Plan Review Details - Permit 05121248
Plan Review Stops For Permit 05121248
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-16 Cont ID  
Sent By jwitmer Date 2006-03-16 Time 12:27 Rev Time 44.00
Received By jwitmer Date 2006-03-02 Time 12:27 Sent To  
Notes
2006-03-30 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05121248
 ADD: 419 LAKEVIEW
 CONT: ? PLAN REVIEW?
 TEL(305) 322-4105
  
  
 -OPERA PLACE-
  
 ARCHITECT FIRM BERMELLO, AJAMIL &
 PARTNERS
 HECTOR R. VALVERDE
  
 ENGINEERS: PEDRO JOSE DUQUESNE
  
  
 1ST REVIEW
 ACTION DENIED
 CODE: 2004 FL BUILDING CODE
  
 * FL BLD CODE = 2004 WEST PALM BEACH
 ADMINISTRATIVE CODE
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE NEW
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1) NOTE THIS IS A THRESHOLD BUILDING
 REQUIRING (3) OF ALL SUBMITTALS,
 PLANS, REPORTS, REVISIONS OR SUBMITTALS
 TO THE BUILDING DEPARTMENT FOR OUR
 RECORD. THESE DOCUMENTS WILL REQUIRE
 ORIGINALS WITH RAISED SEAL, SIGNATURE
 AND DATE.
 PLANS, SPECIFICATIONS,REPORT OR
 OTHER DOCUMENTS PREPARED BY THE
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE
 SEAL OF THE DESIGN PROFESSIONAL
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEER
 FL ATATE STAT: 61G16.003 ARCHITECT
  
 2)FL S S 713.13:
 NOTICE OF COMMENCEMENT, TO BE RECORDED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE:
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) DISCREPANCY BETWEEN THE PERMIT
 APPLICATION AND THE SURVEY. THE
 APPLICATION INDICATES THE STREET
 LAKEVIEW WHEREAS THE SURVEY IN
 THE SOUTH SIDE OF THE PROPERTY
 OKEECHOBEE BLVD. OKEECHOBEE BLVD ISN'T
 DESIGNATED UNTIL AFTER THE WEST BOUND
 TRAFFIC CROSSES OVER THE FEC RAILROAD
 TRACKS.
  
 4)SURVEY ONLY ONE ORIGINAL, SUBMIT (3)
 ORIGINAL SURVEYS WITH RAISED SEAL,
 SIGNATURE W/ DATE.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 6) FL S. S. 553.71(7)
 (THRESHOLD BUILDING)
 ANY BUILDING GREATER THAN (3) STORIES OR
 50 FEET IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS
 DENIED IN FLORIDA BUILDING CODE WHICH
 EXCEEDS 5,000 SQ FT IN AREA AND AN
 OCCUPANT LOAD OF GREATER THAN 500 PEOPLE
 105.13.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD
 BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER
 OF RECORD. THE STRUCTURAL INSPECTION
 PLAN MUST BE SUBMITTED TO THE
 ENFORCEMENT
 AGENCY PRIOR TO THE ISSUANCE OF A
 PERMIT FOR THE CONSTRUCTION OF THRESHOLD
 BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC
 INSPECTION PROCEDURES AND STANDARDS
 SO THAT THE BUILDING CAN BE ADEQUATELY
 INSPECTED FOR COMPLIANCE WITH THE
 PERMITTED DOCUMENTS.
  
 7)WPB AMENDMENT 105.13.6. W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S.
 553.79(5) FLORIDA STATUTES TO THE MIN-
 IMUM INSPECTIONS REQUIRED BY THIS CODE.
 CONTACT HAROLD PISKURA MANAGER OF THE
 SPECIAL INSPECTOR PROGRAM AT (561)
 805-6711 FOR FURTHER INFORMATION BEFORE
 THE PERMIT MAY BE ISSUED.
  
 8) W.P.B. AMENDMENT 105.13.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO
 BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR
 ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 9 ) 109.3.10* IMPACT OF CONSTRUCTION.
 ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER
 SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS
 SUCH ACTIVITY IS PERMITTED TO AFFECT
 SAID PROPERTY PURSUANT TO A CONSENT BY
 THE APPLICABLE PROPERTY OWNER, UNDER
 TERMS & CONDITIONS AGREEABLE TO THE
 APPLICABLE PROPERTY OWNER. THIS INCLUDES
 BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION
 MATERIALS. NEW CONSTRUCTION ACTIVITY
 SHALL NOT ADVERSELY IMPACT
 HISTORIC SURFACE WATER DRAINAGE FLOWS
 SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING
 WITH ENGINEERING STANDARDS TO PRESERVE
 THE POSITIVE PATTERNS OF THE AFFECTED
 SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING
 ADDITIONS, POOLS, PATIOS, DRIVEWAYS,
 DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN
 EXCESS OF 800SQ FT OF PERMEABLE LAND
 AREA ON ANY PARCEL SHALL AS A PERMIT
 CONDITION, PROVIDE A PROFESSIONALLY
 PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE
 IMPROVEMENT, A CERTIFICATE FROM A
 LICENSED ENGINEER SHALL BE SUBMITTED TO
 THE INSPECTOR IN ORDER TO RECEIVE
 APPROVAL OF THE FINAL INSPECTION.
  
 10) 109.3.10.1 HURRICANE PROTECTION.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO
 ALLOW CONSTRUCTION RELATED MATERIALS
 EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION
 SITE FROM 24 HRS. AFTER A HURRICANE
 WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN
 LIFTED. ALL SUCH CONSTRUCTION MATERIALS,
 EQUIPMENT AND DEBRIS SHALL BE EITHER
 REMOVED FROM THE CONSTRUCTION SITE OR
 SECURED IN SUCH A MANNER AS TO MINIMIZE
 THE DANGER OF SUCH CONSTRUCTION
 MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM
 HIGH WINDS.
 ANY PERSON WHO FAILS TO COMPLY TO
 REMOVE OR SECURE THE CONSTRUCTION
 MATERIALS EQUIPMENT AND DEBRIS WITHIN
 24 HRS AFTER A HURRICANE WATCH HAS BEEN
 ISSUED SHALL BE SUBJECT TO A FINE NOT TO
 EXCEED $500.00.
 IN ADDITION TO THE ABOVE, A LICENSED
 CONTRACTOR WHO VIOLATES THIS SECTION
 SHALL BE SUBJECT TO DISCIPLINE PURSUANT
 TO SECTION 113 OF THIS CHAPTER.
  
 11) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601. A OR B.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 12)1609.1.4 PROTECTION OF OPENINGS
 IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE
 OPENINGS AND THE BALANCE OF GLAZED
 OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH
 GLAZING THAT RECEIVES POSITIVE PRESSURE
 IS IMPACT RESISTANT OR PROTECTED WITH
 IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886
 ASTM E 1996, OR MIAMI-DADE TAS 201,202
 AND 203 REFERENCED THEREIN AS FOLLOWING:
  
 1.GLAZED OPENINGS LOCATED WITHIN 30
 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
  
 13) PLANS INDICATE THAT THIS PERMIT
 WILL BE PHASED, DOES THIS MEAN
 ENTIRE BUILDING IS UNDER ONE PERMIT OR
 WILL THIS PROJECT BE PERMITTED
 SEPARATELY ?
  
 14) PLEASE CONTACT LILI URSA, MIS
 TECHNICIAN MIS CONTACT FOR ADDRESSING
 ISSUES.
 PLEASE SEE ADDRESSING REQUIREMENT FOR
 TWIN TOWERS UNDER ONE PROPERTY CONTROL
 NUMBER. LILI URSA (561)822-1234
  
 15) VARIOUS SHEETS EXAMPLE A-2.01 OR
 A-3.01 FOR SCALE OF DRAWINGS NOTED IN
 TITLE BLOCK SCALE AS NOTED, BUT NOT ON
 THAT PAGE BUT ON THE PROJECT INDEX PAGE
 THE PROCESS TO GO BACK TO THIS PAGE IS
 VERY TIMELY!!!! PLEASE PUT THE SCALE ON
 THE SAME SHEET!
  
 16) A-2.01 THE ELEVATOR LOBBY E118
 COMMON TO ELE CORE 2 & 3 SHOWS A 2INCHES
 CHANGE IN GRADE? VERTICAL ACCESSIBILITY
 11-4.1.2 VERTICAL ACCESSIBILITY NOTHING
 IN THIS CODE SHALL BE CONSTRUED TO
 RELIEVE THE OWNER OF ANY BUILDING OR
 STRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIABLE
 GRADE LEVEL.
  
 17) A-2.01 UNKNOWN ROOM USAGE BY
 ROOM W125 & W109?
  
 18) RETAIL# 9 AS WELL AS THE MAIN
 LOADING DOCK W142, PLEASE INDICATE A
 TRUCK IN THE LOADING BAY, IT APPEARS
 THOSE 2 TRAFFIC LANES TO THE PARKING
 GARAGE WOULD BE BLOCKED.
 106.1.2 ADDITIONAL DATA. THE BUILDING
 OFFICIAL MAY REQUIRE DETAILS,
 COMPUTATIONS, STRESS DIAGRAMS, AND OTHER
 DATA NECESSARY TO DESCRIBE THE
 CONSTRUCTION OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THEIR OFFICIAL
 SEAL, SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 19)A-2.01- A-2.02
 19A)THE MEZZANINE LEVEL,
 PLEASE PROVIDE THE GROSS FLOOR AREA FOR
 EACH TENANT SPACE AND THE FLOOR AREA FOR
 THE MEZZANINE LEVEL IN EACH TENANT SPACE
 505.2 AREA LIMITATION.
 THE AGGREGATE AREA OF A MEZZANINE OR
 MEZZANINES WITHIN A ROOM SHALL NOT
 EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
 THE ENCLOSED PORTIONS OF ROOMS SHALL NOT
 BE INCLUDED IN A DETERMINATION OF THE
 SIZE OF THE ROOM IN WHICH THE MEZZANINE
 IS LOCATED. IN DETERMINING THE ALLOWABLE
 MEZZANINE AREA, THE AREA OF THE
 MEZZANINE SHALL NOT BE INCLUDED IN THE
 AREA OF THE ROOM.
 505.4 OPENNESS. A MEZZANINE SHALL BE
 OPEN
 AND UNOBSTRUCTED TO THE ROOM IN WHICH
 SUCH MEZZANINE IS LOCATED EXCEPT FOR
 WALLS NOT MORE THAN 42 INCHES HIGH,
 COLUMNS AND POSTS. SEE EXAMPLE
  
 19B) PLANS DO NOT SHOW STAIRS TO THE
 MEZZANINE LEVEL, WILL THE MEZZANINE
 LEVEL BE BUILT AS PART OF THE PERMIT
 OR WOULD THIS LEVEL BE BUILT AS PART OF
 A TENANT FIT UP?
  
 19C) ONE CONSIDERATION THAT NEEDS TO BE
 NOTED BY THE DESIGN TEAM.
 ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT),IF THE MEZZANINE
 LEVEL IS BUILT WITH THE SHELL WITH
 STAIRS, IT SHOULD BE NOTED THAT THE AREA
 BENEATH THE MEZZANINE CAN NOT BE
 ENCLOSED SEE 505.2: THE ENCLOSED
 PORTIONS OF ROOMS SHALL NOT BE FIGURED
 IN A DETERMINATION OF THE SIZE
 ROOM IN WHICH THE MEZZANINE IS LOCATED.
 IN DETERMINING THE ALLOWABLE MEZZANINE
 AREA, THE AREA BENEATH THE MEZZANINE CAN
 NOT BE INCLUDED IN THE 1/3RD AREA OF THE
 ROOM.
  
 20) A-2.01 NOTE UPPER RIGHT OF SHEET
 INDICATES THAT MECHANICAL EQUIPMENT
 PROVIDE INFORMATION SHOWING COMPLIANCE
 WITH: VAN ACCESSIBILITY,11-4.1.
 IN PARKING STRUCTURES, ONE IN
 EIGHT ACCESSIBLE SPACES, BUT NOT LESS
 THAN ONE, SHALL BE VAN ACCESSIBLE.
 SHALL BE DESIGNED AS REQUIRED, SEE
 11-4.6.3 . THE VERTICAL CLEARANCE OF
 SUCH SPACES SHALL COMPLY WITH
 11-4.6.5 . ALL SUCH SPACES MAY BE
 GROUPED ON ONE LEVEL OF A PARKING
 STRUCTURE. WHEN SUCH SPACES ARE
 IN A PARKING STRUCTURE AND ONLY
 EIGHT MEET THE HEIGHT REQUIREMENT
 SECTION 11-4.6.5 , THEY SHALL BE
 DESIGNATED AS REQUIRED BY SECTION
 11-4.6.4 .
  
 21) LS-2.09 POOL DECK, THE CALCULATION
 FOR THE GYM TO USE THE 50 OCCUPANT LOAD
 / SQ FT, SEE TABLE 1004.1.2 THIS
 USED WHEN EQUIPMENT IS SHOWN
 PLAN. WHEN NO EQUIPMENT IS SHOWN ON THE
 PLAN
 OCCUPANT LOAD IS FIGURED @ 15 SQ FT/
 OCCUPANT. THIS CALCULATION WILL BE OVER
 THE ALLOWABLE
 STAIRWELLS AND DOORWAYS OCCUPANT LOADS.
  
 22)A-2.01/ A-2.02/ A-3.02CD/
 A7.13 DETAIL# 2THE MAIN LOBBY
 CUTS OFF THE AREA JUST PAST THE ELEVATOR
 BALCONY WITH HANDRAIL OR IF A GLAZED
 ENCLOSURE. THIS INFORMATION IS REQUIRED
 TO
 DETERMINE IF AN ATRIUM WAS CREATED.
 ATRIUM . AN OPENING CONNECTING
 MORE STORIES OTHER THAN ENCLOSED
 STAIRWAYS, ELEVATORS, HOIST WAYS,
 ESCALATORS, PLUMBING, ELECTRICAL,
 AIR-CONDITIONING OR OTHER EQUIPMENT
 WHICH IS CLOSED AT THE TOP AND NOT
 DEFINED AS A MALL. STORIES, AS
 THIS DEFINITION, DO NOT INCLUDE
 BALCONIES WITHIN ASSEMBLY GROUPS
 MEZZANINES THAT COMPLY WITH SECTION 505.
  
 23A) A-3.01AB: SUBMIT STATE APPROVED
 PLANS FOR THE PRE-MANUFACTURED TICKET
 BOOTH, FOR THIS WIND ZONE.
  
 23B) PROVIDE PLANS THAT SHOW VERTICAL
 ACCESSIBILITY FOR BOOTH. PLANS
 SHOW A RAISED CURB, NOT MEETING
 ACCESSIBILITY REQUIREMENTS.
  
 24) A-3.01AB CORRIDOR E140 SHOW
 CHANGE IN ELEVATION REQUIRING
 ON BOTH SIDES OF THE CORRIDOR.
 11.4.8.5. HANDRAILS: IF A RAMP HAS A
 RISE GREATER THAN 6? OR A HORIZONTAL
 PROJECTION GREATER THAN 72INCHESTHEN
 IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 25) STORAGE ROOM E141 PROVIDE WHAT TYPE
 OF MATERIALS ARE TO BE STORED.
 INDICATE IF S1 OR S2 TYPE STORAGE,
 WALL AND DOOR RATINGS ACCORDING TO
 311.2 MODERATE-HAZARD S-13HR
 311.3 LOW-HAZARD S-22HR
 SAME ISSUES WITH STORAGE ROOMS
 E124 & E127.
  
 26) A3.01AB ROOM E109A PROVIDE
 ACCESSIBILITY:11-4.1.2 VERTICAL
 ACCESSIBILITY, NOTHING IN THIS CODE
 SHALL BE CONSTRUED TO RELIEVE THE OWNER
 OF ANY BUILDING, STRUCTURE OR FACILITY
 FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE OR
 BELOW THE OCCUPIBLE GRADE LEVEL.
  
 27) A3.01AB ROOM E125 RES # 2 THE
 PLANS INDICATE 2HR RATED WALLS,
 DOOR LISTING OR RATING?
  
 28)A3.01BC RAMPS ON BOTH SIDES OF THE
 TRASH ROOM E119 OVER 30?-0" REQUIRE
 HANDRAILS.11-4.8.2
 THE MAXIMUM RISE FOR ANY RUN SHALL BE 30
 INCHES (760 MM) (SEE FIGURE 11-16)
 CURB RAMPS AND RAMPS TO BE CONSTRUCTED
 ON EXISTING SITES OR IN EXISTING
 BUILDINGS OR FACILITIES MAY HAVE LIMITS.
 11-4.8.5 HANDRAILS.
 IF A RAMP RUN HAS A RISE GREATER THAN 6
 INCHES (150 MM) OR A HORIZONTAL
 PROJECTION GREATER THAN 72 INCHES
 MM), THEN IT SHALL HAVE HANDRAILS
 BOTH SIDES. HANDRAILS ARE NOT REQUIRED
 ON CURB RAMPS OR ADJACENT TO SEATING IN
 ASSEMBLY AREAS. HANDRAILS SHALL COMPLY
 WITH SECTION 11-4.26
  
 29) NOT USED
  
 30) A3.01BC ROOM E103 FIRE COMMAND
 CENTER MISSING 1HR RATED WALLS
 911.1WHERE REQUIRED BY OTHER SECTIONS
 THIS CODE, A FIRE COMMAND CENTER FOR THE
 FIRE DEPARTMENT OPERATIONS SHALL BE
 PROVIDED. THE LOCATION AND ACCESSIBILITY
 OF THE FIRE COMMAND CENTER SHALL
 SEPARATED FROM THE REMAINDEROF THE
 BUILDING BY NOT LESS THAN A 1-HOUR
 FIRE-RESISTANCE-RATED FIRE BARRIER.
  
 31)SAME COMMENT AS 22, ELEVATOR LOBBY
 IS
 OPEN TO FLOOR ABOVE, IS THIS AN ATRIUM?
  
 32) A3.02BC TRASH ROOM CHUTE #1
 DESIGNATION FOR FIRE RATING? LOCATED IN
 ELECTRIC ROOM?
  
 33) A3.02BC STAIRWELL# 2A AT CORRIDOR
 EM30 WALL DESIGNATION ?D? REQUIRES A
 2 HR RATED WALL. CORRECT SEE 707.4.
  
 34) A3.02BC MESSAGE ROOM VS STAIRWELL
 ALSO REQUIRES A 2HR RATED WALL.707.4
  
 35) A3.02BC MEDIA ROOM EM 33
 11-4.1.2 VERTICAL ACCESSIBILITY,
 NOTHING IN THIS CODE SHALL BE CONSTRUED
 TO RELIEVE THE OWNER OF ANY BUILDING,
 STRUCTURE OR FACILITY FROM THE DUTY TO
 PROVIDE VERTICAL ACCESSIBILITY TO ALL
 LEVELS ABOVE OR BELOW THE OCCUPIBLE
 GRADE LEVEL.
  
 36) A3.02 BC MEETING ROOM EM23 PLANS
 INDICATE
 A SHAFT NEXT TO THIS ROOM, PLANS DO NOT
 INDICATE THE
 FIRE RATING OF THIS SHAFT. SEE 707.4.
  
 37) A3.02CD SAME COMMENTS AS 27- 36.
  
 38) STAIR TOWER # 1 INDICATES A WALL
 SECTION # 11
 OF A7.01 ON THIS SHEET,SEE NOTE # 1
 ABOUT PIPES
 SHOULD ALSO INCLUDE:
 1019.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH
 AN EXIT ENCLOSURE ARE PROHIBITED, EXCEPT
  
 FOR REQUIRED EXIT DOORS, EQUIPMENT AND
 DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION AND ELECTRICAL
 RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M 2 ). SUCH
 PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 712 . THERE
 SHALL BE NO PENETRATIONS OR
 COMMUNICATION
 OPENINGS, WHETHER THE PROTECTED OR NOT,
 BETWEEN ADJACENT EXIT ENCLOSURES.
  
 39) A3.02CD PLANS INDICATE ROOM # WM29
 AN ELECTRICAL ROOM AND WITHIN THE ROOM A
 TRASH CHUTE.707.13.3 REFUSE AND LAUNDRY
 REQUIRE ACCESS ROOMS BEFORE ENTERING THE
 REFUSE CHUTE ROOM.
 ACCESS OPENINGS FOR REFUSE AND CHUTES
 SHALL BE LOCATED IN ROOMS, COMPARTMENTS
 COMPLETELY ENCLOSED BY CONSTRUCTION THAT
 HAS A FIRE-RESISTANT
 RATING OF NOT LESS THAN 1 HOUR OPENINGS
 INTO THE ACCESS ROOMS AND PROTECTED BY
 OPENING PROTECTIVE OF A FIRE PROTECTION
 RATING OF NO LESS THAN 3/4 HOUR AND
 SHALL BE SELF-AUTOMATIC-CLOSING UPON THE
 DETECTION OF SMOKE.
 ELECTRICAL ROOMS ARE TO BELOCKED AN
 ONLY
 AUTHORIZED PERSONAL HAVE ACCESS KEYS TO
 THIS
 AREA. THE SECOND ISSUE IS THRASH CHUTES
 HAVE A HIGHER RISK OF FIRE (NFPA 70
 AUTOMATIC FIRE SPRINKLERS), IT
 UNWISE TO PUT SUCH A HIGH RISK AREA
 INTO THE ELECTRICAL ROOMS. SEE
 COMMENTARY 707.13.707.13.1 & 707.13.3.
  
 40) A3.02 DA IT APPEARS THAT THE REFUSE
  
 CHUTE ENCLOSURE HAS A DOOR ON THE CHUTE
 BUT NO ACCESS ROOM.707.13.3 REFUSE AND
 LAUNDRY CHUTE ACCESS ROOMS REQUIRED.
  
 41) A3.02DA COMMON WALL BETWEEN THE
 PARKING GARAGE AND RETAIL #9 NO FIRE
 RATING
 DESIGNATION.
  
 42) A3.03AB STAIRWELL 3A & 3,THIS
 COMMENT IS
 TRUE FOR ALL FLOORS WITH THE TWO EGRESS
 DOORS: FL ACCESSIBILITY 11-4.13.7
 TWO DOORS IN SERIES. THE MINIMUM SPACE
 BETWEEN TWO HINGED OR PIVOTED DOORS IN
 SERIES SHALL BE 48 INCHES (1219 MM) PLUS
 THE WIDTH OF ANY DOOR SWINGING INTO THE
 SPACE. DOORS IN SERIES SHALL SWING
 EITHER IN THE SAME DIRECTION OR AWAY
 FROM THE SPACE BETWEEN THE DOORS FIGURE
 11-26 (A)].
 FAIR HOUSING ANSI A117.1-4
  
 43) A3.03BC SEE STAIR 2A AND 2 , A
 COLUMN (J1/9.3) IS LOCATED IN THE MEANS
 OF EGRESS
 FROM THE GARAGE TO STAIR TOWER.
 ACCESSIBLE ROUTE WILL REQUIRE A 44".
  
 44) A3.03CD SEE STAIR 2A AND 2, A COLUMN
 (J1/9.3) IS LOCATEDIN THE MEANS OF
 EGRESS
 FROM THE GARAGE TO THE STAIR TOWER.
 ACCESSIBLE ROUTE WILL REQUIRE 44 INCHES.
  
 45) A3.03BC PARKING SPACE 96 SHOULD BE
 12 FT WIDE , HANDICAPPED ACCESSIBILITY.
  
  
 46) A3.03BC SHAFT BY STAIRWELL
 COMMON TO ALL FLOORS, IS MISSING THE
 FIRE
 RATING.707.4 FIRE RESISTANCE
  
 47) A3.03AB UNIT 2B EXTERIOR SLIDING
 GLASS DOOR TO THE BALCONY, THROUGH A4.05
 AND ALL SIMILAR DETAILS HAVE THE DOORS
 LABELED OR DIMENSIONED.
  
 48) NOTE PLANS INDICATE USE OF SLIDING
 GLASS DOORS
 FOR VARIOUS UNITS, PROVIDE DETAILS AND
 PRODUCT APPROVAL THAT INDICATEWHEN THE
 UNIT IS OPEN, THERE WILL BE 32 INCHES
 CLEAR SPACE. FAIR HOUSING. THIS WILL
 HOLD TRUE FOR ALL UNITS PROVIDING ACCESS
 TO
 BALCONY THROUGH SLIDING GLASS DOORS.
 PLEASE PROVIDE A SILL DETAIL INDICATING
 COMPLIANCE WITH
 SLIDING GLASS DOOR FOR FAIR HOUSING,
 SLIDING GLASS DOORS ARE SECONDARY DOOR
 LEADING TO BALCONIES OR LANDINGS .FAIR
 HOUSING CHAPTER 4.
  
 49) A3.03BC UNIT 2C MASTER BED, SEE
 SHEET A4.06 ANDB2" A8.05 LISTING. THE
 ACTIVE LEAF OF THE PAIR OF DOORS MUST BE
 32 CLEAR WHEN MEASURE 90 DEGREESTO THE
 DOOR JAMB.
  
 50) SAME SHEET A4.06 UNIT 3A,
 FH 404.2.2 DOUBLE LEAF DOORWAY
 LEAST ONE OF THE ACTIVE LEAVES OF THE
 PAIR OF
 DOORS TO BE 32 INCHES WITH 2 INDEPENDENT
 LEAVES SHALL COMPLY WITH 404.2 WIDTH)
 AND 404.2.4 (MANEUVERING CLEARANCES).
  
 51) A4.07 PH-1 2 PROBLEMS ENTRY DOORS
 WHERE THE DOORWAY IS DIMENSIONED FH
 404.2.2 DOUBLE LEAF DOORWAY LEAST ONE OF
 THE ACTIVE LEAVES 32 INCHES DOORWAYS
 WITH 2 INDEPENDENTLY
 LEAVES SHALL COMPLY WITH 404.2 (WIDTH)
 AND 404.2.4 (MANEUVERING
 CLEARANCES).
  
 52) THE SAME DETAIL INDICATES DOUBLE
 DOORS AT
 BEDROOM.
  
  
 53) A4.08 PH-3 THE EXTERIOR SWINGDOORS
 ARE
 MISSING A DESIGNATION. THE SWING DOOR TO
 THE MASTER BEDROOM INDICATES AFIVE
 FOOT SWING WHERE AS THE DOOR SCHEDULE
 INDICATES A PAIR OF DOORS.
 FH 404.2.2 DOUBLE LEAF DOORWAY, LEAST
 ONE OF THE ACTIVE LEAVES TO BE 32INCHES
 WITH 2 INDEPENDENT LEAVES SHALL COMPLY
 WITH 404.2 (WIDTH) AND404.2.4
 (MANEUVERING
 CLEARANCES).
  
 54) SAME SHEET A4.06 UNIT 3A FH 404.2.2
 DOUBLE LEAF DOORWAY LEAST ONE OF THE
 ACTIVE LEAVES
 CLEARANCES).
  
 55) A4.07 PH-1 2 PROBLEMS ENTRY DOORWAY,
 WHERE THE DOORWAY IS DIMENSIONED
 FH 404.2.2 DOUBLE LEAF DOORWAY
 DOORWAYS WITH 2 INDEPENDENT LEAVES SHALL
 COMPLY WITH 404.2 WIDTH) AND 404.2.4
 (MANEUVERING
 CLEARANCES).
  
 56) THE SAME DETAIL INDICATES
 BEDROOM.
  
 57) A4.08 PH-3 THE EXTERIOR SWING DOOR
 IS MISSING A DESIGNATION. MASTER BEDROOM
 SWING DOOR VS A PAIR OF DOORS.FH
 404.2.2 DOUBLE LEAF DOORWAY
 LEAST ONE OF THE ACTIVE LEAVES IN
 DOORWAYS WITH 2 INDEPENDENT LEAVES SHALL
 COMPLY WITH 404.2
 WIDTH) AND 404.2.4 (MANEUVERING
 CLEARANCES).
  
 58) A4.08 PH-3, DOORS TO BALCONY NOT
 LABELED, NO
 DOOR DESIGNATION. SEE NOTE 48 THIS IS
 COMMON TO ALL UNITS!!!
  
  
 60) A4.11 PH LOFT-01 ENTRY DOOR, SEE HOW
 THE ENTRY DOOR IS DIMENSIONED VS THE
 DOOR SCHEDULE.
  
 61) A4.11 PH L-01 BEDROOM DOOR IS A PAIR
 OF DOORS, FH 404.2.2 DOUBLE LEAF DOORWAY
 AT
 LEAST ONE OF THE ACTIVE LEAVES IN
 DOORWAYS WITH 2 INDEPENDENT LEAVES SHALL
 COMPLY WITH 404.2
 (WIDTH) AND 404.2.4 (MANEUVERING
 CLEARANCES).
  
 62) A4.12 BEDROOM DOOR B1 BEDROOM DOOR
 IS A PAIR OF DOORS, FH 404.2.2 DOUBLE
 LEAF DOORWAY AT LEAST ONE OF THE ACTIVE
 LEAVES IN DOORWAYS WITH 2 INDEPENDENT
 LEAVESSHALL COMPLY WITH 404.2
 (WIDTH) AND 404.2.4 (MANEUVERING
 CLEARANCES).
  
 63) A3.04CD SHAFT WALL DETAIL AT LINE
 J.2/6 INDICATES A SECTION OF FLOOR SLAB.
 A10.02 FLOOR SLAB EXPANSION JOINT
 DETAILS INDICATE A SHAFT THROUGH THE
 FLOOR SLAB. THEN NEXT TO IT IS THE 8
 INCH MASONRY WALL WILL ADDITIONAL STEEL
 BE REQUIRED IN THE SLAB FOR REINFORCING
  
 64) A3.09BC/ A3.09CD ROOM E808 THE PLANS
 INDICATE GENERATOR ROOMS WHAT TYPE OF
 GENERATOR THIS WILL BE.
  
 65) A3.09BC/ A3.09CD RESTROOMS E809,
 E810, W809 & W810. PROVIDE DIMENSIONS TO
 PLAN SEE, FAIR HOUSING ANSI
 A117.1/403.5.1
 CLEAR WIDTH AT TURNS.
  
 66) A3.09 BC/ A3.09CD PROVIDE DETAILS
 FOR
 LOBBY E808A/ W808A AND HANDICAPPED
 SHOWER .FAIR HOUSING GUIDELINES
  
 67) A3.09 BC/ A3.09CD IT APPEARS THAT
 NUMBER 2/808 & 1/804 DOES NOT HAVE THE
 REQUIRED 18 INCHES ON THE PULL SIDE OF
 THE LATCH. FAIR HOUSING ANSI A117.1
 404.2 MANEUVERING CLEARANCES AT DOOR
  
 68) A3.09AB/ A3.09DA POOL DECK. L -2.3
 FOR TRELLIS PLANS. THE TRELLIS PLANS
 INDICATE SEE STRUCTURAL PLANS FOR
 DETAILS. THERE IS NO INFORMATION ON THE
 STRUCTURAL PLANS AS TO DESIGN OF THE
 TRELLIS SYSTEMS. SEE NOTE ON SHEET ABOUT
 THE EMBEDDED ELEMENTS AND FASTENING
 ELEMENT AT POST TENSION SLABS AND BEAM.
  
 69) A3.09AB/ A3.09DA TRELLIS SYSTEM IF
 FABRIC IS TO BE APPLIED, SEE 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH
 A QUICK REMOVAL OR BREAKAWAY MEMBRANE
 FABRIC AT WIND VELOCITIES OF 75MPH
 SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1.MINIMUM WIND VELOCITY OF
 WIND GUST 90 MPH
 2.IMPORTANCE FACTOR BASED
 HAZARD TO HUMAN LIFE OF 0.77.
 3.EXPOSURE CATEGORY B FOR
 DEFINED IN CHAPTER 16 .
 3105.4.2.2 THE WIND DESIGN LOADS FOR ANY
 MEMBRANE COVERED STRUCTURE DESIGN WITH
 A PERMANENT OR NONREMOVABLE FABRIC
 MEMBRANE SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1.MINIMUM WIND VELOCITY AS REQUIRED
 IN CHAPTER 16.
 2.IMPORTANCE FACTOR BASED ON LOW
 HAZARD TO HUMAN LIFE OF 0.77.
 3.EXPOSURE CATEGORY B OR C AS
 DEFINED IN CHAPTER 16 .
  
 70) A3.09AB, A3.09DA NOTE ON POOL PATIO
 DRAWINGS FOR ANCHORING TO CONCRETE
 PAVERS.
 STRUCTURAL PLANS DO NOT HAVE
 INFORMATION ON THIS NOTE. WIND AND
 UPLIFT CRITERIA.
 106.1.2 ADDITIONAL DATA.
 BUILDING OFFICIAL MAY REQUIRE ADDITIONAL
 COMPUTATIONS, STRESS DIAGRAMS, DATA
 NECESSARY TO DESCRIBE THE CONSTRUCTION
 OR INSTALLATION AND THE
 BASIS OF CALCULATION. ALL DRAWINGS
 SPECIFICATIONS AND ACCOMPANYING DATA
 REQUIRED BY THE BUILDING OFFICIAL TO BE
 PREPARED BY AN ARCHITECT OR ENGINEER
 SHALL BE AFFIXED WITH THEIR OF OFFICIAL
 SEAL,SIGNATURE AND DATE AS STATE LAW
 REQUIRES.
  
 71)A3.09AB/ A3.09DA. PLEASE PROVIDE
 THE CHANGE IN GRADE FOR THE POOL DECK.
 INCLUDE STAIR INFORMATION FOR THE TREAD
 & RISER AND THE HANDICAPPED RAMP RISE
 AND LENGTH OF RAMPS, IF AN INTERMEDIATE
 LANDING IS REQUIRED, IF HANDRAILS ARE
 REQUIRED. FAIR HOUSING
  
 72) A3.09AB/ A3.09CD ELEVATOR SHAFT WALL
 CONSTRUCTION FBC 707.4 2HR WALLS WITH1
 1/2 HR PROTECTIVE.
  
 73) A3.09AB/ A3.09BC PLANS INDICATE
 DECORATIVE MANSARD ROOF, PROVIDE A
 SECTION PROVIDING THE BUILDING ELEMENTS.
 (2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTSSHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED & SHOW DETAIL THAT IT WILL
 CONFORM TO THE
  
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, AND RULES, REGULATIONS
 AS DETERMINED BY THE BUILDING OFFICIAL.
  
 74) A5.01-A5.04 ELEVATIONS FOR BUILDING
 PROVIDE THE POSITIVE AND NEGATIVE
 PRESSURES FOR ALL WINDOW AND DOOR
 OPENINGS. INDICATE THE INTERIOR ZONES
 WELL AS END ZONES. 1609.1.1
 DETERMINATION OF WIND LOADS WIND LOADS
 ON EVERY BUILDING OR
 STRUCTURE SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 6 OF ASCE 7 WIND
 SHALL BE ASSUMED TO COME FROM ANY
 HORIZONTAL DIRECTION AND WIND PRESSURES
 SHALL BE ASSUMED TO ACT NORMAL TO THE
 SURFACE CONSIDERED.
  
 75) PROVIDE THE POSITIVE AND NEGATIVE
 PRESSURES FOR THE VARIOUS ROOF ZONES
 INTERIOR ROOF ZONE#1, EDGE ZONE # 2 &
 END ZONE S# 3. 1609.1.1.
  
 76) NOTE THIS PROJECT DOES HAVE VARIOUS
 TYPE OF ROOF FINISHES. EACH OF THE ROOF
 FINISHES AND UNDERLAYMENTS WILL REQUIRE
 FL COVERSHEETS WITH THE ASSOCIATED NOA
 OR PRODUCT TESTING REPORT.
 NOTE IF THE PRODUCT APPROVALS HAVE A
 LIMITATION#7 OR LIMITATION #9.
 LIMITATION# 7 ALLOWS FOR THE DESIGN
 PROFESSIONAL TO CALCULATE AND FIGURE
 ENHANCED FASTENING IN THE ZONES 2 & 3.
  
 77)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN
 APPLICATION FOR LOCAL PRODUCT APPROVAL
 OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 78) 1609.6.5 COMPONENTS AND CLADDING
 PRESSURE FOR WIND LOADING ACTIONS ON
 COMPONENTS AND CLADDING SHALL BE
 DETERMINED FROM TABLE 1609.6B FOR
 ENCLOSED PORTIONS OF THE BUILDINGS TABLE
 1609.6C FOR OVERHANGS, BASED ON THE
 EFFECTIVE AREA FOR THE ELEMENTS UNDER
 CONSIDERATION. THE PRESSURES IN 1609.6C
 INCLUDE INTERNAL PRESSURE.
 THE PRESSURE SHALL BE APPLIED IN
 ACCORDANCE
 WITH THE LOADING DIAGRAMS IN FIGURE
 1609.6C .
 FL BLD CODE 1609.6.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF
 THRESHOLD OR RESIDENT INSPECTOR) OF
 TESTING REPORTS,MISSING REPORT AS
 FOLLOWS:
 A) WINDOWS FIXED, STOREFRONT
 B) OPERABLE WINDOWS
 C) SPANDREL GLASS
 D) MULLIONS
 E) EXTERIOR SWING METAL DOORS
 F) EXTERIOR SWING GLAZED DOORS
 G) SLIDING GLASS DOORS
 H) WALL LOUVERS
 I) TRUSS ANCHORS
 J) STORM SHUTTERS
 K) PRE-MANUFACTURED A/C STANDS
 L) ROOFING ASSEMBLIES
 M) EFIS SYSTEMS
  
 79) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
  
 80) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBSTRATE.
  
 81) PARKING GARAGE THE BOTTOM FLOORS ARE
 TO BE
 CONSIDERED ENCLOSED AND TO MEET THE
 VENTILATION REQUIREMENTS 406.6.3 AND THE
 F BC MECHANICAL.
  
 82) THE UPPER LEVELS OF THE PARKING
 GARAGE ABOVE
 THE MEZZANINE LEVEL PLEASE PROVIDE
 CALCULATIONS TO SHOW COMPLIANCE WITH
 406.3.3.1 FOR OPEN PARKING GARAGE.
 406.3.3.1 OPENINGS.
 FOR NATURAL VENTILATION PURPOSES, THE
 EXTERIOR SIDE OF THE STRUCTURE SHALL
 HAVE UNIFORMLY DISTRIBUTED OPENINGS ON
 TWO OR MORE SIDES. THE AREA OF SUCH
 OPENINGS IN EXTERIOR WALLS ON A TIER
 MUST BE AT LEAST 20 PERCENT OF THE TOTAL
 PERIMETER WALL AREA OF EACH TIER.
 THE AGGREGATE LENGTH OF THE OPENINGS
 CONSIDERED TO BE PROVIDING NATURAL
 VENTILATION SHALL CONSTITUTE A MINIMUM
 OF 40 PERCENT OF THE PERIMETER OF THE
 TIER. INTERIOR WALLS SHALL BE AT LEAST
 20 PERCENT OPEN WITH UNIFORMLY
 DISTRIBUTED OPENINGS.
  
 EXCEPTION: OPENINGS ARE NOT REQUIRED TO
 BE DISTRIBUTED OVER 40 PERCENT OF THE
 BUILDING PERIMETER WHERE THE REQUIRED
 OPENINGS ARE UNIFORMLY DISTRIBUTED OVER
 TWO OPPOSING SIDES OF THE BUILDING.
  
 83) VERTICAL EXIT ENCLOSURES IN HIGH
 RISE BUILDINGS
 WILL REQUIRE SMOKE DETECTION AT THE
 ENTRANCE TO THE ENCLOSURES. THE ACCESS
 CORRIDORS SHOW SMOKE DETECTION IN THE
 CORRIDORS BUT NOT DIRECTLY IN FRONT OF
 THE DOORWAY, SEE 909.20.6
  
 84) E SHEETS, HIGHRISE VERTICAL EXIT
 ENCLOSURES THAT OPEN
 DIRECTLY INTOPARKING GARAGES SHOULD
 ALSO HAVE SMOKE DETECTORS IN ACCORDANCE
 WITH 909.20.6
  
 85) REVISIT E SHEETS SOME OF THE UNITS
 ARE MISSING
 THE SMOKE DETECTORS ON THE EXTERIOR OF
 THE BEDROOM SIDE, NOTE LOCATION OF
 SUPPLIES AND RETURN AIR SHOULD BE
 INDICATED FOR LOCATION OF DETECTORS.
  
 COMMENTS 86-105 TO BE FORTH COMING !
 COPYING FROM WORD.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-03-13 Cont ID  
Sent By dpalmer Date 2006-03-13 Time 18:54 Rev Time 0.00
Received By dpalmer Date 2006-03-06 Time 18:08 Sent To  
Notes
2006-03-13 00:00:00NOTES
 ********** UNSAT **********
  
 OPERA PLACE.
 419 LAKE VIEW AVE.
  
 1) NOTE: PLEASE SEE PLANS WERE SUBMITTED
 FOR "PLAN REVIEW" ONLY AND NOT BEEN
 SUBMITTED FOR PERMIT. PLEASE KNOW THERE
 WAS AN INCREASE IN PALM BEACH COUNTY
 IMPACT FEE SCHEDULE WHICH WENT INTO
 EFFECT ON JAN 12, 2006 5PM. ALL PROJECTS
 WOULD BE REQUIRED TO BE SUBMITTED FOR
 "PERMIT" AND PAID FEE BEFORE THAT DATE.
  
 2) NOTE: PLEASE SEE COMMENTS FROM OTHER
 TRADES WITH RESPECT TO ADDRESSING OF
 TOWERS EAST AND WEST. PLEASE SEE
 COMMENTS WHICH MAY REQUIRE SOME
 ADJUSTMENT IN TITLE BLOCKS FOR SITE
 ADDRESS ETC. PLEASE KNOW, SIGNAGE FOR
 EACH WILL BE REQUIRED. PLEASE SEE FIRE
 REVIEW COMMENTS AS THIS WILL AFFECT THE
 911 RESPONSE ALONG WITH SIGNAGE AT
 BUILDINGS, FIRE COMMAND ROOMS AND ALL
 ELECTRICAL ROOMS.230.2E, 700.8 ETC.
 * PLEASE ALSO KNOW PLANS AND PERMITTING
 FOR THE PROJECT IS COMING IN UNDER ONE
 PERMIT AND BOTH TOWERS BEING BUILT AND
 CONSTRUCTED AT THE SAME TIME. PLEASE
 KNOW THIS MAY CREATE AN ISSUE FOR ANY
 CO'S OR TCO'S OF THIS ONE PERMIT. SEE
 REVIEW COMMENTS FROM BUILDING.
  
 3) NOTE: PLEASE SEE MANY TITLE BLOCKS ON
 SAID PLANS ARE MISSING ALL INFORMATION
 AS REQUIRED UNDER FLORIDA ADMINISTRATIVE
 CODE 61G1-16.004 FOR ARCHITECTURAL
 FIRM(S) AND 61G15-23.002 FOR ENGINEERING
 FIRMS. PLEASE SEE ONLY ONE FIRM AS SHOWN
 ON TITLE BLOCKS CONTAINS THE CERTIFICATE
 OF AUTHORIZATION NUMBER. FLORIDA STATUES
 481.219, 471.023
 PLEASE ALSO SEE OTHER INFORMATION
 MISSING, THE PRINTED NAME AND LICENSE
 NUMBER FOR THE DESIGN PROFESSIONAL.
 PLEASE SEE THIS IS SHOWN FOR HNGS.
 * PLEASE KNOW, THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE BE SURE ALL THE CURRENT
 CODES ARE REFERENCED ON PLANS. PLEASE BE
 SUE THE FOLLOWING ARE SHOWN AND DESIGNS
 ARE SHOWN ACCORDINGLY.
 NFPA-20 (2002), NFPA-110 (2002),
 NFPA-101 (2003), NFPA-70 (2002), NFPA-72
 (2002).
 PLEASE SEE THERE ARE MANY LOCATIONS ON
 PLANS WHICH REFERENCES REQUIREMENTS FROM
 THE 1996 NATIONAL ELECTRICAL CODE
 NFPA-70.
 PLEASE SEE NOTES ETC.
  
 5) NOTE: PLEASE SEE COLOR CODING OF
 277/480V SYSTEMS SHALL BE "BROWN,
 PURPLE, AND YELLOW". ORANGE IS ONLY FOR
 HIGH-LEG SYSTEMS AND IS NOT PERMITTED
 FOR 277/480V.
 215, 90.4.
  
 6) NOTE: PLEASE KNOW, "LIGHTNING
 PROTECTION"SYSTEM AS SHOWN IF
 INSTALLED BY A SUB CONTRACTOR WILL
 REQUIRED THIS TO BE PULLED UNDER A
 SEPARATE PERMIT.PLANS INDICATE "BONDED
 LIGHTNING" AS THIS SUB.
  
 7) NOTE: PLEASE SUBMIT WIND LOAD
 CALCULATIONS FOR ALL SITE LIGHTING POLES
 INCLUSIVE OF ATTACHED LIGHT FIXTURES.
 PLEASE KNOW, THIS SHOULD INCLUDE ANY
 POLE FIXTURES ON POOL DECK/ROOF
 LEVEL(S).
  
 8) NOTE: PLEASE SHOW AND INDICATE ALL
 ROOM/AREA DESIGNATIONS ON PLANS.
 PLEASE SEE SOME AREAS ARE UNCLEAR FOR
 USE.
 PLEASE SEE ONE OF THESE AREAS APPEARS TO
 SHOW ACCESS TO THE TRASH SHOOT THROUGH
 ONE OF THE ELECTRICAL ROOMS ON
 MEZZ/FIRST FLR. PLEASE SEE BUILDING
 REVIEW COMMENTS FOR THIS. PLEASE KNOW,
 ACCESS THROUGH THIS ELECTRICAL ROOM IS
 NOT PERMITTED. 110.26, 110.27, 240.4
 ETC.
  
 9) NOTE:PLEASE SEE NFPA-110 7.2.3*
 WITH RESPECT TO THE LOCATION OF
 GENERATORS AND ELEVATION. PLEASE SEE
 EXPLANATION OF THIS REQUIREMENT WHICH
 REQUIRES THE MIN AS SET PER THE ?SLOSH?
 PREDICTION. (SEA, LAKE, OVERLAND,
 SURGES, FROM HURRICANES.)
  
 10) NOTE: PLEASE KNOW, DOORS FOR
 ELECTRICAL ROOMS, GENERATOR ROOM, AND
 FIRE PUMPS ROOMS WILL BE REQUIRED TO
 OPEN OUTWARD IN THE DIRECTION OF EGRESS.
 PLEASE KNOW THE MAIN ELECTRICAL ROOMS
 AND GENERATOR ROOM WILL REQUIRED PANIC
 HARDWARE ON DOORS. 110.26.
 PLEASE BE SURE TO SEE ANY INTERFERENCE
 WITH MINIMUM EGRESS WIDTHS IN HALL
 OUTSIDE THE MAIN ELECTRICAL ROOMS.
  
 11) NOTE: PLEASE LABEL MAINS 1 OF 5, 2
 OF 5 ETC PLEASE SEE MAINS AS SHOWN MAY
 LEAD TO SOME CONFUSION IN ORDER TO SHUT
 DOWN BLDG IN CASE OF AN EMERGENCY.
 PLEASE KNOW, THESE MAINS SHOULD ALSO BE
 IDENTIFIED FOR EACH SECTION /USE OF SHUT
 DOWN. FLOORS 1-13 , 13-26, HOUSEPOWER,
 EM ETC.
 215.5
  
 12) NOTE: PLEASE SEE 110.26 FOR MINIMUM
 CLEARANCES REQUIRED FOR ALL ELECTRICAL
 EQUIPMENT IN ELECTRICAL ROOMS.PLEASE
 SEE ENLARGE ELECTRICAL ROOM PLAN SEEMS
 TO NOT SHOW THE MIN. CLEARANCE FOR DPE.
 PLEASE ALSO PROVIDE A NOTE ON E-4.01 FOR
 ALL CLEARANCES TO MEET 110.26, NO
 EXCEPTIONS.
  
 13) NOTE: PLEASE SEE SEF PANEL SHALL BE
 LABELED AS ONE OF THE EMERGENCY MAINS
 FROM GENERATOR.
 215.5, 230.2,230.72 ETC
  
 14) NOTE: PLEASE SEE DPE SHALL CONTAIN A
 MCB IN THE EVENT OF SHUTTING DOWN OF
 POWER ON THE EM SIDE OF GENERATOR.
 230.76, 230.72, 230.79 ETC.
 ACCESS TO GENERATOR ROOM TO QUALIFIED
 PERSONNEL DURING AN EMERGENCYTO SHUT
 DOWN POWER TO DPE DURING THEOPERATION
 OF THIS GENERATORPOSES A CONCERN TO
 THIS OFFICE AND FIRE MARSHAL'S OFFICE.
 "PLEASE KNOW,"SHUNT TRIPS"ARE NOT
 PERMITTED AS THE MEANS OF DISCONNECT ,
 HOWEVER MAY BE INSTALLED AND LABELED
 ACCORDINGLY IN MAIN ELECTRICAL ROOM OR
 FIRE COMMAND ROOM.
  
 15)NOTE:PLEASE PROVIDE A DETAIL FOR
 GATES UNDER POWER FAILURE FOR ACCESS
 INTO AND EGRESS OUT OF BLDG. THESE MAY
 BE PERMITTED SEPARATELY, HOWEVER A NOTE
 FOR A MIN SHOULD BE PROVIDED AT THIS
 TIME.
  
 16) NOTE:PLEASE PROVIDE AN EMERGENCY
 BATTERY BACK UP FIXTURE OF SOME TYPE IN
 ALL ELEVATOR EQUIPMENT ROOMS.
 700.16, LS101 7.8, 7.9
  
 17) NOTE: PLEASE SEE 620.22, 620.23, AND
 620.24 FOR ALL MINIMUM REQUIRED
 DEDICATED BRANCH CIRCUITS. PLEASE SEE
 SOME APPEAR TO SHARE WITH OTHER AREAS
 BESIDES ONLY THE ELEVATOR EQUIPMENT
 ROOMS.
 ALL ROOMS SHALL CONTAIN THEIR OWN
 DEDICATED CIRCUITS AND MAY NOT FEED
 OTHER ROOMS OR OTHER COMMON ARES.
  
 18) NOTE: PLEASE CLARIFY AS IT APPEARS
 ONLY ONE ELEVATOR PIT INDICATES SUMP
 PUMP CIRCUIT?
 PLEASE SHOW OTHER PIT CIRCUIT(S).
  
 19) NOTE: PLEASE SEE FBC 2004 CHAPTER 13
 FOR MEANS OF CONTROL REQUIRED FOR
 EXTERIOR LIGHTING. PLEASE PROVIDE AREA
 CALCULATIONS AS SET FORTH.
 13-415.1.ABC.2
  
 20) NOTE: PLEASE SEE 13-415.1.ABC.1.1 &
 .2 FOR CONTROL OF INTERIOR LIGHTS.
 PLEASE KNOW, ALL ROOMS NOT IN USE FOR
 24HR OPERATION SHALL CONTAIN MEANS OF
 BEING AUTOMATICALLY TURNED OFF.PLEASE
 KNOW, THIS INCLUDES ANY STORAGE,
 MECHANICAL, CLOSETS ETC.
 PLEASE SEE OTHER NEW REQUIREMENTS OF
 CHAPTER 13.
  
 21) NOTE: PLEASE COMPLETE CIRCUITING ON
 PLANS, STAIRS ETC. PLEASE SEE SOME STAIR
 TOWERS SHOWN FIXTURES, HOWEVER CIRCUIT
 IS NOT SHOWN?
 215.5
  
 22) NOTE:PLEASE PROVIDE COMPLETE
 PHOTO-METRICS FOR ALL CORRIDORS, EGRESS
 PATHS, STAIR TOWERS.
 PLEASE SEE 2003 NFPA-101 7.8 AND 7.9,
 THIS REQUIRES A MIN OF 10 FT CANDLES
 FOR STAIRS UNDER NORMAL POWER AND A
 MINIMUM
 OF 1 FT CANDLE UNDER EM POWER.
 PLEASE ALSO KNOW THAT BATTERY BACK UP
 FIXTURE IS ALREADY BEING SHOWN IN STAIR
 TOWERS.
 PLEASE KNOW THIS MAY BE A "TYPICAL"
 DETAIL FOR THESE AREAS. PLEASE SEE THAT
 SOME SORT BATTERY BACK UP FIXTURE WILL
 BE REQUIRED TO PROVIDE A MIN AMOUNT OF
 LIGHT IN HALLWAYS AND GARAGE ARE IN THE
 EVENT OF THE TRIPPING OF THE SINGLE
 MEANS OF OCP ON THE EM SIDE OF SYSTEM.
 PLEASE SEE OTHER AREAS BESIDES STAIRS
 SHALL BE PERMITTED TO PROVIDE 1FT CANDLE
 (AVERAGE) UNDER NORMAL AND EMERGENCY.
 PLEASE SEE 7.9 WHICH REQUIRES THIS
 TO ALLEVIATE ANY ONE AREA BEING IN
 TOTAL DARKNESS UPON THE TRIPPING OF A
 SINGLE DEVICE, SWITCH, BRKR ETC.
  
 23) NOTE:PLEASE SEE THAT ANY AFTER
 DUSK BEFORE DAWN SWIMMING WILL REQUIRE
 PHOTO-METRICS FOR POOL AREA(S). PLEASE
 KNOW, ALL PHOTO-METRICS WILL BE REQUIRED
 TO BE SUBMITTED TO PALM BEACH COUNTY
 HEALTH DEPARTMENT FOR REVIEW AND
 STAMPING. ONLY THE STAMPED PLANS/SHEETS
 FROM PBCHD SHOULD BE SUBMITTED.
  
 24) NOTE: PLEASE SEE NFPA-1107.3.3*
 THE INTENSITY OF ILLUMINATION IN THE
 ROOM HOUSING THE EPS EQUIPMENT FOR LEVEL
 1 SHALL BE 32.3 LUX (30 FT-CANDLES).
 PLEASE SHOW DETAIL.
  
 25) NOTE: PLEASE SEE NFPA-110 7.7 FOR
 EPS VENTILATION. PLEASE SEE LOADING DOCK
 AREA IS BEING SHOWN AS THE AIR INTAKE
 FOR THE GENERATOR WHICH SHOWS A DOOR TO
 CLOSE OFF THIS ARE TO OUTSIDE AIR.
 PLEASE SEE 7.7.2.1 FOR EPS SUPPLYING
 LEVEL 1 EPSS, VENTILATION AIR SHALL BE
 SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE
 OF THE BUILDING BY AN EXTERIOR WALL
 OPENING OR FROM A SOURCE OUTSIDE THE
 BUILDING BY A 2-HOUR FIRE RATED AIR
 TRANSFER SYSTEM.
 PLEASE SEE BUILDING REVIEW COMMENTS AS
 WALLS/ LOUVERS AS SHOWN SEEM TO CREATE
 AN ISSUE FOR THE MIN 2 HR RATING.
  
 26) NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL EPS EQUIPMENT. (ATS). PLEASE SEE
 6.5.2 NFPA-110.
 UNABLE TO VERIFY AT THIS TIME.
  
 27) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR ALL EQUIPMENT:
 ATS?S, GENERATOR, FIRE PUMP FIRE PUMP
 CONTROLLER, SUB-BASE FUEL TANK ETC.
 PLEASE SEE OTHER COMMENTS AND KNOW THAT
 MANY ITEMS FOR CODE COMPLIANCE CAN NOT
 BE REVIEW AT THIS TIME DUE TO THESE
 ITEMS NOT BEING SUBMITTED FOR REVIEW.
  
 28) NOTE: PLEASE SEE NFPA-20 9.6.2.2
 WHICH REQUIRES A MIN OF 8HRS RUNNING @
 100% LOAD FOR FIRE PUMP. PLEASE ALSO
 BEAR IN MIND THE MINIMUM 100% LOADS FOR
 ALL OTHER LEGALLY REQUIRED STAND-BY
 ITEMS.
  
 29) NOTE: PLEASE SEE NFPA-20 7.2FOR
 LOCATION OF FP CONTROLLER, HEIGHT, NEMA
 TYPE 2 ENCLOSURES AND ROOM CONTAINING A
 FLOOR DRAIN.
  
 30) NOTE:PLEASE NOTE ON PLANS THE
 ACCEPTANCE OF THE EPS AS REQUIRED IN
 NFPA-110 7.13.
 THE SYSTEM SHALL BE TESTED AS REQUIRED
 BEFORE CERTIFICATE OF OCCUPANCY OR
 TEMPORARY CO.
  
 31) NOTE: PLEASE SEE SQUARES LOCATED ON
 PLANS SEEM TO REFERENCE NOTES, HOWEVER
 PLEASE SEE THESE NOTES SHOULD BE LABELED
 AS TYPICAL ON ALL SHEETS WITH THESE
 "SQUARES" REFERENCING THESE.
  
 32) NOTE: PLEASE SEE PLANS INDICATE A
 ?GENERATOR ROOM? FOR GYM/ SPA AREA. THIS
 SEEMS IT SHOULD BE LABELED AS ?STEAM
 GENERATOR ROOM.
 215.5
  
 33) NOTE:PLEASE COMPLETE FIXTURE
 SCHEDULE AND CORRELATE WITH PLANS.
 PLEASE SEE SOME FIXTURES ARE NOTED ON
 PLANS AS BEING CHOSEN BY ARCHITECT OR
 THEY ARE NOT NOTED AT ALL. A FIXTURE
 TYPE OF SOME SORT SHOULD BE INDICATED AT
 THIS TIME. THIS CAN BE CHANGE OR REVISED
 LATER. PLEASE SEE ANY ADJUSTMENT IN
 FIXTURE SCHEDULE SHOULD BE UPDATED
 PENDING ANY CHANGES IN EM/EXT LTS.
  
  
  
 34) NOTE: PLEASE SEE NOTE TO BE PROVIDED
 ON ALL E-2.09AB FOR MINIMUM CLEARANCES
 FOR POOL AREA FIXTURES. PLEASE 680.22
 FOR HIGH VOLTAGE FIXTURES (5FT MIN W/
 GFI PROTECTION AND 10FT MIN FOR LOW
 VOLTAGE TYPE FIXTURES. 411.4
  
 35) NOTE: PLEASE SEE 680.22 FOR GFI
 RECEPTACLES TO BE LOCATED A MIN OF 20?
 OF POOL. PLEASE ALSO SEE EXCEPTION WITH
 RESPECT PH-L3 UNITS.
  
 36) NOTE: PLEASE PROVIDE NOTE ON PLANS
 WHICH PROHIBITS THE INSTALLATION OF ANY
 ELECTRICAL CONDUITS ETC IN STAIRS UNLESS
 SPECIFICALLY DESIGNATED TO THE STAIRS.
 PLEASE ALSO PROVIDE NOTE FOR ELEVATOR
 EQUIPMENT ROOMS.
 215.5
  
 37) NOTE: PLEASE SEE ENLARGED ELEVATOR
 EQUIPMENT ROOMS, SOME ITEMS DO NOT SEEM
 TO CORRELATE.
  
 38) NOTE: PLEASE PROVIDE ROOM AND AREA
 DESIGNATIONS ON ALL UNIT PLANS.
 PLEASE BE SURE TO ADDRESS "DINING AREAS"
 AS CIRCUITING IS TO BE VERIFIED. PLEASE
 SEE OTHER COMMENT WHICH THIS AFFECTS.
  
 39) NOTE: PLEASE PROVIDE VOLTAGE DROP
 ANALYSIS FOR ALL FEEDERS AND BRANCH
 CIRCUITS. THIS MAY BE A WORST CASE
 SCENARIO FOR EACH. PLEASE SEE FBC
 CHAPTER 13, 13-413.1.ABC.1.1, &.2.
  
 40) NOTE: PLEASE SEE FAIR HOUSING ACT
 REGULATIONS, 24 CFR 100.205 WITH RESPECT
 TO HEIGHTS AND LOCATIONS FOR ALL
 ACCESSIBLE DEVICES.
 PLEASE SEE SOME ITEMS ON PLANS ARE SHOWN
 TO EXCEED THE MAX OF 48?.
  
 41) NOTE: PLEASE SEE CODES NOTE #12 WITH
 RESPECT TO LOCATIONS OF SMOKE DETECTORS.
 PLEASE SEE 2002 NFPA-72 11.5.1.1,
 11.5.8.3.5.
 SD'S ARE TO BE LOCATED A MIN OF 3FT FROM
 KITCHEN AND BATH DOORS AND A MIN OF 20FT
 FROM COOKING APPLIANCES. (WITH
 EXCEPTIONS TO THE DISTANCE FROM COOKING
 APPLIANCES.
 PLEASE ADJUST THIS "CODES NOTE".
  
 42) NOTE: PLEASE SEE NFPA-72 WHICH
 REQUIRES ALL SD'S TO BE WIRED "IN-LINE".
 PLEASE SEE NUMEROUS UNITS WHERE THE SD?S
 ARE WIRED UP TO AS MANY AS 7 INDIVIDUAL
 CIRCUITS. THIS IS NOT POSSIBLE WHEN THEY
 ARE ALL REQUIRED TO BE WIRED INLINE.
 PLEASE ADJUST CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES
 SUBMITTED. PLEASE ALSO SEE THE FOLLOWING
 COMMENT.
  
 43) NOTE: PLEASE SEE 210.12 IN THE 2002
 NEC WHICH REQUIRES ARC FAULT PROTECTION
 FOR ALL "OUTLETS" ( SD'S, LTS, FANS,
 RECEPTS ETC.)IN BEDROOMS. PLEASE SEE
 SOME CIRCUITING ON PLANS DOES NOT
 INDICATE ARC FAULT PROTECTION FOR SOME
 ITEMS SHOWN IN THE SLEEPING ROOMS.
 PLEASE SEE SD'S CIRCUITED ON PLANS WHICH
 SOME OF THESE CIRCUITS ON PANEL
 SCHEDULES, WHICH DO NOT SHOW AFCI BRANCH
 CIRCUIT PROTECTION.
  
 44) NOTE: PLEASE SEE PLANS SEEM TO
 INDICATE ONLY A "J-BOX" FOR DISHWASHER
 AND DISPOSAL WHICH LENDS TO THESE
 APPLIANCES NOT BEING INSTALLED UNDER THE
 PERMIT FOR THIS BUILDING? PLEASE VERIFY,
 IF INDEED THESE APPLIANCES ARE BEING
 INSTALLED, THEN THE RECEPTACLES WOULD BE
 REQUIRED TO BE SHOWN ON PLANS.
  
 44) NOTE: PLEASE SEE LV PANEL LOCATIONS
 SHOWN IN CLOSETS MAY NOT BE PERMITTED IF
 CONTAINING OCP. PLEASE KNOW, THE
 RECEPTACLES AS SHOWN ON ELECTRICAL PLANS
 IN CLOSETS IN CLOSE PROXIMITY OF
 SHELVING AND/OR STORAGE WILL NOT BE
 PERMITTED FOR ANY "PLUG-IN" TYPE
 TRANSFORMERS. PLEASE KNOW, THIS
 JURISDICTION HAS HAD MANY SCENARIO?S
 WHERE THE HEATING AND OR MELTING OF THE
 PLUG-IN TYPE TRANSFORMER HAS CAUSED
 FIRES. PLEASE KNOW THIS IS A LIFE SAFETY
 AND PROPERTY HAZARD AND LOCATIONS OF
 THESE UNITS/DEVICES WILL NEED TO BE
 ADJUSTED.
 * PLEASE KNOW, IT IS NOTED THAT MANY OF
 THE UNITS DO NOT SHOW THESE LOCATED IN
 CLOSETS AND DO NOT NEED TO BE MOVED.
 240.24,110.26 ETC
  
 45) NOTE: PLEASE VERIFY UNIT BALCONIES,
 AS UNITS DO NOT SHOW ANY LIGHTING OR
 RECEPTACLES ALL THE WAY UP TO THE PH
 UNITS??
 THIS IS ONLY A NOTE AS UNLESS THESE
 BALCONIES CONTAIN DIRECT GRADE LEVEL
 ACCESS, LIGHTING IS NOT REQUIRED. PLEASE
 REVISE IF ANY OF THESE ARE INDEED GOING
 TO CONTAIN LTS ETC.
  
 46) NOTE: PLEASE SEE PLANS WHICH
 MENTIONS "THEATRE" AND NOTES
 ACCORDINGLY. PLEASE SEE NOTES MENTIONS
 "STEP-LTS" WHICH COULD NOT BE LOCATED ON
 PLANS?
 PLANS ALSO INDICATE THIS ARE AS A
 "MULTI-PURPOSE" ROOM?PLEASE CLARIFY
 USE.
  
 47) NOTE: PLEASE PROVIDE EMERGENCY
 LIGHTING FOR EGRESS TO THE PUBLIC RIGHT
 OF WAY. PLEASE SEE THE BREEZEWAY AREAS/
 DRIVE AREA WHICH MAY BE USED AS AN
 EGRESS PATH WAY.
 LS 101-7.8,7.9
  
 48) NOTE: PLEASE SEE NFPA-72 11.8.3.5
 WHICH REQUIRES THE UNIT SMOKE DETECTORS
 TO BE LOCATED ON THE LOWER LEVEL OF A
 MULTI-STORY DWELLING UNIT AND IN CLOSE
 PROXIMITY LEADING TO THE FLOOR ABOVE.
 PLEASE SEE SOME OF THESE ARE LOCATED
 AWAY FROM THIS AREA.
  
 48) NOTE: PLEASE SEE MISSING CIRCUITING
 ON MANY OF THE SMOKE DETECTORS SHOWN ON
 PLANS.
 PLEASE COMPLETE. PLEASE ALSO SEE
 PREVIOUS NOTES ABOVE WITH RESPECT TO THE
 CIRCUITING AND AFCI.
 215.5
  
 49) NOTE: PLEASE SEE MISSING SMOKE
 DETECTORS OUTSIDE SLEEPING ROOMS.
 NFPA-72 11.5.1.1
  
 50) NOTE: PLEASE SEE 210.52 FOR
 RECEPTACLE SPACING INSIDE DWELLING UNITS
 FOR 2 FT, 6FT AND 12 FT RULE.
 PLEASE SEE UNIT LAYOUT AS MANY OF THESE
 HAVE BEEN REDLINED.
  
 51) NOTE: PLEASE SEE MANY UNITS ARE
 SHOWING "J-BOXES" FOR THE REQUIRED MEANS
 OF EGRESS LIGHT FIXTURE REQUIRED. PLEASE
 SEE 210.70, AND LS 101 7.8
 PLEASE SEE A MIN OF ONE FIXTURE OF SOME
 TYPE WILL BE REQUIRED FOR THESE AREAS.
 HALL, DINING, LIVING AREAS ETC.
  
 52) NOTE: PLEASE SEE 210.52C2,4 FOR
 ISLANDS AND SEPARATE COUNTER SPACES
 WHICH REQUIRED ADDITIONAL GFI RECETPS.
  
 53) NOTE: PLEASE SEE 210.52C1 FOR
 COUNTER SPACES ALONG WALLS AND
 210.52C3,4 FOR PENINSULA'S. PLEASE SEE
 WALL SPACES BELOW SOME OF THESE
 PENINSULAR LOCATIONS MAY REQUIRE RECEPTS
 AS THESE APPEAR TO BE WALL SPACES.
 PLEASE SEE 210.8A6 AS ALL RECEPTACLES
 SERVING KITCHEN COUNTER SPACES SHALL BE
 GFI/GFI PROTECTED.
  
 54) NOTE: PLEASE SEE WHAT APPEARS TO
 MISSING "WALLS" IN UNIT 2A-3.05.
  
 55) NOTE: PLEASE SEE WHAT APPEARS TO BE
 A SHIFT IN PLANS IN UNIT "3A". 3.06
  
 56) NOTE: PLEASE SEE CIRCUITING FOR
 DINING ROOMS AND AREAS OF THE LIKE SHALL
 BE ON ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS. PLEASE SEE ALMOST ALL OF THE
 DINING AREAS SHOWN CONTAIN CIRCUITS
 WHICH ARE 15A AND #14 AWG. 210.52B1
 PLEASE ADJUST CIRCUITS, CONDUCTOR SIZES
 AND SEE PREVIOUS NOTE WITH RESPECT TO
 ROOM AND AREA DESIGNATIONS.
  
 57) NOTE: PLEASE SEE MISSING HALL
 RECEPTACLE FOR HALLS CONTAINING 10FT OR
 MORE OF CONTINUOUS WALL SPACE.
 210.52H
  
 58) NOTE: PLEASE SEE UNIT PANELS WHICH
 INDICATE 12KW FOR RANGE LOADS AND LOAD
 CALCULATIONS INDICATE 10KW.
 PLEASE CORRELATE 215.5
  
 59) NOTE: PLEASE SEE A 60A BREAKER
 FEEDING WHAT WOULD BE A 50A RATED DEVICE
 FOR RANGE. PLEASE SEE THIS DOES NOT
 CORRELATE WITH LOAD CALCULATIONS AS
 CALCULATIONS SHOW A LOWER LOAD. PLEASE
 SEE NOTE ABOVE AND CORRELATE LOADS AT
 208V.
 PLEASE SEE 210.21B3
  
 60) NOTE: PLEASE CORRELATE PANEL FOR
 PH-L3 AS SOME AREAS OF PLANS MENTIONS
 THIS AS 225A WITH LOADS EXCEEDING THIS
 RATING. PLEASE SEE OTHER AREAS OF PLANS
 WHICH INDICATE THIS PANEL AS 400A.
 PLEASE ALSO INDICATE IF SECTION ONE
 CONTAINS FEED-THRU LUGS.
 PLEASE SEE METER CENTERRISER ETC.
 215.5, 240.4, 408,310.16 ETC
  
 61) NOTE: PLEASE VERIFY LABELING OF
 UNITS AND PANELS, AS SOME AREAS SHOW
 "A-1" AND OTHER ?1-A?, AND OTHER UNITS
 AND PANELS.
  
 62) NOTE: PLEASE SEE FEEDERS SHOWN AT
 250MCM FOR WHAT APPEARS TO BE 400A PANEL
 AND 400A OCP FOR PH-L3??
 240.4, 310.16
  
 63) NOTE: PLEASE SEE 4.05 MENTIONS ONE
 A/C SYSTEM FOR PH-L3 WITH 70A OCP, YET
 PANEL SCHEDULE FOR THIS UNIT SHOWS 2
 SYSTEMS. PLEASE VERIFY THIS AND ADJUST
 ACCORDINGLY.
  
  
 64) NOTE: PLEASE PROVIDE THE PANEL
 SCHEDULE FOR EACH UNIT AND CORRELATE
 WITH CIRCUITING FOR EACH UNIT AS THE
 CIRCUITING SHOWN DOES NOT CORRELATE TO
 ALL UNITS AND TYPE OF PANEL FOR EACH
 UNIT.
 EACH UNIT SHOULD INDICATE LOADS, OCP AND
 CIRCUITING.
 215.5
  
 65) NOTE: PLEASE SEE METER CENTER RISER
 WHICH INDICATES A 150A BREAKER FEEDING
 PH-L3, WHICH IS 400A?S ETC. PLEASE
 CORRELATE AND SEE NOTE ABOVE.
 215.5
  
 66) NOTE: PLEASE CORRELATE LOAD FOR WHAT
 IS SHOWN AS A POOL HEATER FOR PH-L3 ON
 LOAD CALCULATIONS, HOWEVER THIS IS NOT
 ON PANEL SCHEDULE?
 215.5
  
 67) NOTE: PLEASE CORRELATE LOADS FOR
 OTHER APPLIANCES. PLEASE SEE DISPOSAL
 800VA ON ONE AND 700VA ON THE OTHER.
 215.5
  
 68) NOTE:PLEASE SEE WHAT APPEARS TO BE
 A NOTE ON PANEL SCHEDULES FOR ARC FAULT
 PROTECTION; HOWEVER THIS SYMBOL DOES NOT
 SEEM TO CORRELATE WITH REQUIRED ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE.
 210.12
  
 69) NOTE: PLEASE CORRELATE DISHWASHER
 LOADS, AS LOAD CALCULATIONS SHOW 800VA
 AND PANEL SCHEDULES SHOW 1200VA.
 215.5
  
 70) NOTE: PLEASE CORRELATE WATER HEATER
 SHOWN FOR A-3 OR 3A? 4.5KVA OR 6KVA?
  
 71) NOTE: PLEASE SEE UNIT PHL2 STAIR
 LAYOUTS DO NOT SEEM TO CORRELATE WITH
 EACH FLOOR AND LOCATION OF ABOVE 2ND
 FLOOR.
 215.5
  
 72) NOTE: PLEASE SEE PHL-1 FOR LIVING
 ROOM NEXT TO KITCHEN BAR AREA AND
 CIRCUITING.
 210.52B1
  
 73) NOTE: PLEASE SEE PHL-4 AND LAYOUTS
 TO CORRELATE.
  
 74) NOTE: PLEASE SEE PHL-5 , IT IS
 UNCLEAR WHICH SIDE OF STAIR IS UP?
  
 75) NOTE: PLEASE SEE UNIT PHL-7 WHICH
 APPEARS TO SHOW THE PANEL LOCATED UNDER
 STAIRS? PLEASE SEE 110.26, 240.24 ETC
 IS THIS ARE OPEN? PLEASE ALSO SEE
 PREVIOUS COMMENTS FOR WALL SPACE IN THIS
 SAME AREA.
  
 76) NOTE: PLEASE SEE MINIMUM CLEARANCE
 FOR 277/480V.
 PLEASE SEE 110.26
  
 77) NOTE: PLEASE CLARIFY AND CORRELATE
 PLANS, RISER AND ELECTRICAL ROOM?S
 LAYOUT AS ELECTRICAL ROOM #7 COULD NOT
 BE LOCATED ON ?ENLARGED? ELECTRICAL ROOM
 LAYOUT.
 215.5
  
 78) NOTE: PLEASE BE SURE TO CORRELATE
 ALL UNIT LOADS FOR A/C UNITS AND NEW
 PANEL SCHEDULES TO BE PROVIDED. 215.5
  
 79) NOTE: PLEASE SEE SOME FIXTURES IN
 COMMON AREAS WHICH SEEM O INDICATE THE
 SAME FIXTURE LABEL; HOWEVER THE SYMBOL
 IS NOT THE SAME? PLEASE CORRELATE.
 215.5
  
 80) NOTE: PLEASE SEE FIRE ALARM SHEETS
 WHICH REFLECT CODES FROM THE SFBC.
 PLEASE ADJUST PER 2004 FBC AND NFPA-72
  
 81) NOTE: PLEASE SEE GROUNDING ELECTRODE
 SYSTEM SHOWS DETAIL AND CODE FROM THE
 1996 NEC/ NFPA-72. PLEASE ADJUST.
  
 82) NOTE: PLEASE COMPLETE THE COMMON
 GROUNDING ELECTRODE ON RISER DIAGRAM.
 THIS MAY BE IN LIGHT GRAY OR DASHED
 LINES FOR ALL REQUIRED ATTACHMENTS PER
 250.50, 250.58
  
 83) NOTE: PLEASE COMPLETE ALL
 TRANSFORMER ATTACHMENT LOCATIONS. PLEASE
 SEE SOME ARE SHOWN BEING CONNECTED TO
 THE BUILDINGS GROUNDING ELECTRODE
 SYSTEM, OTHERS ARE NOT.
 250.30, 215.5.
  
 84) NOTE: PLEASE SEE RISER SHOWS MAINS
 ONE , TWO AND SWBD BEING FED FROM
 OVERHEAD ON RISER, HOWEVER ELECTRICAL
 ROOM LAYOUT/ PLANS INDICATE THESE AS
 BEING FED BACK TO BACK WITH FPL VAULT.
 (BUS-STAB?). PLEASE KNOW, NOT MORE THAN
 8? OF UNPROTECTED CONDUCTORS OR BUS DUCT
 IS PERMITTED INSIDE THE BUILDING.230.70,
 230.71
  
 85) NOTE: PLEASE CORRELATE RISER AND
 6.01. ONE SHOWS SWBD AND THE OTHER
 SWGRA?
 215.5
  
 86) NOTE: PLEASE CORRELATE THE NUMBER OF
 PANEL AND UNITS ON RISER DIAGRAM WITH
 THE NUMBER OF UNITS SHOWN ON METER
 CENTER RISER/ SCHEDULE.
 PLEASE SEE ALL FLOORS SHOW DIFFERENT
 NUMBER OF UNITS FOR EACH.
 215.5
 A) PLEASE SEE MC 16, SHOWS 16 ON RISER
 AND 18 ON METER CENTER SCHEDULE.
 B) PLEASE SEE MC # 15 SHOWS 13 ON METER
 SCHEDULE AND 14 ON RISER.
 C) PLEASE SEE MC #14, SHOWS 19 ON RISER
 AND 18 ON METER CENTER SCHEDULE.
 D) PLEASE SEE MC #13 SHOWS 20 ON RISER
 AND 19 ON MC SCHEDULE.
 E) PLEASE SEE MC #12, SHOWS 19 ON RISER
 AND SHOWS 18 ON SCHEDULE.
  
 *** PLEASE SEE ALL OTHERS AND CORRELATE
 AS MOST OF THESE DO NOT MATCH.
 215.5
  
 87) NOTE: PLEASE SPECIFY ALL AIC RATINGS
 FOR ALL EQUIPMENT. PLEASE PROVIDE
 RATINGS FOR ANY FUSE AS INDICATED.
 PROVIDE RATINGS ON CURRENT LIMITING
 FUSES AS NOTED. 110.9, 215.5
  
 88) NOTE:PLEASE KNOW, IF 1000A'S, GFP
 SENSING WILL BE REQUIRED ON SECONDARY
 SIDE, GFP WILL BE REQUIRED ON MAIN ALSO
 AS NOTED
 PER 240.13,230.95.
 PLEASE SEE 700.7D, 700.26, 701.9D
 PLEASE SEE TEXT TAKEN DIRECTLY FROM ASCO
 MANUFACTURE WRITTEN DIRECTIVE FOR EPSS
 SYSTEMS. WHERE AS A 4-POLE ATS MAY BE
 REQUIRED FOR THE
 CORRECT COORDINATION OF ELECTRICAL
 SYSTEMS.
 "WHERE GROUND FAULT PROTECTION IS
 TRIGGERED BY THE CODE AND AN ALTERNATE
 POWER SUPPLY IS INCLUDED,SWITCHING OF
 THE NEUTRAL BECOMES NECESSARY. THE
 CIRCUIT SHOWN ABOVE ILLUSTRATESSUCH A
 CIRCUMSTANCE. THE SERVICE IS LARGER THAN
 1,000 AMPS. CONSEQUENTLY, GROUND FAULT
 PROTECTION IS REQUIRED AT THE MAIN
 SERVICE DISCONNECT AT A MINIMUM. IF IT
 IS INSTALLED THERE AND THE GENERATOR
 NEUTRAL GROUNDING WAS THROUGH A SOLID
 CONNECTION TO THE MAIN SERVICE NEUTRAL,
 A GROUND FAULT WHEN THE GENERATOR IS
 FEEDING THE LOAD WILL CAUSE THE MAIN
 SERVICE DISCONNECT TO OPEN. THIS WILL
 NOT DISCONNECT THE ARCING FAULT FROM THE
 GENERATOR. COORDINATION IS THUS LOST."
 PLEASE VERIFY AS SYSTEMMAY BE REQUIRED
 TO BE SEPARATELY DERIVED GENERATOR AND
 THUS A4-POLE SWITCH MAY BE REQUIRED.
  
 89) NOTE:PLEASE SEE 695.4B1 FOR OCP
 REQUIRED FOR LOCKED ROTOR. PLEASE ALSO
 SEE NFPA-20
 FOR ELECTRICAL REQUIREMENTS FOR MEANS OF
 DISCONNECT, LOCATION ETC. PLEASE SEE
 NFPA-20 AS THE MEANS OF DISCONNECTING IS
 REQUIRED ON THE OUTSIDE OF THE FIRE PUMP
 CONTROLLER. PLEASE SEE SPECS WERE NOT
 SUBMITTED AND UNABLE TO VERIFY THIS AT
 THIS TIME.
  
 90) NOTE:PLEASE SEE 240.13, 230.95
 WHERE GROUND FAULT PROTECTION IS
 REQUIRED FOR MAIN TO GUTTER "RT". THIS
 MAIN COULD NOT BE LOCATED AT THIS TIME.
 215.5
  
 91) NOTE: PLEASE SEE THAT ALL GUTTER
 SIZES ARE TO BE SHOWN FOR A MIN SIZE
 REQUIRED AND DESIGNED BY THE DESIGN
 PROFESSIONAL AT THIS TIME. PLANS NOTE
 THIS IS TO BE SIZED PER CONTRACTOR;
 HOWEVER THIS SHOULD BE ON RECORD SET OF
 PLANS FOR MIN. SIZES. THESE CAN ALWAYS
 BE REVISED AT A LATER DATE.215.5
 PLEASE ALSO SEE CODE AS REFERENCE IS
 FROM THE 1996 NEC.
  
 92) NOTE: PLEASE SEE DP WHICH INDICATES
 MANY BRANCH BREAKERS WHICH ARE SHOWN AS
 4-POLE? THIS IS UNCLEAR AS PANELS ARE 3
 PHASE.
  
 93) NOTE: PLEASE SEE PANEL DPE WHICH
 SHOWS 4-POLE BREAKERS FOR MANY
 ITEMS/CIRCUITS? PLEASE CLARIFY THIS>
 215.5
  
 94) NOTE: PLEASE SPECIFY PANEL "SEF" IF
 CONTAINING FEED-THRU LUGS.
 215.5
  
 95) NOTE: PLEASE SEE SOME PASSENGER
 ELEVATORS SHOWN ON RISER COULD NOT BE
 LOCATED ON PANEL SCHEDULE AS CIRCUITED.
 PLEASE SEE THESE ARE REDLINED.
 215 PLEASE LABEL, AND CORRELATE.
  
 96) NOTE: PLEASE LABEL RISER FOR ALL
 CIRCUITS FOR ELEVATOR CARS/ LTS ETC AND
 CORRELATE WITH PANEL SCHEDULES PROVIDED.
 215.5,620.22, (NOTED ABOVE).
  
 97) NOTE: PLEASE CLARIFY PIT SUMP PUMPS,
 AS PANEL SCHEDULES ONLY SEEM TO INDICATE
 ONE PUMP IN ONE PIT?
 PLEASE INDICATE, REVISE, AND ADJUST.
 215.5
  
 98) NOTE: PLEASE PROVIDE LABELING FOR
 ALL ELEVATORS AND LABEL ON PANEL
 SCHEDULES.?IE? ELEV 1, ELEV 2,,,, ETC.
 PLEASE SEE PANEL "HER".
  
 99) NOTE: PLEASE SEE "HER" SHOWS A
 "SPR", THIS EQUIPMENT COULD NOT BE
 LOCATE ON EQUIPMENT SCHEDULE?
 PLEASE SHOW, LABEL ? 215.5
  
 100) NOTE: PLEASE SEE TXL1A WHICH IS
 LABELED AS #29 FROM RISER. PLEASE
 CORRELATE. 215.5
  
 101) NOTE: PLEASE SEE SERVICE ENTRANCE
 CONDUCTORS INDICATE AN "EQUIPMENT
 GROUNDING CONDUCTOR" FROM FPL VAULT TO
 THE FIRST MEANS OF DISCONNECT. PLEASE
 SEE 250.6 THE GROUNDING OF ELECTRICAL
 SYSTEMS, CIRCUIT CONDUCTORS, SURGE
 ARRESTERS, AND CONDUCTIVE
 NON"CURRENT-CARRYING MATERIALS AND
 EQUIPMENT SHALL BE INSTALLED AND
 ARRANGED IN A MANNER THAT WILL PREVENT
 OBJECTIONABLE CURRENT OVER THE GROUNDING
 CONDUCTORS OR GROUNDING PATHS.THE
 "EQUIPMENT GROUNDING CONDUCTORS" SHALL
 ONLY BE INSTALLED AFTER THE FIRST MEANS
 OF DISCONNECT.
  
 102) NOTE:PLEASE SHOW ALL CONTINUOUS
 LOADS AT 125%, PER 215.3,230.42 ETC.
  
 103) NOTE: PLEASE SEE COMPLETE LOAD
 CALCULATIONS COULD NOT LOCATED FOR
 BUILDING, FUTURE ESTIMATED LOADS FOR
 RETAIL SPACE ETC. LOAD ANALYSIS AS SHOWN
 DOES NOT INDICATE HOW THIS LOAD CAME
 ABOUT? 220.3,220.10,220.13,220.11, ETC
 *UNIT METER CENTERS LOADS ARE SHOWN.
  
 104) NOTE: PLEASE PROVIDE LOADS FOR
 GENERATOR AND DIRECT LOAD CALCULATIONS
 FOR SHEDDING OF LOADS.
 PLEASE SEE THAT PLANS, RISER DID NOT
 INCLUDE A LOAD SUMMARY FOR THIS UNIT.
 215.5, 700.5
  
 105) NOTE: PLEASE SEE NOTE #16 ON RISER
 NOTES WHICH MENTIONS ONLY TWO MAIN
 CIRCUIT BREAKERS FOR STAND-BY SYSTEM,
 HOWEVER RISER SHOWS MORE THAN THE TWO
 LISTED? PLEASE CORRELATE. ONCE AGAIN THE
 GENERATOR SPECS ETC WERE NOT SUBMITTED.
 215.5
  
 106) NOTE: PLEASE CLARIFY WHY SOME
 ELEVATORS INDICATE "SHUNT TRIPS" AND
 OTHER DOES NOT?
 215.5
  
 107) NOTE: PLEASE VERIFY THE TAPPED
 CONDUCTORS SHOWN FROM TXRL TO RL. PLEASE
 SEE 240.21 AS THIS INSTALLATION DOES NOT
 SEEM TO MEET ANY OF THE EXCEPTIONS
 LISTED.
 I215.5
  
 108) NOTE: PLEASE SHOW VOLTAGE DROP FOR
 PANEL "HER". THIS MAY BE PART OF LOAD
 ANALYSIS AS PREVIOUSLY NOTED.
 FEEDER SCHEDULE MENTIONS FEEDERS ARE
 UPDATED FOR VD, HOWEVER THESE DO NOT
 SEEM TO SHOW THIS?
 215.5, 13.413.1.ABC.1
  
 109) NOTE: PLEASE ALSO SUBMIT THE
 VOLTAGE DROP FOR PANEL "HR" AS NOTED
 ABOVE.
  
 110) NOTE:PLEASE SEE MISSING
 CONDUCTORS FROM H-3 TO TRANSFORMER AND
 TO PANEL L3. 215.5, 240.4,310.16,240.21
 ETC
  
 111) NOTE: PLEASE SEE "HE3", MISSING
 CONDUCTORS FROM THIS PANEL TO
 TRANSFORMER AND TO PANEL
 LE3.215.3,240.4,310.16, 240.21
  
 112) NOTE:PLEASE SEE PANEL "HIA" SHOWS
 15 KVA TRANSFORMER, YET RISER SHOWS 75
 KVA. PLEASE CORRELATE>
 215.5
  
 113) NOTE: PLEASEPANEL "LR" WHICH IS
 SHOWN WITH A 100A MCB , HOWEVER THE
 CONDUCTORS TO THIS PANEL IS RATED FOR
 50A?S. PLEASE VERIFY THE CONDUCTORS AS
 THEY DO NOT TERMINATE IN OCP WHICH
 LIMITS THE LOADS FOR THE CONDUCTORS.
 PLEASE VERIFY WITH240.21C, (1-6)
  
 114) NOTE:PLEASE SEE THAT PANEL "LI"
 INDICATES FEED-THREE LUGS IF INDEED THIS
 IS THE INSTALLATION. 215.5
  
 115) NOTE:PLEASE SEE RETAIL COMMON
 "SHELL AREAS" SHALL CONTAIN MINIMUM
 LIGHTING AS REQUIRED AND PERFIRE
 MARSHAL'S OFFICE, HOWEVER PLEASE SEE
 THESE AREAS ARE ALL BEING SHOWN
 CIRCUITED TO PANELSWHICH UNDER THE
 BASE BUILDING. PLEASE PROVIDE NOTES ON
 PLANS, AS ALL OF THIS INTERIOR
 CIRCUITING WILL BE REQUIRED TO BE
 REMOVED AND RE-CIRCUITED TO THE PANELS
 AND SERVICE THESE TENANT SPACES ONCE
 PERMITTED.
 CROSSING OVER OF SERVICES, COMMON AREA
 BRANCH CIRCUITS IS NOT PERMITTED.
 230.70,225.25 ETC
  
 116) NOTE: PLEASE SEE 250.104 WHICH
 REQUIRES ?ALL OTHER METAL PIPING SYSTEMS
 TO BE PART OF THE BUILDINGS GROUNDING?.
 PLEASE SHOW ATTACHMENT OR NOTE;
  
 117) NOTE: PLEASE KNOW, MANY OF THE
 ABOVE ITEMS ARE REDLINED ON ONE SET OF
 THE MEP'S FOR MANY OF THE SD'S, RECEPTS,
 LTS ETC AND LOCATIONS NEEDED. PLEASE
 KNOW, THIS IS IN NO WAY ALL LOCATIONS
 WHICH MAY BE NEEDED. PLEASE GO OVER
 PLANS FOR ALL ITEMS.
  
 118) NOTE: PLEASE KNOW A DETAILED
 RESPONSE LETTER ON HOW ALL COMMENTS WERE
 ADDRESSED AND CLARIFICATIONS NEEDED.
 THIS WILL HELP IN EXPEDITING THE REVIEW
 PROCESS.
  
 119) NOTE: PLEASE SEE ALL COMMENTS FROM
 OTHER REVIEWS WHICH MAY AFFECT
 ELECTRICAL PLANS AND DESIGN.
  
 120) NOTE:ONCE ALL REVIEWS ARE
 COMPLETE AND BEFORE RESUBMITTING PLANS:
 "ALL OLD/VOIDED SHEETS SHALL BE REMOVED
 AND ONLY THE NEW REVISED SHEETS SHOULD
 BE INSERTED INTO THREE COMPLETE SETS FOR
 REVIEW AND STAMPING".
 ONE SET OF ALL OLD/VOIDED SHEETS WHICH
 ARE REMOVED SHOULD BE SUBMITTED FOR
 REFERENCE ALONG WITH THE NEW SETS. ALL
 VOIDED SHEETS MUST BE REMOVED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-03-10 00:00:00*** ELECTRICAL REVIEW COMPLETED ***
 NOTES TO BE ENTERED ON MONDAY 3/13/06
 STATUS WILL BE "F".
2006-03-08 00:00:00REVIEW STILL IN PROGRESS,NOTES TO
 FOLLOW.
2006-03-06 00:00:00REVIEW CONTINUED.
2006-03-03 00:00:00REVIEW STOPPED. REVIEW TO CONTINUE ON
 MONDAY 3/6
2006-03-02 00:00:00ELEC REVIEW STARTED FOR REVIEW, NOTES TO
 FOLLOW. REVIEW IN PROGRESS.
2006-02-10 00:00:00ONE ROLL OF MEP'S IN ELECTRICALTO
 REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-06-05 Cont ID  
Sent By pkrauss Date 2006-06-05 Time 12:34 Rev Time 0.00
Received By pkrauss Date 2006-06-05 Time 12:33 Sent To  
Notes
2006-06-05 00:00:00PER STEVE SARLEY THE FOLLOWING NOTE WAS
 ENTERED UNDER THE FOUNDATION PERMIT IN
 ERROR; WATER AND SEWER CIVIL PLANS HAVE
 NOT BEEN APPROVED BY UTILITIES REVIEWER

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-03-03 Cont ID  
Sent By mcarsill Date 2006-03-03 Time 07:48 Rev Time 0.00
Received By mcarsill Date 2006-02-16 Time 12:14 Sent To  
Notes
2006-02-16 00:00:001. ELECTRONIC SWITCHES, CHAIN AND LOCK
 REQUIRED ON FIRE LINE BACKFLOW DEVICE.
  
 2. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 3. EXIT STAIRS ARE TO BE KEPT UP WITH
 CONSTRUCTION.
  
 4. TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE STORIES
 OR THIRTY FEET IN HEIGHT.
  
 5. DEBRIS SHALL BE REMOVED THE BUILDING
 DAILY.
  
 6. NO CUTTING OR WELDINGALLOWED
 WITHOUT APPROVAL OF THE BUREAU OF FIRE
 PREVENTION AND COMPLIANCE WITH NFPA 51B.
  
 7. PLEASE EXPLAIN "PROP. 6" FIRE
 SERVICE" SHOWN IN DETAIL B ON PAGE
 C-2.0.
  
 8. WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING, AND AFTER CONSTRUCTION.
  
 9. KNOX-BOXES WILL BE REQUIRED FOR THE
 PROJECT.
  
 10. LANDSCAPE AREAS SHALL NOT INTERFERE
 WITH ANY ACCESS TO AND FIRE HYDRANTS OR
 FIRE PROTECTION DEVICES LIKE FIRE
 DEPARTMENT CONNECTIONS.
  
 11. BUILDING ADDRESS REQUIRED. A MINIMUM
 OF AT LEAST 6" HIGH NUMBERS ARE
 REQUIRED.
  
 12. WHAT WILL THE 24 FOOT DRIVEWAY BE
 USED FOR.
  
 13. ARE ANY STEPS LOCATED NEAR WATER
 FEATURES SLIP RESISTANT.
  
 14. ALL NEW STAIRS AND RAMPS SHALL BE
 PROVIDED HANDRAILS ON BOTH SIDES.
  
 15. ELEVATOR WARNING SIGNS REQUIRED.
  
 16. TACTILE SIGNAGE REQUIRED AT EXIT
 DOOR LOCATIONS.
  
 17. ALL MECHANICAL, ELECTRICAL, AND
 STORAGE ROOMS SHALL BE IDENTIFIED WITH
 SIGNAGE.
  
 18.WRONG LIFE SAFETY CODE REFERENCED ON
 PAGE A-0.02.SHOULD READ THE FLORIDA FIRE
 PREVENTION CODE WHICH CONSISTS OF 2003
 EDITION OF THE LIFE SAFETY CODE AND NFPA
 1, 2003 EDITION.
  
 19. DUE TO THE SIZE OF THE PROJECT, A
 FIRE AND EMERGENCY SAFETY PLAN WILL BE
 REQUIRED. THIS COMPREHENSIVE PLAN SHALL
 BE SUBMITTED TO THE CHIEF FIRE
 PREVENTION OFFICER OF THE BUREAU OF FIRE
 PREVENTION AND A COPY WILL BE PROVIDED
 TO THE DIRECTOR OF CONSTRUCTION
 SERVICES.
  
 20. THIS PROJECT WILL BE REVIEWED UNDER
 THE MULTIPLE OCCUPANCY CONCEPT SINCE
 SEVERAL DIFFERENT OCCUPANCY TYPES WILL
 EXIST.
  
 21. HOW WILL THE THEATRE DROP OFF AREA
 WORK ON QUADRILLE, PAGE A-1.02.
  
 22. ALL PROPOSED RETAIL SPACES SHALL BE
 EQUIPPED WITH FIRE SPRINKLER AND FIRE
 ALARM PROTECTION PRIOR TO THE
 BUILDING(S) RECEIVING A CERTIFICATE OF
 OCCUPANCY. THE RETAIL SPACES MAY NOT BE
 COMPLETE OR LEASED AT THAT TIME.
  
 23. EXIT SIGNS SHALL NOT EXCEED 100 FEET
 APART.
  
 24. EXIT SIGNS APPEAR TO DIRECT PERSONS
 OUT OF THE STORAGE ROOM ON PAGE LS-2.03
 INTO THE PARKING GARAGE. THIS DOES NOT
 APPEAR TO BE CORRECT.
  
 25. NO EXIT SIGNS SHOWN IN STORAGE ROOMS
 ON PAGES LS-2.05, LS-2.06, LS-2.07.
  
 26. PLEASE EXPLAIN GENERATOR ROOMS
 LOCATED ON THE FLOOR LEVEL EIGHT.
  
 27. HOW WILL THE BUILDINGS BE SEPARATELY
 IDENTIFIED SHOULD AN EMERGENCY CONDITION
 OCCUR.
  
 28. SIAMESE CONNECTIONS NOTED ON PAGE
 LS-2.13. THESE SHOULD BE CALLED OUT ON
 THE PLANS AS ROOF MANIFOLDS.
  
 29. AFTER PERSONS EXIT STAIRS 4 & 4A,
 WHAT PREVENTS THEM FROM BEING HIT BY
 VEHICLES.
  
 30. ALL MEZZANINES ILLUSTRATED ON THE
 PLANS SHALL COMPLY WITH ALL APPLICABLE
 BUILDING AND FIRE CODE REQUIREMENTS.
  
 31. THERE APPEARS TO BE COLUMNS NEAR THE
 OPENINGS OF THE PARKING GARAGE EXITS
 SHOWN ON PAGE A-2.03.
  
 32. PLEASE VERIFY THAT ALL DOORS THAT
 OPEN ONTO EXIT CORRIDORS (ELECTRICAL
 ROOM) DO NOT REDUCE THE CORRIDORS DWON
 TO THE REQUIRED WIDTH.
  
 33. STAIRWELL IDENTIFICATION SIGNS WILL
 BE REQUIRED INDICATING STAIR NUMBER,
 FLOOR LEVEL, TERMINATION POINTS TOP AND
 BOTTOM.
  
 34. ELECTRICAL ROOM AND TRASH ROOM DOORS
 OPPOSE ONE ANOTHER ON PAGE A-2.09.
 SIMILAR CONDITIONS EXIST ON OTHER PAGES.
  
 35. BOTH FIRE COMMAND ROOMS SHALL COMPLY
 WITH THE FLORIDA FIRE PREVENTION CODE
 AND THE FLORIDA BUILDING CODE AND SHALL
 CONTAIN ALL OF THE REQUIRED OUTLINED
 WITHIN THESE CODES.
  
 36. STRETCHER ACCESSIBLE ELEVATORS SHALL
 BE IDENTIFIED BY APPROPRIATE SIGNAGE.
  
 37. FOUR CIRCLES SHOWN IN KITCHEN ON
 PAGE A-3.02-BC. DOES THIS INDICATE A
 STOVE. PLEASE EXPLAIN. PAGE A-3.02CD.
  
 38. HOW DOES THE PROPOSED SLIDE GATE ON
 PAGE A-3.03BC RESTICT MOVEMENT. DOES IT
 RESTRICT MOVEMENT OR TRAVEL TO ANY
 EXITS.
  
 39. SAME SITUATION EXISTS ON PAGE
 A-3.03CD.
  
 40. ROOM BEHIND ELECTRICAL ROOM E329 IS
 NOT LABELED ON PAGE A-3.04BC. PLEASE
 IDENTIFY.
  
 41. SIMILAR CONDITION EXISTS ON OTHER
 PAGES.
  
 42. ON SEVERAL SHEETS IT IS PRESUMED
 THAT A PARKING SPACE THAT IS CALLED OUT
 AS EJ IS NEXT TO A COLUMN THAT IS IN THE
 VICINITY OF AN EXIT DOOR.
  
 43. PLEASE EXPLAIN STORAGE ROOM E535 ON
 PAGE A-3.06 AB. PLEASE INDICATE INGRESS/
 EGRESS INTO AREA.
  
 44. FIRE ALARM CIRCUITS ARE REQUIRED TO
 MEET SURVIVABILITY REQUIREMENTS OF THE
 APPLICABLE CODES.
  
 45. SMOKE DETECTORS SHALL BE MOUNTED A
 MINIMUM OF AT LEAST THREE FEET FROM AC
 DIFFUSERS.
  
 46. MORE DETAILS REQUIRED FOR POOL
 CABANAS SHOWN ON PAGE A-3.09AB.
  
 47. SMOKE DETECTORS ARE REQUIRED ON
 EVERY LEVEL OF THE LOFTS.
  
 48. ALL FIRE RATED DOORS AND WINDOWS
 SHALL COMPLY WITH NFPA 80 FIRE DOORS AND
 WINDOWS.
  
 49. FIRE RATED WALLS AND DOORS SHALL BE
 GIVEN PRIORITY DURING CONSTRUCTION.
  
 50. ON PAGE A-4.15, SEVERAL ELEMENTS
 APPEAR TO HANG OVER THE PROPERTY LINE.
  
 51. PLEASE PROVIDE PRODUCT APPROVALS FOR
 ALL FIRE RATED AWNINGS.
  
 52. MECHANICAL GRILLS SHOWN IN CLOSE
 PROXIMITY TO OTHER BUILDING OPENINGS ON
 PAGE A-5.01.
  
 53. THE FIRE SPRINKLER HEADS PLANNED FOR
 USE SHALL BE QUICK RESPONSE OR BE
 RESIDENTIAL TYPE.
  
 54. MORE DETAILS NEEDED FOR ORNAMENTAL
 GRILL ON PAGE A-5.06.
  
 55. ALL RETAIL SPACES SHALL BE SEPERATED
 FROM PARKING AREAS BY A MINIMUM OF AT
 LEAST TWO HOUR CONSTRUCTION.
  
 56. ANY DECORATIVE SOFFITS PLANNED TO BE
 USED SHALL NOT INTERFERE WITH THE
 OPERATION OF ANY REQUIRED FIRE
 SPRINKLERS.
  
 57. PLEASE PROVIDE RATING OF TRASH CHUTE
 DOORS ON PAGES A-6.10-A-6.13.
  
 58. NOTE # 1 ON PAGE A-7.01 IS NOT
 CORRECT. DESIGN ISSUES WITH PIPES SHALL
 BE AVOIDED.
  
 59. PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS SHALL BE
 SHOWN ON PAGE A-7.06.
  
 60. ELEVATOR MACHINE ROOMS MUST BE
 PROVIDED WITH VENTILATION AND AIR
 CONDITIONING.
  
 61. EMERGENCY GENERATORS PROPOSED FOR
 THIS PROJECT SHALL COMPLY WITH NFPA 110.
  
 62. DOOR SCHEDULE LEGEND ON A-8.05 DOES
 NOT INDICATE WHAT ELEC. OPER
 MEANS ON DOOR SCHEDULE. PLEASE PROVIDE
 DETAILS.
  
 63. ON PAGE A-10.05 "BREAK GLASS" NOTE
 FOR (1) A-10.5. HOW IS THIS TO BE
 ACCOMPLISHED IS A HANDLE OR HAMMER
 PROVIDED.
  
 64. PLEASE VERIFY THAT ALL MATERIAL SUCH
 AS UPOSTERED MATERIAL AND DRAPERY
 MATERIAL DISPLAYED ON ID-5.06. DOES THIS
 PROPOSED MATERIAL MEET FLAME SPREAD
 REQUIREMENTS.
  
 65. EXIT SIGN APPEARS TO BE MISSING IN
 RETAIL SPACE # 4 ON PAGE E-2.01-BC.
  
 66. EXIT SIGN LOCATED OUTSIDE OF PUMP
 ROOM ON PAGE E-2.01-BC LEADS WHERE.
  
 67. SOME EXIT DOORS IN RETAIL SPACE # 9
 ON PAGE E-2.01-DA. VERIFY OCCUPANCY
 TYPE.
  
 68. ON SHEETS E-2.02 BC AND E-2.20 CD
 EXIT SIGNS ARE DIRECTING PERSONS TO EXIT
 INTO THE GARAGE. PLEASE EXPLAIN.
  
 69. SOME EXIT SIGNS APPEAR TO BE MISSING
 ON PAGE E-2.05-AB.
  
 70. NO EXIT SIGNS SHOWN IN GYM ON PAGE
 E-2.09-BC.
  
 71. EXIT SIGNS APPEAR TO BE MISSING ON
 PAGE E-2.08-AB.
  
 72. ADDITIONAL EXIT SIGN NEEDED NEAR
 BATHROOMS ON PAGE E-2.09-BC TO DIRECT
 PERSONS TO STAIRWAY.
  
 73. THE EMERGENCY LIGHTING AND GENERATOR
 SHALL COMPLY WITH NFPA 101, SECTION
 11.8.4.
  
 74. THE REQUIRED FIRE ALARM SYSTEM SHALL
 BE MONITORED BY A UL LISTED CENTRAL
 STATION APPROVED FOR CENTRAL STATION
 SERVICE. SEPERATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM SYSTEM.
  
 75. THE FIRE COOMAND ROOM SHOWN ON PAGE
 E-5.01C MUST CONTAIN ALL OF THE REQUIRED
 EQUIPMENT AS PER SECTION 11-8 OF THE
 LIFE SAFETY CODE.
  
 76. THE ENTIRE BUILDING WILL BE REQUIRED
 TO BE FIRE SPRINKLER PROTECTED. SEPERATE
 PLANS AND PERMITS REQUIRED.
  
 77. THE 2 1/2 FIRE DEPARTMENT HOSE VALVE
 CONNECTIONS SHOWN ON THE FP PAGES SHALL
 BE REDUCED WITH 1 1/2 REDUCERS.
  
 78. NO COMBUSTIBLES ALLOWED IN ANY AREAS
 USED AS RETURN AIR PLENUMS. ALTHOUGH
 THIS INFORMATION IS NOTED IT MAY BE
 MISSED. PLEASE CLEARLY ILLUSTRATE THIS
 ON THE APPROPRIATE SHEETS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-04-21 Cont ID  
Sent By kstevens Date 2006-04-21 Time 17:55 Rev Time 0.00
Received By kstevens Date 2006-04-21 Time 17:55 Sent To  
Notes
2006-04-21 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. SHT P-4.15 GAS REQUIREMENTS:
 A. SUBMIT MANUFACTURE SPECIFICATION
 SHEETS FOR 5PSI TO .5PSI REGULATORS. IF
 REGULATORS ARE VENTED, SUBMIT AN
 ISOMETRIC PIPING DIAGRAM FOR THE VENTING
 AND INDICATE TERMINATION POINT. INDICATE
 MATERIAL FOR VENT PIPING.
 B. SHUT OFF VALVES ARE REQUIRED
 UPSTREAM OF EACH REGULATOR. SECTION
 409.4
 C. SUBMIT AN APPROVED TABLE FOR 5PSI UP
 TO 800 FEET TO VERIFY PIPE SIZE IN
 SYSTEM. SECTION 402.3(2)
 D. INDICATE LENGHTS OF PIPE FOR EACH
 CUT SECTION FROM THE METER TO THE FIRST
 RISER, AND FOR ALL CUT SECTIONS
 DOWNSTREAM OF THE 5PSI TO .5PSI
 REGULATOR. FBC-2004 FUEL GAS
 E. GALVANIZED PIPING IS NOT APPROVED
 FOR UNDERGROUND INSTALLATION. SECTION
 404.8.
 F. SLEEVE FOR UNDERGROUND PIPING SHALL
 BE INSTALLED PER SECTION 404.11.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-05 Cont ID  
Sent By pkrauss Date 2006-06-05 Time 12:37 Rev Time 0.00
Received By pkrauss Date 2005-12-29 Time 16:29 Sent To  
Notes
2006-01-31 00:00:00TO "COMM" BD#6
2005-12-29 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-05-30 Cont ID  
Sent By pkrauss Date 2006-05-30 Time 10:37 Rev Time 0.00
Received By pkrauss Date 2006-05-30 Time 10:37 Sent To  
Notes
2006-05-30 00:00:00DENIED:2004 FLORIDA BUILDING CODE
  
 1.PLAN SHEET M-2.01-AB, PLEASE PROVIDE
 THE DISTANCE FROM PROPERTY LINES,
 STREETS, ALLEYS, PARKING LOTS AND
 LOADING DOCKS FOR THE FRESH AIR INTAKES
 INTERIOR AND EXTERIOR OF THE BUILDING.
 SHOW COMPLIANCE WITH 2004 FMC 401.5 &
 401.5.1.
  
 2.PLAN SHEET M-2.01-AB, 12 X 12 O.A.
 INTAKE AT THE PARKING MAIN ENTRANCE,
 SHOW COMPLIANCE WITH FMC 401.5, 401.5.1.
  
 3.PLAN SHEET M-2.01-AB, PLEASE CLARIFY
 THE FOLLOWING; R1-SSF-1 IS A SUPPLY FAN
 FOR THE PURPOSE OF SMOKE CONTROL TO THE
 RETAIL SPACE 1 & COORIDOR?ON PLAN
 SHEET THE SYMBOL FOR RETURN DUCT IS
 INDICATED.PLEASE CLARIFY ALSO FIRE
 DAMPERS INDICATED INSTEAD FO FIRE/SMOKE
 DAMPERS.
  
 4.R1-SSF-1 IS ALSO DUCTED TO UNIT 3-3
 (WHICH IS NOT INDICATED ON THE EQUIPMENT
 SCHEDULE),PLEASE CLARIFY WHAT THIS
 EQUIPMENT FUCTION IS, (AHU, RTU, ETC.)?
  
 5.PLAN SHEET M-2.01-AB, PLEASE
 INDICATE THE ELEVATIONS & DISTANCES FROM
 PROPERTY LINES ADJACENT BUILDING ETC.
 FOR THE EXHAUST TERMIANTIONS.SHOW
 COMPLIANCE WITH 2004 FMC 401.5.1,
 401.5.2, & 501.2.
  
 6.PLAN SHEET M-2.01-AB, PLEASE CLARFY
 THE TOILET & SMOKE EXHAUST TO RETAIL 2
 IN RELATION TO THE DOUBLE DOOR,
 SIDEWALK, AND PROPERTY LINES.
  
 7.PLAN SHEET M-2.01-BC, GENERATOR
 ROOM.PLEASE ADDRESS THE FOLLOWING
 ITEMS:
 A) EXHAUST LOUVER TERMINATES IN A 2HR
 RATEDWALL WITHOUT PROTECTION.PLEASE
 NOTE, FIRE DAMPER TO MANUFACTURER
 APPROVAL AT THIS TERMIANTION.
 B) PLAN DOES NOT INDICATE TERMINATION OF
 THE MUFFLER EXHAUST TO THE GENERATOR.
 C) AIR MAKE-UP FOR THE GENERATOR ROOM IS
 TAKEN FROM THE LOADING DOCK AREA WHICH
 IS NON-COMPLIANT WITH 2004 FMC 401.5.1.
 D) PLEASE CLARIFY DETAIL OF THE
 GENERATOR INDICATED ON PLAN M-4-04. THIS
 DETAIL ALSO INDICATES A REMOTE FILL
 WHICH IS NOT DEPICTED ON THE PLAN.
 E) DETAIL INDICATES THE SUB-BASE FUEL
 TANK IS A 300 GALLON, WILL THERE BE
 ANOTHER REMOTE FUEL TANK?
  
 8.INSTALLATION OF THE GENERATOR SHALL
 COMPLY WITH THE FOLLOWING NFPA 110
 REQUIREMENTS:
 7.7.2.1 FOR EPS SUPPLYING LEVEL 1 EPSS,
 VENTILATION AIR SHALL BE SUPPLIED
 DIRECTLY FROM A SOURCE OUTSIDE THE
 BUILDING BY AN EXTERIOR WALL OPENING OR
 FROM A SOURCE OUTSIDE THE BUILDING BY A
 2-HOUR FIRE RATED AIR TRANSFER SYSTEM.
  
 7.7.2.2 FOR EPS SUPPLYING LEVEL 1 EPSS,
 DISCHARGE AIR SHALL BE DIRECTED OUTSIDE
 THE BUILDING BY AN EXTERIOR WALL OPENING
 OR TO AN EXTERIOR OPENING BY A 2-HOUR
 FIRE RATED AIR TRANSFER SYSTEM.
  
 7.7.2.3 FIRE DAMPERS, SHUTTERS, OR OTHER
 SELF-CLOSING DEVICES SHALL NOT BE
 PERMITTED IN VENTILATION OPENINGS OR
 DUCTWORK FOR SUPPLY OR RETURN/DISCHARGE
 AIR TO EPS EQUIPMENT FOR LEVEL 1 EPSS.
  
 7.7.3 VENTILATION AIR SUPPLY SHALL BE
 FROM OUTDOORS OR FROM A SOURCE OUTSIDE
 THE BUILDING BY AN EXTERIOR WALL OPENING
 OR FROM A SOURCE OUTSIDE THE BUILDING BY
 A 2-HOUR FIRE RATED AIR TRANSFER SYSTEM.
  
 9.PLAN SHEET M-2.01-BC, FIRE CONTROL
 ROOM, ARCHITECTURAL PLANS INDICATE THIS
 ROOM IS AS NOT HAVING A FIRE RATING AS
 REQUIRED PER 2004 FBC 911.1.PLEASE
 CLARIFY.ALL PENETRATIONS SHALL COMPLY
 WITH 2004 FBC 712.
  
 10. PLEASE CLARIFY SMOKE CONTROL METHOD
 FOR THE EXIT CORRIDORS FOR THE RESIDANT
 FLOORS (M-2.03-BC THROUGH M-2.09-CD, AND
 M-2,10-BCM-2.13-CD).SMOKE CONTROL
 THROUGH PRESSURIZATION.PLEASE INDICATE
 WHERE THE FLOOR OF INCIDENT WILL THE
 SMOKE BE MIDIGATED TO.SHOW COMPLIANCE
 WTIH 2004 FMC 513.10.3.
  
 11. PLAN SHEET M-3.01 INDICATES R/A
 GRILLE IN THE LAUNDRY ROOM.LAUNDRY
 ROOMS ARE NOT REQUIRED TO HAVE RETURN
 AIR PER 2004 FMC 601.4 EXCEPTION #3.
  
 12. PLAN SHEET P-4.15 INDICATES GAS
 RISER.PLEASE INDICATE IF ANY OF THE
 APPLIANCES LOCATED IN THE CONDO UNITS
 WILL BE GAS (DRYER, WATER HEATER, RANGE,
 ETC.).
  
 13. PLAN SHEET P-1.01, DETAIL FOR THE
 GENERATOR ROOM SHOWS AN EXTERIORFILL
 POINT.THIS LOCATION IS "INSIDE" THE
 GARAGE AREA, AS IS THE MUFFLER EXHAUST.
 PER 2004 FMC 1305.6, FILL PIPE SHALL
 TERMINATE OUTSIDE THE BUILDING AT A
 POINT AT LEAST 2 FEET FROM ANY BUILDING
 OPENING AT THE SAME OR LOWER LEVEL.IT
 SHALL ALSO TERMINATE IN SUCH A MANNER TO
 MINIMIZE SPILLING WHEN FILL HOSE IS
 DISCONNECTED.
  
 14. PLAN SHEET P-5.01 DETAIL FOR THE
 GENERATOR SIMPLEX FUEL PORT.IS THIS A
 DAY TANK?
  
 15. PLEASE PROVIDE SUBMITTAL DATA &
 INSTALLATION INSTRUCTIONS FOR THE DIESEL
 GENERATOR.
  
 16. PLEASE PROVIDE SUBMITTAL DATA &
 INSTALLATION INSTRUCTIONS FOR THE
 "VENTLESS DRYERS" INDICATED ON PLAN
 SHEET M-3.02.
  
 17. PROVIDE SUBMITTAL DATA FOR ALL
 EQUIPMENNT FANS, BOILERS, COOLING
 TOWERS, ETC.
  
 18. PROVIDE ENERGY CALCUALTIONS IN
 ACCORDANCE WITH 2004 FBC CHAPTER 13.
 PROVIDE SIZING CALCS FOR SPACE COOLING
 UNITS AND DUCT SIZING PER 2004 FBC
 13-407.1.ABC.1 & 13-410.1.ABC.1.2.
  
 19. RETAIL SPACE FOR FUTURE BUILD-OUT -
 PLEASE NOTE, ARE ANY PROVISIONS SET IN
 PLACE FOR A GREASE DUCT INSTALLATION &
 TERMINATION SHOULD A RESTAURANT OCCUPY
 ONE OR MORE OF THE RETAIL SPACES.
  
 20. PLEASE PROVIDE OUTSIDE AIR
 CALCULATIONS IN ACCORDANCE WITH 2004 FMC
 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-04-15 Cont ID  
Sent By kstevens Date 2006-04-15 Time 19:03 Rev Time 0.00
Received By kstevens Date 2006-03-11 Time 17:09 Sent To  
Notes
2006-03-30 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FHA-98 DESIGN MANUAL
 WPB MUNICIPAL CODE
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. FIRM LICENSE NUMBER IS
 REQUIRED IN THE TITLE BLOCK OF ALL
 DESIGN PROFESSIONALS. FAC 61G1-16.004(2)
 AND FS 481.219. FAC 61G15-23.002(2) AND
 FS 471.025.
 2. SHT A-0.02 APPLICABLE CODES SHALL
 READ FBC-2004.
 3. SHT A-2.01 SUBMIT CALCULATIONS FOR
 MINIMUM FACILITIES REQUIRED FOR ALL
 COMMON AREAS ON THE GROUND FLOOR AND ON
 THE 9TH FLOOR. THIS SHALL INCLUDE THE
 RETAIL AREAS. SHOW THE SQUARE FOOTAGE
 AREA OF EACH COMMON SPACE AND RETAIL
 SPACE AND INDICATE COMPLIANCE WITH
 SECTIONS 1004.1.2 AND 403.1. SHOW THE
 OCCUPANCY FOR COMMON AREAS.
 4. SHT A-2.03 ROOFS OVER SECONDARY
 ENTRIES, SUBMIT CALCULATIONS FOR PRIMARY
 AND SECONDARY ROOF DRAINS. SHOW THE
 SQUARE FOOTAGE OF ROOF PLUS 1/2 AREA OF
 ALL VERTICAL WALLS, INCLUDING PARAPETS.
 SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE LOCATION OF
 SECONDARY ROOF DRAIN REQUIRED BY
 SECTIONS 1107.1 & 1107.2.
 5. SHT A-2.06 UNIT TYPE MISSING FROM
 MANY UNITS. PLEASE INDICATE UNIT TYPE
 FOR ALL UNITS. SECTION 106.1.1.
 6. SHT A-2.09 SEPARATE POOL PERMITS
 REQUIRED. PLANS SHALL BE REVIEWED AND
 APPROVED BY THE PALM BEACH COUNTY HEALTH
 DEPT. PRIOR TO SUBMITTING FOR REVIEW BY
 THE CITY WPB. 3 COPIES REQUIRED. SECTION
 102.2.1.
 7. SHT A-2.09 MORE INFORMATION REQUIED
 FOR THIS SHEET. ARE THERE SPA'S ON THIS
 SHEET. NO SPAS ARE IDENTIFIED. PLEASE
 CLARIFY. SECTION 106.1.1.
 8. SHTS A-2.09,A-2.10, & A-2.13,
 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. SHOW THE SQUARE
 FOOTAGE FOR EACH AREA BEING DRAINED,
 ALONG WITH 1/2 THE AREA OF ALL VERTICAL
 WALLS INCLUDING PARAPETS ALONG WITH ANY
 ROOF AREA THAT DRAINS ONTO A ROOF AREA
 FROM ABOVE. SECTIONS 1106 & 1107 AND ALL
 SUBSECTIONS. THE SIZING OF SCUPPERS CAN
 NOT BE DETERMINED WITHOUT REFERENCE TO
 THE DEFLECTION OF THE ROOF. PLEASE STATE
 ON PLANS CALCULATIONS FOR SCUPPERS WERE
 ACCORDING TO SECTIONS 1101.7, 1107.3 AND
 TABLE 1106.7. SHOW THE LOCATION OF ALL
 PRIMARY AND SECONDARY ROOF DRAINS AND/OR
 SCUPPERS.
 9. SHT A-2.13 DETAILS 1, 2, & 3.
 SEPARATE SECONDARY ROOF DRAINS ARE
 REQUIRED PER SECTIONS 11-7.1 & 1107.2.
 10. SHT A-2.13 DETAIL 4 TABLE 1616.3 IS
 FOR HIGH VELOCITY WIND ZONES ONLY.
 SIZING OF SCUPPERS SHALL BE PER SECTIONS
 1101.7, 1107.3 AND TABLE 1106.7. (SEE
 COMMENT 8).
 11. SHT A-2.13 DETAIL 4 REFERENCES SHT
 A-10.03 DETAIL 7. DETAIL 7 IS A
 THRESHOLD DETAIL. PLEASE CLARIFY.
 SECTION 106.1.1.
 12. SHT A-3.01 TOILET ROOMS W-108A &
 W-108B SHALL BE ACCESSIBLE. PLEASE
 PROVIDE A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22
 WITH ALL SUBSECTIONS.
 13. SHTS A-3.02BC & A-3.02CD TOILET
 ROOMS SHALL BE ACCESSIBLE. PLEASE
 PROVIDE A DETAIL SHOWING COMPLIANCE WITH
 SECTIONS 11-4.16, 11-4.19, & 11-4.22
 WITH ALL SUBSECTIONS.
 14. SHTS A-3.02BC & A-3.02CD KITCHEN
 LOUNGE SINKS SHALL BE ACCESSIBLE. PLEASE
 PROVIDE A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 CLEAR FLOOR SPACE SHALL BE FORWARD
 APPROACH AND SHALL EXTEND A MAXIMUM OF
 19" UNDERNEATH THE SINK.
 15. ALL DWELLING UNITS SHALL COMPLY WITH
 FHA-98 DESIGN MANUAL REQUIREMENTS 1 THRU
 7. INDICATE SPECIFICATION "A" OR "B" FOR
 EACH UNIT/BATHROOM. SHOW THE CLEAR FLOOR
 SPACE FOR ALL USABLE FIXTURES IN THE
 BATHROOMS AND KITCHEN. SHOW THE BACKING
 REQUIRED BY REQUIREMENT 6 FOR THE W/C'S,
 TUBS & SHOWERS.
 16. SHTS A-3.09BC & A-3.09AD TOILET
 ROOMS SHALL BE ACCESSIBLE. SUBMIT
 DETAILS SHOWING COMPLIANCE WITH SECTIONS
 11-4.16, 11-4.18, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 17. SHTS A-3.09AB & A-3.09DA POOL PUMP
 ROOM SHALL COMPLY WITH SECTIONS
 424.1.5.3 THRU 424.1.5.9. SUBMIT
 DETAILS. INDICATE WHERE CHEMICALS ARE TO
 BE STORED AND IN WHAT QUANTITY. SECTION
 424.1.5.8.
 18. SHTS A-4.01 & A-4.02 POWDER ROOM AT
 LOWER LEVELS SHALL COMPLY WITH
 REQUIREMENTS 6 AND 7. SEE PAGE 7.33OF
 THE FHA-98 DESIGN MANUAL. SHOW CLEAR
 FLOOR SPACE FOR THE LAV AND W/C. LAV TO
 BE CENTERED ON THE 48" LENGTH IF
 PARALLEL APPROACH, OR THE CABINET BASE
 SHALL BE REMOVABLE AND THE LAV SHALL BE
 MINIMUM 15" OFF THE WALL. THE W/C SHALL
 BE 18" OFF THE WALL TO THE CENTER TO THE
 FIXTURE AND SHALL HAVE A MINIMUM OPENING
 OF 33". INDICATE ON THE FLOOR PLAN. SEE
 PAGES 7.43, 7.44, 7.45 & 7.46. THE
 KITCHEN SHALL SHOW THE CLEAR FLOOR SPACE
 FOR EACH APPLIANCE AND A 5' TURNING
 AREA. SEE PAGES 7.3 THRU 7.11.
 19. SHTS A-4.03 THRU A-4.14 CLEAR FLOOR
 SPACE FOR ALL REQUIRED FIXTURES SHALL BE
 SHOWN ON THE ENLARGED PLANS. FOR W/C'S
 SEE PAGE 7.43, ONE OF THREE SHALL BE
 PROVIDED. FOR LAVS SEE PAGES 7.47 &
 7.48. LAVS SHALL BE 2'10" MAXIMUM OFF
 THE FLOOR. SEE PAGE 7.52. CLEAR FLOOR
 SPACE SHALL BE PARALLEL TO THE SHOWER
 AND FLUSH WITH THE CONTROL WALL. SEE
 PAGE 7.56. FOR KITCHENS SEE REQUIREMENT
 7.
 20. SHTS A-4.03 THRU A-4.14 MINIMUM
 OPENING SIZE FOR W/C'S IS 33" AND THE
 FIXTURE SHALL BE 18" OFF THE WALL AND
 18" OFF ONE FIXTURE AND MINIMUM 15" OFF
 THE OTHER FIXTURE WHEN BETWEEN TWO
 FIXTURES. SEE PAGES 7.43 THRU 7.46.
 BIDETS SHALL NOT BE IN THE CLEAR FLOOR
 SPACE OF THE W/C PER INTERPRETATION OF
 THE ARCHITECTURAL BOARD FOR HUD.
 21. SHT A-4.12A PH LOFT 03 ROOF LEVEL
 SHOWS A POOL. MORE INFORMATION IS
 REQUIRED FOR POOL. INDICATE TYPE OF POOL
 AND USE OF POOL. INDICATE IF THERE IS
 POOL EQUIPMENT SUCH AS A PUMP, FILTER,
 ETC. SECTION 106.1.1.
 22. SHT A-8.03 FINISH SCHEDULE. ROOMS
 W-108A & W-108B, INDICATE HOW DRYWALL/PT
 IN TOILET ROOMS COMPLY WITH THE
 REQUIREMENT OF SECTION 1210.2 WALLS.
 WALLS WITHIN 2' OF URINALS AND W/C'S
 SHALL BE NONABSORBENT.
 23. SHT P-1.01 COL LINE R.7 SOUTH OF COL
 LINE K SHOWS "4 INCH RWL STUBBED UP 36
 INCHES ABOVE FINISHED FLOOR FLR BACKWASH
 DISCHARGE." PLEASE INDICATE WHAT IS
 DISCHARGING INTO STUB UP. ONLY STORM
 WATER SHALL DISCHARGE INTO STORM LINES
 PER MUNICIPAL CODE SECTION 90.203.
 24. SHT P-1.01 CODED NOTES (1), 3"
 DISCHARGE FROM FIRE PROTECTION DRAIN
 RISER TO SANITARY SYSTEM NOT THE STORM
 SYSTEM PER MUNICIPAL CODE SECTION
 90.203.
 25. SHT P-1.01 BACKFLOW PREVENTORS AND
 GAS METER DO NOT REFLECT THE LOCATION
 SHOWN ON THE CIVIL PLANS. THEY APPEAR TO
 BE ON THE SIDEWALK. ALSO THE CIVIL
 SHEETS INDICATE 3 BACKFLOWS, (1 FOR
 IRRIGATION). PLEASE CORRELATE THE
 PLUMBING SHEETS WITH THE CIVIL SHEETS.
 SECTION 106.1.1.
 26. SHT P-1.01 OFFICE MANAGER PLUMBING
 FLOOR PLAN TO SHOW REVENT TO REFLECT
 RISER DIAGRAM. SECTION 106.1.1.
 27. SHT P-1.01 SECTION 404.11 FUEL GAS
 PIPING UNDERGROUND BENEATH BUILDINGS.
 PLEASE INDICATE IF THE GAS PIPING IS
 UNDER THE BUILDING OR UNDER A SLAB
 OUTSIDE THE BUILDING. SLEEVE SHALL BE
 SEALED ON BOTH ENDS TO PREVENT OF WATER
 AND INSECTS. SLEEVE SHALL BE VENTED.
 28. SHT P-1.01 OFFICE MANAGER WATER
 DISTRIBUTION RISER DIAGRAM, AIR CHAMBERS
 ARE NOT APPROVED. DELETE FROM RISER.
 SECTION 604.9.
 29. SHT P-1.01 PLEASE SUBMIT THE
 INFORMATION FOR THIS SHEET DRAWN TO A
 MINIMUM OF 1/8" SCALE AS REQUIRED IN
 SECTION 106.1.3.
 30. SHT P-1.02 SALON, KITCHEN AND REST
 ROOMS WATER DISTRIBUTION RISER DIAGRAMS,
 AIR CHAMBERS ARE NOT APPROVED. DELETE
 FROM RISER DIAGRAMS. WATER HAMMER
 ARRESTOR IS REQUIRED AT THE REFRIGERATOR
 PER SECTION 604.9. - THERMAL EXPANSION
 CONTROL IS REQUIRED AT THE WATER HEATER
 PER SECTION 607.3.2. SHOW ON RISER
 DIAGRAM.
 31. SHT P-1.02 4" GAS LINES IN BLOCK
 WALL NOT APPROVED. SECTION 1925.3.5(1) -
 THIS IS SHOWN AS 6" GAS LINES ON THE
 PLUMBING SHEETS. PLEASE CORRELATETHE
 FLOOR PLAN WITH THE GAS RISER DIAGRAM.
 32. SHTS P-2.04AB & P-2.04BC HAVE NOT
 BEEN SUBMITTED. SECTION 106.1.1. (SEE
 PROJECT DRAWING INDEX)
 33. SHT P-2.04CD 6" RWL IS SHOWN AS 4"
 RWL ON THE FLOOR ABOVE AND THE FLOOR
 BELOW. PLEASE CLARIFY. SECTION 106.1.1.
 34. SHT P-2.05AB PIPING TO W/C'S AND
 LAVS DO NOT PIPE TO THE FIXTURES. PLEASE
 CLARIFY. SECTION 106.1.1.
 35. SHT P-2.05DA INDICATE THE LOCATION
 OF RISER J/3. SECTION 106.1.1.
 36. SHTS P-2.07AB & P-2.07DA, INDICATE
 UNIT TYPES. SECTION 106.1.1.
 37. SHTS P-2.07AB, P-2.07BC, P-2.07CD,
 P-2.07DA INDICATE 3"(40SF) "DOWN" WHEN
 THEY APPEAR TO BE GOING "UP" TO THE 7TH
 FLOOR. PLEASE CLARIFY. SECTION 106.1.1.
 38. SHTP-2.08AB SHOWS RISER K3 VTR IN
 TWO LOCATIONS. THIS DOES NOT REFLECT THE
 RISER DIAGRAM. PLEASE CLARIFY. SECTION
 106.1.1.
 37. SHT P2.08AB COOLING TOWER
 DRAIN/OVERFLOW DETAILS SHOW THE DRAIN
 AND OVERFLOW DRAINING TO THE SANITARY.
 OVERFLOW SHALL DISCHARGE SEPARATELY TO
 THE STORM SYSTEM. MUNICIPAL CODE SECTION
 90-125.
 38. SHT P-2.08AB SHOW THE LOCATION OF
 RISERS J/2 & J/1. SECTION 106.1.1.
 39. SHT P-2.08DA COOLING TOWER
 DRAIN/OVERFLOW DETAILS SHOW THE DRAIN
 AND OVERFLOW DRAINING INTO THE SANITARY.
 THE OVERFLOW SHALL DISCHARGE SEPARATELY
 INTO THE STORM SYSTEM. MUNICIPAL CODE
 SECTION 90-125.
 40. SHTS P-2.09AD, P-2.09BC, P-2.09CD,
 P-2.09DA SHOW THE LOCATION OF ALL
 SECONDARY DRAINS. SUBMIT THE
 CALCULATIONS FOR ALL PRIMARY & SECONDARY
 DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. SHOW THE SQUARE FOOTAGE
 AREA DRAINING INTO EACH DRAIN ALONG WITH
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS, MANSARDS, & BUILDING WALLS
 CONTRIBUTING TO THE AREA BEING DRAINED
 IN CALCULATIONS.
 41. SHTS P-2.09AB, P-2.09DA 4" RWL
 STUBBED UP FOR BACKWASH DISCHARGE SHALL
 DRAIN TO SANITARY SYSTEM. MUNICIPAL CODE
 SECTION 90-203.
 42. SHTS P-2.09AB, P-2.09DA SHOWS PD
 50SF, BUT DISCHARGE LINE SHOWS 150SF.
 PLEASE CLARIFY. SECTION 106.1.1.
 43. SHTS P-2.10BC, P-2.10CD RISER
 DESIGNATIONS L/1, L/2, L/3 SUPERIMPOSED
 OVER "FIRE ALARM ROOMS" AND HARD TO
 READ. PLEASE FIX TYPE-O. SECTION
 106.1.1.
 44. SHTS P-2.10BC, P-2.10CD, P-2.11BC,
 P-2.11CD, P-2.12BC, P-2.12CD INDICATE
 UNIT TYPES ON FLOOR PLAN. SECTION
 106.1.1.
 45. SHTS P-2.13BC, P-2.13CD SANITARY
 RISER FOR W/M IN PH-LOFT 05 IS NOT SHOWN
 ON THE FLOOR BELOW. INDICATE FIXTURE
 TYPE ON FLOOR PLAN. SECTION 106.1.1.
 46. SHTS P-2.13BC, P-2.13CD SHOWS 2
 RWL'S BEHIND THE POWDER ROOM W/C IN
 PH-LOFT 05 NOT SHOWN ON THE FLOOR ABOVE.
 PLEASE CLARIFY. SECTION 106.1.1.
 47. SHTS P-2.13BC, P-2.13CD SHOW RISER
 NUMBERS FOR KITCHEN SINK, POWDER ROOM,
 AND BATHROOM RISERS IN PH-LOFT 04.
 SECTION 106.1.1.
 48. SHTS P-2.14BC, P-02.14CD4" RWL &
 OFFSET NOT SHOWN ON ROOF. PLEASE
 CLARIFY. SECTION 106.1.1.
 49. SHTS P-2.14BC, P-02.14CD 3" REQUIRED
 TO WASH MACHINE FOR PH-LOFTS 04 & 07.
 SECTION 406.3.
 50. SHTS P-2.15BC, P-2.15CD SEPARATE
 SYSTEMS FOR DRAIN & OVERFLOW FROM THE
 COOLING TOWER. DRAIN TO SANITARY AND
 OVERFLOW TO STORM. MUNICIPAL CODE
 SECTION 90-203.
 51. SHTS P-2.15BC, P-2.15CD 4" RWL
 STUBBED UP TO 36" FINISHED FLOOR FOR
 BACKWASH DISCHARGE SHALL DRAIN TO
 SANITARY. MUNICIPAL CODE SECTION 90-203.
 52. SHTS P-2.15BC, P-2.15CD COOLING
 TOWER DRAIN/OVERFLOW DETAIL, DRAIN TO
 SANT. & OVERFLOW TO STORM. SECTION
 90-203. - INDICATE MATERIAL FOR SYSTEM &
 SUPPORTS TO BE SPACED PER TABLE 308.5.
 53. SHT P-2.15CD SHOWS 6" RD(3490SF),
 BUT NO ROOF DRAIN SHOWN. PLEASE CLARIFY.
 SECTION 106.1.1.
 54. SHTS P-3.01 THRU P-3.14 NOTE:
 "DISCHARGE DRYER CONDENSATE INTO W/M
 WASTE TRAP". SUBMIT A DETAIL SHOWING
 CONNECTIONS TO THE DRYER & WASTE TRAP,
 PIPE SIZE, PIPING MATERIAL, AND MANUF.
 SPECIFICATION SHEETS ALONG WITH
 INSTALLATION INSTRUCTIONS. SECTION
 106.1.1.
 55. SHT P-3.03 UNIT TYPE "1C' STATES
 "SEE DWG. P-3.03 FOR CONTINUATION RISER
 N/1". CONTINUATION NOT FOUND ON THIS
 SHEET. PLEASE CLARIFY. SECTION 106.1.1.
 56. SHT P-3.04 UNIT TYPE "2G" STATES
 "SEE DWG. P-3.02 FOR CONTINUATION",
 CONTINUATION NOT FOUND ON P-3.02. PLEASE
 CLARIFY. SECTION 106.1.1.
 57. SHT P-3.05 UNIT TYPES "2B" & "2B-1"
 SHOW TWO DIFFERENT RISERS FOR RISERS
 H/1, H/2, & G/3. PLEASE CLARIFY. SECTION
 106.1.1.
 58. SHT P-3.05 WATER RISER DIAGRAM FOR
 UNIT "2B-1", AIR CHAMBERS ARE NOT
 APPROVED. DELETE FROM RISER. SECTION
 604.9. SHOW COMPLIANCE WITH SECTION
 607.3.2 FOR THERMAL EXPANSION CONTROL.
 59. SHT P-3, (BETWEEN P-3.06 & P-3.08),
 WATER RISER DIAGRAM, AIR CHAMBERS ARE
 NOT APPROVED. DELETE FROM RISER DIAGRAM.
 SECTION 604.9. - SHOW COMPLIANCE WITH
 SECTION 607.3.2 THERMAL EXPANSION
 CONTROL.
 60. SHT P3.08 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED, DELETE FROM
 RISER DIAGRAM. SECTION 604.9. - SHOW
 COMPLIANCE WITH SECTION 6-7.3.2 THERMAL
 EXPANSION CONTROL.
 61. SHT P-3.10 PH-LOTS 02, SHOW PIPING
 ON FLOOR PLANS. SECTION 106.1.1. - WATER
 RISER DIAGRAM, AIR CHAMBERS ARE NOT
 APPROVED, DELETE FROM RISER DIAGRAM. -
 SHOW COMPLIANCE WITH SECTION 607.3.2
 THERMAL EXPANSION CONTROL.
 62. SHT P-3.12 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 RISER DIAGRAM. SECTION 604.9. - SHOW
 COMPLIANCE WITH SECTION 607.3.2 THERMAL
 EXPANSION CONTROL.
 63. SHT P-3.14 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED. DELETE FROM
 RISER DIAGRAM. SECTION 604.9. - SHOW
 COMPLIANCE WITH SECTION 607.3.2. THERMAL
 EXPANSION CONTROL.
 64. SHT P-4.0 CONDENSATE RISER DIAGRAM,
 VENT SHALL NOT TERMINATE INSIDE A WALL,
 OR IN A PLENUM. PLEASE INDICATE WHERE
 THE VENT WILL TERMINATE TO COMPLY WITH
 THIS INFORMATION. SUBMIT A DETAIL
 SECTION 106.1.1.
 65. SHT P-4.0 WATER RISER DIAGRAMS, RPZV
 BACKFLOWS ARE REQUIRED ON THE WATER
 SUPPLYS FOR THE POOL EQUIPMENT ROOM,
 (UNLESS AN AIR GAP IS SHOWN ON WATER
 MAKEUP), AND AT SUPPLY FOR THE
 IRRIGATION. BACKFLOW PREVENTION IS ALSO
 REQUIRED FOR THE SUPPLY OF THE TRASH
 CHUTE WASHDOWN. PLEASE INDICATE METHOD
 OF BACKFLOW PREVENTION. SECTION 608.
 66. SHTS P-4.1, P-4.2, P-4.3, P-4.5
 WATER RISER DIAGRAMS, AIR CHAMBERS ARE
 NOT APPROVED. DELETE FROM RISER
 DIAGRAMS. SECTION 604.9. SHOW COMPLIANCE
 WITH SECTION 607.3.2 THERMAL EXPANSION
 CONTROL.
 67. SHTS P-4.5 THRU P-4.12 FIXTURE UNITS
 FOR SANITARY RISER DIAGRAMS SHALL BE
 RECHECKED. PER TABLE 709.1, A BATHROOM
 GROUP IS 5FU AS DEFINED IN SECTION 202,
 BUT EXTRA FIXTURES SHALL BE ADDED PER FU
 VALUE OF EACH FIXTURE. FLOOR DRAINS ARE
 2FU WITH A 2" TRAP, BUT LARGER TRAPS
 SHALL BE SIZED FOR FIXTURE UNITS PER
 TABLE 709.2. A POWDER ROOM IS 4FU. SINKS
 ARE 2FU AND LAVS ARE 1FU BUT LAVS ARE
 ONLY LOCATED IN POWDER ROOMS OR
 BATHROOMS.
 68. SHTS P-4.5 THRU P-4.12 ALL SANITARY
 RISERS, INDICATE WHERE OR WHAT SHEET THE
 CONTINUATIONS FOR EACH RISER UPPER OR
 LOWER SECTIONS ARE LOCATED, OR SUBMIT
 RISER DIAGRAMS THAT ARE CONTINUOUS FROM
 THE BUILDING DRAIN THRU THE VENT THRU
 ROOF. (MANY HOURS PLAN REVIEW WERE SPENT
 TRYING TO TRACK THE RISER DIAGRAMS AS
 SUBMITTED). SHOW ALL OFFSET VENTS PER
 SECTION 915.2 & 915.3, SHOW ALL VENT
 CONNECTIONS PER SECTION 903.4 FOR ALL
 STACKS THAT REQUIRE A VENT STACK PER
 SECTION 903.2.
 69. SHT P-4.6 RISER E/2 INDICATES NO
 FIXTURES ABOVE THE 23RD FLOOR, BUT THIS
 DOES NOT REFLECT THE FLOOR PLAN FOR THE
 24TH FLOOR AS A KITCHEN SINK AND A
 POWDER ROOM ARE SHOWN. PLEASE CORRELATE
 THE RISER DIAGRAM AND THE FLOOR PLAN.
 SECTION 106.1.1.
 70. SHT P-4.6 RISER G/1 IDENTIFY ALL
 FIXTURES. SECTION 106.1.1.
 71. SHT P-4.6 RISER H/1 3" BRANCH LINE
 REQUIRED TO WASH MACHINE. SECTION 606.3.
 - OFFSET VENTS REQUIRED PER SECTIONS
 915.2 AND 915.3.
 72. SHT P-4.6 RISER H/2 INDICATE
 FIXTURES FOR 3RD, 4TH, & 6TH FLOORS.
 SECTION 106.1.1.
 73. SHT P-4.6 RISER G/3 5TH & 7TH FLOORS
 DO NOT REFLECT THE FLOOR PLAN. DOES NOT
 SHOW THE OTHER BATHROOM. NOT CHANGED ON
 FLOOR PLAN. SECTION 106.1.1.
 74. SHT P-4.7 RISER H/5 INDICATE ON
 RISER WHERE 8TH FLOOR PIPING CAN BE
 LOCATED. - 3RD THRU 7TH FLOORS DO NOT
 REFLECT THE FLOOR PLAN. NO FIXTURES
 SHOWN. SECTION 106.1.1.
 75. SHT P-4.7 RISER N/3 DOES NOT REFLECT
 THE 24TH FLOOR FIXTURE UNITS. (+2)
 SECTION 106.1.1 AND TABLE 710.1(2).
 76. SHT P-4.8 RISER N/3 3" REQUIRED ON
 ALL WASH MACHINE BRANCH LINES. SECTION
 406.3.
 77. SHT P-4.8 RISERS J/1, J/2, J/3, K/1,
 K/2, 11, 12, 13, & 14 7TH FLOOR, 3"
 REQUIRED FOR WASH MACHINE BRANCH LINES.
 SECTION 406.3.
 78. SHT P-4.8 4TH LEVEL RISERS K/2, J/3,
 11/12, 14 DO NOT REFLECT THE FLOOR PLAN.
 SECTION 106.1.1.
 79. SHT P-4.8 4TH LEVEL TWO J/2 SANT.
 RISERS SHOWN. PLEASE CLARIFY. SECTION
 106.2.1.
 80. SHT P-4.8 4TH LEVEL RISER J/3 NOT
 SHOWN ON THE FLOOR PLAN. PLEASE CLARIFY
 SECTION 106.1.1.
 81. SHT P-4.8 4TH LEVEL RISER 14, 3"
 REQUIRED FOR WASH MACHINE BRANCH LINE.
 SECTION 406.3.
 82. SHT P-4.8 3RD LEVEL RISERS 11/12 AND
 FLOOR PLAN SHOWS RISER 12 TERMINATING AT
 THE 3RD LEVEL, BUT 3RD THRU 7TH FLOOR
 RISERS ARE SHOWN AS RISERS 11/12. PLEASE
 CORRELATE RISERS AND FLOOR PLAN. SECTION
 106.1.1.
 83. SHT P-4.8 2ND FLOOR RISER K/1, J/2,
 J/3, 3" REQUIRED FOR WASH MACHINE BRANCH
 LINE. SECTION 406.3.
 84. SHT P-4.8 2ND FLOOR RISER 13/12
 SHOWS 4" TO WASH MACHINE & 2" TO RISER
 12. MINIMUM 3" TO WASH MACHINE BRANCH
 LINE AND THE SIZE OF DRAINAGE PIPING
 SHALL NOT BE REDUCED IN SIZE IN THE
 DIRECTION OF FLOW AS SHOWN IN THE 2"
 RISER LINE. SECTIONS 406.3 & 704.2.
 85. SHT P-4.9 PH UPPER LEVEL RISER M/1
 OVERFLOW FROM COOLING TOWER NOT
 APPORVED. OVERFLOW SHALL DRAIN TO THE
 STORM SYSTEM. MUNICIPAL CODE SECTION
 90-125.
 86. SHT P-4.9 PH UPPER LEVEL RISER H/3
 3" REQUIRED ON WASH MACHINE BRANCH LINE.
 SECTION 406.3.
 87. SHT P-4.9 PH UPPER LEVEL RISER G/1
 DOES NOT REFLECT THE FLOOR PLAN. (SHOWS
 W/M). 3" REQUIRED ON THE WASH MACHINE
 BRANCH LINE. SECTION 406.3.
 88. SHT P-4.9 PH UPPER LEVEL, RISERS
 C/1, B/1, 3" REQUIRED ON THE WASH
 MACHINE BRANCH LINE. SECTION 406.3
 89. SHT P-4.9 PH LOWER LEVEL, TWO G/1
 VTR'S SHOWN, AND TWO B/2 VTR'S SHOWN.
 PLEASE CLARIFY. SECTION 106.1.1.
 90. SHT P-4.9 PH LOWER LEVEL, RISER D/3,
 AND 2" (4FU) FROM ABOVE TO BE THE
 MINIMUM OF 3" TO WASH MACHINES. BRANCH
 LINE OR STACK. SECTION 406.3.
 91. SHT P-4.10 24TH LEVEL RISER F/3, 3"
 REQUIRED FOR WASH MACHINE BRANCH LINE
 AND RISER FROM ABOVE. SECTION 406.3.
 92. SHT P-4.10 24TH LEVEL, INDICATE
 RISER NUMBER FOR SANT. RISER BY VENT
 E/1. SECTION 106.1.1.
 93. SHT P-4.10 24TH LEVEL, RISERS D/1,
 C/3, M/2 MINIMUM 3" REQUIRED FOR WASH
 MACHINE BRANCH LINES. SECTION 406.3.
 94. SHT P-4.10 9TH LEVEL, RISER L/1,
 L/2, L/3, DOES NOT REFLECT THE FLOOR
 PLAN ON THE 9TH LEVEL. PLEASE CORRELATE
 RISER AND FLOOR PLAN. SECTION 106.1.1.
 95. SHT P-4.10 9TH LEVEL, THE SIZE OF
 THE DRAINAGE PIPING SHALL NOT BE REDUCED
 IN SIZE IN THE DIRECT OF THE FLOW.
 SECTION 704.2.
 96. SHT P-4.10, 9TH LEVEL RISERS
 N/3,N/4,O/1 AND M/1,M2,N/1,N/2, MINIMUM
 3" BRANCH LINE TO WASH MACHINE REQUIRED.
 SECTION 406.3.
 97. SHT P-4.10 9TH LEVEL RISER
 M/1,M/2,N/1,N/2 DOES NOT REFLECT THE
 FLOOR PLAN DOWNSTREAM OF RISER M/2.
 PLEASE CORRELATE RISER AND FLOOR PLAN.
 SECTION 106.1.1.
 98. SHT P-4.10 8TH LEVEL RISERS H/1,
 H/5, H/2 OFF SET VENTS REQUIRED PER
 SECTIONS 915.2 AND 915.3.
 99. SHT P-4.10 8TH LEVEL RISER H/2,
 WHERE A HORIZONTAL STACK OFFSET IS
 LOCATED MORE THAN FOUR BRANCH INTERVALS
 BELOW THE TOP OT THE STACK, A HORIZONTAL
 BRANCH SHALL NOT CONNECT WITHIN THE
 HOROZONTAL STACK OFFSET OR WITHIN 2FT
 ABOVE OR BELOW SUCH OFFSET. SECTION
 711.2.
 100. SHT P-4.10 8TH LEVEL, RISER H/1
 MINIMUM 3" REQUIRED FOR WASH MACHINE
 BRANCH LINE. SECTION 406.3.
 101. SHT P-4.11 7TH LEVEL, RISER H/2,
 MINIMUM 3" REQUIRED FOR WASH MACHINE
 BRANCH LINE. SECTION 406.3
 102. SHT P-4.11 3RD LEVEL RISERS
 M/1,M/2,N/1,N/2,N/3 AND N/4,O/1,O/2 ARE
 NOT SHOWN ON THE FLOOR PLANS FROM THE
 7TH THRU 4TH FLOORS. PLEASE CORRELATE
 RISERS AND FLOOR PLANS. SECTION 106.1.1.
 103. SHT P-4.11 2ND LEVEL RISERS H/1,
 F/2, G/1,G/2,G/3, A/1,A/2,A/3, B/1,B/2,
 E/1,E/2,D/3, C/2,C/3,D/1,D/2, MINIMUM 3"
 REQUIRED FOR WASH MACHINE BRANCH LINE.
 SECTION 406.3.
 104. SHT P-4.11 2ND LEVEL RISERS
 L/1,L/2,L/3, ARE NOT SHOWN FROM THE 8TH
 FLOOR THRU 3RD FLOOR. PLEASE CLARIFY.
 SECTION 106.1.1.
 105. SHT P-4.11 3RD LEVEL, RISERS
 G/1,G/2,G/3, NOT SHOWN FROM 9TH FLOOR
 THRU 3RD FLOOR. PLEASE CLARIFY. SECTION
 106.1.1.
 106. SHT P-4.113RD LEVEL, SHOW THE RISER
 DESIGNATION NUMBERS AT THE BOTTOM AND
 TOP OF EACH RISER SECTION. (SEE F/2,
 B/1,B/2) SECTION 106.1.1.
 107. SHT P-4.12 MEZZANINE LEVEL, RISERS
 E/3,E/4, E/2,E/1,D/3, SHOW RISER
 DESIGNATION NUMBERS ON BOTH THE TOP AND
 BOTTOM OF EACH RISER SECTION. SECTION
 106.1.1.
 108. SHT P-4.12, MEZZANINE LEVEL, TWO
 LINES "4IN. SANT. FROM ABOVE COOLING
 TOWER OVERFLOW" SHALL BE CONNECTED TO
 STORM SYSTEM. MUNICIPAL CODE SECTION
 90-125.
 109. SHT P-4.13, 2 LINES "4IN SANT. FROM
 ABOVE COOLING TOWER OVERFLOW" SHALL BE
 CONNECTED TO THE STORM SYSTEM. MUNICIPAL
 CODE SECTION 90-125.
 110. SHT P-4.13 SHOW ALL PIPE SIZES AND
 DFU'S FOR THE CIVIL LINES BETWEEN
 MANHOLES. RECHECK ALL DFU'S & PIPE SIZES
 AS WELL AS THE SLOPE OF PIPE. TABLES
 704.1 AND 710.1(1).
 111. (SECOND) SHT P-4.13 RECHECK PIPE
 SIZE FOR HORIZONTAL8400SF.
 112. SECOND SHT P-4.13 CONTACT LYNN
 MASSON, ENVIRONMENTAL COMPLIANCE MGR.
 FOR SIZING OF GREASE INTERCEPTORS AND
 OIL/GAS/SAND INTECEPTORS. CONTACT HER AT
 (561) 822-2271, OR FAX (561) 822-2279,
 OR E-MAIL HER [email protected]. PLEASE
 SUBMIT DETERMINATION SHEETS WHEN
 RESUBMITTING FOR REVIEW BY CITY. WASTE
 ORDINANCE #3434.
 113. SHT P-4.14 EACH RWL SHALL HAVE A
 RISER DESIGNATION NUMBER SO THE RISERS
 CAN BE TRACED FROM ROOF DRAINS TO
 BUILDING STORM DRAIN UNDERGROUND IE:
 RWL-1, RWL-2, RWL-3 ETC. SHOW RWL NUMBER
 ON EACH FLOOR THRU BUILDING. SECTION
 106.1.1.
 114. SHT P-4.14 SOME RWL RISERS, (7), DO
 NOT REFLECT THE FLOOR PLAN AT OFFSETS.
 PLEASE CORRELATE RISERS AND FLOOR PLANS.
 SECTION 106.1.1.
 115. SHT P-4.14 BACKWASH DISCHARGE TO
 SANITARY SYSTEM NOT STORM. SECTION
 90.203 MUNICIPAL CODE.
 116. SHT P-4.14 ROOF AREA DRAIN DOES NOT
 INDICATE SQUARE FOOTAGE BEING DRAINED.
 PLEASE CLARIFY. SECTION 106.1.1 AND
 TABLE 1106.3.
 117. SHT P-4.14 ONE RWL RISER INDICATES
 2005SF ON THE RWL BUT 2805SF ON THE ROOF
 PLAN. PLEASE CORRELATE RISER AND ROOF
 DRAIN ON THE ROOF PLAN. SECTION 106.1.1.
 118. SHT P-4.14 ONE RWL RISER CHANGES
 FROM 6" TO 4" DOWNSTREAM. THIS IS NOT
 ALLOWED PER SECTION 704.2.
 119. SHT P-4.14 DRAIN FROM THE FIRE
 PROTECTION DRAIN RISER SHALL NOT BE
 DRAINED TO STORM. FIRE PROTECTION DRAIN
 SHALL CONNECT TO SANITARY. SECTION
 90-203 MUNICIPAL CODE.
 120. SHT P-4.14 ONE BUILDING STORM DRAIN
 DOES NOT REFLECT THE FLOOR PLAN FOR RWL
 RISER CONNECTIONS. PLEASE CORRELATE.
 SECTION 106.1.1.
 121. SHT P-4.15 GAS REQUIREMENTS:
 A. SUBMIT MANUFACTURE SPECIFICATION
 SHEETS FOR 5PSI TO .5PSI REGULATORS. IF
 REGULATORS ARE VENTED, SUBMIT AN
 ISOMETRIC PIPING DIAGRAM FOR THE VENTING
 AND INDICATE TERMINATION POINT. INDICATE
 MATERIAL FOR VENT PIPING.
 B. SHUT OFF VALVES ARE REQUIRED
 UPSTREAM OF EACH REGULATOR. SECTION
 409.4
 C. SUBMIT AN APPROVED TABLE FOR 5PSI UP
 TO 800 FEET TO VERIFY PIPE SIZE IN
 SYSTEM. SECTION 402.3(2)
 D. INDICATE LENGHTS OF PIPE FOR EACH
 CUT SECTION FROM THE METER TO THE FIRST
 RISER, AND FOR ALL CUT SECTIONS
 DOWNSTREAM OF THE 5PSI TO .5PSI
 REGULATOR. FBC-2004 FUEL GAS
 E. GALVANIZED PIPING IS NOT APPROVED
 FOR UNDERGROUND INSTALLATION. SECTION
 404.8.
 F. SLEEVE FOR UNDERGROUND PIPING SHALL
 BE INSTALLED PER SECTION 404.11.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 122. SHT P-5.01 WATER HEATER CLOSET
 DETAIL: THERMAL EXPANSION CONTROL IS
 REQUIRED PER SECTION 607.3.2. INDICATE
 METHOD. - WATER HEATER AND AIR
 CONDITIONER DISCONNECTS APPEAR TO BE IN
 FRONT OF THE WATER HEATER AND APPEAR TO
 BE IMPEDE THE ACCESS TO REPLACEMENT OF
 THE WATER HEATER REQUIRED IN SECTION
 501.4. PLEASE CLARIFY.
 123. SHT P-5.01 TYPICAL AIR CHAMBER
 DETAIL: AIR CHAMBERS ARE NOT APPROVED.
 DELETE DETAIL. SECTION 604.9.
 124. SHT P-5.01 SUBMIT MANUFACTURE
 SPECIFICATION SHEETS FOR THE DOMESTIC
 WATER PUMPS. PUMPS SHALL BE LISTED.
 SECTION 303.4.
 125. SHT P-5.02 PUBLIC WATER HEATER
 DETAIL: INDICATE COMPLIANCE WITH SECTION
 607.3.2 THERMAL EXPANSION CONTROL.
 126. SHT P-5.02 TYPICAL CONDENSATE PIPE
 SUPPORT ON ROOF: ACCORDING TO TABLE
 308.5 INDICATE MATERIAL FOR CONDENSATE
 PIPING.
 127. SHT P-5.02 GENERAL PLUMBING NOTES:
 DOMESTIC WATER PIPING C(2), AIR CHAMBERS
 ARE NOT APPROVED. DELETE REFERENCE.
 SECTION 604.9.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REMOVE ALL OLD SHEETS AND RESUBMIT THE
 SET OF PLUMBING PLANS HIGHLIGHTED AND
 MARKED UP FROM THE FIRST REVIEW TO HELP
 SPEED UP SECOND REVIEW.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-21 Cont ID  
Sent By mflis Date 2006-04-21 Time 09:46 Rev Time 0.00
Received By mflis Date 2006-04-21 Time 09:46 Sent To  
Notes
2006-04-21 00:00:00OPERA PLACE: BUILDING PERMIT
  
 1) INDICATE TYPICAL SIDEWALK WIDTHS ALL
 SIDES; (SITE, LANDSCAPE, OR PAVING PLAN)
 2) SHOW ON-STREET PARK AND NUMBER; TABLE
 INDICATES 13 SPACES?
 3) A-1.02 ? INDICATE COMPACT/REGULAR
 PARKING BREAKDOWN; DEMONSTRATE NOT
 MEETING 30% MAXIMUM ALLOWABLE
 4) PHASING DIAGRAMS DO NOT MATCH ACTUAL
 SITE PLAN
 5) A-2.02 ? PARKING SPOT #1 ? NEEDS
 5?-0? SIDE PULLBACK AREA; 5?-0? CLEAR
 REQUIRED AT ALL DRIVE ENDS / PARKING
 STALL ENDS
 6) A-2.03 ? PARKING SPOT #96 ? HAS
 COLUMN INSIDE SPACE
 7) A-2.08 ? REMOVE PARKING SPOT #514 AND
 STRIPE TO ALLOW TURN-AROUND AT END OF
 DRIVE
 8) AIR RIGHTS EASEMENTS WILL BE
 NECESSARY FOR ANY CANOPIES/OVERHANGS
 THAT INTRUDE INTO THE ROW; FIRST FLOOR
 SHOULD CLARIFY CANOPY PLACEMENT; CITY
 AND/OR FDOT APPROVAL NECESSARY
 9) PAVING, PLANTING ETC ALONG DIXIE
 SHALL COORDINATE WITH FDOT INSTALLATION;
 TREES ALONG DIXIE SHALL BE HIGHRISE OAK
 10) COORDINATE WITH LANDSCAPE PLANNER
 ALAN BARATTA REGARDING PLANTINGS ALONG
 QUADRILLE
 11) A-5.06 - ADJUST MECHANICAL/ELEVATOR
 TOWER PARAPET LOWER TO MATCH SOUTH
 ELEVATION PARAPET PER APPROVED
 RESOLUTION.