Plan Review Details - Permit 05121074
Plan Review Stops For Permit 05121074
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-02-13 Cont ID  
Sent By alange Date 2006-02-13 Time 16:10 Rev Time 0.50
Received By alange Date 2006-02-13 Time 16:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-02-08 Cont ID  
Sent By alange Date 2006-02-08 Time 07:13 Rev Time 0.50
Received By alange Date 2006-02-08 Time 07:07 Sent To  
Notes
2006-02-08 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SHOW SLAB DETAIL AND METHOD OF
 GENERATOR ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-01-25 Cont ID  
Sent By btrobaug Date 2006-01-25 Time 14:00 Rev Time 0.50
Received By btrobaug Date 2006-01-25 Time 13:09 Sent To M
Notes
2006-01-25 00:00:00 
 GAS APPLIED FOR UNDER 05111014./WRT.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-13 Cont ID  
Sent By btrobaug Date 2006-02-13 Time 12:50 Rev Time 0.00
Received By btrobaug Date 2006-02-13 Time 12:50 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-12 Cont ID  
Sent By adarroug Date 2006-01-12 Time 12:25 Rev Time 0.00
Received By adarroug Date 2006-01-12 Time 12:25 Sent To E
Notes
2006-01-12 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-08 Cont ID  
Sent By alange Date 2006-02-08 Time 07:17 Rev Time 0.00
Received By alange Date 2005-12-27 Time 15:16 Sent To  
Notes
2005-12-27 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-01-25 Cont ID  
Sent By tgordon Date 2006-01-25 Time 15:21 Rev Time 0.15
Received By tgordon Date 2006-01-25 Time 15:21 Sent To E
Notes
2006-01-25 00:00:00*** PROVISO ***
 1)GENERATOR EXHUST MUST BE TEN FEET AWAY
 FROM ANY BUILDING OPENINGS (WINDOWS,
 DOORS, ROOF & EAVE VENTS), AND TEN FEET
 AWAY FROM ADJECENT BUILDING OPENS. PER
 2004 FBC/M 401.5.1 .
 2)NEED DETAILED MANUFACTURE'S
 SPECIFICATION'S AND INSTALLATION
 INSTRUCTIONS ON JOB SITE FOR INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-09 Cont ID  
Sent By mmclean Date 2006-01-09 Time 15:46 Rev Time 0.00
Received By mmclean Date 2006-01-09 Time 15:46 Sent To I
Notes
***NONE***