Plan Review Details - Permit 06010282
Plan Review Stops For Permit 06010282
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-06-14 Cont ID  
Sent By jgomez Date 2006-06-14 Time 13:03 Rev Time 0.50
Received By jgomez Date 2006-06-14 Time 12:20 Sent To PC
Notes
2006-06-14 00:00:00NOC EXPIRED AFTER 90 DAYS IF WORK IS NOT
 STARTED. NEED RE-RECORDED NOC.
 APPLICATION UNDER "S". JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2006-03-28 Cont ID  
Sent By jgomez Date 2006-03-28 Time 14:32 Rev Time 1.00
Received By jgomez Date 2006-03-28 Time 14:32 Sent To  
Notes
2006-03-28 00:00:00BUILDING REVIEW 4TH CHECKLIST:
 1- ON THIRD PLAN REVIEW CHECKLIST,
 ENGINEER WAS ASKED TO REVIEW GENERAL
 LIMITATION #7 AND TO PROVIDE
 CALCULATIONS BASED ON THE STANDARD RAS
 117. INFORMATION SUBMITTED DOESN'T
 ADDRESS THIS COMMENT.
  
 2- ENGINEER TO SEE SPECIFIC ROOF PRODUCT
 APPROVAL SUBMITTED TO SEE APPROVED
 FASTENER TYPE AND SPACING AND MAXIMUM
 DESIGN PRESSURES ALLOWED FOR THE SYSTEM.
 INFORMATION SUBMITTED HAS NOT
 COORDINATION WITH PRODUCT APPROVAL.
 PRODUCT APPROVAL SYSTEM DESIGN PRESSURE
 OF -52.5PSF IS ASSUMED TO BE FOR ZONE
 ONE. ENGINEER NEEDS TO PROVIDE FASTENER
 ENHANCING TO RESIST DESIGN PRESSURES AT
 ZONES 2 AND 3.
  
 3- ENGINEER TO SEE ATTACHED COPY OF
 FLORIDA STATUTE 553.80(2)(B) REGARDING
 DESIGN PROFESSIONAL DOCUMENTS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-28 Cont ID  
Sent By jgomez Date 2006-02-28 Time 15:17 Rev Time 0.33
Received By jgomez Date 2006-02-28 Time 15:16 Sent To  
Notes
2006-02-28 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- PRODUCT APPROVAL FOR POLYGLASS USA
 MODIFIED BITUMEN ROOF SYSTEM IS LIMITED
 BY GENERAL LIMITATION #7, WHICH REQUIRES
 REQUIRES ENHANCED UPLIFT CALCULATIONS
 FOR ROOF SYSTEM AT PERIMETER AND CORNER
 AREAS TO BE PREPARED, SIGNED AND SEALED
 BY A PROFESSIONAL AS LISTED IN
 LIMITATION #7.
 SUCH CALCULATIONS NEED TO BE DONE IN
 COMPLIANCE WITH ROOFING APPLICATION
 STANDARD RAS 117. CALCULATIONS SUBMITTED
 BY THE PROFESSIONAL ENGINEER RICHARD
 BOYETTE DON'T ADDRESS THE STANDARD CITED
 ON LIMITATION #7. NEED CALCULATIONS FOR
 THE ENHANCING OF THE FLAT ROOF SYSTEM TO
 BE INSTALLED, NOT THE ROOF SHEATHING.
 ENGINEER TO READ LIMITATION #7 AND
 PROVIDE REQUESTED CALCULATIONS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-17 Cont ID  
Sent By jgomez Date 2006-01-17 Time 14:41 Rev Time 1.00
Received By jgomez Date 2006-01-17 Time 14:41 Sent To  
Notes
2006-01-17 00:00:00BUILDING REVIEW SECOND CHECKLIST:
  
 1- FROM PREVIOUS CHECKLIST: NEED
 CALCULATIONS FOR ENHANCED UPLIFT
 PRESSURE REQUIREMENTS AT PERIMETER AND
 CORNER AREAS. CALCULATIONS NEED TO BE
 PREPARED AND SIGNED, SEALED BYFLORIDA
 REGISTERED PROFESSIONAL ENGINEER,
 REGISTERED ARCHITECT OR REGISTERED ROOF
 CONSULTANT AS REQUIRED BY GENERAL
 LIMITATION #7 ON PAGE 45 OF 45 OF DADE
 COUNTY NOA.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-09 Cont ID  
Sent By jgomez Date 2006-01-09 Time 15:45 Rev Time 0.33
Received By jgomez Date 2006-01-09 Time 15:45 Sent To PC
Notes
2006-01-09 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED TO PROVIDE CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS.
 CALCULATIONS TO BE PREPARED BY ENGINEER,
 ARCHITECT OR REGISTERED ROOF CONSULTANT
 AS REQUIRED BY LIMITATION #7 OF DADE
 COUNTY NOA.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712