Plan Review Details - Permit 06010436
Plan Review Stops For Permit 06010436
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-07 Cont ID  
Sent By jgomez Date 2006-09-07 Time 09:56 Rev Time 2.00
Received By jgomez Date 2006-09-07 Time 09:56 Sent To  
Notes
2006-09-07 00:00:00BUILDING REVIEW PROVISO:
 1- PROVIDE COMPLETE AND CORRECT
 INFORMATION FOR STORM SHUTTERS UNDER A
 SEPARATE PERMIT AS AGREED ON WITH
 CONTRACTOR OVER THE PHONE.
  
 2- DADE COUNTY NOA FOR ALUMINUM WINDOWS
 IS EXPIRED. PROVIDE CURRENT ONE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-29 Cont ID  
Sent By jgomez Date 2006-06-29 Time 19:28 Rev Time 2.00
Received By jgomez Date 2006-06-29 Time 19:28 Sent To  
Notes
2006-06-29 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK COPY OF PAID RECEIPT AND
 STAMPED PLANS.
  
 2- NOC IS EXPIRED AFTER 90 DAYS OF BEEN
 RECORDED IF WORK IS NOT COMMENCED. NEED
 RE-RECORDED NOC. SEE SEC. 713.13. 9(2)
 OF FLORIDA STATUTES.
  
 3- PROVIDE SPECS/SECTION/DETAILS FOR
 INSTALLATION OF DECORATIVE STORM
 SHUTTERS. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 4- PROVIDE PRODUCT APPROVAL FOR:
 A) SINGLE HUNG WINDOWS. DADE COUNTY NOA
 SUBMITTED IS EXPIRED AND IT DOESN'T
 MATCH THE NOA SUBMITTED TO OBTAIN THE
 FLORIDA PRODUCT APPROVAL. RESUBMIT. GO
 TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 CORRECT NOA.
 B) CONCRETE LINTELS. DADE COUNTY NOA
 SUBMITTED IS FOR 4", 6" & 12" LINTELS.
 NEED NOA FOR 8"X8" LINTELS AS SPECIFIED
 ON PLANS.
 ***NOTE: NOA FOR 8"X8" LINTELS IS
 EXPIRED. NEED TO PROVIDE CURRENT ONE.
 C) ALUMINUM SIDING. PRODUCT APPROVAL
 SUBMITTED IS FOR CEMENTITIOUS SIDING
 PRODUCTS, NOT ALUMINUM AS SPECIFIED ON
 PLANS. NEED SPECIFIED PRODUCT APPROVAL.
 D) ALL SIMPSON STRUCTURAL CONNECTORS
 AS SPECIFIED ON PLANS. PRODUCT APPROVALS
 SUBMITTED ARE FOR USP AND ONLY ONE WAS
 GOOD FOR THE USP HLPTA75 CONNECTOR. THE
 REST OF THE PRODUCT APPROVALS SUBMITTED
 WERE NOT SPECIFIED ON PLANS.
 E) ALUMINUM VENTS SHOWN ON ELEVATIONS.
 F) ASPHALT SHINGLES NOA THAT MATCHES
 NOA SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL. GO TO WWW.FLORIDABUILDING.ORG
 TO DOWNLOAD CORRECT NOA.
  
 5- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS, INCLUDING THE STORM SHUTTERS
 AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC.
 TYPICALLY THIS IS DONE USING THE
 STANDARD REVIEW STAMP USED FOR SHOP
 DRAWINGS REVIEW.
  
 6- STORM SHUTTERS:
 A) PRODUCT APPROVAL SUBMITTED IS
 INCOMPLETE. IT DIDN'T INCLUDE THE DWGS.
 B) INSTALLATION SCHEDULE:
 * WHY THE DESIGN PRESSURES ARE N/A?.
 THIS IS THE MOST IMPORTANT INFORMATION
 TO VERIFY COMPLIANCE OF PRODUCT BASED ON
 THE CALCULATED DESIGN PRESSURES. NEED
 THIS INFORMATION. SEE PLANS.
 C) VERIFY SIZES FOR PANEL SPAN. EG:
 OPENINGS 8 AND 9. IF THE OPENINGS ARE
 5'X6'-8" HOW COME THE PANEL SPAN IS
 88"?. ALSO, THIS APPLIES TO 4' HIGH
 OPENINGS. WHY USING 68" LONG PANELS?.
 D) VERIFY STRUCTURE TO BE ATTACHED TO.
 THIS IS A CONCRETE BLOCK STRUCTURE, NOT
 POURED CONCRETE. REVISE AS REQUIRED.
  
 7- DRAWING A-1: UPDATE CODE REFERENCE
 SPECIFIED FOR ATTIC ACCESS, FIREBLOCKING
 AND WINDOW/DOOR GLAZING PROTECTION. THIS
 IS A RESIDENCE THE CORRECT CODE THAT
 REGULATES DWELLINGS IS THE RESIDENTIAL
 2004 CODE, NOT THE FBC 2004. REVISE AS
 REQ'D AND CITE CORRECT CODE REFERENCE
 SECTIONS FROM THE RESIDENTIAL CODE.
  
 8- SHEET SP-1: REVISE NORTH ARROW
 ORIENTATION. SEE SURVEY FOR CORRECT
 ORIENTATION.
  
 9- DRAWING A-2: A) BEDROOM #1 WINDOW
 DOESN'T COMPLY WITH EGRESS SECTIONS
 R310.1.1 AND R310.1.2.BOTH WINDOWS IN
 FRONT ELEVATION ARE SHOWN AS 3'X4'
 WINDOWS. ACCORDING TO FLOOR PLAN WINDOW
 IS 3'X5'. CLARIFY/REVISE AS REQUIRED.
 B) WHAT ARE THE LETTERS IDENTIFYING THE
 OPENINGS FOR? THEY DON'T MATCH FLOOR
 PLAN AND THERE IS NOT LEGEND IDENTIFYING
 THIS LETTERS. CLARIFY AS REQUIRED.
 C) SPECIFY SIZE FOR MANUFACTURED
 ALUMINUM LOUVERS AT FRONT AND BACK
 ELEVATIONS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004 AND SECTION R806.
  
 10- DRAWING A-3: SECTION "A", WHERE IS
 DETAIL SHT 5?
  
 11- DRAWING A-4: WALL SECTION "A".
 SPECIFY FIREBLOCKING MATERIAL AND
 REVISE REFERENCE FOR FIREBLOCKING. SEE
 RESIDENTIAL 2004 FOR CORRECT CODE
 SECTION.
  
 12- DRAWING S-1: A) PROVIDE DETAIL/SPECS
 FOR 4"X4" WOOD POST AT REAR WOOD DECK.
 NEED TO SPECIFY ATTACHMENT OF WOOD POST
 TO FOOTING. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
 B) SPECIFY TRUSS CONNECTORS ON ROOF
 FRAMING PLAN. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 13- DRAWING S-2: A) TYP. ONE STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. PROVIDE SPECIFIC
 INFORMATION. SECTION R806 2004.
 B) DETAIL H: USP RT24 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
  
 14- DRAWING S-3: A) REVISE TRUSS ANCHOR
 SCHEDULE. UPLIFT CAPACITY DOESN'T MATCH
 UPLIFT CAPACITY SHOWN ON CURRENT USP
 CATALOGUE. REVISE AS REQUIRED OR PROVIDE
 COMPLETE ENGINEERING PACKAGE SHOWING WHY
 CHANGING THE VALUES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 15- ENERGY CALCULATIONS:
 A) IF THIS IS A MODEL HOUSE. ENERGY
 CALCULATIONS NEED TO BE DONE FOR WORST
 CASE SCENARIO OR MUST BE SITE SPECIFIC
 WITH CORRECT HOUSE ORIENTATION.
 CALCULATIONS SUBMITTED ARE NOT FOR WORST
 CASE SCENARIO.
 B) OVERHANG LENGTH AND HEIGHT DON'T
 MATCH PLANS. SEE SECTION 13-601.2.A.3
 FOR PROPER WAY OF CALCULATING OVERHANG
 LENGTH AND HEIGHT. AND REVISE AS
 REQUIRED.
  
 16- ARCHITECT'S TITLE BLOCK TO INCLUDE
 ALL INFORMATION REQUIRED BY CHAPTER 481
 FLORIDA STATUTES AND 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE. SEE
 ATTACHED COPY.NEED NAME OF ARCHITECT
 SIGNING AND SEALING PLANS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-01 Cont ID  
Sent By jgomez Date 2006-03-01 Time 17:14 Rev Time 0.00
Received By jgomez Date 2006-03-01 Time 17:14 Sent To  
Notes
2006-03-01 00:00:00BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 NEED PAID RECEIPT & STAMPED DRAWINGS.
  
 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY
 SEC. R401.3 2004 RESIDENTIAL CODE.
  
 3- PROVIDE STRUCTURAL BUCK DETAIL USING
 2X BUCK AS REQUIRED BY ENTRY DOORS
 PRODUCT APPROVAL SUBMITTED. ALSO, SEE
 SEC. R613.6.2 OF 2004 RESIDENTIAL CODE
 FOR PROPER BUCK INSTALLATION.
  
 4- OWES $296.42 FOR UPDATED BUILDING
 VALUATION AND RADON FEES.
  
 5- PROVIDE SPECS/SECTION/DETAILS FOR
 DECORATIVE STORM SHUTTERS INSTALLATION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 6- DRAWINGS S-1, S-2 AND S-3 ARE MISSING
 THE ENGINEER'S INFO. CHAPTER 471 FL. ST.
  
 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR FRENCH DOOR WITH TRANSOM
 ABOVE SINGLE ASSEMBLY UNIT AS SHOWN ON
 PLANS IN REAR ELEVATION. OTHERWISE,
 PROVIDE COMPLETE INFORMATION FOR
 STRUCTURAL MULLION AS REQ'D BY SEC.
 R613.7 2004 RESIDENTIAL CODE.
 B) SPECIFY SIZE OF FIXED WINDOW.
  
 8- ARCHITECT TO PROVIDE FIRM LICENSE
 NUMBER AS REQ'D BY CHAPTER 481 FL. ST.
 AND FLORIDA ADMINISTRATIVE CODE.
  
 9- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72 FOR:
 A) FRENCH DOORS WITH W/ TRANSOM
 ABOVE. SEE ITEM #7 ABOVE.
 B) STRUCTURAL MULLIONS. SEE ITEM #7.
 C) FIXED WINDOWS.
 D) ALL TRUSS CONNECTORS. SEE PLANS.
 E) SINGLE HUNG WINDOWS. PROVIDE SAME
 DADE COUNTY NOA THAT WAS SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
 F) ROOF SHINGLES. PROVIDE SAME DADE
 COUNTY NOA THAT WAS SUBMITTED FOR
 FLORIDA PRODUCT APPROVAL.
 G) PRECAST LINTELS.
 H) ALUMINUM VENTS.
 I) ALUMINUM SIDING.
  
 10- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS PRIOR TO SUBMITTAL TO THIS
 OFFICE AS REQUIRED BY SEC. 106.3.3 OF
 CITY AMENDMENTS TO FBC 2004.
  
 11- ARCHITECTURAL DRAWING A-1: UPDATE
 BUILDING CODE DATA INFORMATION. SEE 2004
 RESIDENTIAL CODE.
  
 12- DRAWING A-1: A) SPECIFY SAFETY GLASS
 FOR BATHROOM WINDOW. SEE PLANS. SEC.
 R308.4 2004 RESIDENTIAL CODE.
 B) UPDATE CODE REFERENCE FOR ATTIC
 ACCES. SEE 2004 RESIDENTIAL CODE.
 C) UPDATE CODE REFERENCES SPECIFIED
 ON GENERAL NOTES AND SCHEDULE NOTES. SEE
 2004 RESIDENTIAL CODE.
  
 13- DRAWING A-2; A) DESIGN PRESSURES
 MARK DOESN'T MATCH MARK SHOWED ON DOORS
 AND WINDOWS. OPENINGS. REVISE AS REQ'D.
 B) SPECIFY SIZE FOR MANUFACTURED
 ALUMINUM LOUVER AT FRONT AND BACK. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 14- DRAWING A-3: A) WHERE IS DETAIL A-5?
 SEE COMMENTS ON PLANS.
 B) SECTION "A": 1) CALLS FOR ALUMINUM
 SIDING. FRONT ELEVATION SHOWS STUCCO.
 REVISE AS REQUIRED.
 2) WHERE IS DETAIL SH 5 SPECIFIED FOR
 WOOD COLUMN SURROUND?
  
 15- DRAWING A-4: A) WALL SECTION "A":
 UPDATE CODE REFERENCE FOR FIREBLOCKING
 AND SPECIFY FIREBLOCKING MATERIAL. SEE
 2004 RESIDENTIAL CODE.
 B) WALL SECTION "B": 1) FOUNDATION
 DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 2) CLARIFY IF USING ALUMINUM SIDING OR
 STUCCO. SEE FRONT ELEVATION.
 3) SPECIFY NAILING SPACING FOR 5/8"
 PLYWOOD SHOWN ON PORCH CEILING. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 16- DRAWING S-1: A) FOUNDATION PLAN:
 1) SPECIFY SIZE OF CONTINUOUS FOOTING
 AT FRONT PORCH. SEE PLANS.
 2) SPECIFY SIZE OF PRECAST CONCRETE
 PAD AT REAR PORCH. SEE PLANS.
 3) WHERE IS DETAIL A ON SHEET S-2?
  
 B) ROOF FRAMING PLAN: 1) SPECIFY
 TRUSS CONNECTORS.
 2) WHERE IS DETAIL 2 SHEET S-2,
 DETAIL E SHEET S-2 AND DETAIL C SHEET
 S-2?. SEE PLANS.
  
 17- DRAWING S-2: A) TYP. 1 STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. R806 2004 RESIDENTIAL CODE
 B) DETAIL D: 1) HOW IS 2"X6" SILL
 PLATE ATTACHED TO CONCRETE BEAM?
 2) HOW IS 2"X6" "L" BRACE NAILED TO
 BOTTOM SILL?
 3) CLARIFY INSTALLATION OF USP TA18.
 IT'S SHOWN AS NAILED TO CONCRETE BEAM
 INSTEAD OF BEING EMBEDED IN CONCRETE
 BEAM. SEE USP CATALOGUE FOR PROPER
 INSTALLATION. REVISE AS REQ'D
 C) DETAIL A. PORCH FOOTING TO SHOW
 CONCRETE STEPS AND DETAILS TO MATCH
 SECTION "A" ON DRAWING A-3.
  
 18- DRAWING S-3: A) GENERAL NOTES.
 UPDATE ALL REFERENCE STANDARDS. SEE 2004
 RESIDENTIAL CODE AND 2004 FBC 2004 FOR
 ADOPTED STANDARDS AND SPECIFIC EDITION.
 B) UPDATE CODE SECTIONS REFERENCED
 FOR WIND LOADS, EMERGENCY EGRESS AND
 GLASS IMPACT PROTECTION. SEE PLANS.
 C) VENTILATION AND EGRESS ARE 2
 DIFFERENT CODE ISSUES. CLEAR OPENING FOR
 EGRESS HAS NOTHING TO DO WITH CLEAR
 OPENING FOR VENTILATION. REVISE NOTE.
 D) TRUSS ANCHOR SCHEDULE: NUMBER OF
 NAILS AND UPLIFT LOADS SPECIFIED TO
 MATCH USP CURRENT CATALOGUE. OTHERWISE,
 PROVIDE COMPLETE ENGINEERING CALCS FOR
 SIZE AND NUMBER OF NAILS THAT ARE
 DIFFERENT THAN THOSE PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 E) ADDITION TO STRUCTURE NOTES DON'T
 APPLY TO THIS JOB.
  
 19- SURVEY TO HAVE SURVEYOR'S ORIGINAL
 SIGNATURE, NOT COPY, AS REQUIRED BY
 CHAPTER 472 FLORIDA STATUTES.
  
 20- STORM SHUTTERS:
 A) PROVIDE KEY PLAN.
 B) PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE THAT
 COVERS ALL REQUIRED INFORMATION TO
 PERFORM BUILDING REVIEW AND PRODUCT
 COMPLIANCE WITH PROPOSED INSTALLATION.
  
 21- ENERGY CALCULATIONS: A) NEED ENERGY
 CALCULATIONS USING FORM 600A-2004.
 B) CONDITIONED FLOOR AREA DOESN'T
 MATCH PLANS.
 C) BUILDING ORIENTATION, OVERHANG
 LENGTH, OVERHANG HEIGHT AND AREA DON'T
 MATCH PLANS. REVISE AS REQUIRED. SEE
 CHAPTER 13 FBC 2004 FOR PROPER WAY OF
 CALCULATING THESE ITEMS.
 D) OWNER/AGENT TO SIGN BOTTOM OF FORM
  
 ***NOTE: TO EXPEDITE REVIEW PROCESS,
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO ORIGINALS.
  
 JULIO GOMEZ
 BUILDIG PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 18:07 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 18:07 Sent To M
Notes
2006-05-14 00:00:00** REDLINED PLANS,
  
 PLEASE SEESD'S ARE NOW SHOWN
 ON CIRCUIT #2 WHICH DOES NOT INDICATE
 ARC FAULT PROTECTION AS REQ'D UDNER 2002
 NEC 210.12B.
 SD'S CAN BE ON A-2, HOWEVER A AFCI TYOE
 BRKR WILL THEN BE REQUIRED.
  
 PLEASE SEE MISSING RECEPT IN MAST BEDRM
 PER 210.52

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 22:21 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 22:18 Sent To M
Notes
2006-01-20 00:00:00******** UNSAT ************
  
 1)NOTE: PLEASE SEE MISSING FIRM LICENSE
 NUMBER ON TITLE BLOCK FOR ARCHITECTUAL
 FIRM. FAC 61G1-16.004, FS 481.219
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEEELECTRICAL PLANS ARE
 SIGNED , DATED AND SEALED BY AN
 ELECTRICAL ENGINEER, HOWEVER PLANS DO
 NOT CONTAIN ANY TITLE BLOCK FOR SAID
 ENGINEER OF RECORD AS REQUIRED PER FAC
 61G15-23.002, FS 471.023
  
 3)NOTE: PLEASE VERIFY THE 1/2" CONDUIT
 SHOWN FOR FUTURE PHONE. IT IS KNOWN TO
 THIS OFFICE THE TELEPHONE COMPANY AND
 CABLE COMPANY REQUIRES A MIN OF 3/4"
 CONDUIT FOR UNDERGROUND INSTALLATIONS.
 THIS IS FOR INFORMATIONAL PURPOSE ONLY
 AS THIS IS NOT AN NEC REQUIREMENT.
  
 4)NOTE: PLEASE CORRELATE LOAD FOR RANGE
 IN LOAD CALCS WITH LOAD ON PANEL
 SCHEDULE.
 PLEASE VERIFY IF INDEED A 40A BRKR WILL
 BE USED AS MOST RANGES REQUIRE A MIN OF
 50A. (RANGE RECEPT IS 50A)
 PLEASE ALSO VERIFY WIRING METHODS TO BE
 USED. PLANS INDICATE CONDUIT AND WIRING,
 HOWEVER IF ROMEX IS USED, THE #8 SHOWN
 WOULD BE REQUIRED TO BE INCREASED TO #6.
 SEE 310.16, 60 DEGREE COL.
 215.5
  
 5)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS IN THE PANEL
 SCHEDULE PROVIDE. IT IS KNOWN THAT NOTE
 #7 ON PLANS MENTIONS TO PROVIDE ARC
 FAULT BRKRS FOR ALL BEDRMS, HOWEVER
 PLEASE SEE 2002 NEC 210.12 WHICH
 REQUIRES ALL "OUTLETS" IN BEDRMS TO BE
 AFCI PROTECTED. THIS INCLUDES SD'S,
 HOWEVER SD'S ARE SHOWN BEING WIRED TO
 FAMILY RM RECEPTS. THIS IS OK, HOWEVER
 THEN THIS CIRCUIT WOULD ALSO BE REQUIRED
 TO BE ARC FAULT, THUS NOTE #7 WOULD NOT
 REFERENCE.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES LANSCAPE LTS, HOWEVER PLANS DO
 NOT SHOW ANY. PLEASE KNOW, IF NONE SHOWN
 ON PLANS, THEN LANDSCAPE LIGHTING WILL
 BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT, WHICH WILL INCLUDE PERMIT, PLANS
 AND FEE.
  
 ** PLEASE VERIFY WIRING METHOD, AS PLANS
 INDICATE CONDUIT AND WIRING FOR ALL
 CIRCUITS. IF SHOWN , ROMEX WOULD NOT BE
 PERMITTED.
 THIS IS ONLY A NOTE.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE ON CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 08:36 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 08:36 Sent To P
Notes
2008-01-04 08:36:33TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 13:51 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 13:51 Sent To B
Notes
2006-09-05 00:00:00TO "JGOMEZ" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 16:53 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 16:53 Sent To E
Notes
2006-05-11 00:00:00TO "DPALMER' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-04 Cont ID  
Sent By adarroug Date 2006-05-04 Time 14:46 Rev Time 0.00
Received By adarroug Date 2006-05-04 Time 14:46 Sent To Z
Notes
2006-05-04 00:00:00TO "Z" BOX/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-06 Cont ID  
Sent By jgomez Date 2006-03-01 Time 17:31 Rev Time 0.00
Received By jgomez Date 2006-01-13 Time 14:38 Sent To  
Notes
2006-01-13 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By tgordon Date 2006-05-15 Time 08:40 Rev Time 0.45
Received By tgordon Date 2006-05-15 Time 08:40 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-25 Cont ID  
Sent By tgordon Date 2006-01-25 Time 09:31 Rev Time 0.30
Received By tgordon Date 2006-01-25 Time 09:31 Sent To B
Notes
2006-01-25 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) NEED A/C CONTRACTOR'S LICENCE NUMBER,
 NAME, AND SIGNATURE ON MECHANICAL PLANS.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3)NEED JOB SITE ADDRESS ON MECHANICAL
 PLANS.
  
 4) SUPPLY AIR DUCTS FROM AHU TO MIXING
 BOXES ARE NOT SIZED.
  
 5) BEDROOM #1 RETURN AIR TRANSFER DUCT
 IS TO SMALL,SEE NOTE #6.
  
 6)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 7) MECHANICAL PLANS HAVE TO MUCH FLOOR
 PLAN INFOMATION ON THEM AND ARE
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-16 Cont ID  
Sent By jleech Date 2006-05-16 Time 13:24 Rev Time 0.00
Received By jleech Date 2006-05-16 Time 13:24 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-23 Cont ID  
Sent By jleech Date 2006-01-23 Time 08:12 Rev Time 0.33
Received By jleech Date 2006-01-23 Time 08:12 Sent To M
Notes
2006-01-23 00:00:00DENIED;
 1.KITCHEN SINK NOT VENTED.
 2.W/M DRAIN TO BE 3" SEE FBC-2004
 PLUMBING SEC. 406.3.
 3.WATER HAMMER ARRESTORS ARE REQUIRED ON
 THE W/M AND KITCHENSINK PER. FBC-2004
 RESIDENTIAL SEC. P2903.5
 4.A SHUTOFF VALVE IS REQUIRED ON THE
 WATER SEVICE PER. RES. CODE SEC
 P2903.9.1.
 5.PLEASE DELETE NOTE 26 TIEING
 IRRIGATION PUMP TO WATER SYSTEM WOULD BE
 A CROSS CONNECTION.
 6.SEE ELECTRICAL NOT # 1 ABOUT LIC.
 NUMBER MISSING.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-11 Cont ID  
Sent By mmclean Date 2006-05-11 Time 15:51 Rev Time 0.00
Received By mmclean Date 2006-05-11 Time 15:51 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By mmclean Date 2006-01-20 Time 19:32 Rev Time 0.00
Received By mmclean Date 2006-01-20 Time 19:32 Sent To E
Notes
2006-01-20 00:00:00NOTE:
 1.THE PORCH MUST SIT 25FT FROM THE FRONT
 SETBACK.
 2.ROOF OVERHANG PROJECTIONS SHALL NOT
 EXTEND FARTHER THAN THREE FEET INTO ANY
 SETBACK.