Plan Review Details - Permit 05120843
Plan Review Stops For Permit 05120843
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-02-07 Cont ID  
Sent By alange Date 2006-02-07 Time 15:53 Rev Time 1.50
Received By alange Date 2006-02-07 Time 14:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-01-19 Cont ID  
Sent By dpalmer Date 2006-01-19 Time 10:30 Rev Time 0.00
Received By dpalmer Date 2006-01-19 Time 09:59 Sent To  
Notes
2006-01-19 00:00:00REDLINED COVER SHEET,
  
 2003 NFPA-101
 2002 NFPA-70

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-01-23 Cont ID  
Sent By mcarsill Date 2006-01-23 Time 13:21 Rev Time 0.00
Received By mcarsill Date 2006-01-23 Time 12:58 Sent To  
Notes
2006-01-23 00:00:001. WRONG LIFE SAFETY CODE EDITION NOTED
 ON PLANS. SHOULD READ NFPA 101, 2003
 EDITION.
  
 2. ALL CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 3. ALL EXITS TO REMAIN CLEAR AND
 UNOBSTRUCTED WHILE WORK ACTIVITIES ARE
 OCCURRING.
  
 4. ANY POTENTIAL FIRE WATCH ACTIVITIES
 MUST BE APPROVED BY THE FIRE MARSHAL OR
 ASSISTANT FIRE MARSHAL. PLEASE SEE NOTE
 # 11, ON PAGE E-3.
  
 5. GASOLINE POWERED DEMOLITION OR
 RENOVATION EQUIPMENT SHALL NOT BE USED
 INDOORS WITHOUT PROPER VENTILATION.
 CARBON MONOXIDE DANGERS COULD PRESENT
 THEMSELVES WITHOUT THE PROPER
 SAFEGUARDS.
  
 6. FIRE SPRINKLER WORK MUST BE DONE BY A
 LICENSED FIRE SPRINKLER CONTRACTOR. (2
 HEADS)
  
 7. TEMPORARY DUST BARRIERS PLANNED FOR
 USE MUST MEET MINIMUM FLAME SPREAD
 CRITERIA. NON FIRE RATED VISQUEEN SHOULD
 NOT BE USED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-07 Cont ID  
Sent By alange Date 2006-02-07 Time 15:53 Rev Time 0.00
Received By alange Date 2005-12-19 Time 08:30 Sent To  
Notes
2006-01-30 00:00:00TO "COMM" BD#53
2005-12-19 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-02-07 Cont ID  
Sent By pkrauss Date 2006-02-07 Time 12:55 Rev Time 0.00
Received By pkrauss Date 2006-02-07 Time 12:55 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2006-02-07 Cont ID  
Sent By pschmitz Date 2006-02-07 Time 11:36 Rev Time 0.00
Received By pschmitz Date 2006-02-07 Time 11:36 Sent To  
Notes
2006-02-07 00:00:00PLUMBING PLAN REVIEW EXAMINER
 PAUL SCHMITZ 561-805-6692
 [email protected]
 FBC PLUMBING 2004
 FBC FUEL GAS 2004
 FBC 2004 BUILDING CH 11
 1) SHT P-2 DEMOLITION NOTE 4
 CONFLICTS WITH GROUND FLOOR PLAN.
 EXISTING ZONE VALVE AND OUTLETS TO
 REMAIN.PLEASE CLARIFY.
 2) IF MEDICAL GAS ZONE STATION IS
 RELOCATED A SEPERATE MEDICAL GAS PERMIT
 IS REQUIRED BEFORE STARTING WORK.
  
 3) MEDICAL GAS PERMIT APPLICATION
 REQUIRMENTS
 SEPERATE PERMIT REQUIRED.
 CERTIFIED OR REGISTERED PLUMBING
 CONTRACTOR ONLY.
 MED GAS CERTIFICATES WITH APPLICATION
 FOR PERMIT.
 PLUMBING COMPANY,
 INSTALLER,
 BRAZER.
 WITH PHOTO ID FOR EACH WORKER TO COMPLY
 WITH NFPA 99-C TO OBTAIN A PERMIT.
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-02-07 Cont ID  
Sent By pschmitz Date 2006-02-07 Time 11:54 Rev Time 0.00
Received By pschmitz Date 2006-02-07 Time 11:54 Sent To  
Notes
2006-02-07 00:00:00RECONNECT NEW SINK TO EXISTING WATER,
 AND DRAIN AFTER NEW COUNTER IS
 INSTALLED.