Plan Review Details - Permit 06010343
Plan Review Stops For Permit 06010343
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-10 Cont ID  
Sent By alange Date 2006-02-10 Time 15:29 Rev Time 3.00
Received By alange Date 2006-02-10 Time 08:22 Sent To  
Notes
2006-02-10 00:00:00DENIED
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3.PRODUCT APPROVALS SUBMITTED SHALL
 SHOW APPROVAL BY THE DESIGNER OF RECORD.
  
 4.PRODUCT APPROVALS REQUIRED FOR
 OVERHEAD DOOR, LINTELS AND STRAPS AND
 TIE-DOWNS.
  
 5.ALL PRODUCT APPROVALS SUBMITED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.SIGN OWNER/AGENT ON ENERGY CALCS.
  
 7.ON THE JOHNS MANSVILLE ROOFING
 PRODUCT APPROVAL SELECT THE ROOFING
 ASSEMBLY UESD.
  
 8. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 9.SUBMIT DETAIL FOR SPIRAL STAIRS.
 INCLUDE WIDTH, CENTER DEPTH OF TREAD AND
 RISER HEIGHT.
  
 10.BASED ONN ICC BUILDING VALUATION
 DATA THE PERMIT VALAUATION HAS BEEN
 REVISED TO
 $253,875ADDITIONAL PERMIT FEES ARE
 DUE.
  
 11.SUBMIT SPECIFICATIONS FOR GAS BBQ
 AND REQUIRED HOOD.
  
 12.PLEASE SIGN AND SEAL ALL PAGES.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-12 Cont ID  
Sent By btrobaug Date 2006-01-12 Time 14:06 Rev Time 0.75
Received By btrobaug Date 2006-01-12 Time 12:34 Sent To Z
Notes
2006-01-12 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ARCHITECT MUST COMPLY WITH FS
 481, SEAL AND SIGN PLANS.
  
 2} THE REQUIRED LAUNDRY CIRCUIT PER
 210.16(B) IS NOT IN THE LOAD CALC, NOR
 THE POOL HAETER OR STEAMER. PLEASE
 CORRELATE THE CALCULATIONS WITH THE
 EQUIPMENT AND BRANCH CIRCUITS ON THE
 PANEL SCHEDULES.
  
 3} PLEASE LIST THE CORRECT CONDUCTOR AND
 OVERCURRENT PROTECTION FOR THE AIR
 HANDLERS, SEE PANEL "B".
  
 4} THE SMALL APPLIANCE CIRCUITS MUST BE
 SHOWN ON THE PANEL SCHEDULE.
 210.11(C)(3).
  
 5} THE GROUNDING ELECTRODE SYSTEM NEEDS
 TO INCLUDE TO THE FOOTER STEEL. 250.52.
  
 6} A SMOKE DETECTOR IS REQUIRED ON THE
 3RD LEVEL PER 313.1 FBC.
  
 7} THE DISCONNECTS SHOWN FOR THE POOL
 AND A/C UNITS MUST COMPLY WITH 110.26
 CLEARANCE REQUIREMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By adarroug Date 2006-01-12 Time 09:40 Sent To  
Notes
2006-01-12 00:00:00TO "SFR" "Z"/COPY OF APPL SENT TO ADDR.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-25 Cont ID  
Sent By tgordon Date 2006-01-25 Time 16:02 Rev Time 0.15
Received By tgordon Date 2006-01-25 Time 16:02 Sent To B
Notes
2006-01-25 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 2) NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.
  
 3)NEED TO FILE A NOTICE OF COMMENCEMENT,
 PER F. S. 713.13 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-18 Cont ID  
Sent By jleech Date 2006-01-18 Time 13:44 Rev Time 1.00
Received By jleech Date 2006-01-18 Time 13:43 Sent To Z
Notes
2006-01-18 00:00:00DENIED;
 1.SHOW ROOF DRAINAGE PER. FBC-2004
 PLUMBING CHAPTER 11. GUTTERS AND DOWN
 SPOUTS REQUIRED. PLEASE SIZE AND SHOW ON
 DRAWINGS. RAIN WATER MUST DISCHARGE A
 MINIMUM OF 12" FROM BUILDING.
 2.SHOW SIZE AND QUANITY OF SCUPPERS ON
 PORCHES.
 3.FLOOR DRAIN NOT PERMITED IN ELEVATOR
 PIT. HYDROLIC FLUID CAN NOT DISCHARGE
 INTO DRAINAGE SYSTEM.
 4.RISER DIAGRAM; 1ST FLOOR LAVITORY AND
 W/C ARE NOT VENTED.
 5.3" RISER TO 2ND AND 3RD FLOOR PLUMBING
 SHOULD BE DOWN STREAM OF FIRST FLOOR
 BATHROOM.
 6.2ND FLOOR KITCHEN SINK (SINGLE BOWL)
 NOT VENTED.
 7.MASTER BATHROOM W/M MUST DISCHARGE
 DOWN STREAM OF THE BATHROOM GROUP. SEC
 909.1.
 8.SIZE ALL SECTIONS OF PIPE ON RISER
 DIAGRAM.
 9.3RD FLOOR SHOWER NOT VENTED.
 SEE ONE SET OF PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-25 Cont ID  
Sent By mmclean Date 2006-01-25 Time 14:02 Rev Time 0.00
Received By mmclean Date 2006-01-20 Time 19:33 Sent To M
Notes
2006-01-25 00:00:00APPROVED, VARIANCE 1-6-05 #2135 (JOSH
 LONG, PLANNER ASSIGNED TO PROJECT)