| 2006-01-19 00:00:00 | 1) THE DRAWINGS SUBMITTED WITH SMITH |
| | MOUNTAIN IMPACT SYSTEMS (FL2830) DOES |
| | NOT MATCH WHAT IN ON THE STATE WEB-SITE. |
| | SEE THE APPROVAL DOCUMENT FROM THE MIAMI |
| | DADE NOA WHICH STATES DRAWING NO.WO3-64. |
| | PLEASE SUBMIT THE CORRECT DRAWINGS TO |
| | MATCH THE MIAMI DADE NOA NO 03-0925.01 |
| | REPORT. |
| | |
| | 2) SUBMIT THE UPDATED PRODUCT APPROVAL |
| | FOR THE AMWELD BUILDING PRODUCTS LLC |
| | (FL3078). SEE THE NEW UNPATED REPORTS. |
| | FL3078R1. |
| | |
| | 3) THE LOCAL PRODUCT APPROVAL |
| | APPLICATION HAS BEEN DENIED AT THIS TIME |
| | DUE TO THE FAILURE OF THE MISSEL INPACT |
| | TEST REPORT #0077-0602-96 PERFORMED BY |
| | HURRICANE TEST LABORATORY, INC.HOWEVEER, |
| | THE GLASS FAILED THE TEST. ALSO THE |
| | POLYCARBONATE PLASTIC SHEETE HAS NO |
| | INPACT RATING,SO HOW WILL THIS PRODUCT |
| | BENEFICIAL TO THE GLAZING OF THE DOOR? |
| | |
| | 4) IN THE LETTER FROM THE CORRIM |
| | COMPANY, THE MENTION OTHER TESTS WERE |
| | CONDUCTED. HOWEVER,THERE WERE NO OTHER |
| | REPORTS SUBITTED. THEREFORE, WE CANNOT |
| | APPROVE THE LOCAL PRODUCT APPROVAL |
| | APPLICATION. |
| | |
| | 5) LIST THE NUMBER OF DOORS TO BE |
| | INSTALLED AND THE ROOM NUMBERS WHERE |
| | THESE DOORS ARE BEING INSTALL |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |