Plan Review Details - Permit 05121124
Plan Review Stops For Permit 05121124
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-06-25 Cont ID  
Sent By lmartine Date 2007-06-25 Time 15:07 Rev Time 0.00
Received By lmartine Date 2007-06-25 Time 15:07 Sent To  
Notes
2007-06-25 17:03:15BUILDING REVIEW COMMENTS
  
 FROM PREVIOUS REVIEW DATED 10/19/06,
  
 #2- OK
 #5- OK
 #6- HOLLOW METAL DOOR, N.O.A. WAS NOT PROVIDED. #7- ALL
 PRODUCT APPROVALS SUBMITTED SHALL BE REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD.
 #11- OK
  
 NEW COMMENTS:
  
 1A- IDENTIFY AND SELECT APPROPRIATE ASSEMBLY FROM YOUR
 ROOF PRODUCT APPROVAL.
 2A- OK
  
 RESPONCE #13, THE NORTH WALL DOES REQUIRE A 1HR RATING
 ACCORDING TO TABLE 602, AS PER BUILDING CODE
 COMMENTARY, SEPERATION DISTANCES SHALL ONLY RECEIVE 50%
 OF RIGHT-OF-WAY, 7' VS. 14'.
  
  
  
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-10-19 Cont ID  
Sent By alange Date 2006-10-19 Time 10:22 Rev Time 0.00
Received By alange Date 2006-10-18 Time 11:45 Sent To  
Notes
2006-10-19 11:03:30DENIED
  
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 ALL WINDOWS, EXTERIOR DOORS,AND ROOFING.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 11.DOOR TO SECOND FLOOR WEST STAIRS OK.AFTER
 RECEIVING THE SURVEY THE DOOR TO THE SPRINKLER ROOM IS
 ALSO OPENING OVER THE PROPERTY LINE.
  
  
 FROM LAST REVIEW:
 A:SHOW PRESSURES FOR DOORS AND
 WINDOWS.
  
 NEW COMMENTS:
 1A.ROOFING NOTES AND DETAILS INTERMIX EXISTING ROOF
 AND NEW ROOF.PLEASE CLARIFY AND SUBMIT THE
 APPROPRIAT PRODUCT APPROVALS WITH THE ROOFING ASSEMBLY
 SELECTED.
  
 2A.GAURDRAIL LOADS SECTION LISTED IS NOT CORRECT FBC
 1607.7 ON PAGE A 4.0
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-17 Cont ID  
Sent By alange Date 2006-07-17 Time 15:40 Rev Time 0.00
Received By alange Date 2006-07-17 Time 11:08 Sent To  
Notes
2006-07-17 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE RE-RECORDED IF
 THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 WINDOWS, EXTERIOR DOORS, STORE FRONT
 SYSTEM, LINTELS, ROOFING AND STRAPS AND TIE-DOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.FIRE DOORS AT 2HR WALLS SHALL BE
 1.5HR.FBC 2004 TABLE 715.3
 SHOW RATED WALLS AND THE APPROPRIATE
 RATED DOORS.
 ALL DOORS SHALL COMPLY WITH THIS
 SECTION.DOORS TO COMMON HALLWAY DO NOT
 SHOW A RATING.
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
 B. SHOW COMPLIANCE WITH 707.5.1
  
 10.INCLUDE A LIFE SAFTEY PLAN SHOWING
 PATH OF TRAVEL AND TRAVEL DISTANCE
 COMPLYING WITH 1015.1.MOST REMOTE
 POINT.
  
 11.SECOND FLOOR STAIRWAY EXIT SHALL
 NOT EXIT TO ALLEY WAY.BUT SHALL EXIT
 ON TO THE SAME PROPERTY.SUBMIT A SITE
 PLAN.WEST STAIRWAY DOES NOT SHOW A
 FIRST FLOOR EXIT ON FLOOR PLAN.
  
 13.BASED ON FBC TABLE 602 THE NORTH
 WALL SHALL HAVE A 1HR. FIRE RATING.
 DOORS AND WINDOWS SHALL BE RATED 3/4 HR.
 FBC 715.3 AND FBC 715.4.SINCE LARGE
 MISSLE IMPACT PROTECTION IS REQUIRED,
 LARGE MISSLE IMPACT GLASS MAY HAVE TO BE
 USED WITH ROLL UP FIRE SHUTTERS
 COMPLYING WITH FBC 715.3.9.
  
 NEW COMMENT:
 A:SHOW PRESSURES FOR DOORS AND
 WINDOWS.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-04 Cont ID  
Sent By alange Date 2006-04-04 Time 08:29 Rev Time 7.00
Received By alange Date 2006-03-31 Time 14:10 Sent To  
Notes
2006-03-31 00:00:00DENIED
 ITEMS REQUIRED WHEN SUBMITTED FOR
 PERMITTING:
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3. ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 4.SUBMIT TWO COPIES OF ENERGY CALCS
 PER 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 WINDOWS, EXTERIOR DOORS, STORE FRONT
 SYSTEM, LINTELS, ROOFING AND STRAPS AND
 TIE-DOWNS.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.FIRE DOORS AT 2HR WALLS SHALL BE
 1.5HR.FBC 2004 TABLE 715.3
 ALL DOORS SHALL COMPLY WITH THIS
 SECTION.EXIT PASSAGE WAY WALLS RATED
 1HR SHALL HAVE A ONE HOUR DOOR.
  
  
 9.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
 A. SHOW COMPLIANCE WITH 703.2.1
 B. SHOW COMPLIANCE WITH 707.5.1
  
 10.INCLUDE A LIFE SAFTEY PLAN SHOWING
 PATH OF TRAVEL.
  
 11.SECOND FLOOR STAIRWAY EXIT SHALL
 NOT EXIT TO ALLEY WAY.BUT SHALL EXIT
 ON TO THE SAME PROPERTY.SUBMIT A SITE
 PLAN.INCLUDE INFORMATION ON ADJACENT
 ATTACHED BUILDING TO THE SOUTH SIDE
 INCLUDING BUILDING HEIGHT.
  
 12.FIRE ALARM SYSTEM IN ACCORDANCE
 WITH 9.7 SHALL BE PROVIDED WHEN THE
 BUILDING IS 2 OR MORE STORIES IN HEIGHT.
 FBC 907.2.2
  
 13.INCLUDE SEPERATION DISTANCES
 BETWEEN ADJACENT BUILDINGS SO THAT TABLE
 602 CALCULATIONS CAN BE MADE.
  
 14.SHOW PARAPET DETAIL SHOWING
 COPLIANCE WITH EXTERIOR WALL RATING IN
 FBC 704.11
  
 15.DOOR 218, SEE FBC CHAPTER 11. MIN
 18" CLEARANCE REQUIRED AT THE LATCH SIDE
 OF THE DOOR.
  
 16.SPECIFY INTERIOR FINISH
 CLASSIFICATIONS FOR CEILINGS AND WALLS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-04-15 Cont ID  
Sent By dpalmer Date 2007-04-15 Time 12:38 Rev Time 0.00
Received By dpalmer Date 2007-04-15 Time 09:23 Sent To  
Notes
2007-04-15 12:39:07********* UNSAT4THREVIEW ***********
  
 ** PLEASE SEE SOME ITEMS FROM THE THREE PREVIOUS
 REVIEWS ARE STILL IN NEED OF ADDRESSING. PLEASE SEE NEW
 COMMENTS DUE TO CHANGES IN PLANS WHICH DECREASED ON OF
 THE UNITS UPSTAIRS AND CHANGED FROM COMMERCIAL OFFICE
 USE TO RESIDENTIAL.
  
 ** IMPORTANT**
 THE OCCUPANCY OF UNITS ON SECOND FLOOR GREATLY AFFECTS
 MANY COMMENTS FOR CODE COMPLIANCE , WHETHER OR NOT THEY
 ARE RESIDENTIAL OR COMMERCIAL OFFICES.
  
  
 1) NOTE:PLEASE SEE NOTE #27 FROM THE PREVIOUS THREE
 REVIEWS FOR COMPLIANCE WITH THE 2004 FBC CHAPTER 13.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT CORRELATE
 WITH PLANS, AND FIXTURE LEGENDS FOR THE NUMBER OF
 FIXTURES, TYPES, WATTAGES ETC. THERE ARE MULTIPLE ITEMS
 WHICH DO NOT MATCH.
 PLEASE SEE THE CONTROLS ON THE CALCULATIONS INDICATE
 MANUAL ON/OFF WHEN AUTOMATED CONTROLS ARE REQUIRED FOR
 CERTAIN AREAS.
 PLEASE SEE NEW RESIDENTIAL UNITS FALL UNDER SEPARATE
 REQUIREMENTS.
 PLEASE SEE NO MAXIMUM TIMES ARE SHOWN FOR DEVICES.
 PLEASE SEE MULTIPLE LOCATIONS WHICH DO NOT INDICATE
 EITHER TIMER TYPE OR OCCUPANCY TYPE DEVICES?
 NOTES LOCATED ON SOME ITEMS, HOWEVER SOME OF THE NOTES
 LIKE NOTES #1 AND #2 INDICATE LIGHTING ON THE INSIDE
 BEING CONTROLLED BY A PHOTO-CELL ALONG WITH OUTSIDE
 LIGHTING?
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1.1, 13-415.2
 PLEASE SEE INPUT DATA REPORT WHICH DOES NOT SEEMS
 COORDINATE WITH TOTAL ALLOWANCE ON FRONT SECTION OF
 CALCULATIONS.
 ** PLEASE SEE NOTES FOR EGRESS STAIRS AND CORRIDORS.
  
 2) NOTE: PLEASE SEE NEW SHEET E-8 NOW SUBMITTED FOR
 FIRE ALARM SYSTEM WHICH WAS NOT ON PREVIOUS PLANS.
 PLEASE SEE ELECTRICAL PLANS INDICATE THE FAAP WITH
 NOTES BEING THE FACP? PLEASE SEE E-8 WHICH INDICATES
 THE FACP LOCATED INSIDE THE TENANT *A* WHICH IS NOT
 PERMITTED. THIS DOES NOT CORRESPOND TO THE E-8 SHEET.
 PLEASE CLARIFY THE DESIGNATED DEDICATED *SMOKE
 DETECTOR* CIRCUIT ON HP WHEN THESE DEVICES SHOULD BE ON
 THE FACP??
 PLEASE SEE NOTES ALSO MENTIONS A COMPLETE FIRE
 SPRINKLER SYSTEM WHICH IS TO BE INSTALLED HOWEVER NO
 BASE DESIGN PLANS WERE SUBMITTED. PLEASE SEE FIRE
 MARSHAL REVIEW NOTES AND SEE FBC 106.3.5.1.2 AS THE
 BASE PLANS SHALL SHOW THE REQUIRED PROPOSED SYSTEM
 ALTHOUGH THE FS WILL BE UNDER A SEPARATE PERMIT. PLEASE
 SEE THAT THE DEVICES FOR HORNS AND STROBES SHALL MEET
 FBC 11-4.28.1,.2 AND .3(4).
 PLEASE INDICATE ALL OF THE MINIMUM LEVELS IN AREAS FOR
 ADA COMPLIANCE.
 PLEASE KNOW, AS THE REQUIRED VERTICAL ACCESSIBILITY HAS
 NOT YET BEEN DETERMINED, THIS MAY REQUIRE OTHER DEVICES
 TO BE INCREASED.
  
 3) NOTE: PLEASE SEE THE PLANS SEEM TO INDICATE COMMON
 AREA ROOMS/CLOSETS WHICH ARE ONLY ACCESSIBLE FROM THE
 TENANT SPACE. THIS WAS BROUGHT UP IN THE PREVIOUS
 MEETING WITH THE DESIGNER. PLEASE COORDINATE WITH NOTES
 ABOVE FOR LOCATION OF *HOUSE* EQUIPMENT AND ACCESS TO
 THESE LOCATIONS.
 IF THESE ROOMS ARE PART OF HOUSE EQUIPMENT, POWER ETC,
 THEN THESE MUST BE ACCESSED FROM OTHER THAN INSIDE THE
 TENANT SPACE.
  
 4) NOTE: PLEASE SEE THE LOCATION OF THE *HP* PANEL
 WHICH IS BEING SHOWN IN THE FIRE RATED EGRESS CORRIDOR
 AND EXIT STAIRS.
 PLEASE SEE THIS WILL BE NOTED FROM BUILDING AND FIRE
 REVIEW FOR EXACT LOCATION WHICH IS NOT PERMITTED IN
 RATED STAIR/EXIT/EXIT ACCESS ETC.
 PLEASE SEE FBC CHAPTER 10 FOR ITEMS WHICH ARE PERMITTED
 IN THESE AREAS MAY ONLY BE PERTAINING TO THE ELECTRICAL
 EQUIPMENT AND DEVICES FOR THESE AREAS.
  
 5) NOTE: PLEASE SEE NOTE #8 FROM ALL PREVIOUS REVIEWS
 WHICH GAVE SECTIONS 210.52B1, 220.16 AND 210.11C1 FOR
 THE MINIMUM OF TWO OR MORE SMALL APPLIANCE CIRCUITS AND
 WHAT IS PERMITTED TO BE ON THESE CIRCUITS.
 PLEASE SEE PLANS WHICH STILL INDICATE DINING ROOM
 RECEPTACLE CIRCUITS WHICH ARE NOT FIGURED AT MINIMUM VA
 AS REQUIRED PER 210.11C1 AND 220.16.
 PLEASE SEE PLANS INDICATE SOME OF THESE AREAS WHICH
 CONTAIN SEVERAL CIRCUITS WHICH ARE BEING SHOWN AS
 GENERAL RECEPTACLE CIRCUITS.
 PLEASE SEE E-17, E-2, C-23, D-2, C-23 ETC.
 PLEASE SEE NEXT COMMENT WITH RESPECT TO 210.52 WHICH IS
 MISSING SOME RECEPTACLES AS REQUIRED IN BREAKFAST/BAR
 AREAS FOR WALL SPACE AND ALSO MISSING DEVICES FOR WALL
 SPACES IN DINING AREAS.
 ** LOADS ON THESE CIRCUITS SHALL BE 1500VA, NO OTHER
 AREAS/DEVICE UNLESS LISTED AS AREAS OF THE LIKE AS
 STATED IN THE CODE ARE PERMITTED ON THESE CIRCUITS. * *
 PLEASE SEE RANGE HOOD J-BOXES WHICH ARE BEING SHOWN ON
 THE SMALL APPLIANCE CIRCUITS WHICH IS NOT PERMITTED. A
 RANGE HOOD IS NOT ONE OF THE PERMITTED APPLIANCES WHICH
 MAY BE ON THE SM APPL. CIRCUITS.
  
 6) NOTE:PLEASE SEE SEVERAL AREAS FOR MISSING
 RECEPTACLES PER 210.52.
 PLEASE SEE UNIT E WHICH IS MISSING DEVICES WITHIN 6FT
 OF DOORWAYS, MORE THAN 12FT OF WALL WITHOUT A DEVICE.
 PLEASE ALSO SEE UNIT *C* AND *D* DINING AREA WALL WHICH
 HAS MORE THAN 12FT OF WALL WITHOUT A DEVICE.PLEASE
 SEE LIVING ROOM AREA IN UNIT E. PLEASE SEE ONE SET OF
 PLANS ARE REDLINED WITH SOME OF THESE LOCATIONS.
  
 7) NOTE: PLEASE SEE UNIT E WHICH SHOWS A WATER HEATER
 DESIGNATION LOCATED IN THE MIDDLE OF THE KITCHEN
 COUNTER SPACE??
 PLEASE ALSO SEE THE PLANS INDICATE THE WATER HEATER IN
 A CLOSET?
 PLEASE SEE 422.17 AS THE WATER HEATER IS BEING SHOWN IN
 A STORAGE CLOSET WHICH CONTAINS EASILY IGNITABLE
 MATERIALS.* EACH ELECTRICALLY HEATED APPLIANCE THAT IS
 INTENDED BY SIZE, WEIGHT, AND SERVICE TO BE LOCATED IN
 A FIXED POSITION SHALL BE PLACED SO AS TO PROVIDE AMPLE
 PROTECTION BETWEEN THE APPLIANCE AND ADJACENT
 COMBUSTIBLE MATERIAL*.
  
 8) NOTE: PLEASE SEE 410.8 AS THE LIGHT FIXTURE IN THE
 CLOSET IN UNIT *C* DOES MEET THE MINIMUM CLEARANCES ARE
 REQUIRED.
 PLEASE RELOCATE OR REMOVE.
  
 9) NOTE: PLEASE SEE UNIT E- WHICH IS MISSING THE
 STOVE/RANGE CIRCUITING FROM PLANS.
 PLEASE ALSO SUBMIT THE MANUFACTURE INFORMATION SPECS ON
 THIS STOVE/RANGE. THE SIZE AND LOAD FOR WHAT IS BEING
 SHOWN ON PLANS AS A FULL SIZE APPLIANCE SEEMS TO BE
 VERY LOW.
 PLEASE SEE THE TABLES IN 220.19.
 ** PLEASE ALSO VERIFY PLANS AS THEY ARE INDICATING GFCI
 PROTECTION FOR THE RANGE/STOVE??
  
 10) NOTE: PLEASE INDICATE THE AIC RATINGS FOR ALL
 SERVICE EQUIPMENT. MAINS, PANELS AND BREAKERS. PLEASE
 SEE PANELS DO INDICATE RATINGS AT 22K, HOWEVER IF SHOWN
 AS 22K FOR THE ENTIRE PANEL AS FULLY RATED, THEN THIS
 WOULD MEAN ALL OF THE BRANCH BREAKERS WOULD BE 22K
 RATED. IS THIS WHAT IS REALLY INTENDED?
  
 11) NOTE: PLEASE COMPLETE THE PHOTO-METRICS AS THE
 LEVELS ARE NOT READABLE ON PLANS SUBMITTED FOR WALKWAY
 AREAS AND STAIRS.
 PLEASE CLARIFY HOW THE PHOTO-METRICS INDICATE ONE TYPE
 OF FIXTURE BEING FIGURED FOR LIGHTING LEVELS, YET THE
 LIGHTING PLANS AND FIXTURE LEGEND INDICATE A DIFFERENT
 TYPE OF FIXTURE? IN FACT THE LIGHTING FIXTURES WHICH
 ARE NOTED TO BE USED ON PHOTO-METRICS ARE NOT EVEN
 LISTED ON THE FIXTURE LEGEND?
 PLEASE SHOW AND INDICATE THE MINIMUM LEVELS FOR
 SECTIONS BELOW, PLEASE SEE THE COMMENTS WITH RESPECT TO
 EGRESS LIGHTING AND CONTROLS FOR CHAPTER 13. PLEASE SEE
 SECTION 1006.1.2 OF THEFBC 2004 PLEASE SEE THE
 FOLLOWING TEXT WHICH WAS EXTRACTED DIRECTLY FROM
 NFPA-101.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTER 11
 THROUGH CHAPTER 42. FOR THE PURPOSES OF THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES, CORRIDORS, RAMPS, ESCALATORS, AND
 PASSAGEWAYS LEADING TO AN EXIT. FOR THE PURPOSES OF
 THIS REQUIREMENT, EXIT DISCHARGE SHALL INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT PASSAGEWAYS LEADING TO A
 PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY
 TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA
 VALUES HEREIN SPECIFIED.
 7.8.1.2.2 AUTOMATIC, MOTION SENSOR?TYPE LIGHTING
 SWITCHES SHALL BE PERMITTED WITHIN THE MEANS OF EGRESS,
 PROVIDED THAT THE SWITCH CONTROLLERS ARE EQUIPPED FOR
 FAIL-SAFE OPERATION, THE ILLUMINATION TIMERS ARE SET
 FOR A MINIMUM 15-MINUTE DURATION, AND THE MOTION SENSOR
 IS ACTIVATED BY ANY OCCUPANT MOVEMENT IN THE AREA
 SERVED BY THE LIGHTING UNITS.
 7.8.1.3* THE FLOORS AND OTHER WALKING SURFACES WITHIN
 AN EXIT AND WITHIN THE PORTIONS OF THE EXIT ACCESS AND
 EXIT DISCHARGE DESIGNATED IN 7.8.1.1 SHALL BE
 ILLUMINATED AS FOLLOWS:
 (1)DURING CONDITIONS OF STAIR USE, THE MINIMUM
 ILLUMINATION FOR NEW STAIRS SHALL BE AT LEAST 108 LUX
 (10 FT-CANDLE), MEASURED AT THE WALKING SURFACES. (2)
 THE MINIMUM ILLUMINATION FOR FLOORS AND WALKING
 SURFACES, OTHER THAN NEW STAIRS, SHALL BE TO VALUES OF
 AT LEAST 10.8 LUX (1 FT-CANDLE), MEASURED AT THE
 FLOOR.
 * PLEASE ALSO SEE SECTION 7.9.2.2. WHERE THE FAILURE OF
 ANY SINGLE DEVICE OR LIGHTINGSHALL NOT LEAVE ANY ONE
 EGRESS AREA IN TOTAL DARKNESS.
  
 12) NOTE: PLEASE COORDINATE ALL CIRCUITS. PLEASE SEE
 CIRCUITING FOR LIGHTING IN UNIT E, WHICH INDICATES E-19
 FOR BEDROOM LIGHTING AND LIGHTING IN OTHER AREAS, YET
 THE PANEL SCHEDULE SHOWS THIS CIRCUIT AS THE CIRCUIT
 FOR THE WASHER??
 PLEASE SEE 210.12 FOR AFCI PROTECTION IN THE 2002 NEC>
  
 13) NOTE: PLEASE CLARIFY THE NOTES ON THE LIGHTING
 PLANS FOR THE RESIDENTIAL UNITS ON THE SECOND FLOOR
 WHICH SEEM TO INDICATE LIGHTS FOR COMMERCIAL SPACE??
 PLEASE SEE NOTE #1 FOR E UNIT WHICH MENTIONS EMERGENCY
 LIGHTING ETC??
 FBC 106.1.2
 SEE E-6.
  
 14) NOTE: PLEASE CLARIFY RISER AS THE RISER SHOWS ONE
 LARGER GUTTER/TROUGH, YET PLANS INDICATE A DOOR LOCATED
 IN THE MIDDLE OF THE GUTTER. PLEASE KNOW IF THE WALL
 SPACE IN NOT CONTINUOUS THEN SOME THING MUST BE DONE
 WITH THE RISER AND ADJUSTED TO INCLUDE FEEDERS TO
 METERS/DISCONNECTS.
 AS SHOWN, THIS IS NOT POSSIBLE.
 PLEASE REVISE RISER, PLANS OR DOOR LOCATION FOR RISER
 TO BE COMPLETE AT ONE LOCATION.
 215.5.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 15) NOTE: PLEASE COMPLETE THE ROOM/AREA DESIGNATIONS ON
 PANEL SCHEDULE TO CORRELATE WITH THE DESIGNATIONS ON
 PLANS.
 PLEASE SEE THE FOLLOWING TEXT FROM 408.4 WHICH MENTIONS
 THE USE OF *GENERAL RECEPTACLES/GENERAL LIGHTING* IS
 NOT PERMITTED.
 SOME CIRCUITS AS SHOWN ARE NOT CLEAR.
 DESIGNATIONS ARE NOT SHOWN ON LIGHTING PLANS.
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 16) NOTE: PLEASE SEE THE PREVIOUS REVIEW GAVE NOTICE TO
 THE FS 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS.
 PLEASE KNOW AT THIS TIME A FEE OF $6,600 HAS NOW BEEN
 ASSESSED AS REQUIRED UNDER THE FLORIDA STATUTES AS
 THERE HAVE BEEN SOME OF THE SAME COMMENTS REPEATED FOR
 CODE COMPLIANCE FROM PREVIOUS REVIEWS
 THIS FEE IS ASSESSED TO THE DESIGN PROFESSIONAL AS
 REQUIRED UNDER THE FLORIDA STATUTES AND MUST BE PAID
 BEFORE THE NEXT RE-SUBMISSION OF PLANS.
 ** PLEASE ALSO KNOW THAT ONE COMPLETE SET OF PLANS WILL
 BE RETAINED BY THIS OFFICE TO BE PLACED WITH PLANS FROM
 PREVIOUS REVIEWS FOR POSSIBLE REVIEW BY THE STATES
 LEGAL COUNSEL TO THE BOARD OF ARCHITECTS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 19:25 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 17:12 Sent To  
Notes
2006-10-15 19:25:27********* UNSAT3RDREVIEW ***********
  
 ** PLEASE SEE MANY ITEMS FROMTHE TWO PREVIOUS REVIEWS
 WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE SEE NEW
 COMMENTS DUE TO
 INFORMATION SHOWN ON PLANS WHICH WAS
 DIFFERENT FROM PREVIOUS REVIEW OR HAS CHANGED IN
 DESIGN
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WITH NEW
 NOTES ADDED TO THE END OF THE PREVIOUS
 NOTES.
  
 ** IMPORTANT**
 THERE IS A BALANCED OWED OF $460, WHICH WILL BE
 REQUIRED TO BE PAID BEFORE ANY PERMIT CAN BE ISSUED.
 PLEASE ALSO BE AWARE THE NEXT RESUB WILL ALSO HAVE FEES
 DUE.
  
  
 ** IMPORTANT**
 THE OCCUPANCY OF UNITS ON SECOND FLOOR GREATLY AFFECTS
 MANY COMMENTS FOR CODE COMPLIANCE , WHETHER OR NOT THEY
 ARE RESIDENTIAL OR COMMERCIAL OFFICES.
  
  
 1)NOTE: OK.
  
 2)NOTE: OK.
  
 3)NOTE: OK SIGNED PLANS.
  
 4)NOTE: OK.
  
 5)NOTE:NO, PLEASE SEE THE NOTE WITH RESPECT THE
 EXHAUST FANS IN OTHER NOTES. OTHER "HOUSE" CIRCUITS
 WERE CORRECTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2
 NO, PLEASE SEE COMMON AREA
 ELECTRICAL STILL BEING SHOWN CIRCUITED
 TO ONE OF THE RESIDENTTIAL UNITS.
 THIS IS NOT PERMITTED.
  
 ** PREVIOUS REVIEW NOTEREVIEW #1**
 PLEASE SEE NO COMMON AREAS SHALL
 BE FED FROM CIRCUIT DERVIED FROM APTS OR
 OFFICE UNITS. PLEASE SEE CIRCUITING OF
 HALL RECEPTS ARE SHOWN TO ONE UNIT.
 PLEASE SEE 210.25
  
 6)NOTE:OK.
  
 7)NOTE: OK.
  
 8)NOTE:NO, PLEASE SEE TWO ACESSIBLE SMALL APPLIANCE
 CIRCUITS ARE REQUIRED ALONG KITCHEN COUNTER SPACE. ONE
 MAY NOT BE LOCATED BEHIOND THE FRIG, ALOTHOUGH MAY BE
 ON ONE OR MORE OF THE SM APPL CIRCUITS. PLEASE SEE
 MINIMUM LOAD WHICHSHALL BE FIGNURED FOR EACH OF THE
 SMALL APPLIANCE CIRCUITS. DINING RMS AND AREASOF THE
 LIKE.
 PLEASE SEE 210.52B1, 210.11C1, 220.16. PLEASE SEE MIN
 VA FOR EACH CIRCUIT. PLEASE SEE OTHER COMMENTS WITH
 RESPECT TO LOAD CALCULATIONS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, STIL SHOWS ONLY ONE.
  
 **PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE A
 MIN OF TWO SMALL
 APPLIANCE CIRCUITS ARE REQUIRED PER
 210.52B1.
  
 9)NOTE: OK.
  
 10)NOTE: OK.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE:NO, PLEASE LOOK AT ALL CIRCUITING AS NOW
 SHOWN. PLEASE SEE ARC FAULT IS BEING SHOWN ON
 DISHWASHER AND MANY OTHER ITEMS NOT REQUIRED?? IT IS
 UNCLEAR OF THE INTENT. THE ORIGINAL AND PREVIOUS
 COMMENTS HAD TO DO WITH THE "OUTLETS" IN SLEEPING ROOMS
 OR ROOMS WILL BE CONSIDERED SUCH.
 IT IS UNCLEAR AT THIS TIME AND RESPONSE LETTER ONLY
 MENTIONS THEY ARE REFLECTED.?
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE THERE ARE
 CIRCUITS NOW SHOWN WITH ARC FAULT
 PROTECTION WHICH ARE NOT REQUIRED AND
 SOME WHICH DO SHOW ARC FAULT PROTECTION
 AND SOME THAT DO NOT??
 PLEASE SEE ALL "OUTLETS".
  
 ** PREVIOUS REVIEW NOTE REVIEW#1 **
 PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS AS REQUIRD
 UNDER THE 2002 NEC 210.12B
 PLEASE KNOW, ALL, ELECTRICAL
 DEVICES/OUTLETS SUCH AS LTS, SD'S
 RECEPTS, FANS ETC SHALL BE AFCI
 PROTECTED.
 ** PLEASE KNOW, AREAS NOW SHOWN AS
 "OFFICES" ARE UNITS WHICH SEEM TO SHOW
 POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF
 THESE AREAS ARE ADAPTABLE FOR
 RESIDENTIAL USE, THEN AFCI PROTECTION
 WILL BE REQUIRED FOR THESE ROOMS.
  
 14)NOTE:NO, PLEASE SEE CIRCUITING NOTES FOR EXHAIST
 FANS. THE CIRCUITING FOR SA'S ARE OK, IT OTHER
 CIRCUITING IS CORRECTED AND AFCI PROTECTION IS
 INDICATED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2 **
 OK, HOWEVER 2ND PART OF THIS
 NOTE WAS NOT DONE.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE NFPA-70 11.5.1.1
 WHICH REQUIRES THE USE OF SMOKE
 DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING RMS OR ADAPTABLE SLEEPING
 ROOMS.** PLEASE SEE PREVIOUS NOTES WITH
 RESPECT TO THE CIRCUITING OF BEDRMS.
  
 15)NOTE: NO, PLEASE SEE THERE ARE STILL MANY ITEMS ON
 PLANS WHICH DO NOT CONTAIN CIRCUITING.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2 **
 NO, PLEASE SEE SOME CIRCUITS
 ARE NOT COMEPLETE AT THIS TIME IN
 DWELLING UNITS AND HOUSE AREAS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE. PLEASE SEE CIRCUTING
 MISSING.
 215.5
  
 16)NOTE: OK.
  
 17)NOTE: OK.
  
  
 18)NOTE: OK.
  
 19)NOTE: OK.
  
 20)NOTE: NO/OK. PLEASE SEE A DETAIL WAS SUBMITTED
 HOWEVER DOES NOT SHOW ALL EGRESS PATHS FOR MIN LIGHTING
 LEVELS UNDER NORMAL AND EMERGENCY. PLEASE ALSO SEE A
 FIXTURE TYPE IS NOW BEING NOTED AT A HID METAL HALIDE
 FOR ONE OF THE EM FIXTURES?? PLEASE SEE THIS DOES NOT
 INDICATE ANY QUARTZ/RE-STRIKE. IF AND WHEN POWER IS
 INTERUPTED IN AN EMERGENCY, THESE FIXTURES WILL NOT
 COME ON PROVIDINGTHE MIN LIGHTING LEVELS WITHIN THE
 TIME REQUIRED BEIGN HID FIXTURES. PLEASE EXPLAIN
 FIXTURE TYPE, AADJUST FIXTURE TYPE ETC?
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE A NOTE WAS ADDED
 TO PLANS IN LEIU OF THE DETAIL NEEDED
 AND REQUIRED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE PROVIDE THE PHOTO-METRICS FOR
 EXITING STAIR AREAS AS NFPA-101 7.8.1.3
 REQUIRES A MIN OF 10FT CANDLES (108 LUX)
 FOR THE ALL AREAS OF WALKING SURFACE IN
 STAIRS UNDER NORMAL POWER AND IS
 PERMITTED TO BE LOWERED TO A MIN OF 1FT
 CANDLE (10.8 LUX) UNDER EMERGENCY
 CONDITIONS, 7.9.2.2
  
 21)NOTE: OK, HOWEVER PLEASE STILL PLEASE SEE NOTE WITH
 RESPECT TO FBC CHAPTER 13 WHICH MAY AFFECT FIXTURES.
  
 22)NOTE: OK.
  
 23)NOTE:NO, SAME NOTE.PLEASE ALSO SEE NEW NOTES FOR
 THE REVISED RISER NOW SUBMITTED FOR FIRST REVIEW.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE "EQUIPMENT
 GROUNDING CONDUCTORS" ARE STILL BEING
 SHOWN BEFORE THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE NEW NOTESAS
 LOCATION WILL CHANGE.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE 250.6, 250.24, NO
 "EQUIPMENT GROUNDING CONDUCTORS" SHALL
 BE INSTALLED BEFORE THEFIRST MEANS OF DISCONNECT.
 PLEASE SEE THESE ARE SHOWN
 FROM FPL, TO GUTTER, TO METER ETC.
  
 24)NOTE:OK.
  
 25)NOTE: OK.
  
 26)NOTE: NO, PLEASE SEE PREVIOUS NOTES. CALCULATIONS
 SUBMITTED AND SHOWN DO NOT CORRELATE WITH SOME PANEL
 SCHEDULES. PLEASE ALSO SEE SOME AS THEY SO NOT MEET NEC
 CODE COMPLIANCE. PLEASE SEE OCCUPANCY WILL AFFECT THIS.
 PLEASE SEE RESIDENTIALUNITS ALSO. ETC
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SUBMIT COMPLETE
 CALCULATIONS FOR EACH PANEL FOR USE AS
 SHOWN ON PLANS.
 PLEASE ALSO SHOW LOADS FOR SERVICE, NONE
 WERE SUBMITTED.
  
 **PREVIOUS REVIEW NOTES REVIEW #1 **
 PLEASE SUBMITLOAD CALCULATIONS FOR
 ALL AREAS, PANELS, BLDG. PLEASE SEE
 THESE ARE SHOWN A MIXED
 USE. PLEASE ADJUST ACCORDINGLY.
 PLEASE ALSO INDICATE OF CONTINUOUS LOADS
 AT 125%. 215.3,230.42,
 220.10,220.11,220.13 ETC
  
 27)NOTE:NO, PLEASE SEE 2004 FBC CHAPTER 13. PLEASE
 SEE OCCUPANCY WILL HAVE AN AFFECT ON THIS. PLEASE SEEE
 ONLY SOME OF THE FOLLOWING SECTIONS WHICH ARE BEING
 BROKEN DOWN. PLEASE KNOW, ALL OF THE CHAPTER WAS GIVEN
 ON PREVIOUS REVIEW AS NOTHING WAS SUBMITTED OR SHOWN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2& .1.3. PLEASE SEE
 MANY ITEMS MISSING.
 PLEASE SEE 13-415.2.ABC.1,TABLES 415.2.C.1, 415.2.B.1
 PLEASE SEE THE ENERGY CALCULATIONS WERE NOT THE ONLY
 ITEM NEEDED.
 PLEASE SEE ALL SEPARATE SPACES ETC
 PLEASE PROVIDE THE MAX TIMES PERMITTED ON OVER RIDE
 DEVICES ETC. ( OS TYPE 30MINS MAX, TIMER TYPE 4HRS
 MAX)
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, THIS WAS NOT ADDRESSED AND
 NO DESIGNS, CALCS, CONTROLS ETC WERE
 SUBMITTED FOR REVIEW. PLEASE SEE MIN
 CALCULATIONS REQUIRED.
 ALSO NO ENERGY CALCULATIONS WERE
 SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE BE SURE TO SEE THE 2004
 FBC CHAPTER 13 WITH RESPECT TO THE
 ENERGY CODE AND DESIGNS. PLEASE KNOW
 THIS IS A COMMERCIAL BLDG WITH A CHANGE
 OF OCCUPANCY WHICH WILL REQUIRE ENERGY
 CODE UPGRADES.
  
 **** NEW NOTES 2ND REVIEW****
  
 28) NOTE: OK, HOWEVER SEE NEW NOTE FROM 3RD REVIEW.
  
 29) NOTE:NO/OK, PLEASE SEE A COMPLETELY NEW RISER
 DIAGRAM HAS BEEN SUBMITTED, HOWEVER LABELING OF ALL
 EQUIPMENT AS PERVIOUSLY NOTED STILL NEEDS TO BE
 ADDRESSED FOR EACH MAIN /PANEL ECT.
 PLEASE ALSO SEE NEW COMMENTS DUE REVISED RISER FOR NEW
 3RD REVIEW NOTES.
  
 ** PREVIOUS REVIEW NOTES REVIEW #2**
 PLEASE SEE RISER WHICH
 INDICATES MORE THAN SEVEN MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.
 230.2,230.70.
 PLEASE KNOW A SEPARATE TYPE OF METER
 BANK SERVICE MAY BE DONE WITH A MAIN
 ETC.
 PLEASE ALSO SEE MANY OF THE TENANT
 METERS, MAINS ETC ARE LABLED AS "HOUSE" EQUIPMENT??
 PLEASE SEE PANEL "HP" SHOULD BE THE ONLY
 PANEL, METER AND MAIN LABLED AS "HOUSE".
 408.4
 30) NOTE: PLEASE SEE CLOSET LT IN UNIT
 "C" WHICH DOES NOT MEET 410.8
  
 30) NOTE:NO, SAME, PLEASE SEE REPSONSE LTR MENTIONS
 THIS WAS ADDRESSED, HOWEVER SEE PLANS ARE STILL SHOWING
 MULTIPLE CIRCUITS FOR THE SAME EXHAUST FANS AND IF SOME
 OF THESE ARE SUPPOSE TO BE ON "HOUSE PANEL " AS
 REPSONSE LETTER MENTIONS, THEN PLEASE SEE PLANS AS
 THESE ARE STILL SHOWN TO UNIT PANELS FOR TENANTS WHICH
 IS NOT PERMITTED. SEE NOTES ABOVE WITH RESPECT TO
 "HOUSE EQUIPMENT' WHICH IS NOT PERMITTED ON TENANT
 PANELS.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE SOME UNITS SHOW AND
 LABEL "TWO" EXHAUST FAN CIRCUITS??
 PLEASE ALSO SEE ARC FAULT CIRCUITING.
 PLEASE SEE MANY OF THESE DO NOT
 CORRELATE WITH CIRCUITING SHOWN ON PLANS
 AND DEVICES. SOME ARE NOT AS LABELED.
 FBC 106.1.2 ADMIN SECT.
  
 31) NOTE: OK, RELOCATED PANELS.
  
 32) NOTE: OK, HOWEVER SEE NOTES FOR CONTROL OF LTS. IF
 THIS DOES BECOME A ROOM WHICH REQUIRES A PUMP OR
 CONTROLLER SOME ELECTRICAL ITEMS WILL BE REQUIRED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 PLEASE SEE PLANS MENTIONS
 "SPRINKLER ROOM" ? WHAT IS THIS AND IS
 THERE LIGHTING FOR SERVICE OF EQUIPMENT
 ETC?
 LS 101 7.8
  
 33) NOTE:NO, PLEASE SEE A NOTICE WAS GIVEN WITH
 RESPECT TO REPEAT COMMENTS. PLEASE KNOW AS PLANS WERE
 SUBMITTED THE FIRST TWO TIMES AS "PLAN REVIEW ONLY" THE
 FEE WILL NOT APPLY FOR THIS REVIEW, HOWEVER PLEASE BE
 AWARE IF "ANY " OF THE SAME CODE COMPLIANT COMMENTS
 COME BACK WHICH ARE REPEAT FOR THENEXT REVIEW A FEE
 WILL BE ASSESSES AS REQUIRED PER FLORIDA STATUE GIVEN.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2 **
 PLEASE SEE COPY OF FS
 553.80(2)B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE AS MANY OF
 THESE COMMENTS ARE THE SAME AS THE
 PREVIOUS REVIEW. THIS IS ONLY BEING
 GIVEN AS A NOTICE AT THIS TIME.
  
  
 **** NEW NOTES FOR 3RD REVIEW *****
  
 34) NOTE: PLEASE SEE 210.52C1-5 FOR SPACING OF GFI
 RECEPTS ALONG KTICHEN COUNTER SPACE. PLEASE SEE AS
 SHOWN AND IF THE OCCUPANCY IS GOING TO BE RESIDENTIAL,
 THEN THE SPACING AS SHOWN IN SOME UNITS DO NOT MEET
 CODE GIVEN.
  
 35) NOTE: PLEASE PROVIDE ALL AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT AS SHOWN. ALL MAINS PANELS ETC SHALL
 MEET 110.9 AND PLEASE SEE 240.12 FOR SELECTIVE
 COORDINATION.
  
 36) NOTE: PLEASE SEE AS RISER CONTAINS A NEW MAIN,
 PLEASE NOW INDICATE A "FLOATING NEUTRAL" FORALL
 METERS ON THE SECONDARY SIDE OF THE NEW MAIN. 250.6,
 250.24B
 PLEASE ALSO SEE NOTE ON RISER SHEETS WHICH BODNIGN W/
 EMT TO MEET 250.66. PLEASE SEE ALL NEUTRALS AND
 EQUIPMENT GROUNDS ARE REQUIRED TO BE SEPARATE AFTER THE
 FIRST MEANS OF DISCONNECT.
  
 37) NOTE: PLEASE SEE PLANS NOW MENTIONS AS FA SYSTEM TO
 BE INSTALLED, YET NO INFORMATION WAS SUBMITTED FOR
 THIS.? PLEASE CLARIFY THE SMOKE DEVICES ON PLANS.
 PLEASE SEE NFPA-72 DEFINITIONS FOR SA (SMOKE ALARMS)
 AND SD (SMOKE DETECTORS). PLEASE ADJUST ACCORDINGLY ID
 UTILIZING A SYSTEM AS PART OF THE BUILDING. NFPA-72
 11.5, 11.8 ETC
  
 38) NOTE: PLEASE SEE A PREVIOUS NOTE MENTIONED
 QUALIFICATIONS FOR LIMITS ON PLAN DESIGN. PLEASE SEE FS
 471.003, 471.025, 481.221. PLEASE KNOW, DUE TO THE
 REPEAT COMMENTS FOR CODE COMPLIANCE REPEATED , ONE SET
 OF EACH ELECTRICAL SET OF PLANS SUBMITTED ARE BEING
 RETAINED FOR POSSIBLE REVIEW AND SUBMISSION TO THE
 FLORIDA BOARD OF ARCHITECTS AND LEGAL COUNSEL TO THE
 BOARD.
 PLEASE ADDRESS ALL COMMENTS. TO DATE, NO ONE HAS
 CONTACTED THIS OFFICE IF THERE WERE ANY COMMENTSOR
 QUESTIONS ON SAID REVIEW COMMENTS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-07-06 Cont ID  
Sent By dpalmer Date 2006-07-06 Time 10:42 Rev Time 0.00
Received By dpalmer Date 2006-07-05 Time 21:01 Sent To  
Notes
2006-07-06 00:00:00**
 ********* UNSAT2ND REVIEW ***********
  
 ** PLEASE SEE MANY ITEMS FROM PREVIOUS
 REVIEW AND SOME NEW ITEMS DUE TO
 INFORMATION SHOWN ON PLANS WHICH WAS
 DIFFERENT FROM PREVIOUS REVIEW.
  
 ** PLEASE KNOW, PLANS HAVE NOW BEEN
 SUBMITTED FOR PERMIT.
 PLEASE SEE THE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WITH NEW
 NOTES ADDED TO THE END OF THE PREVIOUS
 NOTES.
  
 ** IMPORTANT**
 PLEASE SEE AS REQUESTED ON PREVIOUS
 REVIEW, PLEASE SUBMIT ONE SET OF THE
 OLD/VOIDED SETS FOR REFERENCE. THIS WAS
 NOT DONE.
  
 1)NOTE:NO, PLEASE SEE COVER SHEETS
 ONLY MENTIONS THE CODES AND NOT THE
 YEARS OF EDITIONS.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE THAT ALL DESIGNS AND
 CODES ARE REFERENCED TO THE CURRENT
 CODES ADOPTED BY THE STATE OF FLORIDA.
 PLEASE KNOW, WE ARE CURRENTLY UNDER THE
 2004 FLORIDA BLDG CODE.
 2002 NFPA-70, 2002 NFPA-72,2003 NFPA-101
 PLEASE ADJUST.
 PLEASE ALSO SEE NOTES BELOW AS
 ELECTRICAL CODE IS BEING REFERENCED FROM
 THE 1996
 NFPA-70 (NEC).
  
 2)NOTE: OK, AS TITLE BLOCKS HAVE BEEN
 REVISED AND ENGINEERING FIRM AND
 ENGINEER IS NO LONGER DOING THE PROJECT.
 HOWEVER PLEASE SEE NEW NOTES.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION
 AND LICENSE INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ARCHITECTUAL FIRM,
 ENGINEER AND FIRM? ETC.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-23.002,
 61G1-16.004 AND FLORIDA
 STATUES, 481.219, 471.023 .
 PLEASE KNOW: THIS IS REQUIRED OF ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3)NOTE: NO, PLEASE SEE IT SEEMS THE
 ENGINEER AS SHOWN ON PREVIOUS PLANS HAS
 BEEN REMOVED AND THE PLANS ARE NOW DONE
 BY AN ARCHITECT. PLEASE SEE NEW COMMENTS PERTAINING TO
 THE PLANS AND PLEASE SEE
 THAT THE PREVIOUS NOTE STILL APPLIES TO
 THE ARCGITECT OF RECORD. PLEASE SEE
 PLANS ARE CLEARLY "SIGNED" WITH
 "INITIALS". IF THIS IS THE "LEGAL
 SIGNATURE" OF SAID ARCHITECT, PLEASE
 PROVIDE A SIGNED,DATED AND SEALED
 NOTORIZED LETTER FOR LEGAL SIGNATURE
 VERIFICATION. THIS WILL BE PLACED IN OUR
 SIGNATURE FILE FOR FUTURE REFERENCE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE ALSO PROVIDE A SIGNED, DATED AND
 SEALED LETTER FOR THE ENGINEER AS SHOWN
 ON PLANS AFFIRMING THE LEGAL SIGNATURE
 ON SAID PLANS. PLANS APEAR TO INDICATE INITIAL(S)? THIS
 LETTER IS TO BE CORRECTLY
 NOTORIZED, AND WILL BE PLACED IN OUR
 SIGNATURE FILE FOR FUTUREREFERENCE.
  
 4)NOTE: NO, PLEASE SEE LOWER POWER PLANS
 INDICATE ROOF TOP GFI'S AND THE TWO ARE
 FED FROM FIRST FLR TENANT PANELS. THESE
 SHOULD BE FED FROM HOUSE PANEL.
  
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE ROOF TOP
 RECEPTS AS GFI OR GFI PROTECTED AS
 REQUIRED PER 210.8B2
  
 5)NOTE: NO, PLEASE SEE COMMON AREA
 ELECTRICAL STILL BEING SHOWN CIRCUITED
 TO ONE OF THE RESIDENTTIAL UNITS.
 THIS IS NOT PERMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NO COMMON AREAS SHALL
 BE FED FROM CIRCUIT DERVIED FROM APTS OR
 OFFICE UNITS. PLEASE SEE CIRCUITING OF
 HALL RECEPTS ARE SHOWN TO ONE UNIT.
 PLEASE SEE 210.25
  
 6)NOTE:NO, PLEASE SEE CODE CHANGED IN
 1993 TO REQUIRED "ALL" NOT ONLY RECEPTS
 LOCATED WITHIN 6' OF SINK.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SHOW ALL KITCHEN
 COUNTERSPACE RECEPTS AS GFI/ GFI
 PROTECTED AS REQUIRED PER 210.8A6
  
 7)NOTE: NO, SAME NOTE: PLEASE SEE
 KITCHENS IN OTHER THAN DWELLING UNITS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE IF OFFICE UNITS WHICH
 WILL ALSO BE REQUIRED TO HAVE GFI
 RECEPTS,IN EITHER CASE ON POSSIBLE USE
 CHANGE TO DWELLING UNITS, OR AS REQUIRED
 PER 210.8B3
  
 8)NOTE: NO, STIL SHOWS ONLY ONE.
  
 **PREVIOUS REVIEW NOTE ** PLEASE SEE A
 MIN OF TWO SMALL
 APPLIANCE CIRCUITS ARE REQUIED PER
 210.52B1.
  
 9)NOTE: OK.
  
 10)NOTE: OK.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE: NO, PLEASE SEE THERE ARE
 CIRCUITS NOW SHOWN WITH ARC FAULT
 PROTECTION WHICH ARE NOT REQUIRED AND
 SOME WHICH DO SHOW ARC FAULT PROTECTION
 AND SOME THAT DO NOT??
 PLEASE SEE ALL "OUTLETS".
  
 ** PREVIOUS REVIEW NOTES **
 PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS AS REQUIRD
 UNDER THE 2002 NEC 210.12B
 PLEASE KNOW, ALL, ELECTRICAL
 DEVICES/OUTLETS SUCH AS LTS, SD'S
 RECEPTS, FANS ETC SHALL BE AFCI
 PROTECTED.
 ** PLEASE KNOW, AREAS NOW SHOWN AS
 "OFFICES" ARE UNITS WHICH SEEM TO SHOW
 POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF
 THESE AREAS ARE ADAPTABLE FOR
 RESIDENTIAL USE, THEN AFCI PROTECTION
 WILL BE REQUIRED FOR THESE ROOMS.
  
 14)NOTE: OK, HOWEVER 2ND PART OF THIS
 NOTE WAS NOT DONE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE NFPA-70 11.5.1.1
 WHICH REQUIRES THE USE OF SMOKE
 DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING RMS OR ADAPTABLE SLEEPING
 ROOMS.** PLEASE SEE PREVIOUS NOTES WITH
 RESPECT TO THE CIRCUITING OF BEDRMS.
  
 15)NOTE:NO, PLEASE SEE SOME CIRCUITS
 ARE NOT COMEPLETE AT THIS TIME IN
 DWELLING UNITS AND HOUSE AREAS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE. PLEASE SEE CIRCUTING
 MISSING.
 215.5
  
 16)NOTE: OK.
  
 17)NOTE: OK.
  
  
 18)NOTE: ? NO, PLEASE SEE A NOTE WAS
 ADDED TO PLANS FOR "NO PLUG-IN TYPE "
 TRANSFORMERS TO BE PLACED IN CLOSETS
 ETC, HOWEVER PLEASE CLARIFY THE USE OF
 THE RECEPTS STILL BEING SHOWN IN THESE
 AREAS.
  
 ** PREVIOUS REVIEW NOTE**
 PELASE SEE RECEPTS FOR LV TYPE
 PLUG-IN TRANSFORMERS ARE NOT PERMITTED
 IN CLOTHES CLOSETS AND LOCATIONS IN
 CLOSE PROXIMITY OF EASILY IGNITIBLE
 MATERIALS.
 PLEASE SEE 110.26,240.24, ETC
 AS THESE TYPE UNITS CREATE HIGH TEMPS
 AND HAVE CAUSED FIRES IN THIS
 JURISDICTION, THESE WILL NOT BE
 PERMITTED IN THESE CLOSETS DUE TO THE
 LIFE SAFETY AND PROPERTY HAZARD IT
 CREATES.
  
 19)NOTE: NO, PLEASE SEE LOWER COMM
 UNITS, PLEASE SEE UPPER UNITS CONTAIN LT
 FIXTURE WHICH ARE ALSO PART OF THE
 NORMAL LIGHTING.
 LOWER FLR DOES NOT MEET THE EXCEPTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 700.12EWHICH
 REQUIRESD THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE ADJUST CIRCUITING AS SHOWN.
  
 20)NOTE: NO, PLEASE SEE A NOTE WAS ADDED
 TO PLANS IN LEIU OF THE DETAIL NEEDED
 AND REQUIRED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE THE PHOTO-METRICS FOR
 EXITING STAIR AREAS AS NFPA-101 7.8.1.3
 REQUIES A MIN OF 10FT CANDLES (108 LUX)
 FOR THE ALL AREAS OF WALKING SURFACE IN
 STAIRS UNDER NORMAL POWER AND IS
 PERMITTED TO BE LOWERED TO A MIN OF 1FT
 CANDLE (10.8 LUX) UNDER EMERGENCY
 CONDITIONS, 7.9.2.2
  
 21)NOTE: NO, PLEASE SEE SOME FIXTURES
 ARE STILL SHOWN AS BLANK. ALL FIXTURES
 SHALL BE SHOWN AT THIS TIME. THESE CAN
 ALWAYS BE REVISED AT A LATER DATE.
  
 **IMPORTANT,PLEASE SEE NEW COMMENTS
 BEFORE FINAL FIXTURES ARE CHOSEN DUE TO
 THE ENERGY CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE THE FIXTURE LEGEND
 WITH PLANS.
 PLEASE ALSO CORRELATE THE FIXTURE
 SCHEDULE WITH PLANS AS SOME FIXTURES ARE
 LABELED ON PLANS , YET NOT ON SCHEDULE.
 E-1).
  
 22)NOTE: OK.
  
 23)NOTE:NO, PLEASE SEE "EQUIPMENT
 GROUNDING CONDUCTORS" ARE STIL BEING
 SHOWN BEFORE THE FIRST MEANS OF
 DISCONNECT. PLEASE SEE NEW NOTESAS
 LOCATION WILL CHANGE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.6, 250.24, NO
 "EQUIPMENT GROUNDING CONDUCTORS" SHALL
 BE INSTALLED BEFORE THEFIRST MEANS OF DISCONNETC.
 PLEASE SEE THESE ARE SHOWN
 FROM FPL, TO GUTTER, TO METER ETC.
  
 24)NOTE:OK.
  
 25)NOTE: OK.
  
 26)NOTE: NO, PLEASE SUBMIT COMPLETE
 CALCULATIONS FOR EACH PANEL FOR USE AS
 SHOWN ON PLANS.
 PLEASE ALSO SHOW LOADS FOR SERVICE, NONE
 WERE SUBMITTED.
  
 **PREVIOUS REVIEW NOTES **
 PLEASE SUBMITLOAD CALCULATIONS FOR
 ALL AREAS, PANELS, BLDG. PLEASE SEE
 THESE ARE SHOWN A MIXED
 USE. PLEASE ADJSUT ACCORDINGLY.
 PLEASE ALSO INDICATE OF CONTINUOUS LOADS
 AT 125%. 215.3,230.42,
 220.10,220.11,220.13 ETC
  
 27)NOTE: NO, THIS WAS NOT ADDRESSED AND
 NO DESIGNS, CALCS, CONTROLS ETC WERE
 SUBMITTED FOR REVIEW. PLEASE SEE MIN
 CALCULATIONS REQUIRED.
 ALSO NO ENERGY CALCULATIONS WERE
 SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO SEE THE 2004
 FBC CHAPTER 13 WITH RESPECT TO THE
 ENERGY CODE AND DESIGNS. PLEASE KNOW
 THIS IS A COMMERCIAL BLGD WITH A CHANGE
 OF OCCUPANCY WHICH WILL REQUIRE ENERGY
 CODE UPGRADES.
  
 **** NEW NOTES ****
  
 28) NOTE: PLEASE SEE ORIGINAL PLANS WERE
 DONE BY A PE AND NOW PLANS ARE DONE BY
 ARCHITECT. PLEASE SEE THE SCOPE OF WORK,
 SIZE ETC REQUIRES THE PLANSTO BE DONE BY
 AN PE. FS 471.003(2)H.
  
 29) NOTE: PLEASE SEE RISER WHICH
 INDICATES MORE THAN SEVEN MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED.
 230.2,230.70.
 PLEASE KNOW A SEPARATE TYPE OF METER
 BACNK SERVICE MAY BE DONE WITH A MAIN
 ETC.
 PLEASE ALSO SEE MANY OF THE TENANT
 METERS, MAINS ETC ARE LABLED AS "HOUSE" EQUIPEMNT??
 PLEASE SEE PANEL "HP" SHOULD BE THE ONLY
 PANEL, METER AND MAIN LABLED AS "HOUSE".
 408.4
 30) NOTE: PLEASE SEE CLOSET LT IN UNIT
 "C" WHICH DOES NOT MEET 410.8
  
 30) NOTE: PLEASE SEE SOME UNITS SHOW AND
 LABEL "TWO" EXHAUST FAN CIRCUITS??
 PLEASE ALSO SEE ARC FAULT CIRCUITING.
 PLEASE SEE MANY OF THESE DO NOT
 CORRELATE WIHT CIRCUITING SHOWN ON PLANS
 AND DEVICES. SOME ARE NOT AS LABELED.
 FBC 106.1.2 ADMIN SECT.
  
 31) NOTE: PLEASE SEE ELECTRICAL PANELS
 ARE NOW BEING SHOWN IN CLOSETS WHICH IS
 NOT PERMITTED. PLEASE ALSO SEE ALL MIN
 CLEARENCES ARE ALSO NOT MET.
 PLEASE SEE 110.26,240.24D,408.7 ETC.
  
 32) NOTE: PLEASE SEE PLANS MENTIONS
 "SPRINKLER ROOM" ? WHAT IS THIS AND IS
 THERE LIGHTING FOR SERVICE OF EQUIPMENT
 ETC?
 LS 101 7.8
  
 33) NOTE: PLEASE SEE COPY OF FS
 553.80(2)B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE AS MANY OF
 THESE COMMENTS ARE THE SAME AS THE
 PREVIOUS REVIEW. THIS IS ONLY BEING
 GIVEN AS A NOTICE AT THIS TIME.
  
  
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVED ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED
 SHEETS SEPARATED FROM NEW SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-07-05 00:00:00IN ELEC FOR REVIEW

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2006-07-05 Cont ID  
Sent By dpalmer Date 2006-06-21 Time 21:00 Rev Time 0.00
Received By dpalmer Date 2006-06-18 Time 16:23 Sent To  
Notes
2006-07-05 00:00:00PLANS WERE PAID FOR ON 6/21/06 WHICH
 STARTED THE RESUBMITTAL DATE.
2006-06-18 00:00:00IN ELEC FOR REVIEW.
 6/18/06 PLANS ARE OUTFRONT ON"HOLD"
 WAITING FOR FEES TO BE PAID.
 PLANS IN LG BINS UNDER "M".
 THIS WAS THE 2ND NOTICE FOR FEES TO BE
 PAID.
 CALLED SPOKE TO RICHARDWATSON
 AND TOLD HIM PLANS ARE NOT BEING
 REVIEWED. . DV PALMER.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-07 Cont ID  
Sent By dpalmer Date 2006-02-07 Time 11:22 Rev Time 0.00
Received By dpalmer Date 2006-02-06 Time 19:17 Sent To  
Notes
2006-02-07 00:00:00********* UNSAT ************
  
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITTED FOR "PLAN REVIEW" ONLY NAD
 HAVE NOT BEEN SUBMITTED FOR PERMIT.
  
 1)NOTE: PLEASE SEE THAT ALL DESIGNS AND
 CODES ARE REFERENCED TO THE CURRENT
 CODES ADOPTED BY THE STATE OF FLORIDA.
 PLEASE KNOW, WE ARE CURRENTLY UNDE THE
 2004 FLORIDA BLDG CODE.
 2002 NFPA-70, 2002 NFPA-72,2003 NFPA-101
 PLEASE ADJUST.
 PLEASE ALSO SEE NOTES BELOW AS ELCTRICAL
 CODE IS BEING REFERENCED FROM THE 1996
 NFPA-70 (NEC).
  
 2)NOTE: PLEASE SEE MISSING INFORMATION
 AND LICENSE INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ARCHITECTUAL FIRM,
 ENGINEER AND FIRM? ETC.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002, 61G1-16.004 AND FLORIDA
 STATUES, 481.219, 471.023 .
 PLEASE KNOW: THIS IS REQUIRED OF ALL
 TRADES AND FOR ALL SHEETS WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3)NOTE: PLEASE ALSO PROVIDE A SIGNED,
 DATED AND SEALED LETTER FOR THE ENGINEER
 AS SHOWN ON PLANS AFFIRMING THE LEGAL
 SIGNATURE ON SAID PLANS. PLANS APPEAR TO
 INDICATE INITIAL(S)?
 THIS LETTER IS TO BE CORRECTLY
 NOTORIZED, AND WILL BE PLACED IN OUR
 SIGNATURE FILE FOR FUTUREREFERENCE.
  
 4)NOTE: PLEASE INDICATE THE ROOF TOP
 RECEPTS AS GFI OR GFI PROTECTED AS
 REQUIRED PER 210.8B2
  
 5)NOTE: PLEASE SEE NO COMMON AREAS SHALL
 BE FED FROM CIRCUIT DERVIED FROM APTS OR
 OFFICE UNITS. PLEASE SEE CIRCUITING OF
 HALL RECEPTS ARE SHOWN TO ONE UNIT.
 PLEASE SEE 210.25
  
 6)NOTE: PLEASE SHOW ALL KITCHEN
 COUNTERSPACE RECEPTS AS GFI/ GFI
 PROTECTED AS REQUIRED PER 210.8A6
  
 7)NOTE: PLEASE SEE IF OFFICE UNITS WHICH
 WILL ALSO BE REQUIRED TO HAVE GFI
 RECEPTS, EITHER BASE ON POSSIBLE USE
 CHANGE TO DWELLING UNITS, OR AS REQUIRED
 PER 210.8B3
  
 8)NOTE: PLEASE SEE A MIN OF TWO SMALL
 APPLIANCE CIRCUITS ARE REQUIED PER
 210.52B1.
  
 9)NOTE: PLEASE SEE 210.52B1, 210.11C1,
 220.16A WHICH REQUIRES EACH TO BE
 FIGURED AT A MIN OF 1500 VA.
  
 10)NOTE: PLEASE SEE 210.52B1 WHICH
 REQUIRE STHE ONE OR MORE SMALL APPLIANCE
 CIRCUITS TO FEED DINING ROOM(S) AND THE
 LIKE AREAS. PLEASE SEE CIRCUITING
 FEEDING DINING RM AREA MAY NOT FEED
 LIVING RMS OR ANY OTHER AREAS.
  
 11)NOTE: PLEASE SEE 210.11C2, 220.16B
 WHICH REQUIRES A MIN LAUNDRY /WASHER
 CIRCUIT TO BE 1500VA .
  
 12)NOTE: PLEASE SEE 220.18, 240.4,
 310.16, DRYER SAHLL BE FIGURED AT A MIN
 OF 5KW, 30A, #10 AWG.
 PLEASE ADJUST AS THESE ARE SHOWN ON A
 2-POLE 20A BRKR?
  
 13)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS AS REQUIRD
 UNDER THE 2002 NEC 210.12B
 PLEASE KNOW, ALL, ELECTRICAL
 DEVICES/OUTLETS SUCH AS LTS, SD'S
 RECEPTS, FANS ETC SHALL BE AFCI
 PROTECTED.
 ** PLEASE KNOW, AREAS NOW SHOWN AS
 "OFFICES" ARE UNITS WHICH SEEM TO SHOW
 POSSIBLE CHANGE IN-USE OR OCCUPANCY. IF
 THESE AREAS ARE ADAPTABLE FOR
 RESIDENTIAL USE, THEN AFCI PROTECTION
 WILL BE REQUIRED FOR THESE ROOMS.
  
 14)NOTE: PLEASE SEE NFPA-70 11.5.1.1
 WHICH REQUIRES THE USE OF SMOKE
 DETECTORS INSIDE AND OUTSIDE ALL
 SLEEPING RMS OR ADAPTABLE SLEEPINS
 ROOMS.** PLEASE SEE PREVIOUS NOTES WITH
 RESPECT TO THE CIRCUITING OF BEDRMS.
  
 15)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE. PLEASE SEE CIRCUTING
 MISSING.
 215.5
  
 16)NOTE: PLEASE SEE MANY AREA WHERE
 THERE ARE HAND-DRAWN CHANGES MADE TO
 PLANS WHICH ARE SIGNED AND SEALED
 DOCUMENTS. PLEASE KNOW, THIS IS NOT
 PERMITTED UDNER FS 471.025.
  
 17)NOTE: PLEASE SEE THAT PANEL SCHEDULES
 INDICATE ALL CONDUCTORSIZES, PER
 240.4,310.16.
  
 18)NOTE: PELASE SEE RECEPTS FOR LV TYPE
 PLUG-IN TRANSFORMERS ARE NOT PERMITTED
 IN CLOTHES CLOSETS AND LOCATIONS IN
 CLOSE PROXIMITY OF EASILY IGNITIBLE
 MATERIALS.
 PLEASE SEE 110.26,240.24, ETC
 AS THESE TYPE UNITS CREATE HIGH TEMPS
 AND HAVE CAUSED FIRES IN THIS
 JURISDICTION, THESE WILL NOT BE
 PERMITTED IN THESE CLOSETS DUE TO THE
 LIFE SAFETY AND PROPERTY HAZARD IT
 CREATES.
  
 19)NOTE: PLEASE SEE 700.12EWHICH
 REQUIRESD THE BRANCH CIRCUIT FEEDING THE
 UNIT EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
 PLEASE ADJUST CIRCUITING AS SHOWN.
  
 20)NOTE: PLEASE PROVIDE THE
 PHOTOMETRICAS FOR EXITING STAIR AREAS AS
 NFPA-101 7.8.1.3 REQUIES A MIN OF 10FT
 CANDLES (108 LUX) FOR THE ALL AREAS OF
 WALKING SURFACE IN STAIRS UNDER NORMAL
 POWER AND IS PERMITTED TO BE LOWERED TO
 A MIN OF 1FT CANDLE (10.8 LUX) UNDER
 EMERGENCY CONDITIONS, 7.9.2.2
  
 21)NOTE: PLEASE CORRELATE THE FIXTURE
 LEGEND WITH PLANS.
 PLEASE ALSO CORRELATE THE FIXTURE
 SCHEDULE WITH PLANS AS SOME FIXTURES ARE
 LABELED ON PLANS , YET NOT ON SCHEDULE.
 E-1).
  
 22)NOTE: PLEASE SEE UNIT "F" AS
 DISCONNECT FOR WH SEEMS TO BE LABELED AS
 "RTU".
  
 23)NOTE: PLEASE SEE 250.6, 250.24, NO
 "EQUIPMENT GROUNDING CONDUCTORS" SHALL
 BE INSTALLED BEFORE THEFIRST MEANS OF
 DISCONNETC. PLEASE SEE THESE ARE SHOWN
 FROM FPL, TO GUTTER, TO METER ETC.
  
 24)NOTE: PLEASE SEE NOTE #3 ON E-7 WHICH
 REFERENCES THE 1996 NEC.
 PLEASE ADJUST.
  
 25)NOTE: PLEASE SEE GROUNDING ELECTRODE
 DETAIL SHALL BE SHOWN IN LEIU OF CODE
 REFERENCE.
 PLEASE SEE FBC 1040.2.1, TECHNICAL CODES
 SHALLL NOT BE REFERENCE IN LEIU OF
 TERCHNICAL INFORMATION REQUIRED ON
 PLANS.
 PLEASE SEE 250.50, FOR MIN CONNECTIONS
 TO BE MADE.
  
 26)NOTE: PLEASE SUBMITLOAD
 CALCULATIONS FOR ALL AREAS, PANELS,
 BLDG. PLEASE SEE THESE ARE SHOWN A MIXED
 USE. PLEASE ADJSUT ACCORDINGLY.
 PLEASE ALSO INDICATE OF CONTINUOUS LOADS
 AT 125%. 215.3,230.42,
 220.10,220.11,220.13 ETC
  
 27)NOTE: PLEASE BE SURE TO SEE THE 2004
 FBC CHAPTER 13 WITH RESPECT TO THE
 ENERGY CODE AND DESIGNS. PLEASE KNOW
 THIS IS A COMMERCIAL BLGD WITH A CHANGE
 OF OCCUPANCY WHICH WILL REQUIRE ENERGY
 CODE UPGRADES.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER REVIEWER(S) WHICH
 MAY AFFECT ELECTRICAL PLANS.
  
 ** PLEASE BE SURE TO REMOVED ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED
 SHEETS SEPARATED FROM NEW SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-02-06 00:00:00IN ELEC FOR REVIEW , REVIEW IN PROGRESS.
 NOTES TO FOLLOW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-06-12 Cont ID  
Sent By mwennerg Date 2007-06-12 Time 14:14 Rev Time 0.00
Received By mwennerg Date 2007-06-12 Time 14:14 Sent To  
Notes
2007-06-12 14:21:52***DENIED***
  
 PLEASE SEE COMMENTS TAKEN FROM PREVIOUS FIRE REVIEW IN
 ADDITION TO NEW COMMENTS:
  
 1) PLEASE NOTE THAT THE RESPONSE LETTER INDICATES THAT
 NFPA 101, SEC. 6.1.14 IS NOW SHOWN ON COVER SHEET.
 PLEASE CLOUD THAT NOTE AS I WAS UNABLE TO LOCATE.
  
 2) THE WORDING SHOULDL BE FIRE ALARM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 3) FIRE EXTINGUISHERS TO BE 2A-10 B,C RATED, NOT C.
 PLEASE MAKE CORRECTION AND SHOW ON PLANS.
  
 NEW COMMENTS:
  
 1) ADDRESS REQUIRED ON BUILDING TO BE AT LEAST 6" IN
 HEIGHT AND CONTRASTING TO BACKGROUND. PLEASE SHOW SIZE
 REQUIREMENTS ON ELEVATIONS.
  
 2) PLEASE SEE ELECTRICAL COMMENTS REGARDING FIRE
 PROTECTION SYSTEMS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-11-06 Cont ID  
Sent By mwennerg Date 2006-11-06 Time 14:06 Rev Time 0.00
Received By mwennerg Date 2006-11-06 Time 14:06 Sent To  
Notes
2006-11-06 14:13:18***PROVISO***
  
 1) PLEASE NOTE THAT THE RESPONSE LETTER INDICATES THAT
 NFPA 101, SEC. 6.1.14 IS NOW SHOWN ON COVER SHEET.
 PLEASE CLOUD THAT NOTE AS I WAS UNABLE TO LOCATE.
  
 2) THE WORDING SHOULDL BE FIRE ALARM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 3) FIRE EXTINGUISHERS TO BE 2A-10 B,C RATED, NOT C.
 PLEASE MAKE CORRECTION AND SHOW ON PLANS.
  
 ALL OTHER COMMENTS HAVE BEEN ADDRESSED. PLANS WILL BE
 STAMPED WHEN RETURNED FOR OTHER REVIEW CORRECTIONS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-08-09 Cont ID  
Sent By mwennerg Date 2006-08-09 Time 14:51 Rev Time 0.00
Received By mwennerg Date 2006-08-09 Time 14:51 Sent To  
Notes
2006-08-09 00:00:00******DENIED******
  
 PLEASE SEE LAST REVIEW COMMENTS THAT
 DON'T APPEAR TO HAVE BEEN ADDRESSED.
 PLEASE SEE SOME ADDITIONAL COMMENTS.
  
 1) IN ADDITION TO APPLICABLE BUILDING
 CODES, NFPA 101, 2003 EDITION SHALL BE
 REFERENCED. THE APPLICABLE EDITION IS
 NOT INDICATED ON THE PLANS.
  
 2) MEANS OF EGRESS ILLUSTRATES BUSINESS
 ONLY, HOWEVER BUILDING MEETS
 REQUIREMENTS FOR MULTIPLE OCCUPANCY.
  
 3) WORK TO COMPLY WITH NFPA 101, SEC.
 6.1.14 MULTIPLE OCCUPANCIES AND ALL
 OTHER APPLICABLE CODES.
  
 4) PLANS SHOW BUILDING TO BE FULLY FIRE
 SPRINKLERED BUT NOT MONITORED. FIRE
 SPRINKLER SYSTEM SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE. FIRE
 SPRINKLER SYSTEMS SHALL BE SUPERVISED.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER/FIRE ALARM
 SYSTEMS.
  
 6) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED. LOCATIONS TO BE SHOWN ON
 DRAWINGS.
  
 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 9) ONE STAIRWELL ON SHT A1.1 APPEARS TO
 BE OPEN TO THE COMMON AREA. ARE
 STAIRWELLS RATED ENCLOSURES?
  
 10) SHT A1.0 INDICATES THAT STAIRWELLS
 ARE 2 HR RATED. THAT BEING THE CASE, ALL
 ASSOCIATED DOORS SHALL HAVE 1 1/2 HR
 RATING.
  
 11 OK
  
 12) PLEASE SHOW LOCATIONS OF REQUIRED
 HARDWIRED SMOKE DETECTORS THAT SHALL BE
 A MINIMUM OF 3' FROM HVAC DIFFUSERS.
  
 13) PLEASE SHOW SMOKE DETECTOR ON LEGEND
 TO CLARIFY WHAT IS SHOWN ON DRAWINGS.
  
 14) SMOKE DETECTORS SHALL OPERATE SO
 THAT ACTIVATION OF ONE WILL OPERATE ALL
 DETECTORS WITHIN DWELLING UNIT, SUITE OF
 ROOMS OR SIMILAR AREA. NFPA SEC.
 9.6.2.10.3.
  
 15) PLANS INDICATE A FIRE SPRINKLER
 SYSTEM. A LAYOUT OF THE SYSTEM IS
 REQUIRED PRIOR TO SEPARATE SUBMITAL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-08 Cont ID  
Sent By mwennerg Date 2006-02-08 Time 13:02 Rev Time 0.00
Received By mwennerg Date 2006-02-08 Time 13:02 Sent To  
Notes
2006-02-08 00:00:00******DENIED******
  
 PLAN REVIEW ONLY
  
 1) IN ADDITION TO APPLICABLE BUILDING
 CODES, NFPA 101, 2003 EDITION SHALL BE
 REFERENCED.
  
 2) MEANS OF EGRESS ILLUSTRATES BUSINESS
 ONLY, HOWEVER BUILDING MEETS
 REQUIREMENTS FOR MULTIPLE OCCUPANCY.
  
 3) WORK TO COMPLY WITH NFPA 101, SEC.
 6.1.14 MULTIPLE OCCUPANCIES AND ALL
 OTHER APPLICABLE CODES.
  
 4) PLANS SHOW BUILDING TO BE FULLY FIRE
 SPRINKLERED BUT NOT MONITORED. FIRE
 SPRINKLER SYSTEM SHALL BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER/FIRE ALARM
 SYSTEMS.
  
 6) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 7) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED. LOCATIONS TO BE SHOWN ON
 DRAWINGS.
  
 8) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENT FOR HANDRAILS AND GUARDS.
  
 9) ONE STAIRWELL ON SHT A1.1 APPEARS TO
 BE OPEN TO THE COMMON AREA. ARE
 STAIRWELLS RATED ENCLOSURES?
  
 10) SHT A1.0 INDICATES THAT STAIRWELLS
 ARE 2 HR RATED. THAT BEING THE CASE, ALL
 ASSOCIATED DOORS SHALL HAVE 1 1/2 HR
 RATING.
  
 11) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS IN
 TERMS OF CLASS A,B OR C.
  
 12) PLEASE SHOW LOCATIONS OF REQUIRED
 HARDWIRED SMOKE DETECTORS THAT SHALL BE
 A MINIMUM OF 3' FROM HVAC DIFFUSERS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 7)
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-26 Cont ID  
Sent By spalmer Date 2007-03-26 Time 18:13 Rev Time 0.00
Received By spalmer Date 2007-03-26 Time 18:13 Sent To  
Notes
2007-03-27 18:52:45TO COMM BOARD # 10
2007-03-26 18:13:47WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-09-25 Cont ID  
Sent By adarroug Date 2006-09-25 Time 16:01 Rev Time 0.00
Received By adarroug Date 2006-09-25 Time 16:01 Sent To  
Notes
2006-10-12 17:50:27TO "COMM" BD#62
2006-09-25 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-06-22 Cont ID  
Sent By adarroug Date 2006-06-22 Time 14:18 Rev Time 0.00
Received By adarroug Date 2006-06-22 Time 14:18 Sent To  
Notes
2006-07-05 00:00:00TO "COMM" BD#6
2006-06-22 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-31 Cont ID  
Sent By adarroug Date 2006-05-31 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-05-31 Time 16:33 Sent To  
Notes
2006-06-18 00:00:00TO COMM BOARD SPACE #15
2006-05-31 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-04 Time 09:47 Rev Time 0.00
Received By adarroug Date 2005-12-28 Time 09:47 Sent To  
Notes
2006-01-26 00:00:00TO "COMM" BD#32
2005-12-28 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2007-04-10 Cont ID  
Sent By hmoser Date 2007-04-10 Time 18:51 Rev Time 0.00
Received By hmoser Date 2007-04-10 Time 18:51 Sent To  
Notes
2007-04-10 19:03:50PLAN DENIED
 1) PLEASE MARK FLEX SIZES ON THE PLANS .
 2) PAGE M-3 GROUND FLOOR GRILL D AT 300 CFM DOES NOT
 MATCH AIR DEVICE SCHEDULE .
 3) PAGE M-3 UPPER FLOOR MECHANICAL SHAFT PLEASE REFER
 TO SECTION 607.5.5.1 FBC (M) 2004
 4) PLEASE PROVIDE A DTAIL FOR CURB TIE DOWN TO ROOF .
 PLAN REVIEW BY HAROLD MOSER 561-805-6732

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-10-30 Cont ID  
Sent By pkrauss Date 2006-10-30 Time 09:03 Rev Time 0.00
Received By pkrauss Date 2006-10-30 Time 08:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-08-14 Cont ID  
Sent By pkrauss Date 2006-08-14 Time 08:00 Rev Time 0.00
Received By pkrauss Date 2006-08-11 Time 14:42 Sent To  
Notes
2006-08-14 00:00:00DENIED:
 ORIGINAL REVIEW BY RON REGUEIRO DATED
 2/7/06.THE FOLLOWING COMMENTS NEED
 FURTHER CLARIFICATION:
  
 COMMENT 1:DUCT SMOKE DETECTOR SHALL BE
 INSTALLED IN THE SUPPLY AIR DUCT PER
 2004 FMC 606.2.1.PLAN SHEET M-1 THE
 HVAC UNIT SCHEDULE NOTE 6 STILL
 INDICATES THE SMOKE DETECTOR IN THE
 RETURN AIR DUCT.PLEASE REVISE.
  
 COMMENT 2:OK
 COMMENT 3:OK
  
 COMMENT 4:PLAN SHEET M-3 THE GROUND
 FLOOR PLAN INDICATES THE SUPPLY, RETURN
 AND EF-2 DUCTS PENETRATING THE FLOOR
 CEILING ASSEMBLY.PLAN SHEET A7.1 &
 A9.0 INDICATE DUCTS IN A 1HR SHAFT
 ENCLOSURE AND SHALL COMPLY WITH 2004 FMC
 607.5.5.1 OR SHOW COMPLIANCE WITH
 2004 FMC 607.6.1, WHERE DUCTS PENETRATE
 A FIRE-RESISTANCE-RATED FLOOR/CEILING
 THAT CONNECTS MORE THAN 2 STORIES, A
 SHAFT ENCLOSURE IS NOT REQUIRED PROVIDED
 A FIRE DAMPER IS INSTALLED AT THE FLOOR
 PENETRATION.
  
 COMMENT 5:SEE ELECTRICAL COMMENTS.
  
 COMMENT 6:OK
 COMMENT 7:OK
 COMMENT 8:OK
 ***************NEW COMMENTS*************
 COMMENT 9:R/A REQUIRED FROM BEDROOM
 AREA (ROOM #213). SHOW COMPLIANCE WITH
 2004 FMC 601.4.
  
 COMMENT 10: PLEASE CLARIFY SUPPLY,
 RETURN, & EF-1 DUCTS PENETRATING
 FLOOR/CEILING ASSEMBLY.PLAN SHEET A7.1
 & A9.0 INDICATE DUCTS IN 1HR SHAFT.
 FIRE DAMPERS REQUIRED WHERE DUCTS
 PENETRATE THE SHAFT ENCLOSURE (2004 FMC
 607.5.5.1. OR SHOW COMPLIANCE WITH 2004
 FMC 601.4. (SEE COMMENT 4)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-07 Cont ID  
Sent By rregueir Date 2006-02-07 Time 18:11 Rev Time 0.00
Received By rregueir Date 2006-02-07 Time 18:11 Sent To  
Notes
2006-02-07 00:00:00----------------DENIED-----------------
 1)DUCT SMOKE DETECTORS INSTALLED WITH
 RTUS 1 & 2 SHALL BE IN SUPPLY DUCT
 RATHER THAN RETURN PER 2004 FBC,M SEC
 606.2.1
  
 2)GRILL TYPES AND CFM RANGES DO NOT
 MATCH THOSE SHOWN ON AIR DEVICE SCHEDULE
  
 3)PAGE M3 UPPER FLOOR PLAN INDICATES A
 CARRIER PACKAGE TERMINAL UNIT.THIS
 EQUIPMENT IS NOT SHOWN ON EQUIPMENT
 SCHEDULE.
  
 4)PAGE M3 GROUND FLOOR PLAN - BRANCH
 DUCT FEEDING HALL 100 APPEARS TO BE
 PENETRATING A RATED PARTITION.A FIRE
 DAMPER IS NEEDED AT THIS LOCATION.THE
 BRANCH DUCT ALSO HAS NO SIZE INDICATED
 ON PLAN.
  
 5)PROVIDE ROOF PLAN SHOWING EF #S AND
 LOCATIONS.EXHAUST FAN SCHEDULE
 INDICATES ALL FANS ARE ON ROOF, BUT
 ELECTRICAL PLAN SHOWS NO PROVISION FOR
 POWER TO FANS ON ROOF.
  
 6)PAGE M3 DUCT PLAN SHOWS 8X8 EXHAUST
 DUCT UP TO EF 1 ON ROOF, TWO LOCATIONS.
 DUCT IS ROUTED IN A RATED SHAFT.HOW
 AND AT WHAT LOCATION WILL EXHAUST DUCT
 EXIT THE RATED SHAFT SINCE IT IS LOCATED
 DIRECTLY BELOW RTUS?
  
 7)PLEASE SHOW FRESH AIR CALCULATIONS PER
 2004 FBC,M SEC 403.3
  
 8)EQUIPMENT REQUIRING SERVICE ON ROOFS
 HIGHER THAN 16' REQUIRE PERMENANT ACCESS
 PER 2004 FBC,M SEC 306.5
  
 RONALD J REGUEIRO
 561.805.6734
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-05-03 Cont ID  
Sent By kstevens Date 2007-05-03 Time 06:25 Rev Time 0.00
Received By kstevens Date 2007-05-03 Time 06:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2006-10-28 Cont ID  
Sent By kstevens Date 2006-10-28 Time 12:45 Rev Time 0.00
Received By kstevens Date 2006-10-28 Time 11:41 Sent To  
Notes
2006-10-28 12:55:43DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. OK
 2. ENGINEER TAKEN OFF PLANS.
 3. ENGINEER TAKEN OFF PLANS.
 4. OK
  
 5. SHT A1.1 KITCHEN SINKS IN ROOMS 218 &
 220 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 ****COMMENT NOT ADDRESSED. NO RESPONSE.
 ******RESPONSE NOTED, BUT THE FOLLOWING INFORMATION IS
 REQUIRED TO SHOW COMPLIANCE:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED - SHOW CABINET/SINK FRONT ELEVATION - CABINET
 DOORS NOT ALLOWED)
 C. 11-4.24.6 EXPOSED PIPES & SURFACES
  
 6. OK
  
 7. THE TOILET ROOMS IN THE BUSINESS AND
 MERCANTILE OCCUPANCIES SHALL BE
 ACCESSIBLE. PLEASE SHOW THE FOLLOWING:
 FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. OK
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 (CLEARANCES NOT SHOWN)
 B. OK
 C. OK
 D. 11-4.19.5 FAUCETS
 E. OK
 FOR SHOWERS:
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT THE ABOVE INFORMATION IS
 STILL REQUIRED.
  
 8. SHT P-4 SANITARY RISER DIAGRAM SHALL
 BE SUBMITTED IN AN ISOMETRIC FORM, AND
 SHALL REFLECT THE PIPING AND FIXTURE
 LAYOUT ON SHEETS P-3 & P-4. SHOW ALL
 PIPE SIZES. SECTION 106.3.5.1.3
 ****RESPONSE NOTED, BUT SANT. RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLANS
 OF SHEETS P-3 OR P-4. - WASH MACHINE
 DRAINS REQUIRE A STANDPIPE. SECTIONS
 802.4 - RISER SHOWS A 4" STACK"DOWN TO
 BELOW SLAB, BUT NOT CONNECTED TO THE
 BUILDING DRAIN.
 ******RESPONSE NOTED, BUT THE PIPING LAYOUT DOES NOT
 REFLECT THE FLOOR PLAN IN SOME AREAS. SEE YELLOW
 HIGHLIGHTES ON SHT P-3 INDICATING AREAS WHERE THE FLOOR
 PLAN AND THE RISER DO NOT REFLECT.
  
 9.OK
 10.OK
 11. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NOT ADDRESSED
  
 **************NEW COMMENTS**************
  
 1B. OK
 2B. OK
 3B. OK
 4B. OK
 5B. OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561)805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-05 Cont ID  
Sent By kstevens Date 2006-08-05 Time 11:51 Rev Time 0.00
Received By kstevens Date 2006-08-05 Time 11:51 Sent To  
Notes
2006-08-05 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. OK
 2. ENGINEER TAKEN OFF PLANS.
 3. ENGINEER TAKEN OFF PLANS.
  
 4. SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1004.1.2 AND
 403.1. SHOW THE SQUARE FOOTAGE OF EACH
 TYPE OF OCCUPANCY FOR MERCANTILE, AND
 BUSINESS. DRINKING FOUNTAINS ARE
 REQUIRED FOR BUSINESS AND MERCANTILE
 OCCUPANCIES. TABLE 403.1.
 ****RESPONSE NOTED ON SHT P-3 INDICATES
 1 SERVICE SINK REQUIRED IN THE
 MERCANTILE AND BUSINESS OCCUPANCIES.
 THIS IS NOT REQUIRED AND SINKS ARE NOT
 SHOWN. CALCULATION TO REFLECT THE FLOOR
 PLAN. - DRINKING FOUNTAINS ARE INDICATED
 AND REQUIRED IN THE BUSINESS OCCUPANCIES
 BUT ARE NOT PROVIDED. SHOW DRINKING
 FOUNTAINS IN THE BUSINESS OCCUPANCIES. -
 WASH MACHINES ARE REQUIRED IN THE
 RESIDENTIAL OCCUPANCIES.
  
 5. SHT A1.1 KITCHEN SINKS IN ROOMS 218 &
 220 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 ****COMMENT NOT ADDRESSED. NO RESPONSE.
  
 6. SHT A1.2 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 THE SQUARE FOOTAGE OF THE ROOF. INDICATE
 THE SQUARE FOOTAGE DRAINED BY EACH
 PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED
 TO THE CALCULATIONS. SHOW THE LOCATION
 OF ALL SECONDARY DRAINS/OVERFLOW
 SCUPPERS. SUBMIT A DETAIL FOR THE
 CONDUCTOR HEAD SHOWING THE SIZE, HEIGHT
 & WIDTH, AS WELL AS THE DOWNSPOUT
 INDICATING SIZE. SECTIONS 1106 & 1107
 WITH ALL SUBSECTIONS.
 ****COMMENT NOT ADDRESSED, NO RESPONSE.
  
 7. THE TOILET ROOMS IN THE BUSINESS AND
 MERCANTILE OCCUPANCIES SHALL BE
 ACCESSIBLE. PLEASE SHOW THE FOLLOWING:
 FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.4 GRAB BARS
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 (CLEARANCES NOT SHOWN)
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
 FOR SHOWERS:
 A. 11-4.21.2 SIZE AND CLEARANCES
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
 ****NO RESPONSE, COMMENT NOT ADDRESSED.
  
 8. SHT P-4 SANITARY RISER DIAGRAM SHALL
 BE SUBMITTED IN AN ISOMETRIC FORM, AND
 SHALL REFLECT THE PIPING AND FIXTURE
 LAYOUT ON SHEETS P-3 & P-4. SHOW ALL
 PIPE SIZES. THE KITCHEN SINKS AND WASH
 MACHINES SHALL NOT DRAIN THROUGH THE
 HORIZONTAL WET VENTS OF THE BATHROOM
 GROUPS. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SECTIONS
 106.3.5.1.3 & 909.1.
 ****RESPONSE NOTED, BUT SANT. RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLANS
 OF SHEETS P-3 OR P-4. - WASH MACHINE
 DRAINS REQUIRE A STANDPIPE. SECTIONS
 802.4 - RISER SHOWS A 4" STACK"DOWN TO
 BELOW SLAB, BUT NOT CONNECTED TO THE
 BUILDING DRAIN.
  
 9. SUBMIT A WATER RISER DIAGRAM
 ISOMETRIC SHOWING ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE", (NOT IN THE CEILING).
 SECTION 106.3.5.1.3.
 ****RESPONSE NOTED, BUT WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9,
 (W/M, D/W, AND ICE MAKER IN REF.), SHALL
 BE SHOWN ON THE RISER. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING. - A FULL OPEN VALVE IS
 REQUIRED AT THE TOP OF EVERY WATER DOWN
 - FEED PIPE. SECTION 606.1(4).
  
 10. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. IF
 EXISTING INDICATE ON THE WATER RISER
 DIAGRAM. SECTION 608.13.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 11. SUBMIT A WATER HEATER DETAIL SHOWING
 THERMAL EXPANSION CONTROL, ALL REQUIRED
 VALVES, PIPING FOR T/P VALVE DISCHARGE
 AND EMERGENCY PAN DRAIN INDICATING
 PIPING MATERIAL AND TERMINATION POINT
 FOR T/P & PAN DRAIN. SECTION 106.1.1.
 12.FLOOR DRAINS ARE NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. IF DRAINING T/P
 AND PAN DRAIN IN HEATER ROOM, A FLOOR
 SINK OR HUB DRAIN WILL BE REQUIRED.
 SECTIONS 802.3 AND 802.3.2.
 ****NO RESPONSE, NOT ADDRESSED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NOT ADDRESSED
  
 **************NEW COMMENTS**************
  
 1B. FOR ACCESSIBLE FIXTURES: DOORS SHALL
 NOT SWING INTO THE CLEAR FLOOR SPACE
 REQUIRED FOR ANY FIXTURE. (SHOW ALL
 CLEAR FLOOR SPACES FOR LAVS, W/C'S,
 SHOWERS, KITCHEN SINKS ETC.). SECTION
 11-4.22.2
  
 2B. PEDISTAL LAVS ARE NOT APPROVED FOR
 ACCESSIBLE TOILET AND BATH ROOMS. SEE
 FIG 11-31 FOR REQUIRED CLEARANCES.
  
 3B. SHT A7.1 FINISH SCHEDULE DOES NOT
 INDICATE FLOOR FINISH FOR BATHROOMS 217
 OR 221. INDICATE FLOOR AND BASE FINISH
 TO COMPLY WITH SECTION 1210.1 (BLDG).
  
 4B. SHT A8.2 FINISH SCHEDULE DOES NOT
 REFLECT FINISH SCHEDULE ON SHT A7.1.
 PLEASE CORRELATE SCHEDULES. - WALL
 FINISH, (LATEX PAINT), DOES NOT MEET THE REQUIREMENT TO
 BE NONABSORBENT PER
 SECTION 1210.2.
  
 5B. SHT P-1 PLUMBING NOTES #1. FBC-2004
 NOT VIRGINA CODE COMPLIANCE REQUIRED.
 CHANGE REFERENCE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561)805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-09 Cont ID  
Sent By kstevens Date 2006-03-09 Time 08:11 Rev Time 0.00
Received By kstevens Date 2006-03-09 Time 08:02 Sent To  
Notes
2006-03-09 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
 1. SHT CS, CODE IN EFFECT AT THIS TIME
 IS THE FBC-2004. PLEASE CHANGE CODE
 REFERENCE.
 2. ALL SHEETS, ENGINEER SHALL SEAL
 SHEETS WITH REQUIRED SEAL. (SEE ATTACHED
 SHEET FROM THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS).
 3. ALL SHEETS, ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME, ADDRESS AND LICENSE
 NUMBER, AS WELL AS, THE NAME, ADDRESS,
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 ON EACH SHEET. FAC 61G15-23.002(2) & FS
 471.025.
 4. SUBMIT CALCULATIONS FOR MINIMUM
 FACILITIES PER TABLES 1004.1.2 AND
 403.1. SHOW THE SQUARE FOOTAGE OF EACH
 TYPE OF OCCUPANCY FOR MERCANTILE, AND
 BUSINESS. DRINKING FOUNTAINS ARE
 REQUIRED FOR BUSINESS AND MERCANTILE
 OCCUPANCIES. TABLE 403.1
 5. SHT A1.1 KITCHEN SINKS IN ROOMS 218 &
 220 SHALL BE ACCESSIBLE. SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 6. SHT A1.2 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 THE SQUARE FOOTAGE OF THE ROOF. INDICATE
 THE SQUARE FOOTAGE DRAINED BY EACH
 PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS ADDED
 TO THE CALCULATIONS. SHOW THE LOCATION
 OF ALL SECONDARY DRAINS/OVERFLOW
 SCUPPERS. SUBMIT A DETAIL FOR THE
 CONDUCTOR HEAD SHOWING THE SIZE, HEIGHT
 & WIDTH, AS WELL AS THE DOWNSPOUT
 INDICATING SIZE. SECTIONS 1106 & 1107
 WITH ALL SUBSECTIONS.
 7. THE TOILET ROOMS IN THE BUSINESS AND
 MERCANTILE OCCUPANCIES SHALL BE
 ACCESSIBLE. PLEASE SHOW THE FOLLOWING:
 FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.4 GRAB BARS
 C. 11-4.16.5 FLUSH CONTROLS
 D. 11-4.16.6 DISPENSERS
 FOR LAVS:
 A. 11-4.19.2 HEIGHT & CLEARANCES
 (CLEARANCES NOT SHOWN)
 B. 11-4.19.3 CLEAR FLOOR SPACE
 C. 11-4.19.4 EXPOSED PIPES & SURFACES
 D. 11-4.19.5 FAUCETS
 E. 11-4.19.6 MIRRORS
 FOR SHOWERS:
 A. 11-4.21.2 SIZE AND CLEARANCES
 B. 11-4.21.3 SEAT
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
 8. SHT P-4 SANITARY RISER DIAGRAM SHALL
 BE SUBMITTED IN AN ISOMETRIC FORM, AND
 SHALL REFLECT THE PIPING AND FIXTURE
 LAYOUT ON SHEETS P-3 & P-4. SHOW ALL
 PIPE SIZES. THE KITCHEN SINKS AND WASH
 MACHINES SHALL NOT DRAIN THROUGH THE
 HORIZONTAL WET VENTS OF THE BATHROOM
 GROUPS. ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECT TO THE
 WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. SECTIONS
 106.3.5.1.3 & 909.1.
 9. SUBMIT A WATER RISER DIAGRAM
 ISOMETRIC SHOWING ALL PIPE SIZES,
 VALVES, AND WATER HAMMER ARRESTORS
 REQUIRED BY SECTION 604.9. ARRESTORS
 SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE", (NOT IN THE CEILING).
 SECTION 106.3.5.1.3.
 10. AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. IF
 EXISTING INDICATE ON THE WATER RISER
 DIAGRAM. SECTION 608.13.2.
 11. SUBMIT A WATER HEATER DETAIL SHOWING
 THERMAL EXPANSION CONTROL, ALL REQUIRED
 VALVES, PIPING FOR T/P VALVE DISCHARGE
 AND EMERGENCY PAN DRAIN INDICATING
 PIPING MATERIAL AND TERMINATION POINT
 FOR T/P & PAN DRAIN. SECTION 106.1.1.
 12.FLOOR DRAINS ARE NOT AN APPROVED
 INDIRECT WASTE RECEPTOR. IF DRAINING T/P
 AND PAN DRAIN IN HEATER ROOM, A FLOOR
 SINK OR HUB DRAIN WILL BE REQUIRED.
 SECTIONS 802.3 AND 802.3.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561)805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 4 Status N Date 2007-04-23 Cont ID  
Sent By mflis Date 2007-04-23 Time 08:35 Rev Time 0.00
Received By mflis Date 2007-04-23 Time 08:35 Sent To  
Notes
2007-04-23 08:36:26ZONING REVIEW: NOT REQUIRED
  
 - PRODUCT SUBMITTALS ONLY; NO DRAWINGS FOR ZONING
 REVIEW
 - GROUND FLOOR RETAIL IS REQUIRED; SECOND FLOOR MAY BE
 COMMERCIAL OR RESIDENTIAL OR MIX OF THOSE USES
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 3 Status P Date 2006-10-31 Cont ID  
Sent By mflis Date 2006-10-31 Time 15:36 Rev Time 0.00
Received By mflis Date 2006-10-31 Time 15:36 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-11 Cont ID  
Sent By mflis Date 2006-07-11 Time 14:49 Rev Time 0.00
Received By mflis Date 2006-07-11 Time 14:49 Sent To  
Notes
2006-07-11 00:00:0007-11-06
  
 **PLEASE NOTE THAT COMMENTS FROM
 PREVIOUS REVIEW ARE STILL TO BE
 ADDRESSED**
  
 MJF

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-04 Cont ID  
Sent By mflis Date 2006-04-04 Time 11:33 Rev Time 0.00
Received By mflis Date 2006-04-04 Time 11:30 Sent To  
Notes
2006-04-04 00:00:00P&Z NOTES:
  
 SHEET A1.1 - SHOW PROPERTY LINE AND/OR
 VERIFY AIR RIGHTS EASEMENT FOR OLIVE
 BALCONIES
 SHEET A2.0 - BLADE SIGNS ALLOWED AT
 4'-0" MAX PROJECTION X 3'-0" MAX HEIGHT;
 MUST BE LOCATED MINIMUM OF 2'-0" FROM
 EDGE OF BUILDING;
 SHEET A4.0 = INDICATE TYPE OF METAL
 GRILLE TO BE USED FOR BALCONY INFILL
  
 MJF


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved