| 2006-03-10 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- PAY IMPACT FEES TO PALM BEACH COUNTY. |
| | BRING BACK STAMPED DRAWINGS AND PAID |
| | RECEIPT. |
| | |
| | 2- PROVIDE DRAINAGE PLANS AS REQUIRED BY |
| | SEC. R401.3 OF 2004 RESIDENTIAL CODE. |
| | |
| | 3- PROVIDE STRUCTURAL BUCK DETAIL USING |
| | 2X BUCK AS REQUIRED BY ENTRY DOOR |
| | PRODUCT APPROVAL SUBMITTED. SEE SECTION |
| | R613.6.2 2004 RESIDENTIAL CODE FOR |
| | PROPER BUCK INSTALLATION. |
| | |
| | 4- OWES $351.21 FOR UPDATED VALUATION |
| | AND RADON FEES. |
| | |
| | 5- PROVIDE SPECS/DETAILS FOR |
| | INSTALLATION OF DECORATIVE STORM |
| | SHUTTERS. SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004. |
| | |
| | 6- DRAWINGS S-2 AND S-3 ARE MISSING THE |
| | ENGINEER'S INFORMATION AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTES. |
| | |
| | 7- A) PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR SLIDING GLASS DOORS AND |
| | FRENCH DOORS WITH TRANSOM ABOVE SINGLE |
| | UNIT AS SHOWN ON PLANS OR PROVIDE |
| | COMPLETE INFORMATION FOR STRUCTURAL |
| | MULLION AS REQUIRED BY SEC. R613.7 2004 |
| | RESIDENTIAL CODE. |
| | B) SPECIFY SIZE OF FIXED WINDOW. |
| | |
| | 8- ARCHITECT TO PROVIDE ALLINFORMATION |
| | ON TITLE BLOCK AS REQUIRED BY CHAPTER |
| | 481 FLORIDA STATUTES AND 61G1-16.004 OF |
| | ADMINISTRATIVE CODE. SEE ATTACHED COPY. |
| | |
| | 9- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL AS REQUIRED BY RULE 9B-72 FOR: |
| | A) FRENCH DOORS WITH TRANSOM ABOVE. |
| | OR FRENCH DOORS ALONE. SEE ITEM #7 ABOVE |
| | B) SLIDING GLASS DOORS WITH TRANSOM |
| | ABOVE. OR SLIDING GLASS DOORS ALONE. SEE |
| | ITEM #7 ABOVE. |
| | C) STRUCTURAL MULLIONS. SEE ITEM #7. |
| | D) FIXED WINDOWS. SEE ITEM #7 ABOVE. |
| | E) ALL TRUSS CONNECTORS. SEE PLANS. |
| | F) SINGLE HUNG WINDOWS. DADE COUNTY |
| | NOA TO MATCH NOA SUBMITTED FOR FLORIDA |
| | PRODUCT APPROVAL. VISIT |
| | WWW.FLORIDABUILDING.ORG TO DOWNLOAD |
| | CORRESPONDING NOA. |
| | G) ROOF SHINGLES. PROVIDE SAME NOA |
| | SUBMITTED FOR FLORIDA PRODUCT APPROVAL. |
| | H) PRECAST LINTELS. |
| | I) ALUMINUM VENTS. |
| | J) ALUMINUM SIDING. |
| | |
| | 10- DESIGNER OF RECORD TO REVIEW AND |
| | APPROVE IN WRITTING ALL PRODUCT |
| | APPROVALS PRIOR TO SUBMITTAL TO THIS |
| | OFFICE AS REQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 11- DRAWING 1: UPDATE BUILDING CODE |
| | DATA. SEE 2004 RESIDENTIAL CODE. |
| | |
| | 12- DRAWING A-1: A) WINDOW C (3'-0" X |
| | 4'-0") DOESN'T MEET THE EGRESS |
| | REQUIREMENTS OF SEC. R310.1.2 2004 |
| | RESIDENTIAL CODE. |
| | B) SPECIFY SAFETY GLASS FOR WINDOW IN |
| | BATHROOM. SEE PLANS. SEC. R308.4 2004 |
| | RESIDENTIAL CODE. |
| | C) UPDATE CODE REFERENCE FOR ATTIC |
| | ACCESS. SEE 2004 RESIDENTIAL CODE. |
| | D) UPDATE CODE REFERENCES SPECIFIED |
| | ON GENERAL NOTES AND SCHEDULE NOTES. SEE |
| | 2004 RESIDENTIAL CODE. |
| | |
| | 13- DRAWING A-2: A) DESIGN PRESSURES |
| | MARK DOESN'T MATCH MARK SHOWED ON DOORS |
| | AND WINDOWS OPENINGS. REVISE AS REQ'D. |
| | B) SPECIFY SIZE OF MANUFACTURED |
| | ALUMINUM LOUVER AT FRONT AND BACK. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 14- DRAWING A-3: A) WHERE IS DETAIL A-5" |
| | SPECIFIED ON PLANS? |
| | B) SECTION "A": 1) THERE IS NOT |
| | ARCHED PORCH BEAM. REVISE AS REQUIRED. |
| | 2) WHERE IS DETAIL SHT 5? |
| | 3) SPECIFIED FIREBLOCKING MATERIAL |
| | AND LOCATION AT CONCEALED SPACES IN |
| | SOFFITS AND WALLS. SEE PLANS. SEC. |
| | R602.8 2004 RESIDENTIAL CODE. |
| | |
| | 15- DRAWING A-4: A) WALL SECTION "A". |
| | UPDATE CODE REFERENCE SPECIFIED FOR |
| | FIREBLOCKING AND SPECIFY FIREBLOCKING |
| | MATERIAL. SEE 2004 RESIDENTIAL CODE. |
| | B) WALL SECTION "B". FOUNDATION PLAN |
| | DOESN'T MATCH PLANS. REVISE AS REQUIRED. |
| | C) PORCH BEAM IS NOT AN ARCHED BEAM. |
| | REVISE AS REQUIRED. SEE PLANS. |
| | |
| | 16- DRAWING S-1: A) PROVIDE COMPLETE |
| | DETAILS AND SPECS FOR WOOD DECK AND WOOD |
| | STEPS AT REAR AREA OUTSIDE MASTER |
| | BEDROOM AND AT COVERED PORCH. |
| | B) ROOF FRAMING PLAN CALLS FOR TRUSS |
| | ANCHOR A3 BY REAR PORCH. THERE IS NOT |
| | A3. REVISE AS REQUIRED. |
| | C) WHERE ARE DETAILS A, C AND E? |
| | D) WWHERE IS DET 2 SHT S-2?. |
| | KEY DETAILS TO MATCH DRAWINGS. |
| | |
| | 17- DRAWING S-2: A) TYP. 1 STORY |
| | SECTION: SPECIFY SIZE AND LOCATION OF |
| | ATTIC VENTS. ALSO, CONSIDER ALUMINUM |
| | VENTS FOR TOTAL VENTING AREA REQUIRED. |
| | SEC. R806 2004 RESIDENTIAL CODE. |
| | B) DETAIL D: 1) HOW IS 2"X6" SILL |
| | PLATE ATTACHED TO CONCRETE BEAM? |
| | 2) HOW IS 2" X 6" "L" BRACE NAILED TO |
| | BOTTOM SILL? |
| | 3) USP TA18 IS SHOWN AS BEING |
| | ATTACHED TO CONCRETE BEAM. THIS |
| | CONNECTOR IS TO BE EMBEDED IN CONCRETE. |
| | REVISE AS REQUIRED. SEE USP CATALOGUE. |
| | 4) DETAIL A: SHOW COMPLETE DETAILS |
| | AND SPECS FOR CONCRETE STEPS AT ENTRY |
| | PORCH. |
| | |
| | 18- DRAWING S-3: A) GENERAL NOTES: |
| | UPDATE ALL REFERENCE STANDARDS AND |
| | SPECIFIC EDITION TO BE USED. SEE 2004 |
| | RESIDENTIAL CODE AND 2004 FBC. |
| | B) UPDATE CODE SECTIONS REFERENCED |
| | FOR WIND LOADS, EMERGENCY EGRESS AND |
| | GLASS IMPACT PROTECTION NOTES. |
| | C) VENTILATION AND EGRESS ARE TWO |
| | DIFFERENT CODE ISSUES.REVISE AS REQ'D. |
| | D) TRUSS ANCHOR SCHEDULE: NUMBER OF |
| | NAILS AND UPLIFT LOADS TO MATCH CURRENT |
| | USP CATALOGUE. OTHERWISE, PROVIDE |
| | COMPLETE ENGINEERING ANALYSIS FOR NUMBER |
| | AND UPLIFT LOADS THAT DIFFER THOSE |
| | PUBLISHED BY MANUFACTURER. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004. |
| | E) DELETE NOTES CORRESPONDING TO |
| | STRUCTURE ADDITIONS. THEY DON'T APPLY TO |
| | THIS PROJECT. |
| | |
| | 19- SURVEY TO HAVE SURVEYOR'S ORIGINAL |
| | SIGNATURE, NOT COPY, AS REQUIRED BY |
| | CHAPTER 472 FLORIDA STATUTES. |
| | |
| | 20- STORM SHUTTERS: |
| | A) PROVIDE KEY PLAN. |
| | B) PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE. PROVIDE |
| | ALL INFORMATION. |
| | |
| | 21- ENERGY CALCULATIONS: |
| | A) USE 2004 FORM, NOT 2001. |
| | B) BUILDING ORIENTATION, OVERHANG |
| | LENGTH AND HEIGHT AND AREA DON'T MATCH |
| | PLANS. REVISE AS REQUIRED. SEE CHAPTER |
| | 13 FBC 2004 FOR PRROPER WAY OF |
| | CALCULATING ENERGY CALCS. REVISE AS |
| | REQUIRED. |
| | ***NOTE: IF ENERGY CALCULATIONS ARE NOT |
| | DONE FOR WORST CASE SCENARIO, THEN THEY |
| | MUST BE DONE ACCORDING TO THE ACTUAL |
| | HOUSE ORIENTATION. SEE SURVEY FOR |
| | CORRECT ORIENTATION. |
| | C) OWNER/AGENT TO SIGN BOTTOM OF FORM |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |