Plan Review Details - Permit 05120783
Plan Review Stops For Permit 05120783
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By lmartine Date 2006-01-20 Time 13:06 Rev Time 0.00
Received By lmartine Date 2006-01-20 Time 13:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2006-01-19 Cont ID  
Sent By dpalmer Date 2006-01-19 Time 09:18 Rev Time 0.00
Received By dpalmer Date 2006-01-19 Time 09:18 Sent To  
Notes
2006-01-19 00:00:00NO ELECTRICAL SCOPE OF WORK SHOWN ON
 PLANS, NO ELECTRICAL CONTRACTOR SIGNED
 ON APPL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-21 Cont ID  
Sent By adarroug Date 2006-02-21 Time 16:16 Rev Time 0.00
Received By adarroug Date 2006-02-21 Time 16:16 Sent To Z
Notes
2006-02-21 00:00:00TO "Z" BOX/RESUB--OK TO EXPIDITE PER
 "RBROWN"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-20 Cont ID  
Sent By lmartine Date 2006-01-20 Time 13:06 Rev Time 0.00
Received By lmartine Date 2005-12-16 Time 10:14 Sent To  
Notes
2006-01-17 00:00:00TO "COMM" BD#29
2005-12-16 00:00:00WAITING FOR "COMM" BD

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-02-23 Cont ID  
Sent By kstevens Date 2006-02-23 Time 13:53 Rev Time 0.00
Received By kstevens Date 2006-02-23 Time 13:53 Sent To B
Notes
2006-02-23 00:00:00 
  
  
  
 SECTION 704.5
 IN THE INSTALLATION OR REMOVAL OF ANY
 PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-01-18 Cont ID  
Sent By kstevens Date 2006-01-18 Time 18:09 Rev Time 0.00
Received By kstevens Date 2006-01-18 Time 18:09 Sent To  
Notes
2006-01-18 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT CS-1 AVAILABLE CODES AND SITE
 DATA INDICATES DESIGNED TO FBC-2001. AS
 OF 10-1-05 THE FBC-2004 HAS BEEN IN
 EFFECT. PLEASE CHANGE CODE REFERENCE.
 SECTION 101.2.
 2. ALL SHEETS. SEARCH OF THE DBPR
 LICENSE SEARCH INDICATES THAT THE
 ARCHITECTURAL BUSINESS NUMBER IS
 AA26000717. (SEE ATTACHED SHEETS). TITLE
 BLOCK INDICATES AAC001708. PLEASE
 CLARIFY. FAC 61G1-16.004(2) & FS
 481.2055.
 3. SHT G-1 DETAIL 4/G-1 ACCESSIBLE
 MOUNTING HEIGHTS SHOW THE W/C TO BE 1'5"
 OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE. PER FIGURE 29 THE W/C SHALL BE
 SET 1'6" TO CENTER OF FIXTURE OFF THE
 WALL. SECTION 11-3.1. - W/C FRONTAL
 ELEVATION SHOWS THE DISPENSER AT 1'6".
 PER SECTION 11-4.16.6 AND FIG. 29B THE
 MINIMUM HEIGHT IS 1'7".
 4. SHT A-1 DETAIL 1B PROPOSED BATHROOM
 FLOOR PLAN SHOWS W/C AS 19" OFF THE WALL
 TO THE CENTER OF THE FIXTURE. PER
 SECTION 11-4.16.2 AND FIGURE 28. SECTION
 11-3.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2006-02-23 Cont ID  
Sent By mmclean Date 2006-02-23 Time 11:17 Rev Time 0.00
Received By mmclean Date 2006-02-23 Time 11:17 Sent To P
Notes
2006-02-23 00:00:00ADA COMPLIANCE RE-STRIP HC PARKING TO
 CONVERT TO A REGULAR PARKING IN REAR OF
 BUILDING & RE-STRIP TWO HC PARKING IN
 FRONT WITH RAMP (SIDEWALK).

Review Stop Z ZONING
Rev No 1 Status F Date 2006-01-19 Cont ID  
Sent By mmclean Date 2006-01-19 Time 08:54 Rev Time 0.00
Received By mmclean Date 2006-01-19 Time 08:54 Sent To B
Notes
2006-01-19 00:00:00DENIED,
 1. NEED A COMPLETE SITEPLAN OF THE
 OVERALL PROPERTY.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720