Plan Review Details - Permit 06010106
Plan Review Stops For Permit 06010106
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-01-26 Cont ID  
Sent By mjacobs Date 2006-01-26 Time 14:39 Rev Time 0.50
Received By mjacobs Date 2006-01-26 Time 14:21 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-01-25 Cont ID  
Sent By mjacobs Date 2006-01-25 Time 07:53 Rev Time 0.75
Received By mjacobs Date 2006-01-25 Time 07:10 Sent To PC
Notes
2006-01-25 00:00:001) PLEASE SEE PREVIOUS NOTES IN PACKAGE
 AND ADDRESSTHE COMMENTS. ONCE AGAIN AN
 APPROVED ASSEMBLY SHALL BE SUBMITTED
 STATING THE DECK TYPE/FASTENING/
 INSTALLATION DETAILS/MATERIALS/GENERAL
 LIMITATIONS ETC.
  
 THE INFORMATION SUBMITTED HAS ALL THE
 DIFFERENT TYPES OF MATERIALS AND
 MANUFACTURES OF THE INSULATIONS,
 FASTENERS AND UNDERLAYMENTS. WHAT WAS
 SUBMITTED IS NOT AN APPROVED ASSEMBLY.
 SEE PAGES 6-43 FOR THE DIFFERENT TYPES
 OF ASSEMBLIES AND CHOOSE ONE. PAGE 44 IS
 THE UNDERLAYMENT BASE SHEET NOT A
 COMPLETE APPROVED ASSEMBLY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561) 805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-05 Cont ID  
Sent By mjacobs Date 2006-01-05 Time 16:06 Rev Time 1.25
Received By mjacobs Date 2006-01-05 Time 11:29 Sent To PC
Notes
2006-01-05 00:00:001) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 AN APPROVED ASSEMBLY IS REQUIRED. SEE
 FL#985-R1 FOR MORE INFORMATION.
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
 ROOF HEIGHT.
  
 _X_ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED.
  
 _X__ CONTRACTOR FAILED TO INDICATE THE
 DECK TYPE FOR THE MODIFIED ROOF. PRODUCT
 APPROVAL IS FOR LIGHRWEIGHT CONCRETE.
  
 _IF__ THE SYSTEM PROVIDED STATES
 LIMITATION# 7, SHOULD THE FASTENER
 RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE
 BUILDING OFFICIAL, A REVISED
 FASTENER SPACING, PREPARED , SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF
 CONSULTANT MAY BE SUBMITTED.
  
 2) GENERAL LIMITATION #9 PROHIBITS
 RATIONAL ANALYSIS OR EXTRAPOLATION TO
 ENHANCE THE UPLIFT PRESSURE AT PERIMETER
 AND CORNER AREAS BY REDUCING THE
 FASTENER SPACING IN THESE AREAS.EITHER
 SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT
 APPROVAL) THAT DOES NOT CITE GENERAL
 LIMITATION #9.ALTERNATIVELY IF THE
 SELECTED SYSTEM DOES CITE GENERAL
 LIMITATION #9, IT MUST HAVE A MAXIMUM
 DESIGN PRESSURE THAT EXCEEDS THE
 PRESSURE IN ROOF ZONE 3 (TYPICALLY -89
 PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR
 LESS).
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL: (561)805-6726
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-05 Cont ID  
Sent By mjacobs Date 2006-01-05 Time 11:28 Rev Time 0.00
Received By mjacobs Date 2006-01-05 Time 11:28 Sent To  
Notes
***NONE***