Plan Review Details - Permit 06010338
Plan Review Stops For Permit 06010338
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-02-07 Cont ID  
Sent By jgomez Date 2006-02-07 Time 19:11 Rev Time 0.50
Received By jgomez Date 2006-02-07 Time 19:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-02-03 Cont ID  
Sent By jgomez Date 2006-02-03 Time 10:55 Rev Time 0.50
Received By jgomez Date 2006-02-03 Time 10:55 Sent To PC
Notes
2006-02-03 00:00:00BUILDING REVIEW 4TH CHECKLIST:
 1- ENGINEER'S LETTER CALLS FOR 1/2"
 THICK ISO INSULATION. ACCORDING TO THE
 ROOF ASSEMBLY ON PAGE 31 OF DADE COUNTY
 NOA #01-0130.01 THE MINIMUM INSULATION
 THICKNESS IS 1.5". ENGINEER TO REVISE
 LETTER AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-02 Cont ID  
Sent By jgomez Date 2006-02-02 Time 10:27 Rev Time 0.33
Received By jgomez Date 2006-02-02 Time 10:27 Sent To  
Notes
2006-02-02 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- SAME COMMENT FROM 2ND CHECKLIST:
 SELECTED FLAT ROOF SYSTEM IS LIMITED TO
 A MAXIMUM DESIGN PRESSURE OF -45PSF AND
 BY GENERAL LIMITATION #9 WHICH DOESN'T
 ALLOW ADDITIONAL NAIL ENHANCING TO
 INCREASE THE DESIGN PRESSURES.
  
 2- A)ENGINEERED CALCULATIONS SUBMITTED
 ARE NOT ALLOWED BECAUSE OF LIMITATION #9
 OF SELECTED ROOF SYSTEM. CALCULATIONS
 CAN ONLY BE PROVIDED WHEN GENERAL
 LIMITATION #7 APPLIES.
  
 B) ADDITIONALY, ENGINEER TO
 CLEARLY IDENTIFY EXACT ROOF ASSEMBLY
 THAT IS REFERENCED IN THE PRODUCT
 APPROVAL WHEN SUBMITTING CALCULATIONS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-30 Cont ID  
Sent By jgomez Date 2006-01-30 Time 14:15 Rev Time 0.50
Received By jgomez Date 2006-01-30 Time 14:15 Sent To PC
Notes
2006-01-30 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 1- FLAT ROOF SYSTEM SELECTED DOESN'T
 WORK. SYSTEM IS LIMITED TO A MAXIMUM
 DESIGN PRESSURE OF -45PSF AND BY GENERAL
 LIMITATION #9 WHICH DOESN'T ALLOW
 ADDITIONAL NAIL ENHANCING TO INCREASE
 THE DESIGN PRESSURES AT PERIMETER AND
 CORNER AREAS. ACCORDING TO TABLE 1609.6B
 FBC 2004 NEED ROOF SYSTEM WITH DESIGN
 PRESSURES OF -89PSF OR MORE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-13 Cont ID  
Sent By jgomez Date 2006-01-13 Time 18:24 Rev Time 0.75
Received By jgomez Date 2006-01-13 Time 18:24 Sent To PC
Notes
2006-01-13 00:00:00BUILDING REVIEW CHECKLIST:
 1- RESIDENTIAL CONTRACTOR (U-8299) SCOPE
 OF WORK IS FOR RESIDENTAIL PROJECTS ONLY
 (ONE AND TWO FAMILY DWELLINGS).
 RESIDENTIAL CONTRACTOR IS NOT ALLOWED TO
 DO COMMERCIAL JOBS OR FLAT ROOFS.
 NEED ROOFING CONTRACTOR TO PERFORM THIS
 ROOFING JOB.
  
 2- NEED NOTICE OF COMMENCEMENT.
  
 3- DADE COUNTY NOA SUBMITTED WITH THE
 FLORIDA PRODUCT APPROVAL FL 1358 IS
 INCOMPLETE. IS MISSING THE SPECIFIC
 APPROVED ASSEMBLY TO BE INSTALLED. SEE
 ATTACHED CITY POLICY FOR RE-ROOFING
 PERMITS FOR REQUIRED INFORMATION.
 NEED TO SPECIFY WHICH ASSEMBLY IS GOING
 TO BE INSTALLED TO VERIFY WHICH GENERAL
 LIMITATION (#7 OR #9) APPLIES TO THE
 SELECTED ASSEMBLY. INFORMATION REQUIRED
 ON SUCH LIMITATIONS WILL BE REQUIRED TO
 BE PROVIDED FOR BUILDING REVIEW.
 EG: CALCULATIONS BY ARCHITECT OR
 ENGINEER. SEE GENERAL LIMITATIONS ON
 LAST PAGE OF THE DADE COUNTY NOA.
  
 4- VALUE DECLARED ON THE PERMIT
 APPLICATION IS TOO LOW. IT WAS UPDATED
 TO $19,120. THEREFORE, OWES $161.60.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.