| 2006-01-13 00:00:00 | DENIED |
| | |
| | REFERENCE:FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR GAS PERMIT: |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS. |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.5.2 AND TABLES 402(1) THRU |
| | 402(34). INDICATE THESE LOADS ON THE |
| | ISOMETRIC DRAWING |
| | 4. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | 5. THE 48" GAS RANGE LOOKS COMERCIAL |
| | GRADE. PLEASE SUBMIT A COPY OF PRODUCT |
| | LISTING FROM MANUFACTURE STATING RANGE |
| | IS ACCEPTABLE FOR RESIDENTIAL USE. MAKE |
| | SURE MODEL NUMBER BEING INSTALLED IS ON |
| | THIS LISTING. SEE FBC-2004 FUEL GAS SEC- |
| | TION 623.2 |
| | |
| | PLAN REVIEW BY MIKE PERSON |
| | (561)805-6730 |
| | FAX (561)805-6731 |
| | UNDER SUPERVISION OF K.STEVENS |
| | (561)805-6721 |
| | |
| | |