Plan Review Details - Permit 06010340
| Plan Review Stops For Permit 06010340 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-01-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-01-13 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-02-07 |
Time |
19:34 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2006-02-07 |
Time |
19:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2006-02-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-02-03 |
Time |
11:35 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2006-02-03 |
Time |
11:34 |
Sent To |
PC |
|
| Notes |
| 2006-02-03 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- ENGINEER'S CALCULATIONS REFER TO DADE | | | COUNTY NOA #01-0130.01. CONTRACTOR FAXED | | | DADE COUNTY NOA #03-0819.04. INFORMATION | | | DON'T MATCH. | | | THESE TWO NOA'S ARE DIFFERENT BECAUSE | | | NOA #01-0130.01 HAVE LIMITATION #9 FOR | | | THIS ROOF ASSEMBLY, WHILE NOA | | | #03-0819.04 HAVE LIMITATION #7. | | | ENGINEER'S LETTER TO ADDRESS WHICH NOA | | | HE IS ANALYSING AND SPECIFIC PAGE OF | | | SELECTED ROOF ASSEMBLY. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-02-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-02-02 |
Time |
10:47 |
Rev Time |
0.33 |
| Received By |
jgomez |
Date |
2006-02-02 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2006-02-02 00:00:00 | BUILDING REVIEW THIRD CHECKLIST: | | | 1- SAME COMMENT FROM SECOND CHECKLIST: | | | SELECTED FLAT ROOF SYSTEM IS LIMITED TO | | | A MAXIMUM DESIGN PRESSURE OF -45PSF AND | | | BY GENERAL LIMITATION #9, WHICH DOESN'T | | | ALLOW ADDITIONAL NAIL ENHANCING TO | | | INCREASE THE DESIGN PRESSURES. | | | | | | 2- A) ENGINEERED CALCULATIONS SUBMITTED | | | ARE NOT ALLOWED BECAUSE OF GENERAL | | | LIMITATION #9 OF ROOF ASSEMBLY SELECTED. | | | ENGINEERED CALCULATIONS CAN ONLY BE | | | PROVIDED WHEN GENERAL LIMITATION #7 | | | APPLIES. | | | | | | B) ENGINEER TO CLEARLY IDENTIFY EXACT | | | ROOF ASSEMBLY THAT IS REFERENCED IN THE | | | PRODUCT APPROVAL WHEN SUBMITTING THE | | | CALCULATIONS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-01-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-01-30 |
Time |
12:46 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2006-01-30 |
Time |
12:45 |
Sent To |
PC |
|
| Notes |
| 2006-01-30 00:00:00 | BUILDING REVIEW 2ND CHECKLIST: | | | 1- NEED NOTICE OF COMMENCEMENT SHOWING | | | THE NEW ROOFING CONTRACTOR. NONE | | | SUBMITTED. | | | | | | 2- FLAT ROOF SYSTEM SELECTED DOESN'T | | | WORK. SYSTEM IS LIMITED TO A MAXIMUM | | | DESIGN PRESSURE OF -45PSF AND BY GENERAL | | | LIMITATION #9 WHICH DOESN'T ALLOW | | | ADDITIONAL NAIL ENHANCING TO INCREASE | | | THE DESIGN PRESSURES AT PERIMETER AND | | | CORNER AREAS. ACCORDING TO TABLE 1609.6B | | | FBC 2004 NEED ROOF SYSTEM WITH DESIGN | | | PRESSURES OF -89PSF OR MORE. THIS WAS | | | REQUESTED ON FIRST CHECKLIST. | | | | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-01-13 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-01-13 |
Time |
17:29 |
Rev Time |
0.75 |
| Received By |
jgomez |
Date |
2006-01-13 |
Time |
17:29 |
Sent To |
PC |
|
| Notes |
| 2006-01-13 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- RESIDENTIAL CONTRACTOR (U-8299) SCOPE | | | OF WORK IS FOR RESIDENTIAL PROJECTS ONLY | | | (ONE AND TWO FAMILY DWELLINGS). | | | RESIDENTIAL CONTRACTOR IS NOT ALLOWED TO | | | DO COMMERCIAL JOBS OR FLAT ROOFS. | | | NEED ROOFING CONTRACTOR TO PERFORM THIS | | | ROOFING JOB. | | | | | | 2- NOTICE OF COMMENCEMENT NEEDS TO BE | | | REVISED SHOWING ROOFING CONTRACTOR. | | | | | | 3- DADE COUNTY NOA SUBMITTED WITH THE | | | FLORIDA PRODUCT APPROVAL FL 1358 IS | | | INCOMPLETE. IS MISSING THE SPECIFIC | | | APPROVED ASSEMBLY TO BE INSTALLED. SEE | | | ATTACHED CITY POLICY FOR RE-ROOFING | | | PERMITS FOR REQUIRED INFORMATION. | | | NEED TO SPECIFY WHICH ASSEMBLY IS GOING | | | TO BE INSTALLED TO VERIFY WHICH GENERAL | | | LIMITATION (#7 OR #9) APPLIES TO THE | | | SELECTED ASSEMBLY. INFORMATION REQUIRED | | | ON SUCH LIMITATIONS WILL BE REQUIRED TO | | | BE PROVIDED FOR BUILDING REVIEW. | | | EG: CALCULATIONS BY ARCHITECT OR | | | ENGINEER. | | | SEE GENERAL LIMITATIONS ON LAST PAGE OF | | | THE DADE COUNTY NOA. | | | | | | 4- VALUE DECLARED ON THE PERMIT | | | APPLICATION IS TOO LOW. IT WAS UPDATED | | | TO $10,516. THEREFORE, OWES $90.21. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
|