Plan Review Details - Permit 06010265
Plan Review Stops For Permit 06010265
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-04-04 Cont ID  
Sent By jgomez Date 2006-04-04 Time 17:58 Rev Time 0.50
Received By jgomez Date 2006-04-04 Time 17:58 Sent To PC
Notes
2006-04-04 00:00:00PERMIT UNDER "R". JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-02-03 Cont ID  
Sent By jgomez Date 2006-02-03 Time 08:46 Rev Time 0.33
Received By jgomez Date 2006-02-03 Time 08:45 Sent To  
Notes
2006-02-03 00:00:00BUILDING REVIEW THIRD CHECKLIST:
 1- FLAT ROOF SYSTEM SUBMITTED IS FOR
 TILE UNDERLAYMENT ONLY. NEED APPROVED
 ASSEMBLY FOR FLAT ROOF SYSTEM.
  
 ***NOTE: WHEN RE-SUBMITTING APPROVED
 ASSEMBLY MAKE SURE TO VERIFY IF GENERAL
 LIMITATION #7 OR #9 APPLIES. REMEMBER
 THAT LIMITATION #9 DOESN'T ALLOW ANY
 CALCULATIONS TO INCREASE THE DESIGN
 PRESSURES OF THE SYSTEM.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-13 Cont ID  
Sent By jgomez Date 2006-01-13 Time 08:48 Rev Time 0.33
Received By jgomez Date 2006-01-13 Time 08:48 Sent To  
Notes
2006-01-13 00:00:00BUILDING REVIEW 2ND CHECKLIST:
 *** COMMENTS FROM PREVIOUS CHECKLIST
 WERE NOT PROPERLY ADDRESSED:
 1- SPECIFY HOW MUCH AREA IS FLAT ROOF
 SYSTEM AND HOW MUCH AREA ARE SHINGLES
 FOR PERMIT EVALUATION PURPOSES. SEE
 ATTACHED CITY POLICY FOR RE-ROOF
 PERMITS.
  
 2- APPROVED FLAT ROOF ASSEMBLY WAS NOT
 SUBMITTED. DADE COUNTY NOA SUBMITTED IS
 NOW INCOMPLETE. IS MISSING THE SPECIFIC
 APPROVED ASSEMBLY THAT IS GOING TO BE
 INSTALLED AND IS ALSO MISSING THE LAST
 PAGE WITH THE GENERAL LIMITATIONS OF THE
 PRODUCT. SEE ATTACHED CITY POLICY FOR
 RE-ROOF PERMITS AND PROVIDE ALL REQUIRED
 INFORMATION.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-09 Cont ID  
Sent By jgomez Date 2006-01-09 Time 14:34 Rev Time 0.50
Received By jgomez Date 2006-01-09 Time 14:34 Sent To  
Notes
2006-01-09 00:00:00BUILDING REVIEW CHECKLIST:
 1- SPECIFY HOW MUCH AREA IS FLAT ROOF
 AND HOW MUCH AREA IS FOR SHINGLES TO
 PROPERLY VALUE THE PERMIT. SEE ATTACHED
 POLICY FOR RE-ROOF PERMITS.
  
 2- NEED TO SPECIFY WHICH APPROVED FLAT
 ROOF SYSTEM IS GOING TO BE INSTALLED.
 SEE ATTACHED POLICY FOR RE-ROOF PERMITS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712