 |
Plan Review Details - Permit 05121124
| Plan Review Stops For Permit 05121124 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2007-06-25 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2007-06-25 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2007-06-25 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2007-06-25 17:03:15 | BUILDING REVIEW COMMENTS | | | | | | FROM PREVIOUS REVIEW DATED 10/19/06, | | | | | | #2- OK | | | #5- OK | | | #6- HOLLOW METAL DOOR, N.O.A. WAS NOT PROVIDED. #7- ALL | | | PRODUCT APPROVALS SUBMITTED SHALL BE REVIEWED AND | | | APPROVED BY THE DESIGNER OF RECORD. | | | #11- OK | | | | | | NEW COMMENTS: | | | | | | 1A- IDENTIFY AND SELECT APPROPRIATE ASSEMBLY FROM YOUR | | | ROOF PRODUCT APPROVAL. | | | 2A- OK | | | | | | RESPONCE #13, THE NORTH WALL DOES REQUIRE A 1HR RATING | | | ACCORDING TO TABLE 602, AS PER BUILDING CODE | | | COMMENTARY, SEPERATION DISTANCES SHALL ONLY RECEIVE 50% | | | OF RIGHT-OF-WAY, 7' VS. 14'. | | | | | | | | | | | | | | | | | | | | | | | | L.MARTINEZ | | | 561-805-6710 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2006-10-19 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-10-19 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-10-18 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2006-10-19 11:03:30 | DENIED | | | | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 5.PRODUCT APPROVALS REQUIRED FOR | | | ALL WINDOWS, EXTERIOR DOORS,AND ROOFING. | | | | | | 6.ALL PRODUCT APPROVALS SUBMITTED WITH | | | QUALITY ASSURANCE SHALL HAVE THE | | | FOLLOWING STATE APPROVAL ATTACHED. | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A STATE PRODUCT APPROVAL | | | SHEETS THAT LISTS THE PRODUCT IDENTITY | | | NUMBER FROM THE STATE. IF THE PRODUCT | | | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT | | | AN APPLICATION FOR LOCAL PRODUCT | | | APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 7.THOSE PRODUCT APPROVALS WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL.WPB | | | AMENDMENT TO FBC 106.3.3. | | | | | | 11.DOOR TO SECOND FLOOR WEST STAIRS OK.AFTER | | | RECEIVING THE SURVEY THE DOOR TO THE SPRINKLER ROOM IS | | | ALSO OPENING OVER THE PROPERTY LINE. | | | | | | | | | FROM LAST REVIEW: | | | A:SHOW PRESSURES FOR DOORS AND | | | WINDOWS. | | | | | | NEW COMMENTS: | | | 1A.ROOFING NOTES AND DETAILS INTERMIX EXISTING ROOF | | | AND NEW ROOF.PLEASE CLARIFY AND SUBMIT THE | | | APPROPRIAT PRODUCT APPROVALS WITH THE ROOFING ASSEMBLY | | | SELECTED. | | | | | | 2A.GAURDRAIL LOADS SECTION LISTED IS NOT CORRECT FBC | | | 1607.7 ON PAGE A 4.0 | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2006-07-17 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-07-17 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
alange |
Date |
2006-07-17 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2006-07-17 00:00:00 | DENIED | | | | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF | | | THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 4.SUBMIT TWO COPIES OF ENERGY CALCS | | | PER 2004 FBC. | | | | | | 5.PRODUCT APPROVALS REQUIRED FOR | | | WINDOWS, EXTERIOR DOORS, STORE FRONT | | | SYSTEM, LINTELS, ROOFING AND STRAPS AND TIE-DOWNS. | | | | | | 6.ALL PRODUCT APPROVALS SUBMITTED WITH | | | QUALITY ASSURANCE SHALL HAVE THE | | | FOLLOWING STATE APPROVAL ATTACHED. | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A STATE PRODUCT APPROVAL | | | SHEETS THAT LISTS THE PRODUCT IDENTITY | | | NUMBER FROM THE STATE. IF THE PRODUCT | | | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT | | | AN APPLICATION FOR LOCAL PRODUCT | | | APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 7.THOSE PRODUCT APPROVALS WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL.WPB | | | AMENDMENT TO FBC 106.3.3. | | | | | | 8.FIRE DOORS AT 2HR WALLS SHALL BE | | | 1.5HR.FBC 2004 TABLE 715.3 | | | SHOW RATED WALLS AND THE APPROPRIATE | | | RATED DOORS. | | | ALL DOORS SHALL COMPLY WITH THIS | | | SECTION.DOORS TO COMMON HALLWAY DO NOT | | | SHOW A RATING. | | | | | | 9.A DESIGN PROFESSIONAL OR AN OWNER | | | MUST ELECT ONE OR A COMBINATION OF | | | LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | SHOW HOW PLANS WILL COMPLY WITH THE | | | SECTION(S) SELECTED.2004 FBC EXISTING | | | BUILDING 301.5 | | | B. SHOW COMPLIANCE WITH 707.5.1 | | | | | | 10.INCLUDE A LIFE SAFTEY PLAN SHOWING | | | PATH OF TRAVEL AND TRAVEL DISTANCE | | | COMPLYING WITH 1015.1.MOST REMOTE | | | POINT. | | | | | | 11.SECOND FLOOR STAIRWAY EXIT SHALL | | | NOT EXIT TO ALLEY WAY.BUT SHALL EXIT | | | ON TO THE SAME PROPERTY.SUBMIT A SITE | | | PLAN.WEST STAIRWAY DOES NOT SHOW A | | | FIRST FLOOR EXIT ON FLOOR PLAN. | | | | | | 13.BASED ON FBC TABLE 602 THE NORTH | | | WALL SHALL HAVE A 1HR. FIRE RATING. | | | DOORS AND WINDOWS SHALL BE RATED 3/4 HR. | | | FBC 715.3 AND FBC 715.4.SINCE LARGE | | | MISSLE IMPACT PROTECTION IS REQUIRED, | | | LARGE MISSLE IMPACT GLASS MAY HAVE TO BE | | | USED WITH ROLL UP FIRE SHUTTERS | | | COMPLYING WITH FBC 715.3.9. | | | | | | NEW COMMENT: | | | A:SHOW PRESSURES FOR DOORS AND | | | WINDOWS. | | | | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2006-04-04 |
|
|
Cont ID |
|
| Sent By |
alange |
Date |
2006-04-04 |
Time |
08:29 |
Rev Time |
7.00 |
| Received By |
alange |
Date |
2006-03-31 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2006-03-31 00:00:00 | DENIED | | | ITEMS REQUIRED WHEN SUBMITTED FOR | | | PERMITTING: | | | | | | | | | 1. 713.13 F.S.A NOTICE OF COMMENCEMENT | | | SHALL BE RECORDED AT PALM BEACH COUNTY | | | COURTHOUSE AND A COPY SUBMITTED TO THIS | | | OFFICE BEFORE A PERMIT CAN BE ISSUED. | | | BLANK FORMS ARE AVAILABLE FROM THIS | | | OFFICE. | | | NOTE: THE NOTICE OF COMMENCEMENT MUST BE | | | RE-RECORDED IF THE DESCRIBED IMPROVEMENT | | | OR CONSTRUCTION IS NOT COMMENCED WITHIN | | | 90 DAYS OF RECORDING. | | | | | | 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY. THE ACTUAL PERMIT | | | SET OF PLANS MUST BE STAMPED BY THAT | | | OFFICE, AND A COPY OF THE PAID RECEIPT | | | ATTACHED TO THE PERMIT APPLICATION. | | | PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 3. ALL PLANS SUBMITTED AFTER OCTOBER, 1, | | | 2004 SHALL BE DESIGNED TO THE 2004 | | | FLORIDA BUILDING CODE. | | | | | | 4.SUBMIT TWO COPIES OF ENERGY CALCS | | | PER 2004 FBC. | | | | | | 5.PRODUCT APPROVALS REQUIRED FOR | | | WINDOWS, EXTERIOR DOORS, STORE FRONT | | | SYSTEM, LINTELS, ROOFING AND STRAPS AND | | | TIE-DOWNS. | | | | | | 6.ALL PRODUCT APPROVALS SUBMITTED WITH | | | QUALITY ASSURANCE SHALL HAVE THE | | | FOLLOWING STATE APPROVAL ATTACHED. | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A STATE PRODUCT APPROVAL | | | SHEETS THAT LISTS THE PRODUCT IDENTITY | | | NUMBER FROM THE STATE. IF THE PRODUCT | | | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT | | | AN APPLICATION FOR LOCAL PRODUCT | | | APPROVAL OR SITE SPECIFIC FORM PER RULE | | | 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 7.THOSE PRODUCT APPROVALS WHICH ARE | | | REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | | FOR JURISDICTIONAL APPROVAL.WPB | | | AMENDMENT TO FBC 106.3.3. | | | | | | 8.FIRE DOORS AT 2HR WALLS SHALL BE | | | 1.5HR.FBC 2004 TABLE 715.3 | | | ALL DOORS SHALL COMPLY WITH THIS | | | SECTION.EXIT PASSAGE WAY WALLS RATED | | | 1HR SHALL HAVE A ONE HOUR DOOR. | | | | | | | | | 9.A DESIGN PROFESSIONAL OR AN OWNER | | | MUST ELECT ONE OR A COMBINATION OF | | | LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | SHOW HOW PLANS WILL COMPLY WITH THE | | | SECTION(S) SELECTED.2004 FBC EXISTING | | | BUILDING 301.5 | | | A. SHOW COMPLIANCE WITH 703.2.1 | | | B. SHOW COMPLIANCE WITH 707.5.1 | | | | | | 10.INCLUDE A LIFE SAFTEY PLAN SHOWING | | | PATH OF TRAVEL. | | | | | | 11.SECOND FLOOR STAIRWAY EXIT SHALL | | | NOT EXIT TO ALLEY WAY.BUT SHALL EXIT | | | ON TO THE SAME PROPERTY.SUBMIT A SITE | | | PLAN.INCLUDE INFORMATION ON ADJACENT | | | ATTACHED BUILDING TO THE SOUTH SIDE | | | INCLUDING BUILDING HEIGHT. | | | | | | 12.FIRE ALARM SYSTEM IN ACCORDANCE | | | WITH 9.7 SHALL BE PROVIDED WHEN THE | | | BUILDING IS 2 OR MORE STORIES IN HEIGHT. | | | FBC 907.2.2 | | | | | | 13.INCLUDE SEPERATION DISTANCES | | | BETWEEN ADJACENT BUILDINGS SO THAT TABLE | | | 602 CALCULATIONS CAN BE MADE. | | | | | | 14.SHOW PARAPET DETAIL SHOWING | | | COPLIANCE WITH EXTERIOR WALL RATING IN | | | FBC 704.11 | | | | | | 15.DOOR 218, SEE FBC CHAPTER 11. MIN | | | 18" CLEARANCE REQUIRED AT THE LATCH SIDE | | | OF THE DOOR. | | | | | | 16.SPECIFY INTERIOR FINISH | | | CLASSIFICATIONS FOR CEILINGS AND WALLS. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. SUBMIT ONE COPY OF | | | OLD PAGES FOR REFERENCE. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER, WITH A DESCRIPTION OF | | | THE REVISION MADE, IDENTIFYING THE SHEET | | | OR SPECIFICATION PAGE WHERE THE CHANGES | | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ART LANGE | | | CONSTRUCTION SERVICES DEPARTMENT | | | BUILDING PLANS EXAMINER | | | 561-805-6672 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2007-04-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-04-15 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-04-15 |
Time |
09:23 |
Sent To |
|
|
| Notes |
| 2007-04-15 12:39:07 | ********* UNSAT4THREVIEW *********** | | | | | | ** PLEASE SEE SOME ITEMS FROM THE THREE PREVIOUS | | | REVIEWS ARE STILL IN NEED OF ADDRESSING. PLEASE SEE NEW | | | COMMENTS DUE TO CHANGES IN PLANS WHICH DECREASED ON OF | | | THE UNITS UPSTAIRS AND CHANGED FROM COMMERCIAL OFFICE | | | USE TO RESIDENTIAL. | | | | | | ** IMPORTANT** | | | THE OCCUPANCY OF UNITS ON SECOND FLOOR GREATLY AFFECTS | | | MANY COMMENTS FOR CODE COMPLIANCE , WHETHER OR NOT THEY | | | ARE RESIDENTIAL OR COMMERCIAL OFFICES. | | | | | | | | | 1) NOTE:PLEASE SEE NOTE #27 FROM THE PREVIOUS THREE | | | REVIEWS FOR COMPLIANCE WITH THE 2004 FBC CHAPTER 13. | | | PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE | | | WITH PLANS, AND FIXTURE LEGENDS FOR THE NUMBER OF | | | FIXTURES, TYPES, WATTAGES ETC. THERE ARE MULTIPLE ITEMS | | | WHICH DO NOT MATCH. | | | PLEASE SEE THE CONTROLS ON THE CALCULATIONS INDICATE | | | MANUAL ON/OFF WHEN AUTOMATED CONTROLS ARE REQUIRED FOR | | | CERTAIN AREAS. | | | PLEASE SEE NEW RESIDENTIAL UNITS FALL UNDER SEPARATE | | | REQUIREMENTS. | | | PLEASE SEE NO MAXIMUM TIMES ARE SHOWN FOR DEVICES. | | | PLEASE SEE MULTIPLE LOCATIONS WHICH DO NOT INDICATE | | | EITHER TIMER TYPE OR OCCUPANCY TYPE DEVICES? | | | NOTES LOCATED ON SOME ITEMS, HOWEVER SOME OF THE NOTES | | | LIKE NOTES #1 AND #2 INDICATE LIGHTING ON THE INSIDE | | | BEING CONTROLLED BY A PHOTO-CELL ALONG WITH OUTSIDE | | | LIGHTING? | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE | | | 13-415.1.AB.1.1, 13-415.2 | | | PLEASE SEE INPUT DATA REPORT WHICH DOES NOT SEEMS | | | COORDINATE WITH TOTAL ALLOWANCE ON FRONT SECTION OF | | | CALCULATIONS. | | | ** PLEASE SEE NOTES FOR EGRESS STAIRS AND CORRIDORS. | | | | | | 2) NOTE: PLEASE SEE NEW SHEET E-8 NOW SUBMITTED FOR | | | FIRE ALARM SYSTEM WHICH WAS NOT ON PREVIOUS PLANS. | | | PLEASE SEE ELECTRICAL PLANS INDICATE THE FAAP WITH | | | NOTES BEING THE FACP? PLEASE SEE E-8 WHICH INDICATES | | | THE FACP LOCATED INSIDE THE TENANT *A* WHICH IS NOT | | | PERMITTED. THIS DOES NOT CORRESPOND TO THE E-8 SHEET. | | | PLEASE CLARIFY THE DESIGNATED DEDICATED *SMOKE | | | DETECTOR* CIRCUIT ON HP WHEN THESE DEVICES SHOULD BE ON | | | THE FACP?? | | | PLEASE SEE NOTES ALSO MENTIONS A COMPLETE FIRE | | | SPRINKLER SYSTEM WHICH IS TO BE INSTALLED HOWEVER NO | | | BASE DESIGN PLANS WERE SUBMITTED. PLEASE SEE FIRE | | | MARSHAL REVIEW NOTES AND SEE FBC 106.3.5.1.2 AS THE | | | BASE PLANS SHALL SHOW THE REQUIRED PROPOSED SYSTEM | | | ALTHOUGH THE FS WILL BE UNDER A SEPARATE PERMIT. PLEASE | | | SEE THAT THE DEVICES FOR HORNS AND STROBES SHALL MEET | | | FBC 11-4.28.1,.2 AND .3(4). | | | PLEASE INDICATE ALL OF THE MINIMUM LEVELS IN AREAS FOR | | | ADA COMPLIANCE. | | | PLEASE KNOW, AS THE REQUIRED VERTICAL ACCESSIBILITY HAS | | | NOT YET BEEN DETERMINED, THIS MAY REQUIRE OTHER DEVICES | | | TO BE INCREASED. | | | | | | 3) NOTE: PLEASE SEE THE PLANS SEEM TO INDICATE COMMON | | | AREA ROOMS/CLOSETS WHICH ARE ONLY ACCESSIBLE FROM THE | | | TENANT SPACE. THIS WAS BROUGHT UP IN THE PREVIOUS | | | MEETING WITH THE DESIGNER. PLEASE COORDINATE WITH NOTES | | | ABOVE FOR LOCATION OF *HOUSE* EQUIPMENT AND ACCESS TO | | | THESE LOCATIONS. | | | IF THESE ROOMS ARE PART OF HOUSE EQUIPMENT, POWER ETC, | | | THEN THESE MUST BE ACCESSED FROM OTHER THAN INSIDE THE | | | TENANT SPACE. | | | | | | 4) NOTE: PLEASE SEE THE LOCATION OF THE *HP* PANEL | | | WHICH IS BEING SHOWN IN THE FIRE RATED EGRESS CORRIDOR | | | AND EXIT STAIRS. | | | PLEASE SEE THIS WILL BE NOTED FROM BUILDING AND FIRE | | | REVIEW FOR EXACT LOCATION WHICH IS NOT PERMITTED IN | | | RATED STAIR/EXIT/EXIT ACCESS ETC. | | | PLEASE SEE FBC CHAPTER 10 FOR ITEMS WHICH ARE PERMITTED | | | IN THESE AREAS MAY ONLY BE PERTAINING TO THE ELECTRICAL | | | EQUIPMENT AND DEVICES FOR THESE AREAS. | | | | | | 5) NOTE: PLEASE SEE NOTE #8 FROM ALL PREVIOUS REVIEWS | | | WHICH GAVE SECTIONS 210.52B1, 220.16 AND 210.11C1 FOR | | | THE MINIMUM OF TWO OR MORE SMALL APPLIANCE CIRCUITS AND | | | WHAT IS PERMITTED TO BE ON THESE CIRCUITS. | | | PLEASE SEE PLANS WHICH STILL INDICATE DINING ROOM | | | RECEPTACLE CIRCUITS WHICH ARE NOT FIGURED AT MINIMUM VA | | | AS REQUIRED PER 210.11C1 AND 220.16. | | | PLEASE SEE PLANS INDICATE SOME OF THESE AREAS WHICH | | | CONTAIN SEVERAL CIRCUITS WHICH ARE BEING SHOWN AS | | | GENERAL RECEPTACLE CIRCUITS. | | | PLEASE SEE E-17, E-2, C-23, D-2, C-23 ETC. | | | PLEASE SEE NEXT COMMENT WITH RESPECT TO 210.52 WHICH IS | | | MISSING SOME RECEPTACLES AS REQUIRED IN BREAKFAST/BAR | | | AREAS FOR WALL SPACE AND ALSO MISSING DEVICES FOR WALL | | | SPACES IN DINING AREAS. | | | ** LOADS ON THESE CIRCUITS SHALL BE 1500VA, NO OTHER | | | AREAS/DEVICE UNLESS LISTED AS AREAS OF THE LIKE AS | | | STATED IN THE CODE ARE PERMITTED ON THESE CIRCUITS. * * | | | PLEASE SEE RANGE HOOD J-BOXES WHICH ARE BEING SHOWN ON | | | THE SMALL APPLIANCE CIRCUITS WHICH IS NOT PERMITTED. A | | | RANGE HOOD IS NOT ONE OF THE PERMITTED APPLIANCES WHICH | | | MAY BE ON THE SM APPL. CIRCUITS. | | | | | | 6) NOTE:PLEASE SEE SEVERAL AREAS FOR MISSING | | | RECEPTACLES PER 210.52. | | | PLEASE SEE UNIT E WHICH IS MISSING DEVICES WITHIN 6FT | | | OF DOORWAYS, MORE THAN 12FT OF WALL WITHOUT A DEVICE. | | | PLEASE ALSO SEE UNIT *C* AND *D* DINING AREA WALL WHICH | | | HAS MORE THAN 12FT OF WALL WITHOUT A DEVICE.PLEASE | | | SEE LIVING ROOM AREA IN UNIT E. PLEASE SEE ONE SET OF | | | PLANS ARE REDLINED WITH SOME OF THESE LOCATIONS. | | | | | | 7) NOTE: PLEASE SEE UNIT E WHICH SHOWS A WATER HEATER | | | DESIGNATION LOCATED IN THE MIDDLE OF THE KITCHEN | | | COUNTER SPACE?? | | | PLEASE ALSO SEE THE PLANS INDICATE THE WATER HEATER IN | | | A CLOSET? | | | PLEASE SEE 422.17 AS THE WATER HEATER IS BEING SHOWN IN | | | A STORAGE CLOSET WHICH CONTAINS EASILY IGNITABLE | | | MATERIALS.* EACH ELECTRICALLY HEATED APPLIANCE THAT IS | | | INTENDED BY SIZE, WEIGHT, AND SERVICE TO BE LOCATED IN | | | A FIXED POSITION SHALL BE PLACED SO AS TO PROVIDE AMPLE | | | PROTECTION BETWEEN THE APPLIANCE AND ADJACENT | | | COMBUSTIBLE MATERIAL*. | | | | | | 8) NOTE: PLEASE SEE 410.8 AS THE LIGHT FIXTURE IN THE | | | CLOSET IN UNIT *C* DOES MEET THE MINIMUM CLEARANCES ARE | | | REQUIRED. | | | PLEASE RELOCATE OR REMOVE. | | | | | | 9) NOTE: PLEASE SEE UNIT E- WHICH IS MISSING THE | | | STOVE/RANGE CIRCUITING FROM PLANS. | | | PLEASE ALSO SUBMIT THE MANUFACTURE INFORMATION SPECS ON | | | THIS STOVE/RANGE. THE SIZE AND LOAD FOR WHAT IS BEING | | | SHOWN ON PLANS AS A FULL SIZE APPLIANCE SEEMS TO BE | | | VERY LOW. | | | PLEASE SEE THE TABLES IN 220.19. | | | ** PLEASE ALSO VERIFY PLANS AS THEY ARE INDICATING GFCI | | | PROTECTION FOR THE RANGE/STOVE?? | | | | | | 10) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL | | | SERVICE EQUIPMENT. MAINS, PANELS AND BREAKERS. PLEASE | | | SEE PANELS DO INDICATE RATINGS AT 22K, HOWEVER IF SHOWN | | | AS 22K FOR THE ENTIRE PANEL AS FULLY RATED, THEN THIS | | | WOULD MEAN ALL OF THE BRANCH BREAKERS WOULD BE 22K | | | RATED. IS THIS WHAT IS REALLY INTENDED? | | | | | | 11) NOTE: PLEASE COMPLETE THE PHOTO-METRICS AS THE | | | LEVELS ARE NOT READABLE ON PLANS SUBMITTED FOR WALKWAY | | | AREAS AND STAIRS. | | | PLEASE CLARIFY HOW THE PHOTO-METRICS INDICATE ONE TYPE | | | OF FIXTURE BEING FIGURED FOR LIGHTING LEVELS, YET THE | | | LIGHTING PLANS AND FIXTURE LEGEND INDICATE A DIFFERENT | | | TYPE OF FIXTURE? IN FACT THE LIGHTING FIXTURES WHICH | | | ARE NOTED TO BE USED ON PHOTO-METRICS ARE NOT EVEN | | | LISTED ON THE FIXTURE LEGEND? | | | PLEASE SHOW AND INDICATE THE MINIMUM LEVELS FOR | | | SECTIONS BELOW, PLEASE SEE THE COMMENTS WITH RESPECT TO | | | EGRESS LIGHTING AND CONTROLS FOR CHAPTER 13. PLEASE SEE | | | SECTION 1006.1.2 OF THEFBC 2004 PLEASE SEE THE | | | FOLLOWING TEXT WHICH WAS EXTRACTED DIRECTLY FROM | | | NFPA-101. | | | 7.8.1 GENERAL. | | | 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE | | | PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY | | | BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTER 11 | | | THROUGH CHAPTER 42. FOR THE PURPOSES OF THIS | | | REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED | | | STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND | | | PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF | | | THIS REQUIREMENT, EXIT DISCHARGE SHALL INCLUDE ONLY | | | DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS, | | | ESCALATORS, WALKWAYS, AND EXIT PASSAGEWAYS LEADING TO A | | | PUBLIC WAY. | | | 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE | | | CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF | | | OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE | | | FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2. | | | 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH | | | LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY | | | TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA | | | VALUES HEREIN SPECIFIED. | | | 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING | | | SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS, | | | PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR | | | FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET | | | FOR A MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR | | | IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA | | | SERVED BY THE LIGHTING UNITS. | | | 7.8.1.3* THE FLOORS AND OTHER WALKING SURFACES WITHIN | | | AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND | | | EXIT DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE | | | ILLUMINATED AS FOLLOWS: | | | (1)DURING CONDITIONS OF STAIR USE, THE MINIMUM | | | ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST 108 LUX | | | (10 FT-CANDLE), MEASURED AT THE WALKING SURFACES. (2) | | | THE MINIMUM ILLUMINATION FOR FLOORS AND WALKING | | | SURFACES, OTHER THAN NEW STAIRS, SHALL BE TO VALUES OF | | | AT LEAST 10.8 LUX (1 FT-CANDLE), MEASURED AT THE | | | FLOOR. | | | * PLEASE ALSO SEE SECTION 7.9.2.2. WHERE THE FAILURE OF | | | ANY SINGLE DEVICE OR LIGHTINGSHALL NOT LEAVE ANY ONE | | | EGRESS AREA IN TOTAL DARKNESS. | | | | | | 12) NOTE: PLEASE COORDINATE ALL CIRCUITS. PLEASE SEE | | | CIRCUITING FOR LIGHTING IN UNIT E, WHICH INDICATES E-19 | | | FOR BEDROOM LIGHTING AND LIGHTING IN OTHER AREAS, YET | | | THE PANEL SCHEDULE SHOWS THIS CIRCUIT AS THE CIRCUIT | | | FOR THE WASHER?? | | | PLEASE SEE 210.12 FOR AFCI PROTECTION IN THE 2002 NEC> | | | | | | 13) NOTE: PLEASE CLARIFY THE NOTES ON THE LIGHTING | | | PLANS FOR THE RESIDENTIAL UNITS ON THE SECOND FLOOR | | | WHICH SEEM TO INDICATE LIGHTS FOR COMMERCIAL SPACE?? | | | PLEASE SEE NOTE #1 FOR E UNIT WHICH MENTIONS EMERGENCY | | | LIGHTING ETC?? | | | FBC 106.1.2 | | | SEE E-6. | | | | | | 14) NOTE: PLEASE CLARIFY RISER AS THE RISER SHOWS ONE | | | LARGER GUTTER/TROUGH, YET PLANS INDICATE A DOOR LOCATED | | | IN THE MIDDLE OF THE GUTTER. PLEASE KNOW IF THE WALL | | | SPACE IN NOT CONTINUOUS THEN SOME THING MUST BE DONE | | | WITH THE RISER AND ADJUSTED TO INCLUDE FEEDERS TO | | | METERS/DISCONNECTS. | | | AS SHOWN, THIS IS NOT POSSIBLE. | | | PLEASE REVISE RISER, PLANS OR DOOR LOCATION FOR RISER | | | TO BE COMPLETE AT ONE LOCATION. | | | 215.5. | | | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. | | | | | | 15) NOTE: PLEASE COMPLETE THE ROOM/AREA DESIGNATIONS ON | | | PANEL SCHEDULE TO CORRELATE WITH THE DESIGNATIONS ON | | | PLANS. | | | PLEASE SEE THE FOLLOWING TEXT FROM 408.4 WHICH MENTIONS | | | THE USE OF *GENERAL RECEPTACLES/GENERAL LIGHTING* IS | | | NOT PERMITTED. | | | SOME CIRCUITS AS SHOWN ARE NOT CLEAR. | | | DESIGNATIONS ARE NOT SHOWN ON LIGHTING PLANS. | | | * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY | | | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE | | | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR | | | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME | | | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR | | | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY | | | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN | | | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL | | | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, | | | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL | | | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR | | | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' | | | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH | | | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE | | | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4, | | | 310.16, 240.4 ETC | | | FBC 106.3.5.4 | | | | | | 16) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO | | | THE FS 553.80(2)(B) WITH RESPECT TO DESIGN | | | PROFESSIONALS AND REPEAT COMMENTS. | | | PLEASE KNOW AT THIS TIME A FEE OF $6,600 HAS NOW BEEN | | | ASSESSED AS REQUIRED UNDER THE FLORIDA STATUTES AS | | | THERE HAVE BEEN SOME OF THE SAME COMMENTS REPEATED FOR | | | CODE COMPLIANCE FROM PREVIOUS REVIEWS | | | THIS FEE IS ASSESSED TO THE DESIGN PROFESSIONAL AS | | | REQUIRED UNDER THE FLORIDA STATUTES AND MUST BE PAID | | | BEFORE THE NEXT RE-SUBMISSION OF PLANS. | | | ** PLEASE ALSO KNOW THAT ONE COMPLETE SET OF PLANS WILL | | | BE RETAINED BY THIS OFFICE TO BE PLACED WITH PLANS FROM | | | PREVIOUS REVIEWS FOR POSSIBLE REVIEW BY THE STATES | | | LEGAL COUNSEL TO THE BOARD OF ARCHITECTS. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2006-10-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-10-15 |
Time |
19:25 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-10-15 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2006-10-15 19:25:27 | ********* UNSAT3RDREVIEW *********** | | | | | | ** PLEASE SEE MANY ITEMS FROMTHE TWO PREVIOUS REVIEWS | | | WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE SEE NEW | | | COMMENTS DUE TO | | | INFORMATION SHOWN ON PLANS WHICH WAS | | | DIFFERENT FROM PREVIOUS REVIEW OR HAS CHANGED IN | | | DESIGN | | | | | | ** PLEASE SEE THE NOTES BELOW ARE TAKEN | | | DIRECTLY FROM PREVIOUS REVIEW WITH NEW | | | NOTES ADDED TO THE END OF THE PREVIOUS | | | NOTES. | | | | | | ** IMPORTANT** | | | THERE IS A BALANCED OWED OF $460, WHICH WILL BE | | | REQUIRED TO BE PAID BEFORE ANY PERMIT CAN BE ISSUED. | | | PLEASE ALSO BE AWARE THE NEXT RESUB WILL ALSO HAVE FEES | | | DUE. | | | | | | | | | ** IMPORTANT** | | | THE OCCUPANCY OF UNITS ON SECOND FLOOR GREATLY AFFECTS | | | MANY COMMENTS FOR CODE COMPLIANCE , WHETHER OR NOT THEY | | | ARE RESIDENTIAL OR COMMERCIAL OFFICES. | | | | | | | | | 1)NOTE: OK. | | | | | | 2)NOTE: OK. | | | | | | 3)NOTE: OK SIGNED PLANS. | | | | | | 4)NOTE: OK. | | | | | | 5)NOTE:NO, PLEASE SEE THE NOTE WITH RESPECT THE | | | EXHAUST FANS IN OTHER NOTES. OTHER "HOUSE" CIRCUITS | | | WERE CORRECTED. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2 | | | NO, PLEASE SEE COMMON AREA | | | ELECTRICAL STILL BEING SHOWN CIRCUITED | | | TO ONE OF THE RESIDENTTIAL UNITS. | | | THIS IS NOT PERMITTED. | | | | | | ** PREVIOUS REVIEW NOTEREVIEW #1** | | | PLEASE SEE NO COMMON AREAS SHALL | | | BE FED FROM CIRCUIT DERVIED FROM APTS OR | | | OFFICE UNITS. PLEASE SEE CIRCUITING OF | | | HALL RECEPTS ARE SHOWN TO ONE UNIT. | | | PLEASE SEE 210.25 | | | | | | 6)NOTE:OK. | | | | | | 7)NOTE: OK. | | | | | | 8)NOTE:NO, PLEASE SEE TWO ACESSIBLE SMALL APPLIANCE | | | CIRCUITS ARE REQUIRED ALONG KITCHEN COUNTER SPACE. ONE | | | MAY NOT BE LOCATED BEHIOND THE FRIG, ALOTHOUGH MAY BE | | | ON ONE OR MORE OF THE SM APPL CIRCUITS. PLEASE SEE | | | MINIMUM LOAD WHICHSHALL BE FIGNURED FOR EACH OF THE | | | SMALL APPLIANCE CIRCUITS. DINING RMS AND AREASOF THE | | | LIKE. | | | PLEASE SEE 210.52B1, 210.11C1, 220.16. PLEASE SEE MIN | | | VA FOR EACH CIRCUIT. PLEASE SEE OTHER COMMENTS WITH | | | RESPECT TO LOAD CALCULATIONS. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2** | | | NO, STIL SHOWS ONLY ONE. | | | | | | **PREVIOUS REVIEW NOTE REVIEW #1 ** | | | PLEASE SEE A | | | MIN OF TWO SMALL | | | APPLIANCE CIRCUITS ARE REQUIRED PER | | | 210.52B1. | | | | | | 9)NOTE: OK. | | | | | | 10)NOTE: OK. | | | | | | 11)NOTE: OK. | | | | | | 12)NOTE: OK. | | | | | | 13)NOTE:NO, PLEASE LOOK AT ALL CIRCUITING AS NOW | | | SHOWN. PLEASE SEE ARC FAULT IS BEING SHOWN ON | | | DISHWASHER AND MANY OTHER ITEMS NOT REQUIRED?? IT IS | | | UNCLEAR OF THE INTENT. THE ORIGINAL AND PREVIOUS | | | COMMENTS HAD TO DO WITH THE "OUTLETS" IN SLEEPING ROOMS | | | OR ROOMS WILL BE CONSIDERED SUCH. | | | IT IS UNCLEAR AT THIS TIME AND RESPONSE LETTER ONLY | | | MENTIONS THEY ARE REFLECTED.? | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2** | | | NO, PLEASE SEE THERE ARE | | | CIRCUITS NOW SHOWN WITH ARC FAULT | | | PROTECTION WHICH ARE NOT REQUIRED AND | | | SOME WHICH DO SHOW ARC FAULT PROTECTION | | | AND SOME THAT DO NOT?? | | | PLEASE SEE ALL "OUTLETS". | | | | | | ** PREVIOUS REVIEW NOTE REVIEW#1 ** | | | PLEASE LIST THE REQUIRED ARC | | | FAULT PROTECTED CIRCUITS AS REQUIRD | | | UNDER THE 2002 NEC 210.12B | | | PLEASE KNOW, ALL, ELECTRICAL | | | DEVICES/OUTLETS SUCH AS LTS, SD'S | | | RECEPTS, FANS ETC SHALL BE AFCI | | | PROTECTED. | | | ** PLEASE KNOW, AREAS NOW SHOWN AS | | | "OFFICES" ARE UNITS WHICH SEEM TO SHOW | | | POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF | | | THESE AREAS ARE ADAPTABLE FOR | | | RESIDENTIAL USE, THEN AFCI PROTECTION | | | WILL BE REQUIRED FOR THESE ROOMS. | | | | | | 14)NOTE:NO, PLEASE SEE CIRCUITING NOTES FOR EXHAIST | | | FANS. THE CIRCUITING FOR SA'S ARE OK, IT OTHER | | | CIRCUITING IS CORRECTED AND AFCI PROTECTION IS | | | INDICATED. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2 ** | | | OK, HOWEVER 2ND PART OF THIS | | | NOTE WAS NOT DONE. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #1 ** | | | PLEASE SEE NFPA-70 11.5.1.1 | | | WHICH REQUIRES THE USE OF SMOKE | | | DETECTORS INSIDE AND OUTSIDE ALL | | | SLEEPING RMS OR ADAPTABLE SLEEPING | | | ROOMS.** PLEASE SEE PREVIOUS NOTES WITH | | | RESPECT TO THE CIRCUITING OF BEDRMS. | | | | | | 15)NOTE: NO, PLEASE SEE THERE ARE STILL MANY ITEMS ON | | | PLANS WHICH DO NOT CONTAIN CIRCUITING. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2 ** | | | NO, PLEASE SEE SOME CIRCUITS | | | ARE NOT COMEPLETE AT THIS TIME IN | | | DWELLING UNITS AND HOUSE AREAS. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #1 ** | | | PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE. PLEASE SEE CIRCUTING | | | MISSING. | | | 215.5 | | | | | | 16)NOTE: OK. | | | | | | 17)NOTE: OK. | | | | | | | | | 18)NOTE: OK. | | | | | | 19)NOTE: OK. | | | | | | 20)NOTE: NO/OK. PLEASE SEE A DETAIL WAS SUBMITTED | | | HOWEVER DOES NOT SHOW ALL EGRESS PATHS FOR MIN LIGHTING | | | LEVELS UNDER NORMAL AND EMERGENCY. PLEASE ALSO SEE A | | | FIXTURE TYPE IS NOW BEING NOTED AT A HID METAL HALIDE | | | FOR ONE OF THE EM FIXTURES?? PLEASE SEE THIS DOES NOT | | | INDICATE ANY QUARTZ/RE-STRIKE. IF AND WHEN POWER IS | | | INTERUPTED IN AN EMERGENCY, THESE FIXTURES WILL NOT | | | COME ON PROVIDINGTHE MIN LIGHTING LEVELS WITHIN THE | | | TIME REQUIRED BEIGN HID FIXTURES. PLEASE EXPLAIN | | | FIXTURE TYPE, AADJUST FIXTURE TYPE ETC? | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2** | | | NO, PLEASE SEE A NOTE WAS ADDED | | | TO PLANS IN LEIU OF THE DETAIL NEEDED | | | AND REQUIRED. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #1** | | | PLEASE PROVIDE THE PHOTO-METRICS FOR | | | EXITING STAIR AREAS AS NFPA-101 7.8.1.3 | | | REQUIRES A MIN OF 10FT CANDLES (108 LUX) | | | FOR THE ALL AREAS OF WALKING SURFACE IN | | | STAIRS UNDER NORMAL POWER AND IS | | | PERMITTED TO BE LOWERED TO A MIN OF 1FT | | | CANDLE (10.8 LUX) UNDER EMERGENCY | | | CONDITIONS, 7.9.2.2 | | | | | | 21)NOTE: OK, HOWEVER PLEASE STILL PLEASE SEE NOTE WITH | | | RESPECT TO FBC CHAPTER 13 WHICH MAY AFFECT FIXTURES. | | | | | | 22)NOTE: OK. | | | | | | 23)NOTE:NO, SAME NOTE.PLEASE ALSO SEE NEW NOTES FOR | | | THE REVISED RISER NOW SUBMITTED FOR FIRST REVIEW. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2** | | | NO, PLEASE SEE "EQUIPMENT | | | GROUNDING CONDUCTORS" ARE STILL BEING | | | SHOWN BEFORE THE FIRST MEANS OF | | | DISCONNECT. PLEASE SEE NEW NOTESAS | | | LOCATION WILL CHANGE. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #1 ** | | | PLEASE SEE 250.6, 250.24, NO | | | "EQUIPMENT GROUNDING CONDUCTORS" SHALL | | | BE INSTALLED BEFORE THEFIRST MEANS OF DISCONNECT. | | | PLEASE SEE THESE ARE SHOWN | | | FROM FPL, TO GUTTER, TO METER ETC. | | | | | | 24)NOTE:OK. | | | | | | 25)NOTE: OK. | | | | | | 26)NOTE: NO, PLEASE SEE PREVIOUS NOTES. CALCULATIONS | | | SUBMITTED AND SHOWN DO NOT CORRELATE WITH SOME PANEL | | | SCHEDULES. PLEASE ALSO SEE SOME AS THEY SO NOT MEET NEC | | | CODE COMPLIANCE. PLEASE SEE OCCUPANCY WILL AFFECT THIS. | | | PLEASE SEE RESIDENTIALUNITS ALSO. ETC | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2** | | | NO, PLEASE SUBMIT COMPLETE | | | CALCULATIONS FOR EACH PANEL FOR USE AS | | | SHOWN ON PLANS. | | | PLEASE ALSO SHOW LOADS FOR SERVICE, NONE | | | WERE SUBMITTED. | | | | | | **PREVIOUS REVIEW NOTES REVIEW #1 ** | | | PLEASE SUBMITLOAD CALCULATIONS FOR | | | ALL AREAS, PANELS, BLDG. PLEASE SEE | | | THESE ARE SHOWN A MIXED | | | USE. PLEASE ADJUST ACCORDINGLY. | | | PLEASE ALSO INDICATE OF CONTINUOUS LOADS | | | AT 125%. 215.3,230.42, | | | 220.10,220.11,220.13 ETC | | | | | | 27)NOTE:NO, PLEASE SEE 2004 FBC CHAPTER 13. PLEASE | | | SEE OCCUPANCY WILL HAVE AN AFFECT ON THIS. PLEASE SEEE | | | ONLY SOME OF THE FOLLOWING SECTIONS WHICH ARE BEING | | | BROKEN DOWN. PLEASE KNOW, ALL OF THE CHAPTER WAS GIVEN | | | ON PREVIOUS REVIEW AS NOTHING WAS SUBMITTED OR SHOWN. | | | PLEASE SEE 13-415.1.ABC.1.1, .1.2& .1.3. PLEASE SEE | | | MANY ITEMS MISSING. | | | PLEASE SEE 13-415.2.ABC.1,TABLES 415.2.C.1, 415.2.B.1 | | | PLEASE SEE THE ENERGY CALCULATIONS WERE NOT THE ONLY | | | ITEM NEEDED. | | | PLEASE SEE ALL SEPARATE SPACES ETC | | | PLEASE PROVIDE THE MAX TIMES PERMITTED ON OVER RIDE | | | DEVICES ETC. ( OS TYPE 30MINS MAX, TIMER TYPE 4HRS | | | MAX) | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2** | | | NO, THIS WAS NOT ADDRESSED AND | | | NO DESIGNS, CALCS, CONTROLS ETC WERE | | | SUBMITTED FOR REVIEW. PLEASE SEE MIN | | | CALCULATIONS REQUIRED. | | | ALSO NO ENERGY CALCULATIONS WERE | | | SUBMITTED. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #1 ** | | | PLEASE BE SURE TO SEE THE 2004 | | | FBC CHAPTER 13 WITH RESPECT TO THE | | | ENERGY CODE AND DESIGNS. PLEASE KNOW | | | THIS IS A COMMERCIAL BLDG WITH A CHANGE | | | OF OCCUPANCY WHICH WILL REQUIRE ENERGY | | | CODE UPGRADES. | | | | | | **** NEW NOTES 2ND REVIEW**** | | | | | | 28) NOTE: OK, HOWEVER SEE NEW NOTE FROM 3RD REVIEW. | | | | | | 29) NOTE:NO/OK, PLEASE SEE A COMPLETELY NEW RISER | | | DIAGRAM HAS BEEN SUBMITTED, HOWEVER LABELING OF ALL | | | EQUIPMENT AS PERVIOUSLY NOTED STILL NEEDS TO BE | | | ADDRESSED FOR EACH MAIN /PANEL ECT. | | | PLEASE ALSO SEE NEW COMMENTS DUE REVISED RISER FOR NEW | | | 3RD REVIEW NOTES. | | | | | | ** PREVIOUS REVIEW NOTES REVIEW #2** | | | PLEASE SEE RISER WHICH | | | INDICATES MORE THAN SEVEN MEANS OF | | | DISCONNECT WHICH IS NOT PERMITTED. | | | 230.2,230.70. | | | PLEASE KNOW A SEPARATE TYPE OF METER | | | BANK SERVICE MAY BE DONE WITH A MAIN | | | ETC. | | | PLEASE ALSO SEE MANY OF THE TENANT | | | METERS, MAINS ETC ARE LABLED AS "HOUSE" EQUIPMENT?? | | | PLEASE SEE PANEL "HP" SHOULD BE THE ONLY | | | PANEL, METER AND MAIN LABLED AS "HOUSE". | | | 408.4 | | | 30) NOTE: PLEASE SEE CLOSET LT IN UNIT | | | "C" WHICH DOES NOT MEET 410.8 | | | | | | 30) NOTE:NO, SAME, PLEASE SEE REPSONSE LTR MENTIONS | | | THIS WAS ADDRESSED, HOWEVER SEE PLANS ARE STILL SHOWING | | | MULTIPLE CIRCUITS FOR THE SAME EXHAUST FANS AND IF SOME | | | OF THESE ARE SUPPOSE TO BE ON "HOUSE PANEL " AS | | | REPSONSE LETTER MENTIONS, THEN PLEASE SEE PLANS AS | | | THESE ARE STILL SHOWN TO UNIT PANELS FOR TENANTS WHICH | | | IS NOT PERMITTED. SEE NOTES ABOVE WITH RESPECT TO | | | "HOUSE EQUIPMENT' WHICH IS NOT PERMITTED ON TENANT | | | PANELS. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2** | | | PLEASE SEE SOME UNITS SHOW AND | | | LABEL "TWO" EXHAUST FAN CIRCUITS?? | | | PLEASE ALSO SEE ARC FAULT CIRCUITING. | | | PLEASE SEE MANY OF THESE DO NOT | | | CORRELATE WITH CIRCUITING SHOWN ON PLANS | | | AND DEVICES. SOME ARE NOT AS LABELED. | | | FBC 106.1.2 ADMIN SECT. | | | | | | 31) NOTE: OK, RELOCATED PANELS. | | | | | | 32) NOTE: OK, HOWEVER SEE NOTES FOR CONTROL OF LTS. IF | | | THIS DOES BECOME A ROOM WHICH REQUIRES A PUMP OR | | | CONTROLLER SOME ELECTRICAL ITEMS WILL BE REQUIRED. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2** | | | PLEASE SEE PLANS MENTIONS | | | "SPRINKLER ROOM" ? WHAT IS THIS AND IS | | | THERE LIGHTING FOR SERVICE OF EQUIPMENT | | | ETC? | | | LS 101 7.8 | | | | | | 33) NOTE:NO, PLEASE SEE A NOTICE WAS GIVEN WITH | | | RESPECT TO REPEAT COMMENTS. PLEASE KNOW AS PLANS WERE | | | SUBMITTED THE FIRST TWO TIMES AS "PLAN REVIEW ONLY" THE | | | FEE WILL NOT APPLY FOR THIS REVIEW, HOWEVER PLEASE BE | | | AWARE IF "ANY " OF THE SAME CODE COMPLIANT COMMENTS | | | COME BACK WHICH ARE REPEAT FOR THENEXT REVIEW A FEE | | | WILL BE ASSESSES AS REQUIRED PER FLORIDA STATUE GIVEN. | | | | | | ** PREVIOUS REVIEW NOTE REVIEW #2 ** | | | PLEASE SEE COPY OF FS | | | 553.80(2)B) WITH RESPECT TO REPEAT | | | COMMENTS FOR CODE COMPLIANCE AS MANY OF | | | THESE COMMENTS ARE THE SAME AS THE | | | PREVIOUS REVIEW. THIS IS ONLY BEING | | | GIVEN AS A NOTICE AT THIS TIME. | | | | | | | | | **** NEW NOTES FOR 3RD REVIEW ***** | | | | | | 34) NOTE: PLEASE SEE 210.52C1-5 FOR SPACING OF GFI | | | RECEPTS ALONG KTICHEN COUNTER SPACE. PLEASE SEE AS | | | SHOWN AND IF THE OCCUPANCY IS GOING TO BE RESIDENTIAL, | | | THEN THE SPACING AS SHOWN IN SOME UNITS DO NOT MEET | | | CODE GIVEN. | | | | | | 35) NOTE: PLEASE PROVIDE ALL AIC RATINGS FOR ALL NEW | | | SERVICE EQUIPMENT AS SHOWN. ALL MAINS PANELS ETC SHALL | | | MEET 110.9 AND PLEASE SEE 240.12 FOR SELECTIVE | | | COORDINATION. | | | | | | 36) NOTE: PLEASE SEE AS RISER CONTAINS A NEW MAIN, | | | PLEASE NOW INDICATE A "FLOATING NEUTRAL" FORALL | | | METERS ON THE SECONDARY SIDE OF THE NEW MAIN. 250.6, | | | 250.24B | | | PLEASE ALSO SEE NOTE ON RISER SHEETS WHICH BODNIGN W/ | | | EMT TO MEET 250.66. PLEASE SEE ALL NEUTRALS AND | | | EQUIPMENT GROUNDS ARE REQUIRED TO BE SEPARATE AFTER THE | | | FIRST MEANS OF DISCONNECT. | | | | | | 37) NOTE: PLEASE SEE PLANS NOW MENTIONS AS FA SYSTEM TO | | | BE INSTALLED, YET NO INFORMATION WAS SUBMITTED FOR | | | THIS.? PLEASE CLARIFY THE SMOKE DEVICES ON PLANS. | | | PLEASE SEE NFPA-72 DEFINITIONS FOR SA (SMOKE ALARMS) | | | AND SD (SMOKE DETECTORS). PLEASE ADJUST ACCORDINGLY ID | | | UTILIZING A SYSTEM AS PART OF THE BUILDING. NFPA-72 | | | 11.5, 11.8 ETC | | | | | | 38) NOTE: PLEASE SEE A PREVIOUS NOTE MENTIONED | | | QUALIFICATIONS FOR LIMITS ON PLAN DESIGN. PLEASE SEE FS | | | 471.003, 471.025, 481.221. PLEASE KNOW, DUE TO THE | | | REPEAT COMMENTS FOR CODE COMPLIANCE REPEATED , ONE SET | | | OF EACH ELECTRICAL SET OF PLANS SUBMITTED ARE BEING | | | RETAINED FOR POSSIBLE REVIEW AND SUBMISSION TO THE | | | FLORIDA BOARD OF ARCHITECTS AND LEGAL COUNSEL TO THE | | | BOARD. | | | PLEASE ADDRESS ALL COMMENTS. TO DATE, NO ONE HAS | | | CONTACTED THIS OFFICE IF THERE WERE ANY COMMENTSOR | | | QUESTIONS ON SAID REVIEW COMMENTS. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | | PICKED UP FOR CORRECTIONS, PLEASE BE | | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | | SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | | AND STAMPING. DO NOT LEAVE ANY | | | OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE | | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | | FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND | | | AVOID ANY DELAYS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2006-07-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-07-06 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-07-05 |
Time |
21:01 |
Sent To |
|
|
| Notes |
| 2006-07-06 00:00:00 | ** | | | ********* UNSAT2ND REVIEW *********** | | | | | | ** PLEASE SEE MANY ITEMS FROM PREVIOUS | | | REVIEW AND SOME NEW ITEMS DUE TO | | | INFORMATION SHOWN ON PLANS WHICH WAS | | | DIFFERENT FROM PREVIOUS REVIEW. | | | | | | ** PLEASE KNOW, PLANS HAVE NOW BEEN | | | SUBMITTED FOR PERMIT. | | | PLEASE SEE THE NOTES BELOW ARE TAKEN | | | DIRECTLY FROM PREVIOUS REVIEW WITH NEW | | | NOTES ADDED TO THE END OF THE PREVIOUS | | | NOTES. | | | | | | ** IMPORTANT** | | | PLEASE SEE AS REQUESTED ON PREVIOUS | | | REVIEW, PLEASE SUBMIT ONE SET OF THE | | | OLD/VOIDED SETS FOR REFERENCE. THIS WAS | | | NOT DONE. | | | | | | 1)NOTE:NO, PLEASE SEE COVER SHEETS | | | ONLY MENTIONS THE CODES AND NOT THE | | | YEARS OF EDITIONS. | | | | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE SEE THAT ALL DESIGNS AND | | | CODES ARE REFERENCED TO THE CURRENT | | | CODES ADOPTED BY THE STATE OF FLORIDA. | | | PLEASE KNOW, WE ARE CURRENTLY UNDER THE | | | 2004 FLORIDA BLDG CODE. | | | 2002 NFPA-70, 2002 NFPA-72,2003 NFPA-101 | | | PLEASE ADJUST. | | | PLEASE ALSO SEE NOTES BELOW AS | | | ELECTRICAL CODE IS BEING REFERENCED FROM | | | THE 1996 | | | NFPA-70 (NEC). | | | | | | 2)NOTE: OK, AS TITLE BLOCKS HAVE BEEN | | | REVISED AND ENGINEERING FIRM AND | | | ENGINEER IS NO LONGER DOING THE PROJECT. | | | HOWEVER PLEASE SEE NEW NOTES. | | | | | | **PREVIOUS REVIEW NOTE ** | | | PLEASE SEE MISSING INFORMATION | | | AND LICENSE INFORMATION REQUIRED ON | | | TITLE BLOCKS FOR THE ARCHITECTUAL FIRM, | | | ENGINEER AND FIRM? ETC. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002, | | | 61G1-16.004 AND FLORIDA | | | STATUES, 481.219, 471.023 . | | | PLEASE KNOW: THIS IS REQUIRED OF ALL | | | TRADES AND FOR ALL SHEETS WHETHER OR NOT | | | COMMENT IS MADE BY OTHER REVIEWER(S). | | | | | | 3)NOTE: NO, PLEASE SEE IT SEEMS THE | | | ENGINEER AS SHOWN ON PREVIOUS PLANS HAS | | | BEEN REMOVED AND THE PLANS ARE NOW DONE | | | BY AN ARCHITECT. PLEASE SEE NEW COMMENTS PERTAINING TO | | | THE PLANS AND PLEASE SEE | | | THAT THE PREVIOUS NOTE STILL APPLIES TO | | | THE ARCGITECT OF RECORD. PLEASE SEE | | | PLANS ARE CLEARLY "SIGNED" WITH | | | "INITIALS". IF THIS IS THE "LEGAL | | | SIGNATURE" OF SAID ARCHITECT, PLEASE | | | PROVIDE A SIGNED,DATED AND SEALED | | | NOTORIZED LETTER FOR LEGAL SIGNATURE | | | VERIFICATION. THIS WILL BE PLACED IN OUR | | | SIGNATURE FILE FOR FUTURE REFERENCE. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE ALSO PROVIDE A SIGNED, DATED AND | | | SEALED LETTER FOR THE ENGINEER AS SHOWN | | | ON PLANS AFFIRMING THE LEGAL SIGNATURE | | | ON SAID PLANS. PLANS APEAR TO INDICATE INITIAL(S)? THIS | | | LETTER IS TO BE CORRECTLY | | | NOTORIZED, AND WILL BE PLACED IN OUR | | | SIGNATURE FILE FOR FUTUREREFERENCE. | | | | | | 4)NOTE: NO, PLEASE SEE LOWER POWER PLANS | | | INDICATE ROOF TOP GFI'S AND THE TWO ARE | | | FED FROM FIRST FLR TENANT PANELS. THESE | | | SHOULD BE FED FROM HOUSE PANEL. | | | | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE INDICATE THE ROOF TOP | | | RECEPTS AS GFI OR GFI PROTECTED AS | | | REQUIRED PER 210.8B2 | | | | | | 5)NOTE: NO, PLEASE SEE COMMON AREA | | | ELECTRICAL STILL BEING SHOWN CIRCUITED | | | TO ONE OF THE RESIDENTTIAL UNITS. | | | THIS IS NOT PERMITTED. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE NO COMMON AREAS SHALL | | | BE FED FROM CIRCUIT DERVIED FROM APTS OR | | | OFFICE UNITS. PLEASE SEE CIRCUITING OF | | | HALL RECEPTS ARE SHOWN TO ONE UNIT. | | | PLEASE SEE 210.25 | | | | | | 6)NOTE:NO, PLEASE SEE CODE CHANGED IN | | | 1993 TO REQUIRED "ALL" NOT ONLY RECEPTS | | | LOCATED WITHIN 6' OF SINK. | | | | | | ** PREVIOUS REVIEW NOTE** | | | PLEASE SHOW ALL KITCHEN | | | COUNTERSPACE RECEPTS AS GFI/ GFI | | | PROTECTED AS REQUIRED PER 210.8A6 | | | | | | 7)NOTE: NO, SAME NOTE: PLEASE SEE | | | KITCHENS IN OTHER THAN DWELLING UNITS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE IF OFFICE UNITS WHICH | | | WILL ALSO BE REQUIRED TO HAVE GFI | | | RECEPTS,IN EITHER CASE ON POSSIBLE USE | | | CHANGE TO DWELLING UNITS, OR AS REQUIRED | | | PER 210.8B3 | | | | | | 8)NOTE: NO, STIL SHOWS ONLY ONE. | | | | | | **PREVIOUS REVIEW NOTE ** PLEASE SEE A | | | MIN OF TWO SMALL | | | APPLIANCE CIRCUITS ARE REQUIED PER | | | 210.52B1. | | | | | | 9)NOTE: OK. | | | | | | 10)NOTE: OK. | | | | | | 11)NOTE: OK. | | | | | | 12)NOTE: OK. | | | | | | 13)NOTE: NO, PLEASE SEE THERE ARE | | | CIRCUITS NOW SHOWN WITH ARC FAULT | | | PROTECTION WHICH ARE NOT REQUIRED AND | | | SOME WHICH DO SHOW ARC FAULT PROTECTION | | | AND SOME THAT DO NOT?? | | | PLEASE SEE ALL "OUTLETS". | | | | | | ** PREVIOUS REVIEW NOTES ** | | | PLEASE LIST THE REQUIRED ARC | | | FAULT PROTECTED CIRCUITS AS REQUIRD | | | UNDER THE 2002 NEC 210.12B | | | PLEASE KNOW, ALL, ELECTRICAL | | | DEVICES/OUTLETS SUCH AS LTS, SD'S | | | RECEPTS, FANS ETC SHALL BE AFCI | | | PROTECTED. | | | ** PLEASE KNOW, AREAS NOW SHOWN AS | | | "OFFICES" ARE UNITS WHICH SEEM TO SHOW | | | POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF | | | THESE AREAS ARE ADAPTABLE FOR | | | RESIDENTIAL USE, THEN AFCI PROTECTION | | | WILL BE REQUIRED FOR THESE ROOMS. | | | | | | 14)NOTE: OK, HOWEVER 2ND PART OF THIS | | | NOTE WAS NOT DONE. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE NFPA-70 11.5.1.1 | | | WHICH REQUIRES THE USE OF SMOKE | | | DETECTORS INSIDE AND OUTSIDE ALL | | | SLEEPING RMS OR ADAPTABLE SLEEPING | | | ROOMS.** PLEASE SEE PREVIOUS NOTES WITH | | | RESPECT TO THE CIRCUITING OF BEDRMS. | | | | | | 15)NOTE:NO, PLEASE SEE SOME CIRCUITS | | | ARE NOT COMEPLETE AT THIS TIME IN | | | DWELLING UNITS AND HOUSE AREAS. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE. PLEASE SEE CIRCUTING | | | MISSING. | | | 215.5 | | | | | | 16)NOTE: OK. | | | | | | 17)NOTE: OK. | | | | | | | | | 18)NOTE: ? NO, PLEASE SEE A NOTE WAS | | | ADDED TO PLANS FOR "NO PLUG-IN TYPE " | | | TRANSFORMERS TO BE PLACED IN CLOSETS | | | ETC, HOWEVER PLEASE CLARIFY THE USE OF | | | THE RECEPTS STILL BEING SHOWN IN THESE | | | AREAS. | | | | | | ** PREVIOUS REVIEW NOTE** | | | PELASE SEE RECEPTS FOR LV TYPE | | | PLUG-IN TRANSFORMERS ARE NOT PERMITTED | | | IN CLOTHES CLOSETS AND LOCATIONS IN | | | CLOSE PROXIMITY OF EASILY IGNITIBLE | | | MATERIALS. | | | PLEASE SEE 110.26,240.24, ETC | | | AS THESE TYPE UNITS CREATE HIGH TEMPS | | | AND HAVE CAUSED FIRES IN THIS | | | JURISDICTION, THESE WILL NOT BE | | | PERMITTED IN THESE CLOSETS DUE TO THE | | | LIFE SAFETY AND PROPERTY HAZARD IT | | | CREATES. | | | | | | 19)NOTE: NO, PLEASE SEE LOWER COMM | | | UNITS, PLEASE SEE UPPER UNITS CONTAIN LT | | | FIXTURE WHICH ARE ALSO PART OF THE | | | NORMAL LIGHTING. | | | LOWER FLR DOES NOT MEET THE EXCEPTION. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE 700.12EWHICH | | | REQUIRESD THE BRANCH CIRCUIT FEEDING THE | | | UNIT EQUIPMENT SHALL BE THE SAME BRANCH | | | CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD | | | OF ANY LOCAL SWITCHES. | | | PLEASE ADJUST CIRCUITING AS SHOWN. | | | | | | 20)NOTE: NO, PLEASE SEE A NOTE WAS ADDED | | | TO PLANS IN LEIU OF THE DETAIL NEEDED | | | AND REQUIRED. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE PROVIDE THE PHOTO-METRICS FOR | | | EXITING STAIR AREAS AS NFPA-101 7.8.1.3 | | | REQUIES A MIN OF 10FT CANDLES (108 LUX) | | | FOR THE ALL AREAS OF WALKING SURFACE IN | | | STAIRS UNDER NORMAL POWER AND IS | | | PERMITTED TO BE LOWERED TO A MIN OF 1FT | | | CANDLE (10.8 LUX) UNDER EMERGENCY | | | CONDITIONS, 7.9.2.2 | | | | | | 21)NOTE: NO, PLEASE SEE SOME FIXTURES | | | ARE STILL SHOWN AS BLANK. ALL FIXTURES | | | SHALL BE SHOWN AT THIS TIME. THESE CAN | | | ALWAYS BE REVISED AT A LATER DATE. | | | | | | **IMPORTANT,PLEASE SEE NEW COMMENTS | | | BEFORE FINAL FIXTURES ARE CHOSEN DUE TO | | | THE ENERGY CODE. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE CORRELATE THE FIXTURE LEGEND | | | WITH PLANS. | | | PLEASE ALSO CORRELATE THE FIXTURE | | | SCHEDULE WITH PLANS AS SOME FIXTURES ARE | | | LABELED ON PLANS , YET NOT ON SCHEDULE. | | | E-1). | | | | | | 22)NOTE: OK. | | | | | | 23)NOTE:NO, PLEASE SEE "EQUIPMENT | | | GROUNDING CONDUCTORS" ARE STIL BEING | | | SHOWN BEFORE THE FIRST MEANS OF | | | DISCONNECT. PLEASE SEE NEW NOTESAS | | | LOCATION WILL CHANGE. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE SEE 250.6, 250.24, NO | | | "EQUIPMENT GROUNDING CONDUCTORS" SHALL | | | BE INSTALLED BEFORE THEFIRST MEANS OF DISCONNETC. | | | PLEASE SEE THESE ARE SHOWN | | | FROM FPL, TO GUTTER, TO METER ETC. | | | | | | 24)NOTE:OK. | | | | | | 25)NOTE: OK. | | | | | | 26)NOTE: NO, PLEASE SUBMIT COMPLETE | | | CALCULATIONS FOR EACH PANEL FOR USE AS | | | SHOWN ON PLANS. | | | PLEASE ALSO SHOW LOADS FOR SERVICE, NONE | | | WERE SUBMITTED. | | | | | | **PREVIOUS REVIEW NOTES ** | | | PLEASE SUBMITLOAD CALCULATIONS FOR | | | ALL AREAS, PANELS, BLDG. PLEASE SEE | | | THESE ARE SHOWN A MIXED | | | USE. PLEASE ADJSUT ACCORDINGLY. | | | PLEASE ALSO INDICATE OF CONTINUOUS LOADS | | | AT 125%. 215.3,230.42, | | | 220.10,220.11,220.13 ETC | | | | | | 27)NOTE: NO, THIS WAS NOT ADDRESSED AND | | | NO DESIGNS, CALCS, CONTROLS ETC WERE | | | SUBMITTED FOR REVIEW. PLEASE SEE MIN | | | CALCULATIONS REQUIRED. | | | ALSO NO ENERGY CALCULATIONS WERE | | | SUBMITTED. | | | | | | ** PREVIOUS REVIEW NOTE ** | | | PLEASE BE SURE TO SEE THE 2004 | | | FBC CHAPTER 13 WITH RESPECT TO THE | | | ENERGY CODE AND DESIGNS. PLEASE KNOW | | | THIS IS A COMMERCIAL BLGD WITH A CHANGE | | | OF OCCUPANCY WHICH WILL REQUIRE ENERGY | | | CODE UPGRADES. | | | | | | **** NEW NOTES **** | | | | | | 28) NOTE: PLEASE SEE ORIGINAL PLANS WERE | | | DONE BY A PE AND NOW PLANS ARE DONE BY | | | ARCHITECT. PLEASE SEE THE SCOPE OF WORK, | | | SIZE ETC REQUIRES THE PLANSTO BE DONE BY | | | AN PE. FS 471.003(2)H. | | | | | | 29) NOTE: PLEASE SEE RISER WHICH | | | INDICATES MORE THAN SEVEN MEANS OF | | | DISCONNECT WHICH IS NOT PERMITTED. | | | 230.2,230.70. | | | PLEASE KNOW A SEPARATE TYPE OF METER | | | BACNK SERVICE MAY BE DONE WITH A MAIN | | | ETC. | | | PLEASE ALSO SEE MANY OF THE TENANT | | | METERS, MAINS ETC ARE LABLED AS "HOUSE" EQUIPEMNT?? | | | PLEASE SEE PANEL "HP" SHOULD BE THE ONLY | | | PANEL, METER AND MAIN LABLED AS "HOUSE". | | | 408.4 | | | 30) NOTE: PLEASE SEE CLOSET LT IN UNIT | | | "C" WHICH DOES NOT MEET 410.8 | | | | | | 30) NOTE: PLEASE SEE SOME UNITS SHOW AND | | | LABEL "TWO" EXHAUST FAN CIRCUITS?? | | | PLEASE ALSO SEE ARC FAULT CIRCUITING. | | | PLEASE SEE MANY OF THESE DO NOT | | | CORRELATE WIHT CIRCUITING SHOWN ON PLANS | | | AND DEVICES. SOME ARE NOT AS LABELED. | | | FBC 106.1.2 ADMIN SECT. | | | | | | 31) NOTE: PLEASE SEE ELECTRICAL PANELS | | | ARE NOW BEING SHOWN IN CLOSETS WHICH IS | | | NOT PERMITTED. PLEASE ALSO SEE ALL MIN | | | CLEARENCES ARE ALSO NOT MET. | | | PLEASE SEE 110.26,240.24D,408.7 ETC. | | | | | | 32) NOTE: PLEASE SEE PLANS MENTIONS | | | "SPRINKLER ROOM" ? WHAT IS THIS AND IS | | | THERE LIGHTING FOR SERVICE OF EQUIPMENT | | | ETC? | | | LS 101 7.8 | | | | | | 33) NOTE: PLEASE SEE COPY OF FS | | | 553.80(2)B) WITH RESPECT TO REPEAT | | | COMMENTS FOR CODE COMPLIANCE AS MANY OF | | | THESE COMMENTS ARE THE SAME AS THE | | | PREVIOUS REVIEW. THIS IS ONLY BEING | | | GIVEN AS A NOTICE AT THIS TIME. | | | | | | | | | | | | ** PLEASE BE SURE TO SEE ANY POSSIBLE | | | COMMENTS FROM OTHER REVIEWER(S) WHICH | | | MAY AFFECT ELECTRICAL PLANS. | | | | | | ** PLEASE BE SURE TO REMOVED ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | | REVISED SHEETS INTO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED | | | SHEETS SEPARATED FROM NEW SETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2006-07-05 00:00:00 | IN ELEC FOR REVIEW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2006-07-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-06-21 |
Time |
21:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-06-18 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2006-07-05 00:00:00 | PLANS WERE PAID FOR ON 6/21/06 WHICH | | | STARTED THE RESUBMITTAL DATE. | | 2006-06-18 00:00:00 | IN ELEC FOR REVIEW. | | | 6/18/06 PLANS ARE OUTFRONT ON"HOLD" | | | WAITING FOR FEES TO BE PAID. | | | PLANS IN LG BINS UNDER "M". | | | THIS WAS THE 2ND NOTICE FOR FEES TO BE | | | PAID. | | | CALLED SPOKE TO RICHARDWATSON | | | AND TOLD HIM PLANS ARE NOT BEING | | | REVIEWED. . DV PALMER. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2006-02-07 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2006-02-06 |
Time |
19:17 |
Sent To |
|
|
| Notes |
| 2006-02-07 00:00:00 | ********* UNSAT ************ | | | | | | | | | ** PLEASE KNOW, PLANS HAVE ONLY BEEN | | | SUBMITTED FOR "PLAN REVIEW" ONLY NAD | | | HAVE NOT BEEN SUBMITTED FOR PERMIT. | | | | | | 1)NOTE: PLEASE SEE THAT ALL DESIGNS AND | | | CODES ARE REFERENCED TO THE CURRENT | | | CODES ADOPTED BY THE STATE OF FLORIDA. | | | PLEASE KNOW, WE ARE CURRENTLY UNDE THE | | | 2004 FLORIDA BLDG CODE. | | | 2002 NFPA-70, 2002 NFPA-72,2003 NFPA-101 | | | PLEASE ADJUST. | | | PLEASE ALSO SEE NOTES BELOW AS ELCTRICAL | | | CODE IS BEING REFERENCED FROM THE 1996 | | | NFPA-70 (NEC). | | | | | | 2)NOTE: PLEASE SEE MISSING INFORMATION | | | AND LICENSE INFORMATION REQUIRED ON | | | TITLE BLOCKS FOR THE ARCHITECTUAL FIRM, | | | ENGINEER AND FIRM? ETC. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE | | | 61G15-23.002, 61G1-16.004 AND FLORIDA | | | STATUES, 481.219, 471.023 . | | | PLEASE KNOW: THIS IS REQUIRED OF ALL | | | TRADES AND FOR ALL SHEETS WHETHER OR NOT | | | COMMENT IS MADE BY OTHER REVIEWER(S). | | | | | | 3)NOTE: PLEASE ALSO PROVIDE A SIGNED, | | | DATED AND SEALED LETTER FOR THE ENGINEER | | | AS SHOWN ON PLANS AFFIRMING THE LEGAL | | | SIGNATURE ON SAID PLANS. PLANS APPEAR TO | | | INDICATE INITIAL(S)? | | | THIS LETTER IS TO BE CORRECTLY | | | NOTORIZED, AND WILL BE PLACED IN OUR | | | SIGNATURE FILE FOR FUTUREREFERENCE. | | | | | | 4)NOTE: PLEASE INDICATE THE ROOF TOP | | | RECEPTS AS GFI OR GFI PROTECTED AS | | | REQUIRED PER 210.8B2 | | | | | | 5)NOTE: PLEASE SEE NO COMMON AREAS SHALL | | | BE FED FROM CIRCUIT DERVIED FROM APTS OR | | | OFFICE UNITS. PLEASE SEE CIRCUITING OF | | | HALL RECEPTS ARE SHOWN TO ONE UNIT. | | | PLEASE SEE 210.25 | | | | | | 6)NOTE: PLEASE SHOW ALL KITCHEN | | | COUNTERSPACE RECEPTS AS GFI/ GFI | | | PROTECTED AS REQUIRED PER 210.8A6 | | | | | | 7)NOTE: PLEASE SEE IF OFFICE UNITS WHICH | | | WILL ALSO BE REQUIRED TO HAVE GFI | | | RECEPTS, EITHER BASE ON POSSIBLE USE | | | CHANGE TO DWELLING UNITS, OR AS REQUIRED | | | PER 210.8B3 | | | | | | 8)NOTE: PLEASE SEE A MIN OF TWO SMALL | | | APPLIANCE CIRCUITS ARE REQUIED PER | | | 210.52B1. | | | | | | 9)NOTE: PLEASE SEE 210.52B1, 210.11C1, | | | 220.16A WHICH REQUIRES EACH TO BE | | | FIGURED AT A MIN OF 1500 VA. | | | | | | 10)NOTE: PLEASE SEE 210.52B1 WHICH | | | REQUIRE STHE ONE OR MORE SMALL APPLIANCE | | | CIRCUITS TO FEED DINING ROOM(S) AND THE | | | LIKE AREAS. PLEASE SEE CIRCUITING | | | FEEDING DINING RM AREA MAY NOT FEED | | | LIVING RMS OR ANY OTHER AREAS. | | | | | | 11)NOTE: PLEASE SEE 210.11C2, 220.16B | | | WHICH REQUIRES A MIN LAUNDRY /WASHER | | | CIRCUIT TO BE 1500VA . | | | | | | 12)NOTE: PLEASE SEE 220.18, 240.4, | | | 310.16, DRYER SAHLL BE FIGURED AT A MIN | | | OF 5KW, 30A, #10 AWG. | | | PLEASE ADJUST AS THESE ARE SHOWN ON A | | | 2-POLE 20A BRKR? | | | | | | 13)NOTE: PLEASE LIST THE REQUIRED ARC | | | FAULT PROTECTED CIRCUITS AS REQUIRD | | | UNDER THE 2002 NEC 210.12B | | | PLEASE KNOW, ALL, ELECTRICAL | | | DEVICES/OUTLETS SUCH AS LTS, SD'S | | | RECEPTS, FANS ETC SHALL BE AFCI | | | PROTECTED. | | | ** PLEASE KNOW, AREAS NOW SHOWN AS | | | "OFFICES" ARE UNITS WHICH SEEM TO SHOW | | | POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF | | | THESE AREAS ARE ADAPTABLE FOR | | | RESIDENTIAL USE, THEN AFCI PROTECTION | | | WILL BE REQUIRED FOR THESE ROOMS. | | | | | | 14)NOTE: PLEASE SEE NFPA-70 11.5.1.1 | | | WHICH REQUIRES THE USE OF SMOKE | | | DETECTORS INSIDE AND OUTSIDE ALL | | | SLEEPING RMS OR ADAPTABLE SLEEPINS | | | ROOMS.** PLEASE SEE PREVIOUS NOTES WITH | | | RESPECT TO THE CIRCUITING OF BEDRMS. | | | | | | 15)NOTE: PLEASE SHOW ALL CIRCUITING ON | | | PLANS AND CORRELATE WITH THE SUBMITTED | | | PANEL SCHEDULE. PLEASE SEE CIRCUTING | | | MISSING. | | | 215.5 | | | | | | 16)NOTE: PLEASE SEE MANY AREA WHERE | | | THERE ARE HAND-DRAWN CHANGES MADE TO | | | PLANS WHICH ARE SIGNED AND SEALED | | | DOCUMENTS. PLEASE KNOW, THIS IS NOT | | | PERMITTED UDNER FS 471.025. | | | | | | 17)NOTE: PLEASE SEE THAT PANEL SCHEDULES | | | INDICATE ALL CONDUCTORSIZES, PER | | | 240.4,310.16. | | | | | | 18)NOTE: PELASE SEE RECEPTS FOR LV TYPE | | | PLUG-IN TRANSFORMERS ARE NOT PERMITTED | | | IN CLOTHES CLOSETS AND LOCATIONS IN | | | CLOSE PROXIMITY OF EASILY IGNITIBLE | | | MATERIALS. | | | PLEASE SEE 110.26,240.24, ETC | | | AS THESE TYPE UNITS CREATE HIGH TEMPS | | | AND HAVE CAUSED FIRES IN THIS | | | JURISDICTION, THESE WILL NOT BE | | | PERMITTED IN THESE CLOSETS DUE TO THE | | | LIFE SAFETY AND PROPERTY HAZARD IT | | | CREATES. | | | | | | 19)NOTE: PLEASE SEE 700.12EWHICH | | | REQUIRESD THE BRANCH CIRCUIT FEEDING THE | | | UNIT EQUIPMENT SHALL BE THE SAME BRANCH | | | CIRCUIT AS THAT SERVING THE NORMAL | | | LIGHTING IN THE AREA AND CONNECTED AHEAD | | | OF ANY LOCAL SWITCHES. | | | PLEASE ADJUST CIRCUITING AS SHOWN. | | | | | | 20)NOTE: PLEASE PROVIDE THE | | | PHOTOMETRICAS FOR EXITING STAIR AREAS AS | | | NFPA-101 7.8.1.3 REQUIES A MIN OF 10FT | | | CANDLES (108 LUX) FOR THE ALL AREAS OF | | | WALKING SURFACE IN STAIRS UNDER NORMAL | | | POWER AND IS PERMITTED TO BE LOWERED TO | | | A MIN OF 1FT CANDLE (10.8 LUX) UNDER | | | EMERGENCY CONDITIONS, 7.9.2.2 | | | | | | 21)NOTE: PLEASE CORRELATE THE FIXTURE | | | LEGEND WITH PLANS. | | | PLEASE ALSO CORRELATE THE FIXTURE | | | SCHEDULE WITH PLANS AS SOME FIXTURES ARE | | | LABELED ON PLANS , YET NOT ON SCHEDULE. | | | E-1). | | | | | | 22)NOTE: PLEASE SEE UNIT "F" AS | | | DISCONNECT FOR WH SEEMS TO BE LABELED AS | | | "RTU". | | | | | | 23)NOTE: PLEASE SEE 250.6, 250.24, NO | | | "EQUIPMENT GROUNDING CONDUCTORS" SHALL | | | BE INSTALLED BEFORE THEFIRST MEANS OF | | | DISCONNETC. PLEASE SEE THESE ARE SHOWN | | | FROM FPL, TO GUTTER, TO METER ETC. | | | | | | 24)NOTE: PLEASE SEE NOTE #3 ON E-7 WHICH | | | REFERENCES THE 1996 NEC. | | | PLEASE ADJUST. | | | | | | 25)NOTE: PLEASE SEE GROUNDING ELECTRODE | | | DETAIL SHALL BE SHOWN IN LEIU OF CODE | | | REFERENCE. | | | PLEASE SEE FBC 1040.2.1, TECHNICAL CODES | | | SHALLL NOT BE REFERENCE IN LEIU OF | | | TERCHNICAL INFORMATION REQUIRED ON | | | PLANS. | | | PLEASE SEE 250.50, FOR MIN CONNECTIONS | | | TO BE MADE. | | | | | | 26)NOTE: PLEASE SUBMITLOAD | | | CALCULATIONS FOR ALL AREAS, PANELS, | | | BLDG. PLEASE SEE THESE ARE SHOWN A MIXED | | | USE. PLEASE ADJSUT ACCORDINGLY. | | | PLEASE ALSO INDICATE OF CONTINUOUS LOADS | | | AT 125%. 215.3,230.42, | | | 220.10,220.11,220.13 ETC | | | | | | 27)NOTE: PLEASE BE SURE TO SEE THE 2004 | | | FBC CHAPTER 13 WITH RESPECT TO THE | | | ENERGY CODE AND DESIGNS. PLEASE KNOW | | | THIS IS A COMMERCIAL BLGD WITH A CHANGE | | | OF OCCUPANCY WHICH WILL REQUIRE ENERGY | | | CODE UPGRADES. | | | | | | ** PLEASE BE SURE TO SEE ANY POSSIBLE | | | COMMENTS FROM OTHER REVIEWER(S) WHICH | | | MAY AFFECT ELECTRICAL PLANS. | | | | | | ** PLEASE BE SURE TO REMOVED ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW | | | REVISED SHEETS INTO COMPLETE SETS FOR | | | REVIEW AND STAMPING. | | | PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED | | | SHEETS SEPARATED FROM NEW SETS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | 2006-02-06 00:00:00 | IN ELEC FOR REVIEW , REVIEW IN PROGRESS. | | | NOTES TO FOLLOW. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
F |
Date |
2007-06-12 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-06-12 |
Time |
14:14 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-06-12 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2007-06-12 14:21:52 | ***DENIED*** | | | | | | PLEASE SEE COMMENTS TAKEN FROM PREVIOUS FIRE REVIEW IN | | | ADDITION TO NEW COMMENTS: | | | | | | 1) PLEASE NOTE THAT THE RESPONSE LETTER INDICATES THAT | | | NFPA 101, SEC. 6.1.14 IS NOW SHOWN ON COVER SHEET. | | | PLEASE CLOUD THAT NOTE AS I WAS UNABLE TO LOCATE. | | | | | | 2) THE WORDING SHOULDL BE FIRE ALARM TO BE UL CERTIFIED | | | FOR CENTRAL STATION SERVICE. | | | | | | 3) FIRE EXTINGUISHERS TO BE 2A-10 B,C RATED, NOT C. | | | PLEASE MAKE CORRECTION AND SHOW ON PLANS. | | | | | | NEW COMMENTS: | | | | | | 1) ADDRESS REQUIRED ON BUILDING TO BE AT LEAST 6" IN | | | HEIGHT AND CONTRASTING TO BACKGROUND. PLEASE SHOW SIZE | | | REQUIREMENTS ON ELEVATIONS. | | | | | | 2) PLEASE SEE ELECTRICAL COMMENTS REGARDING FIRE | | | PROTECTION SYSTEMS. | | | | | | 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2006-11-06 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-11-06 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-11-06 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2006-11-06 14:13:18 | ***PROVISO*** | | | | | | 1) PLEASE NOTE THAT THE RESPONSE LETTER INDICATES THAT | | | NFPA 101, SEC. 6.1.14 IS NOW SHOWN ON COVER SHEET. | | | PLEASE CLOUD THAT NOTE AS I WAS UNABLE TO LOCATE. | | | | | | 2) THE WORDING SHOULDL BE FIRE ALARM TO BE UL CERTIFIED | | | FOR CENTRAL STATION SERVICE. | | | | | | 3) FIRE EXTINGUISHERS TO BE 2A-10 B,C RATED, NOT C. | | | PLEASE MAKE CORRECTION AND SHOW ON PLANS. | | | | | | ALL OTHER COMMENTS HAVE BEEN ADDRESSED. PLANS WILL BE | | | STAMPED WHEN RETURNED FOR OTHER REVIEW CORRECTIONS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW (561) 805-6722 OR 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2006-08-09 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-08-09 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-08-09 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2006-08-09 00:00:00 | ******DENIED****** | | | | | | PLEASE SEE LAST REVIEW COMMENTS THAT | | | DON'T APPEAR TO HAVE BEEN ADDRESSED. | | | PLEASE SEE SOME ADDITIONAL COMMENTS. | | | | | | 1) IN ADDITION TO APPLICABLE BUILDING | | | CODES, NFPA 101, 2003 EDITION SHALL BE | | | REFERENCED. THE APPLICABLE EDITION IS | | | NOT INDICATED ON THE PLANS. | | | | | | 2) MEANS OF EGRESS ILLUSTRATES BUSINESS | | | ONLY, HOWEVER BUILDING MEETS | | | REQUIREMENTS FOR MULTIPLE OCCUPANCY. | | | | | | 3) WORK TO COMPLY WITH NFPA 101, SEC. | | | 6.1.14 MULTIPLE OCCUPANCIES AND ALL | | | OTHER APPLICABLE CODES. | | | | | | 4) PLANS SHOW BUILDING TO BE FULLY FIRE | | | SPRINKLERED BUT NOT MONITORED. FIRE | | | SPRINKLER SYSTEM SHALL BE UL CERTIFIED | | | FOR CENTRAL STATION SERVICE. FIRE | | | SPRINKLER SYSTEMS SHALL BE SUPERVISED. | | | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS | | | REQUIRED FOR FIRE SPRINKLER/FIRE ALARM | | | SYSTEMS. | | | | | | 6) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED. LOCATIONS TO BE SHOWN ON | | | DRAWINGS. | | | | | | 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENT FOR HANDRAILS AND GUARDS. | | | | | | 9) ONE STAIRWELL ON SHT A1.1 APPEARS TO | | | BE OPEN TO THE COMMON AREA. ARE | | | STAIRWELLS RATED ENCLOSURES? | | | | | | 10) SHT A1.0 INDICATES THAT STAIRWELLS | | | ARE 2 HR RATED. THAT BEING THE CASE, ALL | | | ASSOCIATED DOORS SHALL HAVE 1 1/2 HR | | | RATING. | | | | | | 11 OK | | | | | | 12) PLEASE SHOW LOCATIONS OF REQUIRED | | | HARDWIRED SMOKE DETECTORS THAT SHALL BE | | | A MINIMUM OF 3' FROM HVAC DIFFUSERS. | | | | | | 13) PLEASE SHOW SMOKE DETECTOR ON LEGEND | | | TO CLARIFY WHAT IS SHOWN ON DRAWINGS. | | | | | | 14) SMOKE DETECTORS SHALL OPERATE SO | | | THAT ACTIVATION OF ONE WILL OPERATE ALL | | | DETECTORS WITHIN DWELLING UNIT, SUITE OF | | | ROOMS OR SIMILAR AREA. NFPA SEC. | | | 9.6.2.10.3. | | | | | | 15) PLANS INDICATE A FIRE SPRINKLER | | | SYSTEM. A LAYOUT OF THE SYSTEM IS | | | REQUIRED PRIOR TO SEPARATE SUBMITAL. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 | | | | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2006-02-08 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2006-02-08 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2006-02-08 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2006-02-08 00:00:00 | ******DENIED****** | | | | | | PLAN REVIEW ONLY | | | | | | 1) IN ADDITION TO APPLICABLE BUILDING | | | CODES, NFPA 101, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2) MEANS OF EGRESS ILLUSTRATES BUSINESS | | | ONLY, HOWEVER BUILDING MEETS | | | REQUIREMENTS FOR MULTIPLE OCCUPANCY. | | | | | | 3) WORK TO COMPLY WITH NFPA 101, SEC. | | | 6.1.14 MULTIPLE OCCUPANCIES AND ALL | | | OTHER APPLICABLE CODES. | | | | | | 4) PLANS SHOW BUILDING TO BE FULLY FIRE | | | SPRINKLERED BUT NOT MONITORED. FIRE | | | SPRINKLER SYSTEM SHALL BE UL CERTIFIED | | | FOR CENTRAL STATION SERVICE. | | | | | | 5) SEPARATE SHOP DRAWINGS AND PERMITS | | | REQUIRED FOR FIRE SPRINKLER/FIRE ALARM | | | SYSTEMS. | | | | | | 6) CONSTRUCTION, ALTERATION AND | | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | | | 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | | REQUIRED. LOCATIONS TO BE SHOWN ON | | | DRAWINGS. | | | | | | 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | | REQUIREMENT FOR HANDRAILS AND GUARDS. | | | | | | 9) ONE STAIRWELL ON SHT A1.1 APPEARS TO | | | BE OPEN TO THE COMMON AREA. ARE | | | STAIRWELLS RATED ENCLOSURES? | | | | | | 10) SHT A1.0 INDICATES THAT STAIRWELLS | | | ARE 2 HR RATED. THAT BEING THE CASE, ALL | | | ASSOCIATED DOORS SHALL HAVE 1 1/2 HR | | | RATING. | | | | | | 11) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS IN | | | TERMS OF CLASS A,B OR C. | | | | | | 12) PLEASE SHOW LOCATIONS OF REQUIRED | | | HARDWIRED SMOKE DETECTORS THAT SHALL BE | | | A MINIMUM OF 3' FROM HVAC DIFFUSERS. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 7) | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2007-03-26 |
|
|
Cont ID |
|
| Sent By |
spalmer |
Date |
2007-03-26 |
Time |
18:13 |
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2007-03-26 |
Time |
18:13 |
Sent To |
|
|
| Notes |
| 2007-03-27 18:52:45 | TO COMM BOARD # 10 | | 2007-03-26 18:13:47 | WAITING FOR COMM BOARD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2006-09-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-09-25 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-09-25 |
Time |
16:01 |
Sent To |
|
|
| Notes |
| 2006-10-12 17:50:27 | TO "COMM" BD#62 | | 2006-09-25 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2006-06-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-06-22 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-06-22 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2006-07-05 00:00:00 | TO "COMM" BD#6 | | 2006-06-22 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2006-05-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-05-31 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2006-05-31 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2006-06-18 00:00:00 | TO COMM BOARD SPACE #15 | | 2006-05-31 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2006-04-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2006-04-04 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2005-12-28 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2006-01-26 00:00:00 | TO "COMM" BD#32 | | 2005-12-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2007-04-10 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2007-04-10 |
Time |
18:51 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2007-04-10 |
Time |
18:51 |
Sent To |
|
|
| Notes |
| 2007-04-10 19:03:50 | PLAN DENIED | | | 1) PLEASE MARK FLEX SIZES ON THE PLANS . | | | 2) PAGE M-3 GROUND FLOOR GRILL D AT 300 CFM DOES NOT | | | MATCH AIR DEVICE SCHEDULE . | | | 3) PAGE M-3 UPPER FLOOR MECHANICAL SHAFT PLEASE REFER | | | TO SECTION 607.5.5.1 FBC (M) 2004 | | | 4) PLEASE PROVIDE A DTAIL FOR CURB TIE DOWN TO ROOF . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2006-10-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-10-30 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-10-30 |
Time |
08:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2006-08-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2006-08-14 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
pkrauss |
Date |
2006-08-11 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2006-08-14 00:00:00 | DENIED: | | | ORIGINAL REVIEW BY RON REGUEIRO DATED | | | 2/7/06.THE FOLLOWING COMMENTS NEED | | | FURTHER CLARIFICATION: | | | | | | COMMENT 1:DUCT SMOKE DETECTOR SHALL BE | | | INSTALLED IN THE SUPPLY AIR DUCT PER | | | 2004 FMC 606.2.1.PLAN SHEET M-1 THE | | | HVAC UNIT SCHEDULE NOTE 6 STILL | | | INDICATES THE SMOKE DETECTOR IN THE | | | RETURN AIR DUCT.PLEASE REVISE. | | | | | | COMMENT 2:OK | | | COMMENT 3:OK | | | | | | COMMENT 4:PLAN SHEET M-3 THE GROUND | | | FLOOR PLAN INDICATES THE SUPPLY, RETURN | | | AND EF-2 DUCTS PENETRATING THE FLOOR | | | CEILING ASSEMBLY.PLAN SHEET A7.1 & | | | A9.0 INDICATE DUCTS IN A 1HR SHAFT | | | ENCLOSURE AND SHALL COMPLY WITH 2004 FMC | | | 607.5.5.1 OR SHOW COMPLIANCE WITH | | | 2004 FMC 607.6.1, WHERE DUCTS PENETRATE | | | A FIRE-RESISTANCE-RATED FLOOR/CEILING | | | THAT CONNECTS MORE THAN 2 STORIES, A | | | SHAFT ENCLOSURE IS NOT REQUIRED PROVIDED | | | A FIRE DAMPER IS INSTALLED AT THE FLOOR | | | PENETRATION. | | | | | | COMMENT 5:SEE ELECTRICAL COMMENTS. | | | | | | COMMENT 6:OK | | | COMMENT 7:OK | | | COMMENT 8:OK | | | ***************NEW COMMENTS************* | | | COMMENT 9:R/A REQUIRED FROM BEDROOM | | | AREA (ROOM #213). SHOW COMPLIANCE WITH | | | 2004 FMC 601.4. | | | | | | COMMENT 10: PLEASE CLARIFY SUPPLY, | | | RETURN, & EF-1 DUCTS PENETRATING | | | FLOOR/CEILING ASSEMBLY.PLAN SHEET A7.1 | | | & A9.0 INDICATE DUCTS IN 1HR SHAFT. | | | FIRE DAMPERS REQUIRED WHERE DUCTS | | | PENETRATE THE SHAFT ENCLOSURE (2004 FMC | | | 607.5.5.1. OR SHOW COMPLIANCE WITH 2004 | | | FMC 601.4. (SEE COMMENT 4) | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected]. | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2006-02-07 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2006-02-07 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2006-02-07 |
Time |
18:11 |
Sent To |
|
|
| Notes |
| 2006-02-07 00:00:00 | ----------------DENIED----------------- | | | 1)DUCT SMOKE DETECTORS INSTALLED WITH | | | RTUS 1 & 2 SHALL BE IN SUPPLY DUCT | | | RATHER THAN RETURN PER 2004 FBC,M SEC | | | 606.2.1 | | | | | | 2)GRILL TYPES AND CFM RANGES DO NOT | | | MATCH THOSE SHOWN ON AIR DEVICE SCHEDULE | | | | | | 3)PAGE M3 UPPER FLOOR PLAN INDICATES A | | | CARRIER PACKAGE TERMINAL UNIT.THIS | | | EQUIPMENT IS NOT SHOWN ON EQUIPMENT | | | SCHEDULE. | | | | | | 4)PAGE M3 GROUND FLOOR PLAN - BRANCH | | | DUCT FEEDING HALL 100 APPEARS TO BE | | | PENETRATING A RATED PARTITION.A FIRE | | | DAMPER IS NEEDED AT THIS LOCATION.THE | | | BRANCH DUCT ALSO HAS NO SIZE INDICATED | | | ON PLAN. | | | | | | 5)PROVIDE ROOF PLAN SHOWING EF #S AND | | | LOCATIONS.EXHAUST FAN SCHEDULE | | | INDICATES ALL FANS ARE ON ROOF, BUT | | | ELECTRICAL PLAN SHOWS NO PROVISION FOR | | | POWER TO FANS ON ROOF. | | | | | | 6)PAGE M3 DUCT PLAN SHOWS 8X8 EXHAUST | | | DUCT UP TO EF 1 ON ROOF, TWO LOCATIONS. | | | DUCT IS ROUTED IN A RATED SHAFT.HOW | | | AND AT WHAT LOCATION WILL EXHAUST DUCT | | | EXIT THE RATED SHAFT SINCE IT IS LOCATED | | | DIRECTLY BELOW RTUS? | | | | | | 7)PLEASE SHOW FRESH AIR CALCULATIONS PER | | | 2004 FBC,M SEC 403.3 | | | | | | 8)EQUIPMENT REQUIRING SERVICE ON ROOFS | | | HIGHER THAN 16' REQUIRE PERMENANT ACCESS | | | PER 2004 FBC,M SEC 306.5 | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2007-05-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-05-03 |
Time |
06:25 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-05-03 |
Time |
06:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2006-10-28 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-10-28 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-10-28 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2006-10-28 12:55:43 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | | | | 1. OK | | | 2. ENGINEER TAKEN OFF PLANS. | | | 3. ENGINEER TAKEN OFF PLANS. | | | 4. OK | | | | | | 5. SHT A1.1 KITCHEN SINKS IN ROOMS 218 & | | | 220 SHALL BE ACCESSIBLE. SUBMIT A DETAIL | | | SHOWING COMPLIANCE WITH SECTION 11-4.24 | | | AND ALL SUBSECTIONS. | | | ****COMMENT NOT ADDRESSED. NO RESPONSE. | | | ******RESPONSE NOTED, BUT THE FOLLOWING INFORMATION IS | | | REQUIRED TO SHOW COMPLIANCE: | | | A. 11-4.24.4 SINK DEPTH | | | B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH | | | REQUIRED - SHOW CABINET/SINK FRONT ELEVATION - CABINET | | | DOORS NOT ALLOWED) | | | C. 11-4.24.6 EXPOSED PIPES & SURFACES | | | | | | 6. OK | | | | | | 7. THE TOILET ROOMS IN THE BUSINESS AND | | | MERCANTILE OCCUPANCIES SHALL BE | | | ACCESSIBLE. PLEASE SHOW THE FOLLOWING: | | | FOR W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. OK | | | C. 11-4.16.5 FLUSH CONTROLS | | | D. 11-4.16.6 DISPENSERS | | | FOR LAVS: | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | (CLEARANCES NOT SHOWN) | | | B. OK | | | C. OK | | | D. 11-4.19.5 FAUCETS | | | E. OK | | | FOR SHOWERS: | | | A. OK | | | B. OK | | | C. OK | | | D. OK | | | E. OK | | | F. OK | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT THE ABOVE INFORMATION IS | | | STILL REQUIRED. | | | | | | 8. SHT P-4 SANITARY RISER DIAGRAM SHALL | | | BE SUBMITTED IN AN ISOMETRIC FORM, AND | | | SHALL REFLECT THE PIPING AND FIXTURE | | | LAYOUT ON SHEETS P-3 & P-4. SHOW ALL | | | PIPE SIZES. SECTION 106.3.5.1.3 | | | ****RESPONSE NOTED, BUT SANT. RISER | | | DIAGRAM DOES NOT REFLECT THE FLOOR PLANS | | | OF SHEETS P-3 OR P-4. - WASH MACHINE | | | DRAINS REQUIRE A STANDPIPE. SECTIONS | | | 802.4 - RISER SHOWS A 4" STACK"DOWN TO | | | BELOW SLAB, BUT NOT CONNECTED TO THE | | | BUILDING DRAIN. | | | ******RESPONSE NOTED, BUT THE PIPING LAYOUT DOES NOT | | | REFLECT THE FLOOR PLAN IN SOME AREAS. SEE YELLOW | | | HIGHLIGHTES ON SHT P-3 INDICATING AREAS WHERE THE FLOOR | | | PLAN AND THE RISER DO NOT REFLECT. | | | | | | 9.OK | | | 10.OK | | | 11. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | ****NOT ADDRESSED | | | | | | **************NEW COMMENTS************** | | | | | | 1B. OK | | | 2B. OK | | | 3B. OK | | | 4B. OK | | | 5B. OK | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561)805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2006-08-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-08-05 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-08-05 |
Time |
11:51 |
Sent To |
|
|
| Notes |
| 2006-08-05 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | | | | 1. OK | | | 2. ENGINEER TAKEN OFF PLANS. | | | 3. ENGINEER TAKEN OFF PLANS. | | | | | | 4. SUBMIT CALCULATIONS FOR MINIMUM | | | FACILITIES PER TABLES 1004.1.2 AND | | | 403.1. SHOW THE SQUARE FOOTAGE OF EACH | | | TYPE OF OCCUPANCY FOR MERCANTILE, AND | | | BUSINESS. DRINKING FOUNTAINS ARE | | | REQUIRED FOR BUSINESS AND MERCANTILE | | | OCCUPANCIES. TABLE 403.1. | | | ****RESPONSE NOTED ON SHT P-3 INDICATES | | | 1 SERVICE SINK REQUIRED IN THE | | | MERCANTILE AND BUSINESS OCCUPANCIES. | | | THIS IS NOT REQUIRED AND SINKS ARE NOT | | | SHOWN. CALCULATION TO REFLECT THE FLOOR | | | PLAN. - DRINKING FOUNTAINS ARE INDICATED | | | AND REQUIRED IN THE BUSINESS OCCUPANCIES | | | BUT ARE NOT PROVIDED. SHOW DRINKING | | | FOUNTAINS IN THE BUSINESS OCCUPANCIES. - | | | WASH MACHINES ARE REQUIRED IN THE | | | RESIDENTIAL OCCUPANCIES. | | | | | | 5. SHT A1.1 KITCHEN SINKS IN ROOMS 218 & | | | 220 SHALL BE ACCESSIBLE. SUBMIT A DETAIL | | | SHOWING COMPLIANCE WITH SECTION 11-4.24 | | | AND ALL SUBSECTIONS. | | | ****COMMENT NOT ADDRESSED. NO RESPONSE. | | | | | | 6. SHT A1.2 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS. SHOW | | | THE SQUARE FOOTAGE OF THE ROOF. INDICATE | | | THE SQUARE FOOTAGE DRAINED BY EACH | | | PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL | | | VERTICAL WALLS INCLUDING PARAPETS ADDED | | | TO THE CALCULATIONS. SHOW THE LOCATION | | | OF ALL SECONDARY DRAINS/OVERFLOW | | | SCUPPERS. SUBMIT A DETAIL FOR THE | | | CONDUCTOR HEAD SHOWING THE SIZE, HEIGHT | | | & WIDTH, AS WELL AS THE DOWNSPOUT | | | INDICATING SIZE. SECTIONS 1106 & 1107 | | | WITH ALL SUBSECTIONS. | | | ****COMMENT NOT ADDRESSED, NO RESPONSE. | | | | | | 7. THE TOILET ROOMS IN THE BUSINESS AND | | | MERCANTILE OCCUPANCIES SHALL BE | | | ACCESSIBLE. PLEASE SHOW THE FOLLOWING: | | | FOR W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.4 GRAB BARS | | | C. 11-4.16.5 FLUSH CONTROLS | | | D. 11-4.16.6 DISPENSERS | | | FOR LAVS: | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | (CLEARANCES NOT SHOWN) | | | B. 11-4.19.3 CLEAR FLOOR SPACE | | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | | D. 11-4.19.5 FAUCETS | | | E. 11-4.19.6 MIRRORS | | | FOR SHOWERS: | | | A. 11-4.21.2 SIZE AND CLEARANCES | | | B. 11-4.21.3 SEAT | | | C. 11-4.21.4 GRAB BARS | | | D. 11-4.21.5 CONTROLS | | | E. 11-4.21.6 SHOWER UNIT | | | F. 11-4.21.7 CURBS | | | ****NO RESPONSE, COMMENT NOT ADDRESSED. | | | | | | 8. SHT P-4 SANITARY RISER DIAGRAM SHALL | | | BE SUBMITTED IN AN ISOMETRIC FORM, AND | | | SHALL REFLECT THE PIPING AND FIXTURE | | | LAYOUT ON SHEETS P-3 & P-4. SHOW ALL | | | PIPE SIZES. THE KITCHEN SINKS AND WASH | | | MACHINES SHALL NOT DRAIN THROUGH THE | | | HORIZONTAL WET VENTS OF THE BATHROOM | | | GROUPS. ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUPS SHALL CONNECT TO THE | | | WET-VENTED HORIZONTAL BRANCH DRAIN. ANY | | | ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. SECTIONS | | | 106.3.5.1.3 & 909.1. | | | ****RESPONSE NOTED, BUT SANT. RISER | | | DIAGRAM DOES NOT REFLECT THE FLOOR PLANS | | | OF SHEETS P-3 OR P-4. - WASH MACHINE | | | DRAINS REQUIRE A STANDPIPE. SECTIONS | | | 802.4 - RISER SHOWS A 4" STACK"DOWN TO | | | BELOW SLAB, BUT NOT CONNECTED TO THE | | | BUILDING DRAIN. | | | | | | 9. SUBMIT A WATER RISER DIAGRAM | | | ISOMETRIC SHOWING ALL PIPE SIZES, | | | VALVES, AND WATER HAMMER ARRESTORS | | | REQUIRED BY SECTION 604.9. ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURE IN AN | | | "EFFECTIVE RANGE", (NOT IN THE CEILING). | | | SECTION 106.3.5.1.3. | | | ****RESPONSE NOTED, BUT WATER HAMMER | | | ARRESTORS REQUIRED BY SECTION 604.9, | | | (W/M, D/W, AND ICE MAKER IN REF.), SHALL | | | BE SHOWN ON THE RISER. WATER HAMMER | | | ARRESTORS SHALL BE LOCATED NEAR THE | | | FIXTURE IN AN "EFFECTIVE RANGE" NOT IN | | | THE CEILING. - A FULL OPEN VALVE IS | | | REQUIRED AT THE TOP OF EVERY WATER DOWN | | | - FEED PIPE. SECTION 606.1(4). | | | | | | 10. AN RPZV BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE TO THE BUILDING. IF | | | EXISTING INDICATE ON THE WATER RISER | | | DIAGRAM. SECTION 608.13.2. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | 11. SUBMIT A WATER HEATER DETAIL SHOWING | | | THERMAL EXPANSION CONTROL, ALL REQUIRED | | | VALVES, PIPING FOR T/P VALVE DISCHARGE | | | AND EMERGENCY PAN DRAIN INDICATING | | | PIPING MATERIAL AND TERMINATION POINT | | | FOR T/P & PAN DRAIN. SECTION 106.1.1. | | | 12.FLOOR DRAINS ARE NOT AN APPROVED | | | INDIRECT WASTE RECEPTOR. IF DRAINING T/P | | | AND PAN DRAIN IN HEATER ROOM, A FLOOR | | | SINK OR HUB DRAIN WILL BE REQUIRED. | | | SECTIONS 802.3 AND 802.3.2. | | | ****NO RESPONSE, NOT ADDRESSED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | ****NOT ADDRESSED | | | | | | **************NEW COMMENTS************** | | | | | | 1B. FOR ACCESSIBLE FIXTURES: DOORS SHALL | | | NOT SWING INTO THE CLEAR FLOOR SPACE | | | REQUIRED FOR ANY FIXTURE. (SHOW ALL | | | CLEAR FLOOR SPACES FOR LAVS, W/C'S, | | | SHOWERS, KITCHEN SINKS ETC.). SECTION | | | 11-4.22.2 | | | | | | 2B. PEDISTAL LAVS ARE NOT APPROVED FOR | | | ACCESSIBLE TOILET AND BATH ROOMS. SEE | | | FIG 11-31 FOR REQUIRED CLEARANCES. | | | | | | 3B. SHT A7.1 FINISH SCHEDULE DOES NOT | | | INDICATE FLOOR FINISH FOR BATHROOMS 217 | | | OR 221. INDICATE FLOOR AND BASE FINISH | | | TO COMPLY WITH SECTION 1210.1 (BLDG). | | | | | | 4B. SHT A8.2 FINISH SCHEDULE DOES NOT | | | REFLECT FINISH SCHEDULE ON SHT A7.1. | | | PLEASE CORRELATE SCHEDULES. - WALL | | | FINISH, (LATEX PAINT), DOES NOT MEET THE REQUIREMENT TO | | | BE NONABSORBENT PER | | | SECTION 1210.2. | | | | | | 5B. SHT P-1 PLUMBING NOTES #1. FBC-2004 | | | NOT VIRGINA CODE COMPLIANCE REQUIRED. | | | CHANGE REFERENCE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561)805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2006-03-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2006-03-09 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2006-03-09 |
Time |
08:02 |
Sent To |
|
|
| Notes |
| 2006-03-09 00:00:00 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | | | | 1. SHT CS, CODE IN EFFECT AT THIS TIME | | | IS THE FBC-2004. PLEASE CHANGE CODE | | | REFERENCE. | | | 2. ALL SHEETS, ENGINEER SHALL SEAL | | | SHEETS WITH REQUIRED SEAL. (SEE ATTACHED | | | SHEET FROM THE FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS). | | | 3. ALL SHEETS, ENGINEERS SHALL LEGIBLY | | | INDICATE THEIR NAME, ADDRESS AND LICENSE | | | NUMBER, AS WELL AS, THE NAME, ADDRESS, | | | AND CERTIFICATE OF AUTHORIZATION NUMBER | | | ON EACH SHEET. FAC 61G15-23.002(2) & FS | | | 471.025. | | | 4. SUBMIT CALCULATIONS FOR MINIMUM | | | FACILITIES PER TABLES 1004.1.2 AND | | | 403.1. SHOW THE SQUARE FOOTAGE OF EACH | | | TYPE OF OCCUPANCY FOR MERCANTILE, AND | | | BUSINESS. DRINKING FOUNTAINS ARE | | | REQUIRED FOR BUSINESS AND MERCANTILE | | | OCCUPANCIES. TABLE 403.1 | | | 5. SHT A1.1 KITCHEN SINKS IN ROOMS 218 & | | | 220 SHALL BE ACCESSIBLE. SUBMIT A DETAIL | | | SHOWING COMPLIANCE WITH SECTION 11-4.24 | | | AND ALL SUBSECTIONS. | | | 6. SHT A1.2 SUBMIT CALCULATIONS FOR | | | PRIMARY AND SECONDARY ROOF DRAINS. SHOW | | | THE SQUARE FOOTAGE OF THE ROOF. INDICATE | | | THE SQUARE FOOTAGE DRAINED BY EACH | | | PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL | | | VERTICAL WALLS INCLUDING PARAPETS ADDED | | | TO THE CALCULATIONS. SHOW THE LOCATION | | | OF ALL SECONDARY DRAINS/OVERFLOW | | | SCUPPERS. SUBMIT A DETAIL FOR THE | | | CONDUCTOR HEAD SHOWING THE SIZE, HEIGHT | | | & WIDTH, AS WELL AS THE DOWNSPOUT | | | INDICATING SIZE. SECTIONS 1106 & 1107 | | | WITH ALL SUBSECTIONS. | | | 7. THE TOILET ROOMS IN THE BUSINESS AND | | | MERCANTILE OCCUPANCIES SHALL BE | | | ACCESSIBLE. PLEASE SHOW THE FOLLOWING: | | | FOR W/C'S: | | | A. 11-4.16.2 CLEAR FLOOR SPACE | | | B. 11-4.16.4 GRAB BARS | | | C. 11-4.16.5 FLUSH CONTROLS | | | D. 11-4.16.6 DISPENSERS | | | FOR LAVS: | | | A. 11-4.19.2 HEIGHT & CLEARANCES | | | (CLEARANCES NOT SHOWN) | | | B. 11-4.19.3 CLEAR FLOOR SPACE | | | C. 11-4.19.4 EXPOSED PIPES & SURFACES | | | D. 11-4.19.5 FAUCETS | | | E. 11-4.19.6 MIRRORS | | | FOR SHOWERS: | | | A. 11-4.21.2 SIZE AND CLEARANCES | | | B. 11-4.21.3 SEAT | | | C. 11-4.21.4 GRAB BARS | | | D. 11-4.21.5 CONTROLS | | | E. 11-4.21.6 SHOWER UNIT | | | F. 11-4.21.7 CURBS | | | 8. SHT P-4 SANITARY RISER DIAGRAM SHALL | | | BE SUBMITTED IN AN ISOMETRIC FORM, AND | | | SHALL REFLECT THE PIPING AND FIXTURE | | | LAYOUT ON SHEETS P-3 & P-4. SHOW ALL | | | PIPE SIZES. THE KITCHEN SINKS AND WASH | | | MACHINES SHALL NOT DRAIN THROUGH THE | | | HORIZONTAL WET VENTS OF THE BATHROOM | | | GROUPS. ONLY THE FIXTURES WITHIN THE | | | BATHROOM GROUPS SHALL CONNECT TO THE | | | WET-VENTED HORIZONTAL BRANCH DRAIN. ANY | | | ADDITIONAL FIXTURES SHALL DISCHARGE | | | DOWNSTREAM OF THE WET VENT. SECTIONS | | | 106.3.5.1.3 & 909.1. | | | 9. SUBMIT A WATER RISER DIAGRAM | | | ISOMETRIC SHOWING ALL PIPE SIZES, | | | VALVES, AND WATER HAMMER ARRESTORS | | | REQUIRED BY SECTION 604.9. ARRESTORS | | | SHALL BE LOCATED NEAR THE FIXTURE IN AN | | | "EFFECTIVE RANGE", (NOT IN THE CEILING). | | | SECTION 106.3.5.1.3. | | | 10. AN RPZV BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE TO THE BUILDING. IF | | | EXISTING INDICATE ON THE WATER RISER | | | DIAGRAM. SECTION 608.13.2. | | | 11. SUBMIT A WATER HEATER DETAIL SHOWING | | | THERMAL EXPANSION CONTROL, ALL REQUIRED | | | VALVES, PIPING FOR T/P VALVE DISCHARGE | | | AND EMERGENCY PAN DRAIN INDICATING | | | PIPING MATERIAL AND TERMINATION POINT | | | FOR T/P & PAN DRAIN. SECTION 106.1.1. | | | 12.FLOOR DRAINS ARE NOT AN APPROVED | | | INDIRECT WASTE RECEPTOR. IF DRAINING T/P | | | AND PAN DRAIN IN HEATER ROOM, A FLOOR | | | SINK OR HUB DRAIN WILL BE REQUIRED. | | | SECTIONS 802.3 AND 802.3.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | | BER, WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561)805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
N |
Date |
2007-04-23 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2007-04-23 |
Time |
08:35 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2007-04-23 |
Time |
08:35 |
Sent To |
|
|
| Notes |
| 2007-04-23 08:36:26 | ZONING REVIEW: NOT REQUIRED | | | | | | - PRODUCT SUBMITTALS ONLY; NO DRAWINGS FOR ZONING | | | REVIEW | | | - GROUND FLOOR RETAIL IS REQUIRED; SECOND FLOOR MAY BE | | | COMMERCIAL OR RESIDENTIAL OR MIX OF THOSE USES | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2006-10-31 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2006-10-31 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2006-10-31 |
Time |
15:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2006-07-11 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2006-07-11 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2006-07-11 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2006-07-11 00:00:00 | 07-11-06 | | | | | | **PLEASE NOTE THAT COMMENTS FROM | | | PREVIOUS REVIEW ARE STILL TO BE | | | ADDRESSED** | | | | | | MJF |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2006-04-04 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2006-04-04 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2006-04-04 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2006-04-04 00:00:00 | P&Z NOTES: | | | | | | SHEET A1.1 - SHOW PROPERTY LINE AND/OR | | | VERIFY AIR RIGHTS EASEMENT FOR OLIVE | | | BALCONIES | | | SHEET A2.0 - BLADE SIGNS ALLOWED AT | | | 4'-0" MAX PROJECTION X 3'-0" MAX HEIGHT; | | | MUST BE LOCATED MINIMUM OF 2'-0" FROM | | | EDGE OF BUILDING; | | | SHEET A4.0 = INDICATE TYPE OF METAL | | | GRILLE TO BE USED FOR BALCONY INFILL | | | | | | MJF |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |