Plan Review Details - Permit 06010427
Plan Review Stops For Permit 06010427
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-07-12 Cont ID  
Sent By alange Date 2006-07-12 Time 10:59 Rev Time 2.00
Received By alange Date 2006-07-12 Time 10:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-27 Cont ID  
Sent By alange Date 2006-06-27 Time 08:07 Rev Time 0.75
Received By alange Date 2006-06-27 Time 08:07 Sent To  
Notes
2006-06-27 00:00:00DENIED
  
 2.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
  
 4.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 NEW COMMENT:
 A.713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-05-17 Cont ID  
Sent By alange Date 2006-05-17 Time 11:22 Rev Time 1.50
Received By alange Date 2006-05-17 Time 11:22 Sent To  
Notes
2006-05-17 00:00:00DENIED
  
 2.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
  
 4.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-13 Cont ID  
Sent By alange Date 2006-02-13 Time 11:22 Rev Time 3.00
Received By alange Date 2006-02-13 Time 11:20 Sent To  
Notes
2006-02-13 00:00:00DENIED
  
 1.BASED ON ICC BUILDING VALUATION DATA
 THE PERMIT VALUATION HAS BEEN REVISED TO
 $145,578.00.ADDITIONAL PERMIT FEES ARE
 DUE.
  
 2.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 3.SUBMIT PRODUCT APPROVALS FOR LINTELS
 AND STRAPS AND TIE-DOWNS.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
 ** PLEASE DO NOT ATTACH PRODUCT
 APPROVALS TO PLANS**
  
 4.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
 SHOW BUILDING CONSTRUCTION TYPE AND
 CHANGE CODE SECTIONS TO REFLECT THE 2004
 FBC.
  
 6.APPLICATION FOR PERMIT HAS NOT BEEN
 COMPLETED BY A NOTARY.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-06-21 Cont ID  
Sent By dpalmer Date 2006-06-21 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2006-06-21 Time 19:34 Sent To B
Notes
2006-06-16 00:00:006/16/06 CALLED CONTRACTOR, SPOKE TO
 HAROLD DAVIDSON, RESUB WAS NOT PAID AND
 PLANS ARE ON "HOLD" AND NOT BEING
 PROCESSED UNTIL FES ARE PAID. PLANS ARE
 UNDER "H", LARGE BINS. ONCE FEE IS PAID
 PLEASE GIVE PLANS DIRECTLY TO DVP. DV
 PALMER

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 17:46 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 17:35 Sent To M
Notes
2006-05-14 00:00:00*** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO CHANGES
 MADE ON PLANS.
  
 PLEASE SEE NOTE BELOW MARKED WITH **,
 ARE NOTES TAKEN DIRECTLY FROM PREVIOUS
 REVIEW.
  
 ******** UNSAT ************
  
 1)NOTE: OK
  
 2)NOTE: OK
  
 3)NOTE: OK
  
 4)NOTE: OK
  
 5)NOTE: OK, SEE NEW NOTES FOR ARC FAULT.
  
  
 NEW NOTE:
  
 1) NOTE: PLEASEHOWEVER SEE SD'S ARE
 NOW SHOWN WIRED TO LIV RM CIRCUIT, THIS
 IS OK, HOWEVER THIS CIRCUIT WOULD NOW
 REQUIRED AFCI PROTECTION. SD'S SHOULD BE
 ON BEDRM CIRCUIT, BUT NOT REQUIRED TO.
 PLEASE EITHER REVISE CIRCUIT NUMBER OR
 PROVIDE ARC FAULT ON PANEL SCHEDULE NOW
 FOR LIV RM.
  
 2)NOTE: OK, HOWEVER PLEASE NOW SEE BATH
 CIRCUITS ARE BEING NOTED AS ARC FAULT??
 THIS IS NOT REQUIRED , HOWEVER CAN BE
 DONE AS AN ARC FAULT/GFI BRKR IS NOW
 MADE. PLEASE CALL TO GO OVER THIS.
  
 3) NOTE: PLEASE SEE FRONT AND REAR GFI
 RECEPTS WERE REMOVED PER 210.52E ?
  
 4) NOTE: PLEASE SEE MISSING KITCHEN
 COUNTER SPACE RECEPT GFI PER 210.52C1,
 210.8A6
  
 5) NOTE: PLEASE SEE MISSING RECEPTS PER
 210.52
  
  
  
 PLEASE SEE REDLINED PLANS FOR MISSING
 RECEPTS PER 210.52
 ** PLEASE KNOW, IF PLANS PASS ALL OTHER
 REIVEWSA "PROVISO" MAY BE SET UP FOR
 THIS PLAN.
 IF PLANS ARE DENIED FOR ANY OTHER
 COMMENTS, PLEASE REVISE AT THIS TIME.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE ON CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 22:03 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 21:58 Sent To M
Notes
2006-01-20 00:00:00******** UNSAT ************
  
 1)NOTE: PLEASE SEE MISSING FIRM LICENSE
 NUMBER ON TITLE BLOCK FOR ARCHITECTUAL
 FIRM. FAC 61G1-16.004, FS 481.219
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEEELECTRICAL PLANS ARE
 SIGNED , DATED AND SEALED BY AN
 ELECTRICAL ENGINEER, HOWEVER PLANS DO
 NOT CONTAIN ANY TITLE BLOCK FOR SAID
 ENGINEER OF RECORD AS REQUIRED PER FAC
 61G15-23.002, FS 471.023
  
 3)NOTE: PLEASE VERIFY THE 1/2" CONDUIT
 SHOWN FOR FUTURE PHONE. IT IS KNOWN TO
 THIS OFFICE THE TELEPHONE COMPANY AND
 CABLE COMPANY REQUIRES A MIN OF 3/4"
 CONDUIT FOR UNDERGROUND INSTALLATIONS.
 THIS IS FOR INFORMATIONAL PURPOSE ONLY
 AS THIS IS NOT AN NEC REQUIREMENT.
  
 4)NOTE: PLEASE CORRELATE LOAD FOR RANGE
 IN LOAD CALCS WITH LOAD ON PANEL
 SCHEDULE.
 PLEASE VERIFY IF INDEED A 40A BRKR WILL
 BE USED AS MOST RANGES REQUIRE A MIN OF
 50A. (RANGE RECEPT IS 50A)
 PLEASE ALSO VERIFY WIRING METHODS TO BE
 USED. PLANS INDICATE CONDUIT AND WIRING,
 HOWEVER IF ROMEX IS USED, THE #8 SHOWN
 WOULD BE REQUIRED TO BE INCREASED TO #6.
 SEE 310.16, 60 DEGREE COL.
 215.5
  
 5)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS IN THE PANEL
 SCHEDULE PROVIDE. IT IS KNOWN THAT NOTE
 #7 ON PLANS MENTIONS TO PROVIDE ARC
 FAULT BRKRS FOR ALL BEDRMS, HOWEVER
 PLEASE SEE 2002 NEC 210.12 WHICH
 REQUIRES ALL "OUTLETS" IN BEDRMS TO BE
 AFCI PROTECTED. THIS INCLUDES SD'S,
 HOWEVER SD'S ARE SHOWN BEING WIRED TO
 MORE THAN ONE CIRCUIT. PLEASE ALSO SEE
 SOME SD'S NOT CIRCUITED AT ALL.
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES LANSCAPE LTS, HOWEVER PLANS DO
 NOT SHOW ANY. PLEASE KNOW, IF NONE SHOWN
 ON PLANS, THEN LANDSCAPE LIGHTING WILL
 BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT, WHICH WILL INCLUDE PERMIT, PLANS
 AND FEE.
  
 ** PLEASE VERIFY WIRING METHOD, AS PLANS
 INDICATE CONDUIT AND WIRING FOR ALL
 CIRCUITS. IF SHOWN , ROMEX WOULD NOT BE
 PERMITTED.
 THIS IS ONLY A NOTE.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE ON CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-06-29 Cont ID  
Sent By adarroug Date 2006-06-29 Time 14:39 Rev Time 0.00
Received By adarroug Date 2006-06-29 Time 14:39 Sent To B
Notes
2006-06-29 00:00:00TO "ALANGE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status F Date 2006-06-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 10:11 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 10:11 Sent To E
Notes
2006-06-15 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 16:38 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 16:38 Sent To E
Notes
2006-05-11 00:00:00TO "DPALMER' DESK/RESU

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-04 Cont ID  
Sent By adarroug Date 2006-05-04 Time 14:50 Rev Time 0.00
Received By adarroug Date 2006-05-04 Time 14:50 Sent To Z
Notes
2006-05-04 00:00:00TO "Z" BOX/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-13 Cont ID  
Sent By alange Date 2006-02-13 Time 11:23 Rev Time 0.00
Received By alange Date 2006-01-13 Time 14:36 Sent To  
Notes
2006-01-13 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By tgordon Date 2006-05-15 Time 09:30 Rev Time 0.30
Received By tgordon Date 2006-05-15 Time 09:30 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-25 Cont ID  
Sent By tgordon Date 2006-01-25 Time 11:34 Rev Time 0.30
Received By tgordon Date 2006-01-25 Time 11:34 Sent To B
Notes
2006-01-25 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) NEED A/C CONTRACTOR'S LICENCE NUMBER,
 NAME, AND SIGNATURE ON MECHANICAL PLANS.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3)NEED JOB SITE ADDRESS ON MECHANICAL
 PLANS.
  
 4) SUPPLY AIR DUCTS FROM AHU TO MIXING
 BOXES ARE NOT SIZED.
  
 5) RETURN AIR TRANSFER DUCT FROM BEDROOM
 #1 TO BEDROOM #2 IS NOT SIZED.
  
 7) MECHANICAL PLANS HAVE TO MUCH FLOOR
 PLAN INFOMATION ON THEM AND ARE
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-16 Cont ID  
Sent By jleech Date 2006-05-16 Time 13:03 Rev Time 0.00
Received By jleech Date 2006-05-16 Time 13:03 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-23 Cont ID  
Sent By jleech Date 2006-01-23 Time 12:36 Rev Time 0.33
Received By jleech Date 2006-01-23 Time 12:36 Sent To M
Notes
2006-01-23 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW NOTE #1
 LIC# MISSING FROM TITAL BLOCK.
 2.WATER HAMMER ARRESTORS REQUIRED AT
 KITCHEN SINK.
 3.AUTOMATIC CLOTHES WASHER DRAIN
 REQUIRED TO BE 3".
 4. CODE BOOK TO BE USED IS THE FBC-2004,
 NOT 2001.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-11 Cont ID  
Sent By mmclean Date 2006-05-11 Time 15:16 Rev Time 0.00
Received By mmclean Date 2006-05-11 Time 15:16 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By mmclean Date 2006-01-20 Time 19:33 Rev Time 0.00
Received By mmclean Date 2006-01-20 Time 19:33 Sent To E
Notes
***NONE***