Plan Review Details - Permit 06010354
Plan Review Stops For Permit 06010354
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-06-21 Cont ID  
Sent By rmcdouga Date 2006-06-21 Time 13:49 Rev Time 0.00
Received By rmcdouga Date 2006-06-21 Time 13:49 Sent To  
Notes
2006-06-21 00:00:00DENIED
  
 1) THE TWO SETS OF PLANS SUBMITTED HAVE
 ITEMS THAT HAVE BEEN WHITED-OUT NAD
 CHANGED. ANY CHANGES MADE TO SIGNED AND
 SEALED PLANS ARE REQUIRED TO BE DONE BY
 THE DESIGNER OF RECORD. THE D.O.R. MUST
 INITAL AND DATE ALL RED LINED CHANGES.
  
 2) PLEASE INDICATE WHAT IS ON THE OTHER
 SIDE OF THE NEW DEMISING WALL THAT YOU
 ARE PROPOSING. SPECIFY THE OCCUPANCY,
 DIMENSIONS, EXITS, ACCESSIBLE BATHROOMS,
 ETC.
  
 3) THE EXISTING DEMISING WALL BETWEEN
 UNITS 200 AND 206 APPEARS TO HAVE BEEN
 BUILT WITHOUT PERMITS. IT LEAVES UNIT
 206 WITHOUT AN ACCESSIBLE BATHROOM.
 PLEASE PROVIDE THE PERMIT NUMBER UNDER
 WHICH THIS WALL WAS CONSTRUCTED.
  
 4) THE GOOD FAITH ESTIMATE LISTING THE
 TENANT SPACE AREAS SHOULD BE NUMBERED TO
 CORRESPOND WITH THE UNIT NUMBERS ON THE
 PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-24 Cont ID  
Sent By rmcdouga Date 2006-04-24 Time 9:42 Rev Time 0.00
Received By rmcdouga Date 2006-04-24 Time 7:12 Sent To  
Notes
2006-04-24 00:00:00DENIED BY BUILDING
  
 1) THE APPLICATION IS TO ADD A DEMISING
 WALL/INTERIOR FIREWALL AT UNIT #200 AT
 4047 OKEECHOBEE BLVD. THE NOC GIVES THE
 DISCRIPTION OF IMPROVEMENTS AS A TENANT
 BUILDOUT OFFICES AT THE SAME LOCATION.
 THE PLANS SHOW A NEW TENANT SEPARATION
 WALL BETWEEN UNITS 204 AND 205 AND
 EXISTING WALLS IN UNITS 205 AND 206. THE
 TITLE BOCK ON THE PLANS STATES BUILDOUT
 UNIT 205-206 DEMISING WALLS. CLARIFY AND
 SPECIFY THE TOTAL SCOPE OF PROPOSED WORK
 ON THE PLANS. INDICATE THE TOTAL SCOPE
 OF WORK TO BE DONE ON THE APPLICATION
 AND NOC, WHICH MUST AGREE WITH THE WORK
 INDICATED ON THE PLANS. ADJUST VALUE OF
 CONSTRUCTION, IF NECESSARY. INDICATE THE
 UNIT NUMBERS WHERE THE WORK WILL BE DONE
 ON THE PLANS, APPLICATION AND NOC.
 PROVIDE THIS INFORMATION TO THE INTAKE
 PERSON WHEN RESUBMITTING SO THAT THE
 CORRECT INFORMATION CAN BE INPUT INTO
 THE COMPUTER.
  
 2) INDICATE THE LOCATION OF FIRE RATED
 TENANT SEPARATION WALL THAT YOU ARE
 PROPOSING TO INSTALL. PROVIDE THE
 INFORMATION REQUESTED IN THE FIRST
 REVIEW FOR THE UNITS ON EACH SIDE OF THE
 PROPOSED WALL.
  
 3) IF YOU ARE ADDING INTERIOR WALLS, THE
 EXISTING FIRE SPRINKLER SYSTEM WILL BE
 AFFECTED. THE LOCATION OF THE SPRINKLER
 HEADS WILL HAVE TO BE ASSESSED TO
 DETERMINE IF ADEQUATE COVERAGE WILL BE
 PROVIDED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-13 Cont ID  
Sent By rmcdouga Date 2006-01-13 Time 14:38 Rev Time 0.00
Received By rmcdouga Date 2006-01-13 Time 14:38 Sent To  
Notes
2006-01-13 00:00:00DENIED
  
 1) SPECIFY THE OCCUPANCY OF AREAS ON
 EACH SIDE OF THE TENANT SEPARATION
 WALLS. SEE 2004 FBC 302
  
 2) SPECIFY THE LOCATIONS OF THE EXITS.
 SEE FBC 1018.
  
  
 3) PROVIDE DIMENSIONS ON THE PLANS IN
 ORDER TO DETERMINE OCCUPANT LOADS. SEE
 FBC 1004.1.2
  
 4) CLARIFY THE RESTROOM LAYOUT.
 LOCATIONS OF WALLS AND DOORS. SEE FBC
 1015 AND 1018.
  
 5) CLARIFY WHY A SECTION OF THE ONE HOUR
 RATED TENANT SEPARATION WALL IS
 SPECIFIED WITH 2 LAYERS ON 5/8" TYPE X
 DRYWALL. NOTE: THE UL WALL ASSEMBLY
 SPECIFIED REQUIRES DRYWALL ON EACH SIDE
 OF WALL.
  
 6) CLARIFY DEMISING CEILING AS SPECIFIED
 ON PLANS AT RESTROOMS. IS IT EXISTING,
 FIRE RATED, ETC.?
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-24 Cont ID  
Sent By jleahy Date 2006-06-24 Time 09:11 Rev Time 0.30
Received By jleahy Date 2006-06-24 Time 09:11 Sent To  
Notes
2006-06-27 00:00:00PLEAS SHOW ELECTRIC FOR BATH AND THE
 REST OF THE SPACE.SEE FORMER REVIEW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-21 Cont ID  
Sent By jleahy Date 2006-04-21 Time 08:10 Rev Time 0.30
Received By jleahy Date 2006-04-21 Time 08:09 Sent To  
Notes
2006-04-21 00:00:00SEE NOTES FROM FIRST PLAN REVIEW.
  
 THIS BATHROOM LOOKS LIKE IT WAS IN THE
 OTHER SPACE SHOW HOW ELECTRIC IS DONE.
  
 ONE SPACE CANNOT BE FED FROM ANOTHER
 SPACE.
  
 JAKE

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-18 Cont ID  
Sent By jleahy Date 2006-01-18 Time 22:06 Rev Time 0.30
Received By jleahy Date 2006-01-18 Time 22:06 Sent To FIRE
Notes
2006-01-18 00:00:00IF BATHROOM WAS IN THE OTHER TENENT
 SPACE HOW WAS THE ELECTRIC CHANGED?
  
 PLEASE SHOW HOW CIRCIT(S) TO BE CHANGED
  
  
 JAKE LEAHY644-7291

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-06-27 Cont ID  
Sent By mwennerg Date 2006-06-27 Time 15:23 Rev Time 0.00
Received By mwennerg Date 2006-06-27 Time 15:23 Sent To  
Notes
2006-06-27 00:00:00***DENIED***
  
 1) PLEASE NOTE THAT THE ADDITION OF
 WALLS MAY HAVE A DIRECT IMPACT ON FIRE
 SPRINKLER COVERAGE. THE FIRE SPRINKLER
 SYSTEM IS ARRANGED BASED ON SQUARE FEET
 PER AREA OF HAZARD. THE INTRODUCTION OF
 NEW WALLS WOULD IMPACT THIS PREVIOUS
 CALCULATION.
  
 2) PLEASE SEE BUILDING REVIEW COMMENTS
 AS SOME CONFUSION DOES SEEM TO EXIST IN
 REGARDS TO THIS SCOPE OF WORK AND
 PREVIOUS WORK.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-04-25 Cont ID  
Sent By mwennerg Date 2006-04-25 Time 15:45 Rev Time 0.00
Received By mwennerg Date 2006-04-25 Time 15:45 Sent To  
Notes
2006-04-25 00:00:00******DENIED******
  
 1) COMMENTS FROM FIRST REVIEW HAVE BEEN
 ADDRESSED, HOWEVER THERE APPEARS TO BE
 SOME CONFUSION REGARDING THE SCOPE OF
 WORK AS IT APPLIES TO THIS PERMIT
 APPLICATION AND THE NOC. PLEASE CLARIFY.
 PLANS WILL BE STAMPED WHEN RETURNED FOR
 OTHER REVIEW NOTES.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-01-19 Cont ID  
Sent By mwennerg Date 2006-01-19 Time 09:33 Rev Time 0.00
Received By mwennerg Date 2006-01-19 Time 09:33 Sent To  
Notes
2006-01-19 00:00:00******DENIED******
  
 1) PLEASE PROVIDE THE COMPLETE LAYOUT OF
 THESE SPACES TO INCLUDE EXIT SIGNS, AND
 EMERGENCY LIGHTING LOCATIONS. (NEW OR
 EXISTING)
  
 2) 2A-10B,C RATED FIRE EXTINGUISHER IS
 REQUIRED. SPACING SHALL MEET THE 75'
 TRAVEL DISTANCE REQUIREMENT.
  
 3) IS THIS SPACE PROTECTED BY FIRE
 SPRINKLER AND OR FIRE ALARM SYSTEMS? IF
 SO, WILL ANY REQUIRED EQUIPMENT BE
 EFFECTED BY THIS WORK?
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 16:53 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 16:53 Sent To  
Notes
2006-06-21 00:00:00TO "BOB"#16
2006-06-14 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-04-18 Time 09:31 Rev Time 0.00
Received By adarroug Date 2006-04-18 Time 09:31 Sent To  
Notes
2006-04-19 00:00:00TO "BOB"#18
2006-04-18 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-18 Cont ID  
Sent By adarroug Date 2006-01-19 Time 09:31 Rev Time 0.00
Received By adarroug Date 2006-01-12 Time 10:16 Sent To  
Notes
2006-01-12 00:00:00TO "BOB"#1