| 2006-02-02 00:00:00 | |
| | |
| | DENIED |
| | |
| | COMMENTS FROM 1ST REVIEW NOT ADDRESSED |
| | |
| | 1) DRAWINGS SHALL REFLECT CHANGE OF |
| | OCCUPANCY TO BUSINESS GROUP B |
| | |
| | 2) EXTERIOR WALL SECTION 4/A2 STATES |
| | THAT A NEW CONCRETE FLOOR WILL BE POURED |
| | BEFORE SLAB IS POURED TERMITE PROTECTION |
| | PER 1816 FBC SHALL BE PERFORMED |
| | |
| | 3) ON EXTERIOR WALL SECTION 4/A2 SPECIFY |
| | THE ANCHOR/CLIP TO BE USED FOR STUD TO |
| | PLATE CONNECTIONS. |
| | |
| | 4) DETAIL 1/A2 IS TITLED EXTERIOR WALL |
| | SECTION SHOULD BE INTERIOR |
| | |
| | 5) ROOF PLAN ON A1 AND DETAIL 2/A2 SHOW |
| | DIFFERENT OVERHANG SIZES |
| | |
| | 6) EXTERIOR WALL SECTION 3/A2 SPECIFIES |
| | HURRICANE TIE IN SCHEDULE ON S-2 NO |
| | STRUCTURAL DRAWINGS WERE SUPPIED. IS NEW |
| | HURRICANE STRAP #1 TYPICAL FOR ALL |
| | TRUSSES, IF SO INDICATE ON DRAWINGS |
| | |
| | 7) ATTIC VENTILATION SHALL COMPLY WITH |
| | 1203.2 FBC 2004. 50% OF THE REQUIRED |
| | VENTILATING AREA SHALL BE PROVIDED BY |
| | VENTILATORS IN THE UPPER PORTION OF THE |
| | SPACE AND AT LEAST 3FT ABOVE THE EAVE |
| | VENTS |
| | |
| | 8) BUSINESS OCCUPANCY SHALL MEET ALL THE |
| | CODE REQUIREMENTS FOR EGRESS AND |
| | ACCESSIBILITY INCLUDING BUT NOT LIMITED |
| | TO: |
| | |
| | A) DOOR OPENINGS SHALL BE 32" CLEAR |
| | FROM STOP TO FACE OF DOOR OPEN AT 90 |
| | DEGREES PER 11-4.13.5 |
| | |
| | |
| | |
| | |
| | |
| | |
| | B) DOORS TO ACCESSIBLE TOILET ROOMS |
| | SHALL COMPLY WITH SECTION 11-4.13 AND |
| | SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE FOR ANY FIXTURE PER 11-4.22.2 |
| | |
| | C) ACCESSIBLE TOILET ROOMS SHALL MEET |
| | ALL OF THE REQUIREMENTS OF CHAPTER 11 |
| | FBC 2004 |
| | |
| | D) DRAWINGS DO NOT SHOW DETAIL OF |
| | ELEVATION CHANGE AT EXIT EGRESS DOOR. |
| | DOOR SHALL COMPLY WITH 11-4.5.2 |
| | |
| | E) DOOR HARDWARE SHALL MEET |
| | ACCESSIBILITY CODES PER 11-4.13.9 |
| | |
| | F) KITCHEN SINK SHALL MEET |
| | ACCESSIBILITY REQUIREMENTS PER 11-4.24 |
| | |
| | G) EXIT/ENTRANCE SHALL BE ACCESSIBLE TO |
| | AN ACCESSIBLE ROUTE TO PUBLIC |
| | TRANSPOTATION STOPS, ACCESSIBLE PARKING |
| | SPACES AND PASSENGER LOADING ZONE |
| | |
| | H) ONE PARKING SPACE SHALL BE HANDI-CAP |
| | ACCESSIBLE AND MEET THE REQUIREMENTS OF |
| | 11-4.6.1 THROUGH 11-4.6.6 AND BE SHOWN |
| | ON DRAWINGS TO MEET COMPLIANCE |
| | |
| | 9) PRODUCT APPROVALS FOR EXTERIOR DOORS |
| | HAVE BEEN REVISED, SUBMIT UPDATED COVER |
| | SHEET. PAGE 1 OF 7 IS MISSING THAT PAGE |
| | HAS THE DESIGN PRESSURES FOR THE PRODUCT |
| | THE METHOD OF ATTACHMENT SHALL BE |
| | CLEARLY MARKED ON THE PRODUCT APPROVALS. |
| | |
| | 10) DRAWINGS SPECIFY THREE DIFFERENT |
| | TYPES OF DOORS IF SO SUBMIT PRODUCT |
| | APPROVALS FOR EACH |
| | |
| | 11) WINDOW AND DOOR PRODUCT APPROVALS |
| | CALL FOR BUCKS BY OTHERS, SUBMIT A |
| | DETAIL ON PLANS FOR BUCK ATTACHMENT THAT |
| | MEETS THE CODE WIND PRESSURES |
| | |
| | 12) ENSURE THAT EXISTING FRAMING HAS |
| | BACKING FOR SHUTTER ATTACHMENT IN WOOD |
| | FRAMED WALL, ROOM 104 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | 15) STORM PANEL PRODUCT APPROVALS SHALL |
| | SPECIFY TYPE OF FASTENER USED IN BOTH |
| | WOOD AND BLOCK,EDGE DISTANCE,SPAN,ETC. |
| | A SCHEDULE WITH ALL THE INFORMATION AND |
| | A KEY PLAN WITH WINDOW LOCATION SHUTTER# |
| | AND LOCATION OF EMERGENCY EGRESS |
| | EXPEDITES THE PLAN REVIEW AND INSPECTION |
| | PROCESS. FIND ENCLOSED A SAMPLE OF AN |
| | INSTALLATION SCHEDULE. MOST SHUTTER |
| | CONTRACTORS MAKE UP SIMILAR SCHEDULES |
| | FOR THE GENERAL CONTRACTOR |
| | |
| | |
| | |