Plan Review Details - Permit 06010282
| Plan Review Stops For Permit 06010282 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2006-06-14 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-06-14 |
Time |
13:03 |
Rev Time |
0.50 |
| Received By |
jgomez |
Date |
2006-06-14 |
Time |
12:20 |
Sent To |
PC |
|
| Notes |
| 2006-06-14 00:00:00 | NOC EXPIRED AFTER 90 DAYS IF WORK IS NOT | | | STARTED. NEED RE-RECORDED NOC. | | | APPLICATION UNDER "S". JG. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2006-03-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-03-28 |
Time |
14:32 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2006-03-28 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2006-03-28 00:00:00 | BUILDING REVIEW 4TH CHECKLIST: | | | 1- ON THIRD PLAN REVIEW CHECKLIST, | | | ENGINEER WAS ASKED TO REVIEW GENERAL | | | LIMITATION #7 AND TO PROVIDE | | | CALCULATIONS BASED ON THE STANDARD RAS | | | 117. INFORMATION SUBMITTED DOESN'T | | | ADDRESS THIS COMMENT. | | | | | | 2- ENGINEER TO SEE SPECIFIC ROOF PRODUCT | | | APPROVAL SUBMITTED TO SEE APPROVED | | | FASTENER TYPE AND SPACING AND MAXIMUM | | | DESIGN PRESSURES ALLOWED FOR THE SYSTEM. | | | INFORMATION SUBMITTED HAS NOT | | | COORDINATION WITH PRODUCT APPROVAL. | | | PRODUCT APPROVAL SYSTEM DESIGN PRESSURE | | | OF -52.5PSF IS ASSUMED TO BE FOR ZONE | | | ONE. ENGINEER NEEDS TO PROVIDE FASTENER | | | ENHANCING TO RESIST DESIGN PRESSURES AT | | | ZONES 2 AND 3. | | | | | | 3- ENGINEER TO SEE ATTACHED COPY OF | | | FLORIDA STATUTE 553.80(2)(B) REGARDING | | | DESIGN PROFESSIONAL DOCUMENTS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-02-28 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-02-28 |
Time |
15:17 |
Rev Time |
0.33 |
| Received By |
jgomez |
Date |
2006-02-28 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2006-02-28 00:00:00 | BUILDING REVIEW THIRD CHECKLIST: | | | 1- PRODUCT APPROVAL FOR POLYGLASS USA | | | MODIFIED BITUMEN ROOF SYSTEM IS LIMITED | | | BY GENERAL LIMITATION #7, WHICH REQUIRES | | | REQUIRES ENHANCED UPLIFT CALCULATIONS | | | FOR ROOF SYSTEM AT PERIMETER AND CORNER | | | AREAS TO BE PREPARED, SIGNED AND SEALED | | | BY A PROFESSIONAL AS LISTED IN | | | LIMITATION #7. | | | SUCH CALCULATIONS NEED TO BE DONE IN | | | COMPLIANCE WITH ROOFING APPLICATION | | | STANDARD RAS 117. CALCULATIONS SUBMITTED | | | BY THE PROFESSIONAL ENGINEER RICHARD | | | BOYETTE DON'T ADDRESS THE STANDARD CITED | | | ON LIMITATION #7. NEED CALCULATIONS FOR | | | THE ENHANCING OF THE FLAT ROOF SYSTEM TO | | | BE INSTALLED, NOT THE ROOF SHEATHING. | | | ENGINEER TO READ LIMITATION #7 AND | | | PROVIDE REQUESTED CALCULATIONS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-01-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-01-17 |
Time |
14:41 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2006-01-17 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2006-01-17 00:00:00 | BUILDING REVIEW SECOND CHECKLIST: | | | | | | 1- FROM PREVIOUS CHECKLIST: NEED | | | CALCULATIONS FOR ENHANCED UPLIFT | | | PRESSURE REQUIREMENTS AT PERIMETER AND | | | CORNER AREAS. CALCULATIONS NEED TO BE | | | PREPARED AND SIGNED, SEALED BYFLORIDA | | | REGISTERED PROFESSIONAL ENGINEER, | | | REGISTERED ARCHITECT OR REGISTERED ROOF | | | CONSULTANT AS REQUIRED BY GENERAL | | | LIMITATION #7 ON PAGE 45 OF 45 OF DADE | | | COUNTY NOA. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-01-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2006-01-09 |
Time |
15:45 |
Rev Time |
0.33 |
| Received By |
jgomez |
Date |
2006-01-09 |
Time |
15:45 |
Sent To |
PC |
|
| Notes |
| 2006-01-09 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- NEED TO PROVIDE CALCULATIONS FOR NAIL | | | ENHANCING AT PERIMETER AND CORNER AREAS. | | | CALCULATIONS TO BE PREPARED BY ENGINEER, | | | ARCHITECT OR REGISTERED ROOF CONSULTANT | | | AS REQUIRED BY LIMITATION #7 OF DADE | | | COUNTY NOA. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
|