Plan Review Details - Permit 06010421
Plan Review Stops For Permit 06010421
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-14 Cont ID  
Sent By jgomez Date 2006-09-14 Time 09:25 Rev Time 2.00
Received By jgomez Date 2006-09-13 Time 15:03 Sent To  
Notes
2006-09-14 00:00:00BUILDING REVIEW PROVISO:
 1- AS AGREED WITH CONTRACTOR, PROVIDE
 COMPLETE AND CORRECT INFORMATION FOR
 STORM SHUTTERS UNDER A SEPARATE PERMIT.
  
 2- DADE COUNTY NOA #04-0528.04 FOR
 WINDOW MULLIONS EXPIRED IN 6/28/06.
 PROVIDE CURRENT DADE COUNTY NOA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-06-29 Cont ID  
Sent By jgomez Date 2006-06-29 Time 18:09 Rev Time 2.00
Received By jgomez Date 2006-06-29 Time 18:09 Sent To  
Notes
2006-06-29 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK COPY OF PAID RECEIPT AND
 STAMPED PLANS.
  
 2- NOC IS EXPIRED AFTER 90 DAYS OF BEEN
 RECORDED IF WORK IS NOT COMMENCED. NEED
 RE-RECORDED NOC. SEE SEC. 713.13. 9(2)
 OF FLORIDA STATUTES.
  
 3- PROVIDE SPECS/SECTION/DETAILS FOR
 INSTALLATION OF DECORATIVE STORM
 SHUTTERS. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 4- PROVIDE PRODUCT APPROVAL FOR:
 A) SINGLE HUNG WINDOWS. DADE COUNTY NOA
 SUBMITTED IS EXPIRED AND IT DOESN'T
 MATCH THE NOA SUBMITTED TO OBTAIN THE
 FLORIDA PRODUCT APPROVAL. RESUBMIT. GO
 TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 CORRECT NOA.
 B) CONCRETE LINTELS. DADE COUNTY NOA
 SUBMITTED IS FOR 4", 6" & 12" LINTELS.
 NEED NOA FOR 8"X8" LINTELS AS SPECIFIED
 ON PLANS.
 ***NOTE: NOA FOR 8"X8" LINTELS IS
 EXPIRED. NEED TO PROVIDE CURRENT ONE.
 C) ALUMINUM SIDING. PRODUCT APPROVAL
 SUBMITTED IS FOR CEMENTITIOUS SIDING
 PRODUCTS, NOT ALUMINUM AS SPECIFIED ON
 PLANS. NEED SPECIFIED PRODUCT APPROVAL.
 D) ALL SIMPSON STRUCTURAL CONNECTORS
 AS SPECIFIED ON PLANS. PRODUCT APPROVALS
 SUBMITTED ARE FOR USP AND ONLY ONE WAS
 GOOD FOR THE USP HLPTA75 CONNECTOR. THE
 REST OF THE PRODUCT APPROVALS SUBMITTED
 WERE NOT SPECIFIED ON PLANS.
 E) ALUMINUM VENTS SHOWN ON ELEVATIONS.
 F) ASPHALT SHINGLES NOA THAT MATCHES
 NOA SUBMITTED FOR FLORIDA PRODUCT
 APPROVAL. GO TO WWW.FLORIDABUILDING.ORG
 TO DOWNLOAD CORRECT NOA.
  
 5- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS, INCLUDING THE STORM SHUTTERS
 AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC.
 TYPICALLY THIS IS DONE USING THE
 STANDARD REVIEW STAMP USED FOR SHOP
 DRAWINGS REVIEW.
  
 6- STORM SHUTTERS:
 A) PRODUCT APPROVAL SUBMITTED IS
 INCOMPLETE. IT DIDN'T INCLUDE THE DWGS.
 B) INSTALLATION SCHEDULE:
 * WHY THE DESIGN PRESSURES ARE N/A?.
 THIS IS THE MOST IMPORTANT INFORMATION
 TO VERIFY COMPLIANCE OF PRODUCT BASED ON
 THE CALCULATED DESIGN PRESSURES. NEED
 THIS INFORMATION. SEE PLANS.
 C) VERIFY SIZES FOR PANEL SPAN. EG:
 SOME OPENINGS ARE 5'X6'-8" HOW COME THE
 PANEL SPAN IS 88"?. ALSO, THIS APPLIES
 TO 4' HIGH OPENINGS. WHY USING 68" LONG
 PANELS?.
 D) VERIFY STRUCTURE TO BE ATTACHED TO.
 THIS IS A CONCRETE BLOCK STRUCTURE, NOT
 POURED CONCRETE. REVISE AS REQUIRED.
  
 7- DRAWING A-1: UPDATE CODE REFERENCE
 SPECIFIED FOR ATTIC ACCESS, FIREBLOCKING
 AND WINDOW/DOOR GLAZING PROTECTION. THIS
 IS A RESIDENCE THE CORRECT CODE THAT
 REGULATES DWELLINGS IS THE RESIDENTIAL
 2004 CODE, NOT THE FBC 2004. REVISE AS
 REQ'D AND CITE CORRECT CODE REFERENCE
 SECTIONS FROM THE RESIDENTIAL CODE.
  
 8- DRAWING S-1 IS MISSING THE ENGINEER'S
 INFORMATION AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTES AND FAC.
  
 9- DRAWING A-2: A) WHAT ARE THE LETTERS
 IDENTIFYING THE OPENINGS FOR? THEY DON'T
 MATCH FLOOR PLAN AND THERE IS NOT LEGEND
 IDENTIFYING THIS LETTERS. CLARIFY AS
 REQUIRED.
 B) SPECIFY SIZE FOR MANUFACTURED
 ALUMINUM LOUVERS AT FRONT AND BACK
 ELEVATIONS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004 AND SECTION R806.
  
 10- DRAWING A-3: SECTION "A", WHERE IS
 DETAIL SHT 5?
  
 11- DRAWING A-4: WALL SECTION "A".
 SPECIFY FIREBLOCKING MATERIAL AND
 REVISE REFERENCE FOR FIREBLOCKING. SEE
 RESIDENTIAL 2004 FOR CORRECT CODE
 SECTION.
  
 12- DRAWING S-1: A) PROVIDE DETAIL/SPECS
 FOR 4"X4" WOOD POST AT REAR WOOD DECK.
 NEED TO SPECIFY ATTACHMENT OF WOOD POST
 TO FOOTING. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
 B) SPECIFY TRUSS CONNECTORS ON ROOF
 FRAMING PLAN. SEC. 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 13- DRAWING S-2: A) TYP. ONE STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. PROVIDE SPECIFIC
 INFORMATION. SECTION R806 2004.
 B) DETAIL H: USP RT24 IS A WOOD TO WOOD
 CONNECTOR. NEED TO SPECIFY WOOD TO
 MASONRY CONNECTOR. REVISE AS REQUIRED.
  
 14- DRAWING S-3: A) REVISE TRUSS ANCHOR
 SCHEDULE. UPLIFT CAPACITY DOESN'T MATCH
 UPLIFT CAPACITY SHOWN ON CURRENT USP
 CATALOGUE. REVISE AS REQUIRED OR PROVIDE
 COMPLETE ENGINEERING PACKAGE SHOWING WHY
 CHANGING THE VALUES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 15- ENERGY CALCULATIONS:
 A) IF THIS IS A MODEL HOUSE. ENERGY
 CALCULATIONS NEED TO BE DONE FOR WORST
 CASE SCENARIO OR MUST BE SITE SPECIFIC
 WITH CORRECT HOUSE ORIENTATION.
 CALCULATIONS SUBMITTED ARE NOT FOR WORST
 CASE SCENARIO.
 B) OVERHANG LENGTH AND HEIGHT DON'T
 MATCH PLANS. SEE SECTION 13-601.2.A.3
 FOR PROPER WAY OF CALCULATING OVERHANG
 LENGTH AND HEIGHT. AND REVISE AS
 REQUIRED.
  
 16- ARCHITECT'S TITLE BLOCK TO INCLUDE
 ALL INFORMATION REQUIRED BY CHAPTER 481
 FLORIDA STATUTES AND 61G1-16.004 OF
 FLORIDA ADMINISTRATIVE CODE. SEE
 ATTACHED COPY.NEED NAME OF ARCHITECT
 SIGNING AND SEALING PLANS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-10 Cont ID  
Sent By jgomez Date 2006-03-10 Time 11:42 Rev Time 3.00
Received By jgomez Date 2006-03-10 Time 11:42 Sent To P
Notes
2006-03-10 00:00:00BUILDING REVIEW CHECKLIST:
 1- PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING BACK STAMPED DRAWINGS AND PAID
 RECEIPT.
  
 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY
 SEC. R401.3 OF 2004 RESIDENTIAL CODE.
  
 3- PROVIDE STRUCTURAL BUCK DETAIL USING
 2X BUCK AS REQUIRED BY ENTRY DOOR
 PRODUCT APPROVAL SUBMITTED. SEE SECTION
 R613.6.2 2004 RESIDENTIAL CODE FOR
 PROPER BUCK INSTALLATION.
  
 4- OWES $351.21 FOR UPDATED VALUATION
 AND RADON FEES.
  
 5- PROVIDE SPECS/DETAILS FOR
 INSTALLATION OF DECORATIVE STORM
 SHUTTERS. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 6- DRAWINGS S-2 AND S-3 ARE MISSING THE
 ENGINEER'S INFORMATION AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTES.
  
 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR SLIDING GLASS DOORS AND
 FRENCH DOORS WITH TRANSOM ABOVE SINGLE
 UNIT AS SHOWN ON PLANS OR PROVIDE
 COMPLETE INFORMATION FOR STRUCTURAL
 MULLION AS REQUIRED BY SEC. R613.7 2004
 RESIDENTIAL CODE.
 B) SPECIFY SIZE OF FIXED WINDOW.
  
 8- ARCHITECT TO PROVIDE ALLINFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAPTER
 481 FLORIDA STATUTES AND 61G1-16.004 OF
 ADMINISTRATIVE CODE. SEE ATTACHED COPY.
  
 9- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY RULE 9B-72 FOR:
 A) FRENCH DOORS WITH TRANSOM ABOVE.
 OR FRENCH DOORS ALONE. SEE ITEM #7 ABOVE
 B) SLIDING GLASS DOORS WITH TRANSOM
 ABOVE. OR SLIDING GLASS DOORS ALONE. SEE
 ITEM #7 ABOVE.
 C) STRUCTURAL MULLIONS. SEE ITEM #7.
 D) FIXED WINDOWS. SEE ITEM #7 ABOVE.
 E) ALL TRUSS CONNECTORS. SEE PLANS.
 F) SINGLE HUNG WINDOWS. DADE COUNTY
 NOA TO MATCH NOA SUBMITTED FOR FLORIDA
 PRODUCT APPROVAL. VISIT
 WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 CORRESPONDING NOA.
 G) ROOF SHINGLES. PROVIDE SAME NOA
 SUBMITTED FOR FLORIDA PRODUCT APPROVAL.
 H) PRECAST LINTELS.
 I) ALUMINUM VENTS.
 J) ALUMINUM SIDING.
  
 10- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS PRIOR TO SUBMITTAL TO THIS
 OFFICE AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 11- DRAWING 1: UPDATE BUILDING CODE
 DATA. SEE 2004 RESIDENTIAL CODE.
  
 12- DRAWING A-1: A) WINDOW C (3'-0" X
 4'-0") DOESN'T MEET THE EGRESS
 REQUIREMENTS OF SEC. R310.1.2 2004
 RESIDENTIAL CODE.
 B) SPECIFY SAFETY GLASS FOR WINDOW IN
 BATHROOM. SEE PLANS. SEC. R308.4 2004
 RESIDENTIAL CODE.
 C) UPDATE CODE REFERENCE FOR ATTIC
 ACCESS. SEE 2004 RESIDENTIAL CODE.
 D) UPDATE CODE REFERENCES SPECIFIED
 ON GENERAL NOTES AND SCHEDULE NOTES. SEE
 2004 RESIDENTIAL CODE.
  
 13- DRAWING A-2: A) DESIGN PRESSURES
 MARK DOESN'T MATCH MARK SHOWED ON DOORS
 AND WINDOWS OPENINGS. REVISE AS REQ'D.
 B) SPECIFY SIZE OF MANUFACTURED
 ALUMINUM LOUVER AT FRONT AND BACK. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 14- DRAWING A-3: A) WHERE IS DETAIL A-5"
 SPECIFIED ON PLANS?
 B) SECTION "A": 1) THERE IS NOT
 ARCHED PORCH BEAM. REVISE AS REQUIRED.
 2) WHERE IS DETAIL SHT 5?
 3) SPECIFIED FIREBLOCKING MATERIAL
 AND LOCATION AT CONCEALED SPACES IN
 SOFFITS AND WALLS. SEE PLANS. SEC.
 R602.8 2004 RESIDENTIAL CODE.
  
 15- DRAWING A-4: A) WALL SECTION "A".
 UPDATE CODE REFERENCE SPECIFIED FOR
 FIREBLOCKING AND SPECIFY FIREBLOCKING
 MATERIAL. SEE 2004 RESIDENTIAL CODE.
 B) WALL SECTION "B". FOUNDATION PLAN
 DOESN'T MATCH PLANS. REVISE AS REQUIRED.
 C) PORCH BEAM IS NOT AN ARCHED BEAM.
 REVISE AS REQUIRED. SEE PLANS.
  
 16- DRAWING S-1: A) PROVIDE COMPLETE
 DETAILS AND SPECS FOR WOOD DECK AND WOOD
 STEPS AT REAR AREA OUTSIDE MASTER
 BEDROOM AND AT COVERED PORCH.
 B) ROOF FRAMING PLAN CALLS FOR TRUSS
 ANCHOR A3 BY REAR PORCH. THERE IS NOT
 A3. REVISE AS REQUIRED.
 C) WHERE ARE DETAILS A, C AND E?
 D) WWHERE IS DET 2 SHT S-2?.
 KEY DETAILS TO MATCH DRAWINGS.
  
 17- DRAWING S-2: A) TYP. 1 STORY
 SECTION: SPECIFY SIZE AND LOCATION OF
 ATTIC VENTS. ALSO, CONSIDER ALUMINUM
 VENTS FOR TOTAL VENTING AREA REQUIRED.
 SEC. R806 2004 RESIDENTIAL CODE.
 B) DETAIL D: 1) HOW IS 2"X6" SILL
 PLATE ATTACHED TO CONCRETE BEAM?
 2) HOW IS 2" X 6" "L" BRACE NAILED TO
 BOTTOM SILL?
 3) USP TA18 IS SHOWN AS BEING
 ATTACHED TO CONCRETE BEAM. THIS
 CONNECTOR IS TO BE EMBEDED IN CONCRETE.
 REVISE AS REQUIRED. SEE USP CATALOGUE.
 4) DETAIL A: SHOW COMPLETE DETAILS
 AND SPECS FOR CONCRETE STEPS AT ENTRY
 PORCH.
  
 18- DRAWING S-3: A) GENERAL NOTES:
 UPDATE ALL REFERENCE STANDARDS AND
 SPECIFIC EDITION TO BE USED. SEE 2004
 RESIDENTIAL CODE AND 2004 FBC.
 B) UPDATE CODE SECTIONS REFERENCED
 FOR WIND LOADS, EMERGENCY EGRESS AND
 GLASS IMPACT PROTECTION NOTES.
 C) VENTILATION AND EGRESS ARE TWO
 DIFFERENT CODE ISSUES.REVISE AS REQ'D.
 D) TRUSS ANCHOR SCHEDULE: NUMBER OF
 NAILS AND UPLIFT LOADS TO MATCH CURRENT
 USP CATALOGUE. OTHERWISE, PROVIDE
 COMPLETE ENGINEERING ANALYSIS FOR NUMBER
 AND UPLIFT LOADS THAT DIFFER THOSE
 PUBLISHED BY MANUFACTURER. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
 E) DELETE NOTES CORRESPONDING TO
 STRUCTURE ADDITIONS. THEY DON'T APPLY TO
 THIS PROJECT.
  
 19- SURVEY TO HAVE SURVEYOR'S ORIGINAL
 SIGNATURE, NOT COPY, AS REQUIRED BY
 CHAPTER 472 FLORIDA STATUTES.
  
 20- STORM SHUTTERS:
 A) PROVIDE KEY PLAN.
 B) PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE. PROVIDE
 ALL INFORMATION.
  
 21- ENERGY CALCULATIONS:
 A) USE 2004 FORM, NOT 2001.
 B) BUILDING ORIENTATION, OVERHANG
 LENGTH AND HEIGHT AND AREA DON'T MATCH
 PLANS. REVISE AS REQUIRED. SEE CHAPTER
 13 FBC 2004 FOR PRROPER WAY OF
 CALCULATING ENERGY CALCS. REVISE AS
 REQUIRED.
 ***NOTE: IF ENERGY CALCULATIONS ARE NOT
 DONE FOR WORST CASE SCENARIO, THEN THEY
 MUST BE DONE ACCORDING TO THE ACTUAL
 HOUSE ORIENTATION. SEE SURVEY FOR
 CORRECT ORIENTATION.
 C) OWNER/AGENT TO SIGN BOTTOM OF FORM
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-09 Cont ID  
Sent By dpalmer Date 2006-09-09 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2006-09-09 Time 18:56 Sent To B
Notes
2006-09-09 00:00:00STAMPED AND REDLINED 2002 NEC.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-05-14 Cont ID  
Sent By dpalmer Date 2006-05-14 Time 17:25 Rev Time 0.00
Received By dpalmer Date 2006-05-14 Time 14:33 Sent To M
Notes
2006-05-14 00:00:00*** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW AND SOME NEW NOTES DUE TO CHANGES
 MADE ON PLANS.
  
 PLEASE SEE NOTE BELOW MARKED WITH **,
 ARE NOTES TAKEN DIRECTLY FROM PREVIOUS
 REVIEW.
  
 ******** UNSAT ************
  
 1)NOTE: NOTE #1 OK
  
 2)NOTE:NOTE #2 NO,
  
 **PLEASE SEEELECTRICAL PLANS ARE
 SIGNED , DATED AND SEALED BY AN
 ELECTRICAL ENGINEER, HOWEVER PLANS DO
 NOT CONTAIN ANY TITLE BLOCK FOR SAID
 ENGINEER OF RECORD AS REQUIRED PER FAC
 61G15-23.002, FS 471.023
 SEE E-2 WAS DONE.
  
 3)NOTE: OK
  
 4)NOTE: OK
  
 5)NOTE:OK, HOWEVER SEE SD'S ARE NOW
 SHOWN WIRED TO LIV RM CIRCUIT, THIS IS
 OK, HOWEVER THIS CIRCUIT WOULD NOW
 REQUIRED AFCI PROTECTION. SD'S SHOULD BE
 ON BEDRM CIRCUIT, BUT NOT REQUIRED TO.
 PLEASE EITHER REVISE CIRCUIT NUMBER OR
 PROVIDE ARC FAULT ON PANEL SCHEDULE NOW
 FOR LIV RM.
  
 **PLEASE SEE SD'S ARE SHOWN BEING
 WIRED TO MORE THAN ONE CIRCUIT. PLEASE
 KNOW, THESE ARE REQUIRED TO BE WIRED
 INLINE AND WILL NOT WORK AS SHOWN.
 PLEASE BE SURE CIRCUIT SI ONE CONTAINING
 ARC FAULT PROTECTION.
  
 6)NOTE: OK
  
 7)NOTE: OK, HOWEVER PLEASE NOW SEE BATH
 CIRCUITS ARE BEING NOTED AS ARC FAULT??
 THIS IS NOT REQUIRED , HOWEVER CAN BE
 DONE AS AN ARC FAULT/GFI BRKR IS NOW
 MADE. PLEASE CALL TO GO OVER THIS.
  
 **PLEASE SEE BATH CIRCUIT SHOWN AS
 #15 AWG? MISPRINT.
 PLEASE ALSO SEE BATH CIRCUITS ARE SHOWN
 WITH ARC FAULT BRKRS?
  
 8)NOTE: NO, SAME COMMENT.
  
 ** PLEASE SEE MISSING KITCHEN
 COUNTER SPACE RECEPTS PER 210.52C1
  
 9)NOTE:NO, SAME COMMENT
  
 **PLEASE SEE MISSINGFRONT/REAR GFI
 RECEPT PER 210.52E
  
 10)NOTE: OK.
  
 NEW NOTE:
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS.
  
 2) NOTE: PLEASE SEE REDLINED PLANS FOR
 MISSING RECEPTS PER 210.52
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE ON CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-20 Cont ID  
Sent By dpalmer Date 2006-01-20 Time 22:37 Rev Time 0.00
Received By dpalmer Date 2006-01-20 Time 22:33 Sent To M
Notes
2006-01-20 00:00:00******** UNSAT ************
  
 1)NOTE: PLEASE SEE MISSING FIRM LICENSE
 NUMBER ON TITLE BLOCK FOR ARCHITECTUAL
 FIRM. FAC 61G1-16.004, FS 481.219
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 2)NOTE: PLEASE SEEELECTRICAL PLANS ARE
 SIGNED , DATED AND SEALED BY AN
 ELECTRICAL ENGINEER, HOWEVER PLANS DO
 NOT CONTAIN ANY TITLE BLOCK FOR SAID
 ENGINEER OF RECORD AS REQUIRED PER FAC
 61G15-23.002, FS 471.023
  
 3)NOTE: PLEASE VERIFY THE 1/2" CONDUIT
 SHOWN FOR FUTURE PHONE. IT IS KNOWN TO
 THIS OFFICE THE TELEPHONE COMPANY AND
 CABLE COMPANY REQUIRES A MIN OF 3/4"
 CONDUIT FOR UNDERGROUND INSTALLATIONS.
 THIS IS FOR INFORMATIONAL PURPOSE ONLY
 AS THIS IS NOT AN NEC REQUIREMENT.
  
 4)NOTE: PLEASE CORRELATE LOAD FOR RANGE
 IN LOAD CALCS WITH LOAD ON PANEL
 SCHEDULE.
 PLEASE VERIFY IF INDEED A 40A BRKR WILL
 BE USED AS MOST RANGES REQUIRE A MIN OF
 50A. (RANGE RECEPT IS 50A)
 PLEASE ALSO VERIFY WIRING METHODS TO BE
 USED. PLANS INDICATE CONDUIT AND WIRING,
 HOWEVER IF ROMEX IS USED, THE #8 SHOWN
 WOULD BE REQUIRED TO BE INCREASED TO #6.
 SEE 310.16, 60 DEGREE COL.
 215.5
  
 5)NOTE: PLEASE SEE SD'S ARE SHOWN BEING
 WIRED TO MORE THAN ONE CIRCUIT. PLEASE
 KNOW, THESE ARE REQUIRED TO BE WIRED
 INLINE AND WILL NOT WORK AS SHOWN.
 PLEASE BE SURE CIRCUIT SI ONE CONTAINING
 ARC FAULT PROTECTION.
  
 6)NOTE: PLEASE SEE ITEMS LISTED
 "OFF"PANEL SCHEDULE.
  
 7)NOTE: PLEASE SEE BATH CIRCUIT SHOWN AS
 #15 AWG? MISPRINT.
 PLEASE ALSO SEE BATH CIRCUITS ARE SHOWN
 WITH ARC FAULT BRKRS?
  
 8)NOTE: PLEASE SEE MISSING KITCHEN
 COUNTERSPACE RECEPTS PER 210.52C1
  
 9)NOTE: PLEASE SEE MISSING REAR GFI
 RECEPT PER 210.52E
  
 10)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES LANSCAPE LTS, HOWEVER PLANS DO
 NOT SHOW ANY. PLEASE KNOW, IF NONE SHOWN
 ON PLANS, THEN LANDSCAPE LIGHTING WILL
 BE REQUIRED TO BE UNDER A SEPARATE
 PERMIT, WHICH WILL INCLUDE PERMIT, PLANS
 AND FEE.
  
 ** PLEASE VERIFY WIRING METHOD, AS PLANS
 INDICATE CONDUIT AND WIRING FOR ALL
 CIRCUITS. IF SHOWN , ROMEX WOULD NOT BE
 PERMITTED.
 THIS IS ONLY A NOTE.
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 REVIEWERS WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE ON CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-01-04 Cont ID  
Sent By adarroug Date 2008-01-04 Time 09:19 Rev Time 0.00
Received By adarroug Date 2008-01-04 Time 09:19 Sent To P
Notes
2008-01-04 09:20:18TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-05 Cont ID  
Sent By adarroug Date 2006-09-05 Time 13:42 Rev Time 0.00
Received By adarroug Date 2006-09-05 Time 13:42 Sent To E
Notes
2006-09-05 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-11 Cont ID  
Sent By adarroug Date 2006-05-11 Time 16:52 Rev Time 0.00
Received By adarroug Date 2006-05-11 Time 16:52 Sent To E
Notes
2006-05-11 00:00:00TO "DPALMER' DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 13:06 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 13:06 Sent To Z
Notes
2006-05-06 00:00:00TO "Z" BOX/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-03-13 Time 13:06 Rev Time 0.00
Received By adarroug Date 2006-01-13 Time 14:27 Sent To  
Notes
2006-01-13 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-05-15 Cont ID  
Sent By tgordon Date 2006-05-15 Time 10:44 Rev Time 0.20
Received By tgordon Date 2006-05-15 Time 10:44 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-25 Cont ID  
Sent By tgordon Date 2006-01-25 Time 10:44 Rev Time 0.30
Received By tgordon Date 2006-01-25 Time 10:44 Sent To B
Notes
2006-01-25 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A .
  
 2) NEED A/C CONTRACTOR'S LICENCE NUMBER,
 NAME, AND SIGNATURE ON MECHANICAL PLANS.
 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 3)NEED JOB SITE ADDRESS ON MECHANICAL
 PLANS.
  
 4) SUPPLY AIR DUCT FROM AHU TO MIXING
 BOX FOR MASTER BEDROOM IS NOT SIZED.
  
 5) RETURN AIR TRANSFER DUCT FROM AHU TO
 MASTER BEDROOM IS SHOWING TWO DIFFERENT
 SIZES, PLEASE CORRECT.
  
 6) MECHANICAL PLANS HAVE TO MUCH FLOOR
 PLAN INFOMATION ON THEM AND ARE
 DIFFICULT TO READ. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-05-16 Cont ID  
Sent By jleech Date 2006-05-16 Time 07:11 Rev Time 0.00
Received By jleech Date 2006-05-16 Time 07:11 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-13 Cont ID  
Sent By jleech Date 2006-03-13 Time 12:20 Rev Time 0.00
Received By jleech Date 2006-03-13 Time 12:19 Sent To  
Notes
2006-03-13 00:00:00DENIED;
 1. SEE ELECTRICAL PLAN REVIEW NOTE ONE.
 2.WATER RISER, WATER HAMMER ARRESTORS
 ARE REQUIRED ON THE AUTOMATIC CLOTHES
 WASHER AND ON KITCHEN SINK. FBC-2004
 PLUMBING SEC.604.9.
 3.HOUSE SHUTOFF VALVE REQUIRED ON WATER
 SERVICE. SEC.606.
 4.3" PIPE REQUIRED FOR AUTOMATIC CLOTHES
 WASHER. SEC.406.3.
 5.KITCHEN SINK WASTE ARM CAN ONLY BE 6'
 FROM A VENT.SEE TABLE906.1. USE A
 MACHANICAL VENT UNDER THE SINK.
 6. REMOVE NOTE 26. SEE SEC. 608. NO
 CROSS CONNECTIONS ARE PERMITED IN THE
 WATER SYSTEM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2006-05-11 Cont ID  
Sent By mmclean Date 2006-05-11 Time 15:38 Rev Time 0.00
Received By mmclean Date 2006-05-11 Time 15:38 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By mmclean Date 2006-01-20 Time 19:34 Rev Time 0.00
Received By mmclean Date 2006-01-20 Time 19:34 Sent To E
Notes
***NONE***