAY.
 B) OVERHANG LENGTH AND HEIGHT DON'T
 MATCH PLANS. SEE SECTION 13-601.2.A.3
 FOR PROPER WAY OF CALCULATING OVERHANG
 LENGTH AND HEIGHT. AND REVISE AS
 REQUIRED.
  
 15- ARCHITECT'S TITLE BLOCK TO INCLUDE
 ALL INFORMATION REQUIRED BY CHAPTER 481
 FLORIDA STATUTES AND 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE. SEE
 ATTACHED COPY.NEED NAME OF ARCHITECT
 SIGNING AND SEALING PLANS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By jgomez Date 2006-03-01 Time 17:00 Rev Time 3.00
Received By jgomez Date 2006-03-01 Time 17:00 Sent To  
Notes
2006-03-01 00:00:00BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 NEED PAID RECEIPT AND STAMPED DRAWINGS.
  
 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY
 SEC. R401.3 OF 2004 RESIDENTIAL CODE.
  
 3- PROVIDE STRUCTURAL BUCK DETAIL USING
 2X BUCK AS REQUIRED BY ENTRY DOORS
 PRODUCT APPROVAL SUBMITTED. SEE SEC.
 R613.6.2 OF 2004 RESIDENTIAL CODE.
  
 4- OWES $374.36 FOR UPDATED BUILDING
 VALUATION AND RADON FEES.
  
 5- PROVIDE SPECS/SECTION/DETAIL FOR
 INSTALLATION OF DECORATIVE STORM
 SHUTTERS. SECTION 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 6- DRAWINGS S-2 & S3 ARE MISSING THE
 ENGINEER INFO. CHAPTER 471 FL. ST.
  
 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR DOOR AND TRANSOM ABOVE
 SINGLE ASSEMBLY AS SHOWN ON PLANS FOR
 SLIDING GLASS DOORS AT FAMILY RM &
 FRENCH DOORS AT MASTER BEDROOM.
 OTHERWISE, PROVIDE COMPLETE INFORMATION
 FOR STRUCTURAL MULLIONAS REQUIRED BY
 SEC. R613.7 OF 2004 RESIDENTIAL CODE.
 B) SPECIFY SIZE OF FIXED WINDOW.
  
 8- ARCHITECT TO PROVIDE FIRM LICENSE
 NUMBER AS REQ'D BY CHAPTER 481 FLORIDA
 STATUTES & FLORIDA ADMINISTRATIVE CODE.
  
 9- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQ'D BY RULE 9B-72 FOR:
 A) FRENCH DOORS W/ TRANSOM ABOVE.
 SEE ITEM #7 ABOVE.
 B) SLIDING GLASS DOORS WITH TRANSOM
 ABOVE. SE ITEM #7 ABOVE.
 C) STRUCTURAL MULLIONS. SEE ITEM #7
 D) FIXED WINDOWS. SEE ITEM #7 ABOVE.
 E) ALL TRUSS CONNECTORS. SEE PLANS.
 F) SINGLE HUNG WINDOWS: FLORIDA
 PRODUCT APPROVAL AND DADE COUNTY NOA
 SUBMITTED DON'T MATCH. NEED TO PROVIDE
 THE EXACT SAME INFORMATION THAT WAS
 PROVIDED TO OBTAIN FLORIDA APPROVAL.
 INFORMATION SUBMITTED ARE FOR 2
 DIFFERENT MODEL TYPES. FL 3041 ISFOR
 MODEL TR-9100. DADE COUNTY NOA SUBMITTED
 IS FOR SERIES 2100 WINDOWS.
 G) ROOF SHINGLES. NEED TO PROVIDE THE
 EXACT SAME DADE COUNTY NOA THAT WAS
 SUBMITTED FOR FLORIDA APPROVAL. GO TO
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 CORRECT NOA.
 H) PRECAST LINTELS.
 I) ALUMINUM VENTS.
 J) ALUMINUM SIDING.
  
 10- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS PRIOR TO SUBMITTAL TO THIS
 OFFICE AS REQUIRED BY SEC. 106.3.3 OF
 CITY AMENDMENTS TO FBC 2004.
  
 11- ARCHITECTURAL DRAWING 1: UPDATE
 BUILDING CODE DATA INFORMATION. SEE 2004
 RESIDENTIAL BUILDING CODE.
  
 12- DRAWING A-1: A) PROVIDE COMPLETE
 DETAILS/SPECS FOR WOOD DECK OUTSIDE
 MASTER BEDROOM AND FOR WOOD STEPS AT
 REAR COVERED PORCH. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 B) SPECIFY SAFETY GLASS FOR WINDOW IN
 BATHROOM LOCATED BETWEEN BEDROOM #1 AND
 #2. SEC. R308.4 2004 RESIDENTIAL CODE.
 C) UPDATE CODE REFERENCE FOR ATTIC
 ACCES. SEE 2004 RESIDENTIAL CODE.
 D) UPDATE CODE REFERENCES SPECIFIED
 ON GENERAL NOTES AND SCHEDULE NOTES. SEE
 2004 RESIDENTIAL CODE. SEE PLANS.
  
 13- DRAWING A-2: A) DESIGN PRESSURES
 MARK DOESN'T MATCH MARK SHOWED ON DOORS
 AND WINDOWS OPENINGS. REVISE AS REQ'D.
 B) SPECIFY SIZE FOR MANUFACTURED
 ALUMINUM LOUVER AT FRONT AND BACK
 ELEVATIONS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 14- DRAWING A-3: A) WHERE IS DETAIL A-5?
 SEE COMMENTS IN PLANS ON SECTIONS A & B.
 B) SECTION "A": 1)PORCH SECTION CALLS
 FOR POURED CONCRETE ARCH. THERE IS NOT
 ARCH ON FRONT PORCH. REVISE AS REQUIRED.
 2) WHERE IS DETAIL SHT 5 SPECIFIED
 FOR WOOD COLUMN?
 3) SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION AT CONCEALED SPACES IN SOFFITS
 AND WALLS. SEC. R602.8 2004 RESIDENTIAL
 CODE. SEE COMMENTS IN PLANS.
  
 15- DRAWING A-4: A) WALL SECTION "A".
 UPDATE CODE REFERENCE SPECIFIED FOR
 FIREBLOCKING AND SPECIFY FIREBLOCKING
 MATERIAL. SEE 2004 RESIDENTIAL CODE.
 B) WALL SECTION "B". FOUNDATION
 DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 C) REVISE PORCH BEAM TO MATCH ELEVATION.
 IT IS NOT AN ARCHED BEAM.
  
 16- DRAWING S-1: A) ROOF FRAMING PLAN
 CALLS FOR CONNECTOR A3 BY REAR PORCH.
 THERE IS NOT CONNECTOR A3. SEE TRUSS
 ANCHOR SCHEDULE. REVISE AS REQUIRED.
 B) WHERE ARE DETAILS A, C AND E KEYED
 ON ROOF PLAN?. ALSO, WHERE IS DET SHT
 S-2.MAKE SURE ALL KEYED DETAIL AND
 PAGE MATCH SPECIFIC DETAIL AND PAGE. SEE
 COMMENTS ON PLAN.
  
 17- DRAWING S-2: A) TYP. 1 STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. R806 2004 RESIDENTIAL CODE.
 B) DETAIL D: 1)HOW IS 2"X6" SILL PLATE
 ATTACHED TO CONCRETE BEAM?.
 2) HOW IS 2"X6" "L" BRACE NAILED TO
 BOTTOM SILL?
 3) USP RT24 IS A WOOD TO WOOD
 CONNECTOR. NEED A WOOD TO MASONRY
 CONNECTOR TO ATTACH TO CONCRETE BEAM.
  
 18- DRAWING S-3: A) GENERAL NOTES.
 UPDATE ALL REFERENCE STANDARDS. SEE 2004
 RESIDENTIAL CODE & 2004 FBC FOR
 CORRESPONDING STANDARDS AND SPECIFIC
 EDITION. EG: ACI 318-02. SEE PLANS.
 B) UPDATE CODE SECTIONS REFERENCED
 FOR WIND LOADS, EMERGENCY EGRESS AND
 GLASS IMPACT PROTECTION. SEE PLANS.
 C) VENTILATION AND EGRESS ARE TWO
 DIFFERENT CODE ISSUES. CLEAR OPENING FOR
 EGRESS HAS NOTHING TO DO WITH CLEAR
 OPENING FOR VENTILATION. REVISE NOTE.
 D) TRUSS ANCHOR SCHEDULE: NUMBER OF
 NAILS AND UPLIFT LOADS SPECIFIED TO
 MATCH THOSE PUBLISHED BY THE
 MANUFACTURER IN RECENT CATALOGUE. IF
 DIFFERENT NUMBER AND UPLIFT CALCS ARE
 SPECIFIED, THEN PROVIDE COMPLETE
 ENGINEERING CALCULATIONS TO SHOW WHY
 NUMBER AND UPLIFT LOADS ARE CHANGED.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 E) DELETE ADDITION TO STRUCTURE NOTES.
 THIS IS NEW CONSTRUCTION AND THEY DON'T
 APPLY TO THIS JOB.
  
 19- SURVEY TO HAVE SURVEYOR'S ORIGINAL
 SIGNATURE, NOT COPY, AS REQUIRED BY
 CHAPTER 472 FLORIDA STATUTES.
  
 20- STORM SHUTTERS:
 A) PROVIDE KEY PLAN.
 B) PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE THAT
 COVERS ALL REQUIRED INFORMATION TO
 PERFORM BUILDING REVIEW AND PRODUCT
 COMPLIANCE WITH PROPOSED INSTALLATION.
  
 21- ENERGY CALCULATIONS: A) NEED ENERGY
 CALCULATIONS USING FORM 600A-2004.
 B) CONDITIONED FLOOR AREA DOENS'T
 MATCH AREA SHOWN ON PLANS. REVISE.
 C) BUILDING ORIENTATION, OVERHANG
 LENGTH, OVERHANG HEIGHT AND AREA DON;'T
 MATCH PLANS. SEE CHAPTER 13 OF FBC 2004
 FOR PROPER WAY OF CALCULATING THESE
 ITEMS. REVISE AS REQUIRED.
 D) OWNER TO DATE BOTTOM OF FORM.
  
 ***NOTE: PLEASE RETURN REVIEWED SET TO
 EXPEDITE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 18:39 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 18:25 Sent To M
Notes
2006-05-14 00:00:00** REDLINED PLANS,
  
 PLEASE SEESD'S ARE NOW SHOWN
 ON CIRCUIT #2 WHICH DOES NOT INDICATE
 ARC FAULT PROTECTION AS REQ'D UDNER 2002
 NEC 210.12B.
 SD'S CAN BE ON A-2, HOWEVER A AFCI TYOE
 BRKR WILL THEN BE REQUIRED.
  
 PLEASE SEE BATHS NOW SHOWN WITH ARC
 FAULT PROTECTION??

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 22:26 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 22:26 Sent To M
Notes
2006-01-20 00:00:00******** UNSAT ************
  
 1)NOTE: PLEASE SEE MISSING FIRM LICENSE
 NUMBER ON TITLE BLOCK FOR ARCHITECTUAL
 FIRM. FAC 61G1-16.004, FS 481.219
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEEELECTRICAL PLANS ARE
 SIGNED , DATED AND SEALED BY AN
 ELECTRICAL ENGINEER, HOWEVER PLANS DO
 NOT CONTAIN ANY TITLE BLOCK FOR SAID
 ENGINEER OF RECORD AS REQUIRED PER FAC
 61G15-23.002, FS 471.023
  
 3)NOTE: PLEASE VERIFY THE 1/2" CONDUIT
 SHOWN FOR FUTURE PHONE. IT IS KNOWN TO
 THIS OFFICE THE TELEPHONE COMPANY AND
 CABLE COMPANY REQUIRES A MIN OF 3/4"
 CONDUIT FOR UNDERGROUND INSTALLATIONS.
 THIS IS FOR INFORMATIONAL PURPOSE ONLY
 AS THIS IS NOT AN NEC REQUIREMENT.
  
 4)NOTE: PLEASE CORRELATE LOAD FOR RANGE
 IN LOAD CALCS WITH LOAD ON PANEL
 SCHEDULE.
 PLEASE VERIFY IF INDEED A 40A BRKR WILL
 BE USED AS MOST RANGES REQUIRE A MIN OF
 50A. (RANGE RECEPT IS 50A)
 PLEASE ALSO VERIFY WIRING METHODS TO BE
 USED. PLANS INDICATE CONDUIT AND WIRING,
 HOWEVER IF ROMEX IS USED, THE #8 SHOWN
 WOULD BE REQUIRED TO BE INCREASED TO #6.
 SEE 310.16, 60 DEGREE COL.
 215.5
  
 5)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS IN THE PANEL
 SCHEDULE PROVIDE. IT IS KNOWN THAT NOTE
 #7 ON PLANS MENTIONS TO PROVIDE ARC
 FAULT BRKRS FOR ALL BEDRMS, HOWEVER
 PLEASE SEE 2002 NEC 210.12 WHICH
 REQUIRES ALL "OUTLETS" IN BEDRMS TO BE
 AFCI PROTECTED. THIS INCLUDES SD'S,
 HOWEVER SD'S ARE SHOWN BEING WIRED TO
 MORE THAN ONE CIRCUIT AND SOME SD'S ARE
 SHOWN WITHOUT ANY CIRCUITS.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES LANSCAPE LTS, HOWEVER PLANS DO
 NOT SHOW ANY. PLEASE KNOW, IF NONE SHOWN
 ON PLANS, THEN LANDSCAPE LIGHTING WILL
 BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT, WHICH WILL INCLUDE PERMIT, PLANS
 AND FEE.
  
 ** PLEASE VERIFY WIRING METHOD, AS PLANS
 INDICATE CONDUIT AND WIRING FOR ALL
 CIRCUITS. IF SHOWN , ROMEX WOULD NOT BE
 PERMITTED.
 THIS IS ONLY A NOTE.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE ON CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 14:04 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 14:04 Sent To B
Notes
2006-09-05 00:00:00TO "JGOME" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 16:50 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 16:50 Sent To E
Notes
2006-05-11 00:00:00TO "DPALMER' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-04 Cont ID  
Sent By adarroug Date 2006-05-04 Time 14:30 Rev Time 0.00
Received By adarroug Date 2006-05-04 Time 14:30 Sent To Z
Notes
2006-05-04 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-01 Cont ID  
Sent By jgomez Date 2006-03-01 Time 17:04 Rev Time 0.00
Received By jgomez Date 2006-01-13 Time 14:22 Sent To  
Notes
2006-01-13 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By tgordon Date 2006-05-15 Time 09:49 Rev Time 0.20
Received By tgordon Date 2006-05-15 Time 09:49 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-25 Cont ID  
Sent By tgordon Date 2006-01-25 Time 11:10 Rev Time 0.30
Received By tgordon Date 2006-01-25 Time 11:10 Sent To B
Notes
2006-01-25 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) NEED A/C CONTRACTOR'S LICENCE NUMBER,
 NAME, AND SIGNATURE ON MECHANICAL PLANS.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3)NEED JOB SITE ADDRESS ON MECHANICAL
 PLANS.
  
 4) SUPPLY AIR DUCTS FROM AHU TO MIXING
 BOXES ARE NOT SIZED.
  
 5) RETURN AIR TRANSFER DUCT FROM BEDROOM
 #1 TO BEDROOM #2 IS NOT SIZED.
  
 7) MECHANICAL PLANS HAVE TO MUCH FLOOR
 PLAN INFOMATION ON THEM AND ARE
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-16 Cont ID  
Sent By jleech Date 2006-05-16 Time 10:20 Rev Time 0.00
Received By jleech Date 2006-05-16 Time 10:20 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-19 Cont ID  
Sent By jleech Date 2006-01-19 Time 07:22 Rev Time 0.33
Received By jleech Date 2006-01-19 Time 07:21 Sent To Z
Notes
2006-01-19 00:00:00DENIED;
 1.W/M DRAIN TO BE 3" PER FBC-2004
 PLUMBING SEC. 406.3.
 2.WATER RISER DIAGRAM; BUILDING SHUTOFF
 REQUIRED PLEASE SHOW. PLEASE SHOW
 WATERHAMMER ARRESTORS ON KIT. SINK.
 3.REMOVE NOTE 26 FROM PLUMBING
 SPECIFCATIONS. HOOKING IRRIGATION PUMP
 TO DOMESTIC WOULD COUSE A CROSS
 CONNECTION.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-11 Cont ID  
Sent By mmclean Date 2006-05-11 Time 15:01 Rev Time 0.00
Received By mmclean Date 2006-05-11 Time 15:01 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By mmclean Date 2006-01-20 Time 18:33 Rev Time 0.00
Received By mmclean Date 2006-01-20 Time 18:33 Sent To E
Notes
2006-01-20 00:00:00NOTE:
 1.THE PORCH MUST SIT 25FT FROM THE FRONT
 SETBACK.
 2.ROOF OVERHANG PROJECTIONS SHALL NOT
 EXTEND FARTHER THAN THREE FEET INTO ANY
 SETBACK.