Plan Review Details - Permit 05120795
Plan Review Stops For Permit 05120795
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-05-30 Cont ID  
Sent By mjacobs Date 2006-05-30 Time 06:51 Rev Time 0.00
Received By mjacobs Date 2006-05-30 Time 06:30 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-05-03 Cont ID  
Sent By mjacobs Date 2006-05-03 Time 17:40 Rev Time 0.00
Received By mjacobs Date 2006-05-03 Time 16:29 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-01-10 Cont ID  
Sent By tgordon Date 2006-02-10 Time 09:19 Rev Time 0.75
Received By mjacobs Date 2006-01-10 Time 07:44 Sent To B
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2005-12-22 Cont ID  
Sent By mjacobs Date 2005-12-22 Time 14:34 Rev Time 2.50
Received By mjacobs Date 2005-12-22 Time 08:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-06-28 Cont ID  
Sent By jleahy Date 2006-06-28 Time 14:48 Rev Time 0.30
Received By jleahy Date 2006-06-28 Time 14:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2006-06-27 Cont ID  
Sent By jleahy Date 2006-06-27 Time 09:17 Rev Time 0.30
Received By jleahy Date 2006-06-24 Time 09:17 Sent To  
Notes
2006-06-27 00:00:00THE JUNCTION BOXES FOR LOW VOLTAGE ARE
 TO BE USED FOR WHAT, ANY DEVICE TIED
 INTO THESE BOXES HAS TO BE DONE BY AN
 ELECTRICAL CONTRACTOR NOT THE LOW
 VOLTAGE CONTRACTOR.LV SCOPE IS LIMITED
 TO 77VOLTS.
  
 PLEASE INDICATED TYPE OF DEVICES AND
 MAKE SURE EC HOOKS THEM UP.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-06-03 Cont ID  
Sent By jleahy Date 2006-06-03 Time 10:02 Rev Time 0.30
Received By jleahy Date 2006-06-03 Time 10:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-04-10 Cont ID  
Sent By jleahy Date 2006-04-10 Time 07:48 Rev Time 0.45
Received By jleahy Date 2006-04-10 Time 07:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-27 Cont ID  
Sent By jleahy Date 2006-03-27 Time 10:44 Rev Time 0.45
Received By jleahy Date 2006-03-27 Time 10:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-02-05 Cont ID  
Sent By jleahy Date 2006-02-05 Time 11:10 Rev Time 1.30
Received By jleahy Date 2006-02-05 Time 11:10 Sent To  
Notes
2006-02-05 00:00:00NEED TO SHOW HOW PANELS WILL BE WIRED
 ACCORDING TO NOTE 4 ON PAGE E.100
  
 JAKE LEAHY644-7291

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-03 Cont ID  
Sent By dpalmer Date 2006-01-03 Time 07:09 Rev Time 0.00
Received By dpalmer Date 2006-01-03 Time 06:58 Sent To  
Notes
2006-01-03 00:00:00********* UNSAT **********
  
  
 1)NOTE: PLEASE SEE PLANS MENTIONS "OLD
 OKEECHOBEE RD." PLEASE KNOW, THIS SHOULD
 READ "OKEECHOBEE RD AS THERE IS NOW
 "OLD" OKEECHOBEE RD LOCATED IN THE CITY
 OF WEST PALM BEACH.
 THIS CAN BE VERIFIED WITH PALM BEACH
 COUNTY PROPERTY APPRAISER'S OFFICE, OR
 THE CITY OF WEST PALM BEACH ADDRESSING
 DEPT IF NEEDED.
  
 2)NOTE: PLEASE SEE MISSING LICENSE
 INFORMATION ON TITLE BLOCK FOR
 ARCHITECTUAL FIRM. PLEASE SEE FS 481.219
 WHICH REQUIRES A CERTIFICATE OF
 AUTHORIZATION NUMBER AND THIS IS
 REQUIRED ON THE SAID TITLE BLOCKS PER
 FLORIDA ADMINISTRATIVE CODE. 61G1-16.004
 PLEASE KNOW, THIS IS REQUIRED OF ALL
 TRADES AND FOR ALL SHEETS WEATHER OR NOT
 COMMENT IS/WAS MADE BY OITHER
 REVIEWER(S).
 PLEASE SEE BLDG REVIEW WAS PASSED ,
 HOWEVER THIS IS REQUIRED.
  
 3)NOTE: PLEASE VERIFY SQ FT OF BUILD
 OUT, PERMIT APPLICATION ORIGINALLY
 INDICATED 10,000 SQ FT(WHICH CORRELATES
 WITH PLANS, THEN IT WAS MARKED OUT AND
 SHOWS 3500 SQ FT??
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASEDO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-21 Cont ID  
Sent By jleahy Date 2005-12-21 Time 09:06 Rev Time 0.30
Received By jleahy Date 2005-12-21 Time 09:05 Sent To  
Notes
2005-12-21 00:00:00NO ELECTRIC SHOWN

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-03-02 Cont ID  
Sent By nmccray Date 2006-03-02 Time 14:43 Rev Time 0.00
Received By nmccray Date 2006-03-02 Time 14:43 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-01-04 Cont ID  
Sent By mwennerg Date 2006-01-04 Time 09:26 Rev Time 0.00
Received By mwennerg Date 2006-01-04 Time 09:26 Sent To  
Notes
2006-01-04 00:00:001) PLANS APPROVED BY M CARSILLO ON
 12/21/05
 STAMPED ON THIS DATE.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS. IF FIRE ALARM IS
 MONITORING A SPRINKLER SYSTEM, IT SHALL
 BE UL CERTIFIED FOR CENTRAL STATION
 SERVICE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLANS REVIEW (561) 805-6722
2006-01-03 00:00:00NEW FIRE SHEETS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2005-12-21 Cont ID  
Sent By mcarsill Date 2005-12-21 Time 11:04 Rev Time 0.00
Received By mcarsill Date 2005-12-21 Time 10:41 Sent To  
Notes
2005-12-21 00:00:001. SEPERATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE SPRINKLER SYSTEM
 ALTERATIONS.
  
 2. SEPERATE PLANS AND PERMITS REQUIRED
 FOR ANY FIRE ALARM SYSTEM REMODELING
 OCCURS.
  
 3. ELECTRONIC DOOR CONTROLS SHALL NOT
 INTERFERE WITH ANY REQUIRED EXITING.
 PLEASE SEE DOOR SCHEDULE NOTES # 3.
  
 4. DELAYED EGRESS OR ACCESS CONTROLLED
 SECURITY DEVICES SHALL COMPLY WITH THE
 REQUIREMENTS FOR SPECIAL LOCKING
 ARRANGEMENTS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-06-23 Cont ID  
Sent By adarroug Date 2006-06-23 Time 11:34 Rev Time 0.00
Received By adarroug Date 2006-06-23 Time 11:34 Sent To E
Notes
2006-06-23 00:00:00TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-06-01 Cont ID  
Sent By adarroug Date 2006-06-01 Time 11:43 Rev Time 0.00
Received By adarroug Date 2006-06-01 Time 11:43 Sent To E
Notes
2006-06-01 00:00:00TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-05-26 Cont ID  
Sent By adarroug Date 2006-05-26 Time 15:51 Rev Time 0.00
Received By adarroug Date 2006-05-26 Time 15:51 Sent To B
Notes
2006-05-26 00:00:00TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-05-02 Cont ID  
Sent By adarroug Date 2006-05-02 Time 12:44 Rev Time 0.00
Received By adarroug Date 2006-05-02 Time 12:44 Sent To B
Notes
2006-05-02 00:00:00TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-04-03 Cont ID  
Sent By adarroug Date 2006-04-03 Time 09:37 Rev Time 0.00
Received By adarroug Date 2006-04-03 Time 09:37 Sent To M
Notes
2006-04-03 00:00:00TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-03-15 Cont ID  
Sent By adarroug Date 2006-03-15 Time 14:52 Rev Time 0.00
Received By adarroug Date 2006-03-15 Time 14:52 Sent To E
Notes
2006-03-15 00:00:00TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-27 Cont ID  
Sent By adarroug Date 2006-01-27 Time 16:14 Rev Time 0.00
Received By adarroug Date 2006-01-27 Time 16:14 Sent To  
Notes
2006-01-27 00:00:00TO "BOB"#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-28 Cont ID  
Sent By adarroug Date 2005-12-28 Time 10:22 Rev Time 0.00
Received By adarroug Date 2005-12-16 Time 15:17 Sent To  
Notes
2005-12-28 00:00:00TO "BOB"#10
2005-12-16 00:00:00TO "BOB"#9

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2006-04-03 Cont ID  
Sent By tgordon Date 2006-04-03 Time 14:57 Rev Time 0.25
Received By tgordon Date 2006-04-03 Time 14:57 Sent To  
Notes
2006-04-03 00:00:00REVISION TO MECH. PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2006-03-02 Cont ID  
Sent By tgordon Date 2006-03-02 Time 14:48 Rev Time 0.30
Received By tgordon Date 2006-03-02 Time 14:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2006-02-10 Cont ID  
Sent By tgordon Date 2006-02-10 Time 08:48 Rev Time 0.35
Received By tgordon Date 2006-02-10 Time 09:18 Sent To  
Notes
2006-02-10 00:00:00*** DENIED ***
 1) AS REQUESTED IN LAST MECHANICAL
 REVIEW, ENERGY CALCULATIONS NEED TO BE
 SIGNED BY OWNER/AGENT.
  
 2) PLEASE ADD THE NAMES AND REGISTRATION
 NO. OF THE ARCHITECT, ELECTRICAL, AND
 LIGHTING SYSTEM DESIGNER TO THE
 COMPLIANCY CERTIFICATION (E-CAL'S).THE
 PROFESSIONALS RESPONSIBLE FOR THE DESIGN
 OF THE BUILDING SHELL AND THE
 ELECTRICAL, LIGHTING, MECHANICAL AND
 PLUMBING SYSTEMS SHALL EACH SIGN THE
 ENERGY CODE COMPLIANCE FORM, TO CERTIFY
 COMPLIANCE, PER 2004 FBC 13-103.1.1.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-01-03 Cont ID  
Sent By tgordon Date 2006-01-03 Time 15:44 Rev Time 0.45
Received By tgordon Date 2006-01-03 Time 15:44 Sent To  
Notes
2006-01-03 00:00:00*** DENIED ***
 1) PLEASE OBSERVE THE SUPPLY AIR CFM'S
 AND RETURN AIR CFM'S AND PROVIDE FOR A
 BALANCED RETURN AIR, PER 2004 FBC/M
 601.4 .
  
 2) PLEASE SEE ELECT. REVIEW NOTE #2 .
  
 3) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-12-19 Cont ID  
Sent By tgordon Date 2005-12-19 Time 12:05 Rev Time 0.15
Received By tgordon Date 2005-12-19 Time 12:05 Sent To  
Notes
2005-12-19 00:00:00NO MECH. PLANS OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-02-08 Cont ID  
Sent By jleech Date 2006-02-08 Time 16:12 Rev Time 0.50
Received By jleech Date 2006-02-08 Time 16:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-01-06 Cont ID  
Sent By jleech Date 2006-01-06 Time 07:35 Rev Time 0.75
Received By jleech Date 2006-01-06 Time 07:35 Sent To  
Notes
2006-01-06 00:00:00DENIED;
 1. SHOW DETAIL OFHANDICAP DRINKING
 FOUNTAIN.
 2. SHOW CLEAR FLOOR SPACE IN TOILET
 ROOMS 107, 115, 116, AND 122. DOOR
 INSWING MUST NOT INTRUDE INTO CLEAR
 FLOOR SPACE OF LAV.
 3. SEE ELECTRICAL PLAN REVIEW NOTE 2.
 MISSING INFORMATION FROM TITAL BLOCK.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-19 Cont ID  
Sent By jleech Date 2005-12-19 Time 07:51 Rev Time 0.50
Received By jleech Date 2005-12-19 Time 07:51 Sent To  
Notes
2005-12-19 00:00:00PLUMBING PAGES MISSING. NOT ENOUGH
 INFORMATION TO DO A PLUMBING PLAN
 REVIEW.