| 2006-07-25 00:00:00 | *********** UNSAT 5TH REVIEW ********* |
| | |
| | ** PLEAS SEE THIS IS THE 5TH REVIEW. |
| | PLEASE SEE SOME COMMENTS BELOW ARE STILL |
| | IN NEED OF BEING ADDRESSED FROM PREVIOUS |
| | REVIEWS AND PLEASE SEE SOME NEW |
| | COMMENTS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE SERVICE RISER IS |
| | STILL VERY UNCLEAR AS THE 100A MCB SUB |
| | PANEL IS NOT FED FROM ANYWHERE? PLEASE |
| | SEE RISER SHOWS THIS PANEL BEING FED |
| | FROM PANEL "A", HOWEVER PANEL "A" DOES |
| | NOT LIST THIS PANEL, OCP ETC ON ITS |
| | PANEL SCHEDULE. WHERE IS THIS PANEL FED |
| | FROM? |
| | FBC 106.1.2 ADMIN SECT., 215.5 , |
| | 240.4,310.16 ETC. |
| | |
| | 2) NOTE: PLEASE CORRELATE AIC RATINGS AS |
| | RISER SHOWS 22K FOR THE MCB AND PANEL |
| | "A" SHOWS 10K? IF THE MAINS ARE 22K AND |
| | THE BRANCH BREAKERS ARE SIZED AT SERIES |
| | RATINGS, THEN PLEASE INDICATE THE 10K |
| | FOR BRANCH BRKRS ONLY. IF IT SOMETHING |
| | DIFFERENT, THEN PLEASE ADJUST. |
| | 110.9, 106.1.2FBC |
| | |
| | 3) NOTE: PLEASE SEE RISER IS SHOWING |
| | "EQUIPMENT GROUNDING CONDUCTORS " FROM |
| | METER TO MAIN. PLEASE SEE 250.6, |
| | 250.24B, AS THE EGC IS ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | 4)NOTE: PLEASE SEE RISER SHOWS 100A SUB |
| | PANEL BEING FED WITH 3-3/0'S?? AND #6 |
| | EQUIPMENT GROUNDING CONDUCTOR?? PLEASE |
| | KNOW, IT IS OK TO USE THESE OVERSIZED |
| | CONDUCTORS, HOWEVER RISER SHOWS THEM IN |
| | A "1/2" CONDUIT?? AND 3/0'S WILL NOT FIT |
| | INTO THE 100A BRKR. PLEASE VERIFY AND |
| | SEE 310.16/310.15B6 FOR SIZING. PLEASE |
| | SEE CHAPTER 9 TABLES FOR CORRECT SIZING |
| | OF CONDUIT FOR CONDUIT FILL. |
| | 215.5. |
| | |
| | 5) NOTE: PLEASE INDICATE METER CAN SIZE |
| | AS PREVIOUS PLANS CALLED FOR 200A |
| | SERVICE. |
| | 106.1.2 |
| | |
| | 6) NOTE: PLEASE CORRELATE ALL A/C |
| | MECHANICAL LOADS, OVER CURRENT |
| | PROTECTION AND WIRE SIZES. PLEASE SEE |
| | OCP IS NOW MISSING FOR SOME AHU'S HEAT? |
| | PLEASE SEE 424.3B FOR MIN SIZING. PLEASE |
| | SEE TWO AHU'S ARE NOW SHOWING 5KW HEAT |
| | YET, STILL IDNCATE 60A OCP ON LOAD |
| | CALCULATIONS AND #6 WIRE. ONCE AGAIN, |
| | PLEASE VERIFY THIS AS 5KW UNITS ARE NOW |
| | BEING SHOWN AND 60A OCP IS WAY TOO HIGH. |
| | PLEASE ALSO KNOW, #6 WIRE WILL NOT FIT |
| | IN THE CORRECT SIZE BRKR THEY NEED TO |
| | BE. |
| | PLEASE ALSO SEE CU'S AS THESE ARE ALSO |
| | SHWOING 60A OCP. UPON REVIWING THE |
| | MECHANICAL EQUIPMENT SCHEDULE UNITS #2 |
| | AND #3 ARE 2.5 AND 3.0 TON UNITS. PLEASE |
| | CONSULT YOUR MECHANICAL PERSON AS THE |
| | OCP IS WAY TOO HIGH. PLEASE ALSO ADJUST |
| | THE CONDUCTOR SIZE CORRECLTY AS THE #6'S |
| | WILL ALSO NOT FIT IN THE OCP NEEDED |
| | ONCE THESE ARE ADJUSTED. |
| | 240, 440, 430, 240.4, 310.16,ETC ETC |
| | 106.1.2 FBC. |
| | |
| | 7) NOTE: PLEASE SEE LOAD FOR ELEVATOR ON |
| | PANEL SCHEDULE DOES NOT CORRELATE WITH |
| | THE LOAD CALCULATIONS.PLEASE SEE A LOAD |
| | OF 3300 VA IS BEING SHOWN ON BOTH "A" |
| | AND "B" PHASE WHICH WOULD BE A TOTAL |
| | LOAD ON LOAD CALCS OF 6600VA. PLEASE |
| | VERIFY WHAT THE LOADS ACTUALLY ARE. |
| | IF LOAD IS INDEED 6600, PLEASE ADJUST |
| | THE OCP AND CONDUCTOR SIZES ALONG WITH |
| | REVISING THE LOAD CALCULATIONS. |
| | 240.4,310.16,220 ETC. |
| | |
| | 8) NOTE: PLEASE SEE SMALL APPLIANCE |
| | CIRCUITS ARE STILL BEING SHOWN AT |
| | 2400VA. PLEASE SEE 210.11C1,220.16 AS SM |
| | APPL CIRCUITS ARE 1500VA. PLEASE SEE |
| | THAT 2400VA WAY EXCEEDS THE RATING OF A |
| | 20A CIRCUIT. (1920VA MAX). |
| | |
| | 9) NOTE: PLEASE SEE LOADS SHOWN FOR |
| | ELEVATOR CAR LTS AND RECEPTS WHICH SEEM |
| | TO INDICATE DEDICATED LOAD OF 1080VA YET |
| | THIS LOAD OS NOT ON LOAD CALCULATIONS? |
| | PLEASE ALSO SEE AN ADDITIONAL LOAD OF |
| | 1080VA IS SHOWN FOR ELEV CAR YET THIS IS |
| | ALSO NOT SHOWN IN LOAD CALCULATIONS? |
| | 220. |
| | |
| | 10 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 11) NOTE: PLEASE LIST ALL CIRCUITING ON |
| | PANEL SCHEDULE(S) FOR SPECIFIC AREAS AND |
| | PLEASE LIST ALL THE REQUIRED ARC FAULT |
| | PROTECTED CIRCUITS AS REQUIRED PER |
| | 210.12B,. 408.4 |
| | IE; MASTERBEDRM LTS, KITCHEN LTS, |
| | LIVING RM RECEPTS ETC. |
| | IT IS KNOWN TO THIS OFFICE THAT THE |
| | BRNACH CIRCUITING WILL MOST LIKELY |
| | CHANGE SURING CONSTRUCTION , HOWEVER THE |
| | MIN CIRCUITS SHALL BE ON PANEL SCHEDULES |
| | AT THIS TIME. |
| | |
| | 12) NOTE: PLEASE SEE AN ESTIMATE LOAD OF |
| | 900VA IS BEING SHOWN FOR ALL THE GEN LT |
| | AND RECEPT CIRCUITS. WHERE IS THIS 900VA |
| | COMING FROM. PLEASE SEE TOTAL GEN LT |
| | DEMAND IS 15,000+ VA AND DOES NOT |
| | CORRELATE WITH THIS. |
| | PLEASE SEE NEC 220,215.5 ETC. |
| | |
| | 13) NOTE: PLEASE SEE THAT SMOKE |
| | DETECTORS ARE REQUIRED WITHIN 12" OF THE |
| | HIGHEST POINT OF ANY FLAT CEILINGS AND |
| | SLOPED CEILING WITHIN 3' OF PEAK. PLEASE |
| | SEE THAT IF THE TRAY CEILINGS AS SHOWN |
| | ARE 12" OR MORE UP FROM OTHER |
| | SURROUNDING CEILINGS AREAS, THEN THE |
| | SD'S ARE REQUIRED TO BE MOVED. PLEASE |
| | SEE SD'S LOCATED WITHIN 20' OF COOKING |
| | APPLIANCES SHALL MEET THE EXCEPTIONS AS |
| | BEING PHOTO-ELECTRIC EYE TYPE/RESETTING |
| | TYPE AS REQUIRED. |
| | PLEASE SEE NFPA-72 2002 11.8.3 FOR THESE |
| | INSTALLATION REQUIREMENTS. |
| | |
| | 14) NOTE: PLEASE SEE 680.71 AS NO GFI |
| | PROTECTION IS NOTED FOR WHIRLPOOL TUB. |
| | PLEASE ALSO SEE THAT NO ELECTRICAL FOR |
| | THIS SAME TUB IS BEING SHOWN ON PLANS?? |
| | PLEASE CORRELATE. |
| | 106.1.2 |
| | |
| | 15) NOTE: PLEASE SEE THAT THE PLANS |
| | SHALL STATE THE CURRENT CODES IN EFFECT |
| | FOR THE FOLLOWING. PLEASE LIST THE |
| | FOLLOWING AT A MINIMUM WHICH ARE |
| | RELEVANT TO THE ELECTRICAL PLANS. |
| | 2002 NFPA-70( NEC), 2002 NFPA-72, 2003 |
| | NFPA-101. |
| | |
| | 16) NOTE: PLEASE SEEMISSING EGRESS |
| | LIGHTING CONTROLS WHEN EXITING TO |
| | OUTSIDE FROM THE FOLLOWING AREAS. MEDIA |
| | RM, LIVING RM, NOOK AND FAMILY RM. |
| | PLEASE KNOW, LIGHTING MAY BE CONTROLLED |
| | BY MULTIPLE LOCATIONS BY 3-/4-WAYS.(ONLY |
| | A SUGGESTIONS) MUST HAVE MIN CONTROL FOR |
| | SOME SORT OF LIGHTING FIXTURE. |
| | NFPA-70 210.70, NFPA-101 7.8 |
| | |
| | 17) NOTE: PLEASE SEE 210.52B1, 210.11C1, |
| | 220.16 AS DINING SHALL BE ON ONE OR MORE |
| | OF THE REQUIRED SMALL APPLIANCE |
| | CIRCUITS. PLEASE LIST AND SEE MIN VA |
| | (1500VA) REQUIRED. |
| | |
| | 18) NOTE: PLEASE SEE PANEL SCHEDULE |
| | SEEMS TO MENTIONS THREE CIRCUITS FOR |
| | "GFI"?? HOWEVER THIS IS UNCLEAR WHAT |
| | THESE ARE FOR. PLEASE LIST. |
| | 408.4 |
| | |
| | 19) NOTE: PLEASE SEE MISSING THE |
| | REQUIRED DEDICATED BATH(S) CIRCUIT(S) |
| | PER 210.52D,210.11C3. MUST BE #12 AND |
| | 20A. (IS CIRCUITS FROM NOTE #18 THESE??) |
| | IF SO, PLEASE LABEL. |
| | |
| | 20) NOTE: PLEASE SEE PLANS SEEM TO |
| | INDICATE SOME SORT OF "HEATER" FOR |
| | FUTURE POOL EQUIPMENT?? PLEASE BE SURE |
| | TO INDICATE IF GAS (FUTURE) OR |
| | ELECTRIC(FUTURE). PLEASE KNOW HOWEVER, |
| | IF THIS IS GOING TO BE AN ELECTRICAL |
| | HEAT PUMP, THEN PLEASE KNOW THE LOAD |
| | NEEDS TO BE FIGURED INTO THE SERVICE AT |
| | THIS TIME. |
| | PLEASE ADJUST OF ELECTRIC HEAT PUMP. |
| | PLEASE ALSO KNOW, ALL CONTINOUS LOADS |
| | ARE SHOWN AT 125%. (HEAT PUMP AND POOL |
| | PUMP) IF THE LOAD IS ALREADY SHOWN AT |
| | 125%, PLEASE NOTE. |
| | 220,680.9,215.3,230.42 |
| | |
| | 21) NOTE: PLEASE SEE LOAD CALCULATIONS |
| | SHOW PANELS AS 40CIR AND PANELS ARE |
| | 42CIR. (MISPRINT/CORRELATE). |
| | 106.1.2 |
| | |
| | 22) NOTE: PLEASE KNOW PLANS HAVE BEEN |
| | SUBMITTED FIVE TIMES FOR REVIEW FOR THIS |
| | SINGLE FAMILY RESIDENCE. |
| | PLEASE KNOW ALL FIVE SETS OF ELECTRICAL |
| | PLANS ARE BEING RETAINED. PLEASE ALSO |
| | KNOW PLANS MAY BE TURNED OVER TO THE |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS |
| | FOR PEIR REVIEWFOR REPEATED COMMENTS FOR |
| | NON-COMPLIANCE. |
| | PLEASE ALSO SEE COPY OF FS 553.80(2)(B) |
| | WITH RESPECT TO DESIGN PROFESSIONALS AND |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | PLEASE KNOW THAT IF ANY OF THE SAME CODE |
| | COMPLIANT COMMENTS ARE STILL NOT |
| | ADDRESSED ON THE NEXT RESUBMITTAL, THIS |
| | OFFICE WILL HAVE NO CHOICE TO ASSESS A |
| | 4X FEE FOR THE PLAN REVIEW PORTION OF |
| | THE PERMIT FEE. |
| | PLEASE SEE THIS FINE WILL BE $10,860.00 |
| | WHICH IS REQUIRED UNDER FLORIDA STATUES |
| | TO BE PAID BY THE DESIGN PROFESSIONAL(S) |
| | OF RECORD. THIS FINE IS "NOT" THE |
| | RESPONSIBILTY OF THE OWNER OR |
| | CONTRACTOR. |
| | PLEASE KNOW THIS OFFICE IS GIVING NOTICE |
| | THAT A MEETING IS REQUIRED AND SHALL BE |
| | HELDWITH THEATTENDANCE OF THE |
| | FOLLOWING PERSONS AT A MINIMUM: GARRISON |
| | DESIGN GROUP, MR. LUIS LOPEZ (ENGINEER |
| | OF RECORD) AND GENERAL CONTRACTOR. |
| | |
| | 23) NOTE: PLEASE KNOW, UPON REVIEW OF |
| | THE SUBMITTED PACKAGE THE ORIGINAL |
| | PERMIT APPLICATION COULD NOT BE READILY |
| | FOUND. PLEASE BE SURE THIS APPLICATION |
| | IS LOCATED AND SUBMITTED WHEN |
| | RESUBMITTING PLANS. |
| | PLEASE ALSO KNOW THAT ANY NOTICE OF |
| | COMMENCEMENTS NOT RECORDED WITHIN 90 |
| | DAYS OF ISSUANCE OF THE PERMMIT WILL |
| | REQUIRE THE NOC TO BE RE-RECORDED PER FS |
| | 713.13(2). PER FS AS NOTED, IF WORK HAS |
| | NOT COMMENCED WITHIN 90 DAYS OF |
| | RECORDING SUCH NOC, THE NOC SHALL BECOME |
| | VOID. |
| | IF THERE ARE ANY QUESTIONS ON THIS, |
| | PLEASE CALL. |
| | |
| | ** PLEASE BE SURE TO CAREFULLY STAPLE |
| | ALL NEW SETS , AS THE SETS WERE ATTACHED |
| | THROUGH THE PANEL SCHEDULES CAUSING |
| | THESE TO BE TORN FOR REVIEW. PLEASE ALSO |
| | TO SUBMIT TWO COMPLETE AND CLEAN SETS |
| | FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |