| Plan Review Stops For Permit 05121245 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-01-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2006-01-17 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2006-01-17 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-12-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2005-12-29 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2005-12-29 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2005-12-29 00:00:00 | DENIED | | | | | | 1) SUBMIT THE FLORIDA PRODUCT APPROVAL | | | COVER SHEET WITH THE FL APPROVAL NUMBER | | | THAT IS LISTED ON THE STATE WEBSITE FOR | | | THE ROOFING SYSTEM. | | | SEE WWW.FLORIDABUILDING.ORG . | | | | | | 2) THE MAXIMUM DESIGN PRESSURE FOR THE | | | ROOF COVERING ASSEMBLY INDICATED IN THE | | | NOA DOES NOT HAVE AN ADEQUATE DESIGN | | | PRESSURE AND LIMITATION #9 DOES NOT | | | ALLOW ENHANCED FASTENING. THE REQUIRED | | | DESIGN PRESSURE IS -89.0 PER 2004 FBC | | | TABLE 1609.6B. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|
|
|