Plan Review Details - Permit 06010196
Plan Review Stops For Permit 06010196
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-28 Cont ID  
Sent By alange Date 2006-02-28 Time 11:18 Rev Time 2.00
Received By alange Date 2006-02-28 Time 11:18 Sent To  
Notes
2006-02-28 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 3.BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 5.PRODUCT APPROVALS REQUIRED FOR
 ROOFING, ROOFING UNDERLAYMENT, STRAPS
 AND TIE-DOWNS.
  
 6.ALL PRODUCT APPROVALS SHALL HAVE THE
 FOLLOWING STATE PRODUCT APPROVAL
 ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 8.SHOW SIZE AND LOCATION OF ATTIC
 ACCESS COMPLYING WITH FBC R-807.1
  
 9.TYPICAL WALL DETAIL ON S-4 SHOWS A
 TRIPLE BLOCK WIDTH.PLEASE VERIFY?
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-31 Cont ID  
Sent By btrobaug Date 2006-01-31 Time 07:13 Rev Time 0.75
Received By btrobaug Date 2006-01-31 Time 06:39 Sent To M
Notes
2006-01-31 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT A RISER DIAGRAM FOR THE
 PROPOSED SERVICE INDICATED ON THE PLAN.
 INCLUDE THE PANEL FOR THE CABANA AND
 COMPLIANCE WITH 225.31 AND 250.32.
  
 2} PROVIDE A PANEL SCHEDULES FOR THE NEW
 EQUIPMENT WHICH INCLUDE THE PANEL
 SPECIFICATIONS FOR BRANCH CIRCUIT
 CAPACITY, VOLT AND AMPERAGE RATINGS.
  
 3} INDICATE THE LOCATION OF THE A/C
 CONDENSING UNIT AN DISCONNECT.
  
 4} PLEASE INDICATE GFI RECEPTACLES PER
 210.8(A)(7) IN THE WET BAR AREA.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-28 Cont ID  
Sent By adarroug Date 2006-01-28 Time 15:45 Rev Time 0.00
Received By adarroug Date 2006-01-28 Time 15:45 Sent To E
Notes
2006-01-28 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-28 Cont ID  
Sent By alange Date 2006-02-28 Time 11:24 Rev Time 0.00
Received By alange Date 2006-01-10 Time 14:38 Sent To  
Notes
2006-01-10 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-01-31 Cont ID  
Sent By tgordon Date 2006-01-31 Time 08:18 Rev Time 0.30
Received By tgordon Date 2006-01-31 Time 08:18 Sent To P
Notes
2006-01-31 00:00:00*** DENIED ***
 1) PLEASE SHOW BATHROOM EXHAUST FAN ON
 MECHANICAL PLAN.
  
 2) NEED TO SHOW LOCATION OF CONDENSER
 UNIT ON MECHANICAL PLAN.
  
 3) PLEASE SHOW CONDENSATE DRAIN LINE ON
 MECHANICAL PLAN.
  
 4) 10X10 RETURN AIR GRILL IS TO SMALL
 FOR A 1 1/2 TON UNIT.
  
 5) RETURN AIR DUCT NEEDS TO BE AS LARGE
 OR LARGER THAN THAN THE SUPPLY AIR DUCT.
  
 6) PLEASE SHOW HEATER SIZE (KW) ON
 MECHANICAL PLAN.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-02-01 Cont ID  
Sent By jleech Date 2006-02-01 Time 14:48 Rev Time 0.33
Received By jleech Date 2006-02-01 Time 14:48 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-27 Cont ID  
Sent By mmclean Date 2006-01-27 Time 18:50 Rev Time 0.00
Received By mmclean Date 2006-01-27 Time 18:50 Sent To I
Notes
2006-01-27 00:00:00NOTE: ACCESSORY STRUCTURE CANNOT BE
 BUILT IN THE 5FT UTILITY EASEMENT IN
 REAR OF PROPERTY.