Plan Review Details - Permit 05121002
Plan Review Stops For Permit 05121002
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-05-08 Cont ID  
Sent By alange Date 2006-05-08 Time 14:04 Rev Time 0.50
Received By alange Date 2006-05-08 Time 14:04 Sent To  
Notes
2006-05-08 00:00:00REVISION TO DRYWALL CEILINGS APPROVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-01-06 Cont ID  
Sent By alange Date 2006-01-06 Time 13:24 Rev Time 0.50
Received By alange Date 2006-01-06 Time 13:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2006-07-11 Time 11:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-06-27 Cont ID  
Sent By dpalmer Date 2006-06-27 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2006-06-27 Time 15:24 Sent To FIRE
Notes
2006-06-27 00:00:00******* UNSAT*********
  
 1) NOTE: PLEASE CORRELATE ELECTRICAL
 PLANS WITH BUILDING REFLECTED CEILING
 PLANS.
 PLEASE SEE EM LTS,,,,
 PLEASE SEE JOB BOXES SHOWN FOR FANS.
  
 2) NOTE: PLEASE SEE MISSING MIN EGRESS
 LIGHTING. PLEASE SEE NOW LOCATIONS WHICH
 REQUIRE A LT FIXTURE OF SOME SORT FOR
 EGRESS IS ONLY SHOWING "J" BOX.??
 PLEASE SEE LS101 7.8, 7.9, 2003
 PLEASE SEE BATH RM SHOWS THE NEW GFI,
 ONLY NO NEW OR EXISTING LTS ARE SHOWN?
 CONTROL?
  
  
 3) NOTE: PLEASE SEE AHU HEAT IS SHOWN AS
 5.5KW AND YET THE OCP SEEMS HIGH AT 60A.
 IS THIS 5.5KW PER PHASE?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-04-26 Cont ID  
Sent By dpalmer Date 2006-04-26 Time 20:31 Rev Time 0.00
Received By dpalmer Date 2006-04-26 Time 20:24 Sent To  
Notes
2006-04-26 00:00:00***** UNSAT ****
  
 1) NOTE: PLEASE SEE REDLINED PLANS FROM
 DEC 05, WHICH REQUESTED ALL CIRCUITING
 TO BE PLACED ON PLANS FOR SCOPE OF WORK
 AND TO CORRELATE WITH A PANEL SCHEDULE
 TO BE SUBMITTED.
 THIS WAS A CONDITION SET UP WITH
 ARCITECT IN ORDER TO HAVE PERMIT ISSUED
 ANDCIRCUITS NOT KNOWN AT THAT TIME.
 PLEASE ADDRESS.215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2005-12-29 Cont ID  
Sent By dpalmer Date 2005-12-29 Time 07:46 Rev Time 0.00
Received By dpalmer Date 2005-12-29 Time 07:41 Sent To  
Notes
2005-12-29 00:00:00REDLINED, RECEPT CIRCUITING SHALL BE
 INDICATED AND SHOWN BEFORE ROUGH.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-05-17 Cont ID  
Sent By mwennerg Date 2006-05-17 Time 11:14 Rev Time 0.00
Received By mwennerg Date 2006-05-17 Time 11:14 Sent To  
Notes
2006-05-17 00:00:00REVISION DATED 3/30/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-12-23 Cont ID  
Sent By mcarsill Date 2005-12-23 Time 13:07 Rev Time 0.00
Received By mcarsill Date 2005-12-23 Time 13:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-07-11 Cont ID  
Sent By pkrauss Date 2006-07-11 Time 10:40 Rev Time 0.00
Received By pkrauss Date 2006-07-11 Time 10:40 Sent To E
Notes
2006-07-11 00:00:00SENT TO BILL TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-06-16 Cont ID  
Sent By adarroug Date 2006-06-16 Time 15:57 Rev Time 0.00
Received By adarroug Date 2006-06-16 Time 15:57 Sent To  
Notes
2006-06-16 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-04-10 Cont ID  
Sent By adarroug Date 2006-04-10 Time 10:09 Rev Time 0.00
Received By adarroug Date 2006-04-10 Time 10:09 Sent To  
Notes
2006-04-25 00:00:00TO "COMM" BD#36
2006-04-10 00:00:00WAITING FOR "COMM" BD--REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-28 Cont ID  
Sent By adarroug Date 2006-01-28 Time 17:31 Rev Time 0.00
Received By adarroug Date 2006-01-28 Time 17:31 Sent To M
Notes
2006-01-28 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-06 Cont ID  
Sent By alange Date 2006-01-06 Time 13:24 Rev Time 0.00
Received By alange Date 2005-12-23 Time 11:27 Sent To  
Notes
2005-12-23 00:00:00TO "BOB"#8

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-06-27 Cont ID  
Sent By tgordon Date 2006-06-27 Time 11:51 Rev Time 0.20
Received By tgordon Date 2006-06-27 Time 11:51 Sent To E
Notes
2006-06-27 00:00:00REVISION TO MECHANICAL PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-05-11 Cont ID  
Sent By tgordon Date 2006-05-11 Time 09:31 Rev Time 0.30
Received By tgordon Date 2006-05-11 Time 09:31 Sent To  
Notes
2006-05-11 00:00:00MECHANICAL REVISION
 *** DENIED ***
 1) SUPPLY AIR GRILLS NEED TO SHOW THE
 CFM'S. PLEASE CORRECT.
  
 2) IF AHU IS TO BE INCLOSED IN A SOFFIT
 PLEASE SHOW HOW RETURN AIR WILL GET TO
 AHU.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-01-31 Cont ID  
Sent By tgordon Date 2006-01-31 Time 15:29 Rev Time 0.20
Received By tgordon Date 2006-01-31 Time 15:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By tgordon Date 2005-12-28 Time 14:25 Rev Time 0.30
Received By tgordon Date 2005-12-28 Time 14:25 Sent To  
Notes
2005-12-28 00:00:00*** DENIED ***
 1) NEW REGISTER IN SECRATARY SPACE IS
 NOT SIZED AND NOT SHOWING CFM'S..
  
 2) CFM'S. ARE NOT SHOWING AT ANY GRILLS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.