Plan Review Details - Permit 05121076
Plan Review Stops For Permit 05121076
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-05-19 Cont ID  
Sent By alange Date 2006-05-19 Time 16:47 Rev Time 1.50
Received By alange Date 2006-05-19 Time 16:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-16 Cont ID  
Sent By alange Date 2006-05-16 Time 10:09 Rev Time 0.00
Received By alange Date 2006-05-16 Time 10:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-04-25 Cont ID  
Sent By alange Date 2006-04-25 Time 11:15 Rev Time 1.00
Received By alange Date 2006-04-25 Time 11:15 Sent To  
Notes
2006-04-25 00:00:00DENIED
  
 4.SUBMIT PRODUCT APPROVALS FOR
 EXTERIOR DOORS AND LINTELS.
  
 5.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-06 Cont ID  
Sent By alange Date 2006-03-06 Time 09:45 Rev Time 4.00
Received By alange Date 2006-03-06 Time 09:45 Sent To  
Notes
2006-03-06 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.ALL PLANS SUBMITTED AFTER OCTOBER,
 1, 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 3.SHOW CORRECT BUILDING CONSTRUCTION
 TYPE.TYPE IV IS NOT CORRECT.SEE FBC
 2004.
  
 4.SUBMIT PRODUCT APPROVALS FOR
 EXTERIOR DOORS AND LINTELS.
  
 5.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMMENDMENT TO FBC 106.3.3
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-05-18 Cont ID  
Sent By dpalmer Date 2006-05-18 Time 14:44 Rev Time 0.00
Received By dpalmer Date 2006-05-18 Time 14:06 Sent To  
Notes
2006-05-18 00:00:00*** PLANS MADE INTO TWO COMPLETE SETS.
  
 PLANS SHALL BE ROUTED TO ALL TRADES FOR
 RE-STAMPING.
  
  
 NO TITLE BLOCK ON "S" SHEETS FOR
 ENGINEER. BUILDING REVIEW TO FOLLOW UP
 ON THIS.
  
  
 ELECTRICAL SHEETS STAMPED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-05-16 Cont ID  
Sent By dpalmer Date 2006-05-16 Time 07:25 Rev Time 0.00
Received By dpalmer Date 2006-05-16 Time 06:51 Sent To  
Notes
2006-05-16 00:00:00******* UNSAT 3RD REVIEW *******
  
  
 1) NOTE: PLEASE SEE COMMENT # 1 FROM THE
 TWO PREVIOUS , WHICH REQUESTED THE
 CERTIFICATE OF AUTHORIZATION NUMBER FOR
 "AE DESIGN INC" TO BE PLACED ON TITLE
 BLOCKS AS REQUIRED UNDER FS 481.219, AND
 FAC 61G1-16.004.
 PLEASE KNOW, BOTH NOTES REQUESTED THIS
 FOR "ALL TRADES" AND FOR "ALL" SHEETS
 CONTAINING SAID TITLE BLOCKS WHETHER
 COMMENT WAS MADE BY ANY OTHER
 REVIEWER(S).
 PLEASE SEE ALL MEP SHEETS INCLUDING NEW
 ELECTRICAL CONTAIN THE SAME
 ARCHITECTURAL FIRM'S TITLE BLOCK WITH
 OUTTHE CA #.
 PLEASE REVISE THESE SHEETS TO CORRELATE
 WITH THE REVISED "A" SHEETSOR INCLUDE
 THE REQUIRED CA #.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-24 Cont ID  
Sent By dpalmer Date 2006-04-24 Time 12:36 Rev Time 0.00
Received By dpalmer Date 2006-04-24 Time 10:23 Sent To  
Notes
2006-04-24 00:00:00******** UNSAT2ND REVIEW ********
  
 ** PLEASE SEE SOME NOTES FROM FIRST
 REVIEW AND NEW NOTE WHICH NEED TO BE
 ADDRESSED.
 SEE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND LABLED ACCORDINGLY.
  
 1)NOTE:NO, PLEASE SEE THE MISSING
 CETIFICATE OF AUTHORIZATION NUMBER FOR
 ARCHITECTURAL FIRM COULD NOT BE LOCATED
 ON SIAD SHEETS.
 THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES.**
 PLANS ARE LABLED THAT THIS # IS PENDING.
 PLEASE KNOW, UNTIL SUCH CA # IS ISSUED
 FROM THE STATE, PLANS MAY NOT LIST
 ANYTHING OTHER THAN THE ARCHITECT AS AN
 INDIVIDUAL.
 THIS A FLORIDA STATUE AND THERE ARE NO
 EXCEPTIONS.
  
 ** PREVIOUS NOTE **
 PLEASE SEE MISSING INFORMATION
 AS REQUIRED FOR TITLE BLOCKS FOR
 ARCHITECTUAL FIRM. PLEASE SEE MISSING
 PRINTED NAME AND LICENSE # FOR SAID
 ARCHITECT. PLEASE SEE MISSING
 CERITFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.001, ABD FLORIDA STATUES 481.219
 * PLEASE KNOW THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S)>
 PLEASE SEE THIS COMMENT IS FOR
 ARCHITECTUAL FIRM AS ENGINEER FIRM SHOWS
 INFORMATION AS NEEDED, HOWEVER TITLE
 BLOCK FOR ARCH FIRM ARE LOCATED ON
 ENGINEERED PLANS.
  
 2)NOTE: OK.
  
 3)NOTE: OK.
  
 4)NOTE: OK, NEW SERVICE.
  
 5)NOTE: OK, NEW SERVICE.
  
 6)NOTE:OK, NEW SERVICE.
  
 7)NOTE:NO, PLEASE SEE TABLE 450.3, A
 MAXOCP FOR THIS 225 KVA TRANSFORMER IS
 350A'S. (125%). CAN NOT USE THE 250% ASS
 THI DOES NOT MEET THE EXCCEPTIONS AS
 NOTED IN TABLE. PLEASE REVISE THE 400A
 OCP AS SHOWN.
  
 ** PREVIOUS NOTE**
 PLEASE SEE MAX OCP FOR TRANSFORMER TO BE
 125% OR PERMITTED TO PROCEED TO THE
 STANDARD OF OCP.
 PLEASE SEE 450.3,240.6
  
 8)NOTE: OK.
  
 9)NOTE: OK.
  
 10)NOTE: OK, NOTED AS 125% FOR THE
 ENTIRE SERVICE ABOVE THE MIN FOR
 CONTINOUS LOADS. OK.
  
 11)NOTE: OK.
  
 12)NOTE: OK.
  
 13)NOTE: OK.
  
 NEW NOTE**
  
 14) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1 , .2 AND .3.
 PLEASE SEE SPACE CONTROL IN SEPARATE
 SPACES AS A TIME CLOCK IS BEING SHOWN
 FOR MAIN BLDG, HOWEVER LIGHTING CONTROLS
 IN SEPARATE SPACES ARE REQUIRED. PLEASE
 SPECIFY AT LOCATIONS ON LIGHTING PLANS
 AND DETAIL DEVICES TO BE IMPLEMENTED.
 PLEASE KNOW, IF USING A TIMED DEVICE,
 NOT MORE THAN 4HRS ON OVER-RIDE IS
 PERMITTED.
 THIS DOES NOT INCLUDE AREAS OF REQUIRED
 EGRESS.
  
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECRTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT "NEW REVISED" SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE COPY OF
 THE OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFOMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-02-08 Cont ID  
Sent By dpalmer Date 2006-02-08 Time 10:20 Rev Time 0.00
Received By dpalmer Date 2006-02-08 Time 07:02 Sent To  
Notes
2006-02-08 00:00:00IN ELEC FOR REVIEW.
 ******** UNSAT ********
  
 1)NOTE: PLEASE SEE MISSING INFORMATION
 AS REQUIRED FOR TITLE BLOCKS FOR
 ARCHITECTUAL FIRM. PLEASE SEE MISSING
 PRINTED NAME AND LICENSE # FOR SAID
 ARCHITECT. PLEASE SEE MISSING
 CERITFICATE OF AUTHORIZATION NUMBER.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.001, ABD FLORIDA STATUES 481.219
 * PLEASE KNOW THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S)>
 PLEASE SEE THIS COMMENT IS FOR
 ARCHITECTUAL FIRM AS ENGINEER FIRM SHOWS
 INFORMATION AS NEEDED, HOWEVER TITLE
 BLOCK FOR ARCH FIRM ARE LOCATED ON
 ENGINEERED PLANS.
  
 2)NOTE: PLEASE BE SURE PLANS AND DESIGN
 REFLECT CURRENT CODES IN EFFECT. PLEASE
 SEE AS OF OCT 1ST,2005, THE CODE HAS
 CHANGED TO THE 2004 FLORIDA BLDG CODE.
 PLEASE ALSO ADJUST OTHER CODES
 ACCORDINGLY.
 PLEASE SEE A0.1 WHICH MENTIONS A 2001
 NEC? PLEASE KNOW THE NFPA-70 (NEC) WENT
 FROM THE 1999 TO 2002 ON JULY 1ST,2003.
 THE 2002 NFPA-70 IS CURRENTLY THE CODE
 IN EFFECT. PLEASE ALSO MAKE REFERENCE TO
 THE CURRENT 2003 NFPA-101,2002 NFPA-72.
  
 3)NOTE: PLEASE PROVIDE A COMMON
 GROUNDING RISER FOR SYSTEMS PROPOSED.
 PLEASE SEE 250.30,250.58. PLEASE SHOW A
 ONE-LINE DIAGRAM FOR THE SYSTEMA DN THE
 ATTACHMENT POINTS.
 ** PLEASE ALSO VERIFY/NOTE THE LOCATION
 IN WHICH THE SEPARATELY DERIVED SYSTEM
 SHALL BE BONDED. (FIRST MEANS OF
 DISCONNECT)? 250.24, 250.66
  
 4)NOTE: PLEASE SEE 225.31- 225.39 FOR
 THE MEANS OF DISCONNECT REQUIRED AT THE
 BLDG AS THE SERVICE MEANS OF DISCONNECT
 IS BEING SHOWN "DETACHED " FROM THE
 BLDG. PLEASE ALSO SEE 230.70 ETC FOR
 SERVICE MEANS OF DISCONNECT AND
 LOCATION.
  
 5)NOTE: PLEASE SEE DETAIL NOTE MENTIONS
 TO MOUNT THE SERVICE MEANS OF DISCONNECT
 ON FENCE AND TO SEE DETAIL ON 2.1.
 PLEASE KNOW, A FENCE DETAIL FOR TYPE AND
 CONTRUCTION COULD NOT BE LOCATED ON 2.1.
 THIS MUST BE A STRUCTUALLY SOUND AND
 SUPPORTIVE TYPE OF INSTALLATION.
 215.5
  
 6)NOTE: PLEASE SEE 250.32 FOR GROUNDING
 ELECTRODE SYSTEM TO BE LOCATED AT THE
 DETACHED BLDG AS SERVICE IS NOT ON OR
 LOCATED AT THE MAIN BLDG.
  
 7)NOTE: PLEASE SEE MAX OCP FOR
 TRANSFORMER TO BE 125% OR PERMITTED TO
 PROCEED TO THE STANDARD OF OCP.
 PLEASE SEE 450.3,240.6
  
 8)NOTE: PLEASE SEE A "POWER CONDITIONER"
 IS SHOWN ON RISER BEING FED FROM MDP,
 HOWEVER THIS COULD NOT BE LCATED ON SAID
 PANEL SCHEDULE?
 215.5
  
 9)NOTE: PLEASE SEE MISSING PANEL(S) L1
 AND N SCHEDULES?
 215.5
  
 10)NOTE: PLEASE SEE ALL CONTINUOUS LOADS
 SHALL BE SHOWN AND BASED ON 125%.
 215.3,2230.42 ETC .
  
 11)NOTE: PLEASE PORVIDE AN EMERGENCY
 BATTERY BACK UP TYPE OF LT FIXTURE IN
 ELECTRICAL ROOM.
 700.16,LS101 7.8,7.9
  
 12)NOTE: PLEASE SHOW ALL CONDUCTOR SIZES
 ON PANEL SCHEDULES FOR ALL BRANCH
 CIRCUITS.
 215.5,240.4,310.16
  
 13)NOTE: PLEASE PROVIDE GROUNDING DETAIL
 FOR PHONE SYSTEMS. INSTALLATION ENTERING
 THE BLDG.
 800.11,800.33,40,44 ETC.
  
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECRTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT "NEW REVISED" SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE ONLY SUBMIT ONE COPY OF
 THE OLD/VOIDED SHEETS FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFOMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-05-19 Cont ID  
Sent By pkrauss Date 2006-05-19 Time 15:37 Rev Time 0.00
Received By pkrauss Date 2006-05-19 Time 15:37 Sent To B
Notes
2006-05-19 00:00:00APPROVED PER MIKE WENNERGREN/PLANS
 STAMPED 5-19-06.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-04-25 Cont ID  
Sent By mwennerg Date 2006-04-25 Time 13:50 Rev Time 0.00
Received By mwennerg Date 2006-04-25 Time 13:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-08 Cont ID  
Sent By mwennerg Date 2006-02-08 Time 15:45 Rev Time 0.00
Received By mwennerg Date 2006-02-08 Time 15:45 Sent To  
Notes
2006-02-08 00:00:00******DENIED******
  
 1) SHT A0.2 ILLUSTRATES (2) SETS OF
 DOORS THAT ARE OPPOSING TO EACH OTHER.
 DOORS SHALL SWING IN DIRECTION OF TRAVEL
 WHERE SERVING OCCUPANT LOAD GREATER THAN
 50.
  
 2) REQUIRED BUILDING FIRE PROTECTION
 SYSTEMS AND MEANS OF EGRESS NOT
 IMMEDIATELY EFFECTED BY THIS WORK TO BE
 MAINTAINED DURING THIS PROJECT.
  
 3) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL.
  
 4) WILL THE NEW LOCK AND CARD READER
 ACCESS SYSTEM IMPACT THE MEANS OF
 EGRESS?
  
 5) DUCT SMOKE DETECTORS SHALL BE
 INSTALLED IN AIR SUPPLY SYSTEM, AND
 INITIATE A GENERAL FIRE ALARM WHEN
 ACTIVATED IN ACCORDANCE WITH LOCAL
 REQUIREMENT.
  
 6) DRAWING INDEX INDICATES A FIRE
 PROTECTION SHEET THAT APPEARS TO HAVE
 BEEN REMOVED PRIOR TO THIS REVIEW.
  
 7) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 8) PLEASE SEE APPLICABLE CODE REVIEW.
 NFPA 101, 2003 EDITION SHALL BE
 REFERENCED.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-05-06 Cont ID  
Sent By adarroug Date 2006-05-06 Time 13:22 Rev Time 0.00
Received By adarroug Date 2006-05-06 Time 13:22 Sent To  
Notes
2006-05-06 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-03-29 Cont ID  
Sent By adarroug Date 2006-03-29 Time 16:29 Rev Time 0.00
Received By adarroug Date 2006-03-29 Time 16:29 Sent To  
Notes
2006-04-18 00:00:00TO "COMM" BD#56
2006-03-29 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-03-06 Cont ID  
Sent By alange Date 2006-03-06 Time 09:46 Rev Time 0.00
Received By alange Date 2005-12-27 Time 14:09 Sent To  
Notes
2006-01-26 00:00:00TO "COMM" BD#41
2005-12-27 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-05-19 Cont ID  
Sent By pkrauss Date 2006-05-19 Time 15:06 Rev Time 0.00
Received By pkrauss Date 2006-05-19 Time 15:06 Sent To  
Notes
2006-05-19 00:00:00PROVISO:
 RTU'S 1 THROUGH 3 ARE REQUIRED TO HAVE
 DUCT SMOKE DETECTORS IN ACCORDANCE WITH
 2004 FMC 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-05-19 Cont ID  
Sent By pschmitz Date 2006-05-19 Time 06:55 Rev Time 0.00
Received By pkrauss Date 2006-05-18 Time 06:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-04-26 Cont ID  
Sent By pkrauss Date 2006-04-26 Time 07:43 Rev Time 0.00
Received By pkrauss Date 2006-04-26 Time 07:43 Sent To  
Notes
2006-04-26 00:00:00PROVISO:
 RTU'S 1 THROUGH 3 ARE REQUIRED TO HAVE
 DUCT SMOKE DETECTORS IN ACCORDANCE WITH
 2004 FMC 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By pkrauss Date 2006-02-15 Time 10:35 Rev Time 0.00
Received By pkrauss Date 2006-02-15 Time 10:35 Sent To  
Notes
2006-02-15 00:00:00DENIED:
 1.PLAN SHEET A0.1 BUILDING CODE REVIEW
 INDICATES THE 2001 FLORIDA BUILDING
 CODE.AS OF OCTOBER 1, 2005 THE 2004
 FLORIDA BUILDING CODE WENT INTO EFFECT.
  
  
 2.PLEASE CLARIFY CLEARANCE FOR SERVICE
 AND REPLACEMENT OF THE ACWS.PLAN SHEET
 M-3 DOES NOT APPEAR TO GIVE ANY
 CLEARANCE.SHOW COMPLIANCE WITH 2004
 306.1.
  
 3.PLEASE INDICATE DUCT SMOKE DETECTORS
 ON PLAN IN ACCORDANCE WITH 2004 FMC
 606.2.1
  
 4.PLAN SHEET M-4 ROOF TOP DETAIL,
 PLEASE INDICATE TERMINATION OF
 CONDENSATE.PLEASE NOTE, PVC INSTALLED
 ON THE ROOF SHALL HAVE PROTECTION FROM
 UV RAYS.PROVIDE INFORMATION HOW THIS
 WILL BE ACCOMPLISHED.
  
 5.PROVIDE DETAIL OF THE SUPPORT FOR
 THE CONDENSATE LINE.
  
 6.PLAN SHEET M-4 PROVIDES SUPPORT
 DETAIL FOR THE RTU.PLEASE INDICATE
 SUPPORT DETAIL FOR THE CHILLER ALSO.
 PLEASE EQUIPMENT & SUPPORTS EXPOSED TO
 THE WIND SHALL BE DESIGNED & INSTALLED
 FOR TO RESIST WIND PRESSURES ON THE
 EQUIPMENT & SUPPORTS AS DETERMINED IN
 CHAPTER 16 OF THE 2004 FBC.
  
 PLEASE PROVIDE INSTALLATION INSTRUCTIONS
 FOR EQUIPMENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-01-18 Cont ID  
Sent By pschmitz Date 2007-01-18 Time 14:33 Rev Time 0.00
Received By pschmitz Date 2007-01-18 Time 14:33 Sent To PC
Notes
2007-01-18 14:34:26REVISION FOR VENTS AND CLEAN OUTS

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-05-19 Cont ID  
Sent By pschmitz Date 2006-05-18 Time 06:56 Rev Time 0.00
Received By pschmitz Date 2006-05-18 Time 06:56 Sent To  
Notes
2006-05-19 00:00:00RE STAMP PLANS

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-04-20 Cont ID  
Sent By pschmitz Date 2006-04-20 Time 10:31 Rev Time 0.00
Received By pschmitz Date 2006-04-20 Time 10:30 Sent To  
Notes
2006-04-20 00:00:00PROVISO:\SHT P-3 SEC 606.1 (4) DOWN FEED
 SOV.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-02-25 Cont ID  
Sent By pschmitz Date 2006-02-25 Time 13:37 Rev Time 0.00
Received By pschmitz Date 2006-02-25 Time 13:37 Sent To  
Notes
2006-02-25 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CH 1, ADMINISTRATION, 2004 EDITION (
 ATFBC)FBC BUILDING 2004, CH 11
 DENIED
  
 1) SHT A9-1BREAK ROOM #102,122.
 DEETAIL 4/A9.3, 9/A9.1
 DEPTH OF SINK SHALL BE A MAXIMUM OF
 6-1/2 INCHES.
 2) SHT A8.1 JANITOR CLOSET RM #126,
 SHOW EXISTING SERVICE SINK.
 3) SHT A8.1 DRINKING FOUNTAIN NOT SHOWN
 (A)WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A
 DRINKING FOUNTAIN WHICH IS ACCESSIBLE TO
 INDIVIDUALS WHO USE WHEELCHAIRS IN
 ACCORDANCE WITH SECTION 11-4.15 AND ONE
 ACCESSIBLE TO THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING. (THIS CAN BE
 ACCOMMODATED BY THE USE OF A ?HI-LO?
 FOUNTAIN; BY PROVIDING ONE FOUNTAIN
 ACCESSIBLE TO THOSE WHO USE WHEELCHAIRS
 AND ONE FOUNTAIN AT A STANDARD HEIGHT
 CONVENIENT FOR THOSE WHO HAVE DIFFICULTY
 BENDING; BY PROVIDING A FOUNTAIN
 ACCESSIBLE UNDER SECTION 11-4.15 AND A
 WATER COOLER; OR BY SUCH OTHER MEANS AS
 WOULD ACHIEVE THE REQUIRED ACCESSIBILITY
 FOR EACH GROUP ON EACH FLOOR.)
 (B)WHERE MORE THAN ONE DRINKING
 FOUNTAIN OR WATER COOLER IS PROVIDED ON
 A FLOOR, AT LEAST 50 PERCENT OF THOSE
 PROVIDED SHALL COMPLY WITH SECTION
 11-4.15 AND SHALL BE ON AN ACCESSIBLE
 ROUTE.
 4) SHT P-3 WATER RISER, SEC 606.1 (4)
 FULLY OPEN VALVES SHALL BE INSTALLEDIN
 THE FOLLOWING LOCATIONS.ON EVERY WATER
 DOWN FEED PIPE.
 5) SHT P.3 WATER RISER.
 SEC 604.9 WATER HAMMER. A WATER HAMMER
 ARESSTOR SHALL BE INSTALLED WHERE QUICK
 CLOSING VALVES ARE UTILIZED.
 COMPLY WITH ASSE 1010
  
 END OF COMMENTS, QUESTIONS 561-805-6692