Plan Review Details - Permit 05120803
Plan Review Stops For Permit 05120803
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-02-10 Cont ID  
Sent By amorse Date 2006-02-10 Time 12:05 Rev Time 0.00
Received By mperson Date 2006-03-01 Time 14:33 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-03-01 Cont ID  
Sent By btrobaug Date 2006-03-01 Time 07:42 Rev Time 0.33
Received By btrobaug Date 2006-03-01 Time 07:25 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-01-11 Cont ID  
Sent By btrobaug Date 2006-01-11 Time 15:22 Rev Time 0.50
Received By btrobaug Date 2006-01-11 Time 14:45 Sent To P
Notes
2006-01-11 00:00:00 
 PLEASE PROVIDE A CALCULATION
 INCLUDING ALL ADDED LOADS ,ALL EXISTING
 LOADS AND THE EXISTINGSERVICE
 SPECIFICATIONS PER 215.15.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-03-01 Cont ID  
Sent By mperson Date 2006-03-01 Time 14:35 Rev Time 0.00
Received By mperson Date 2006-03-01 Time 14:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-28 Cont ID  
Sent By adarroug Date 2006-02-28 Time 13:19 Rev Time 0.00
Received By adarroug Date 2006-02-28 Time 13:19 Sent To E
Notes
2006-02-28 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-09 Cont ID  
Sent By adarroug Date 2006-01-09 Time 09:13 Rev Time 0.00
Received By adarroug Date 2006-01-09 Time 09:13 Sent To E
Notes
2006-01-09 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-10 Cont ID  
Sent By amorse Date 2006-02-10 Time 12:05 Rev Time 0.00
Received By amorse Date 2005-12-16 Time 14:34 Sent To  
Notes
2005-12-16 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-03-01 Cont ID  
Sent By mperson Date 2006-03-01 Time 14:34 Rev Time 0.33
Received By mperson Date 2006-03-01 Time 14:34 Sent To PC
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-19 Cont ID  
Sent By mperson Date 2006-01-19 Time 11:38 Rev Time 1.25
Received By mperson Date 2006-01-19 Time 11:38 Sent To B
Notes
2006-01-19 00:00:00DENIED
  
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW:
  
 1) FBC-2004 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
  
 2) FBC-2001 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL REQUIRED ON
 HEAT PUMP)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-07 Cont ID  
Sent By mmclean Date 2006-01-07 Time 07:06 Rev Time 0.00
Received By mmclean Date 2006-01-07 Time 07:06 Sent To I
Notes
***NONE***