Plan Review Details - Permit 05121211
Plan Review Stops For Permit 05121211
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2006-01-19 Cont ID  
Sent By nmccray Date 2006-01-19 Time 12:35 Rev Time  
Received By nmccray Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-01-08 Cont ID  
Sent By mawillia Date 2007-01-08 Time 11:06 Rev Time 0.00
Received By mawillia Date 2007-01-08 Time 11:06 Sent To  
Notes
2007-01-08 11:11:23*****PROVISO*****
  
  
 1.NEWLY INSTALLED FIRE HYDRANT TO BE NO GREATER THAN
 150 FEET TO THE FIRE DEPARTMENT CONNECTION (FDC).
  
 2.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2006-11-27 Cont ID  
Sent By mawillia Date 2006-11-27 Time 11:22 Rev Time 0.00
Received By mawillia Date 2006-11-27 Time 11:22 Sent To  
Notes
2006-11-27 11:37:41*****DENIED*****
  
  
  
  
 1. THE SUBMITTED PLANS INDICATE THAT THE DISTANCE FROM
 THE FIRE DEPARTMENT CONNECTION (FDC) TO THE NEAREST
 FIRE HYDRANT IS GREATER THAN 150 FEET.AS PER THE FIRE
 MARSHAL, THE FDC SHALL BE NO GREATER THAN 150 FEET TO
 THE NEAREST HYDRANT.
  
 2.KNOX LOCKING CAPS ARE REQUIRED FOR NEW FIRE
 DEPARTMENT CONNECTIONS.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-05-01 Cont ID  
Sent By nmccray Date 2006-05-01 Time 15:01 Rev Time 0.00
Received By nmccray Date 2006-05-01 Time 15:01 Sent To  
Notes
2006-05-01 00:00:00***********DENIED********************
 PERMITS 05121211 AND 05121212
  
 1) THE FIRE DEPARTMENT CONNECTION (FDC)
 SHALL BE 2 1/2 INCH CONNECTION. THE WEST
 PALM BEACH FIRE DEPT USES 5 INCH HOSE.
  
 2) EXACTLY HOW FAR IS THE NEAREST FIRE
 HYDRANT. THE FIRE MARSHAL (AHJ) MAY
 REQUIRE A FIRE HYDRANT INSTALLED THAT'S
 CLOSER.
  
 3) WHEN THIS PROJECT WAS REVIEWED BY
 PLANNING & ZONING AND FIRE,THE FDC WERE
 NOTED TO BE MINIMUM OF 150 FEET TO THE
 NEAREST FIRE HYDRANT.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-01-19 Cont ID  
Sent By nmccray Date 2006-01-19 Time 12:36 Rev Time 0.00
Received By nmccray Date 2006-01-19 Time 12:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-04 Cont ID  
Sent By adarroug Date 2007-01-04 Time 12:52 Rev Time 0.00
Received By adarroug Date 2007-01-04 Time 12:52 Sent To FIRE
Notes
2007-01-04 12:53:04TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-04-12 Cont ID  
Sent By adarroug Date 2006-04-12 Time 14:19 Rev Time 0.00
Received By adarroug Date 2006-04-12 Time 14:19 Sent To FIRE
Notes
2006-04-12 00:00:00TO "F" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-19 Cont ID  
Sent By nmccray Date 2006-01-19 Time 12:36 Rev Time 0.00
Received By nmccray Date 2005-12-29 Time 08:47 Sent To  
Notes
2005-12-29 00:00:00TO "F" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-01-19 Cont ID  
Sent By nmccray Date 2006-01-19 Time 12:36 Rev Time  
Received By nmccray Date   Time   Sent To  
Notes
***NONE***