Plan Review Details - Permit 05120782
Plan Review Stops For Permit 05120782
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2005-12-22 Cont ID  
Sent By pkrauss Date 2005-12-19 Time 11:22 Rev Time 0.00
Received By pkrauss Date 2005-12-16 Time 08:54 Sent To  
Notes
2005-12-16 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-08-08 Cont ID  
Sent By pkrauss Date 2006-08-08 Time 09:45 Rev Time 0.00
Received By pkrauss Date 2006-08-08 Time 09:44 Sent To  
Notes
2006-08-08 00:00:00AS BUILT DRAWING

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2005-12-22 Cont ID  
Sent By pkrauss Date 2005-12-22 Time 11:22 Rev Time 0.00
Received By pkrauss Date 2005-12-22 Time 11:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-19 Cont ID  
Sent By tgordon Date 2005-12-19 Time 08:09 Rev Time 0.30
Received By tgordon Date 2005-12-19 Time 08:09 Sent To  
Notes
2005-12-19 00:00:00*** DENIED ***
 1) KITCHEN EXHAUST EQUIPMENT MANUFACTURE
 REQUIRES 10" ROUND STEEL DUCT NOT 6".
  
 2) PLEASE SUPPLY THE COMPLETE
 MANUFACTURE'S INSTALLATION INSTRUCTIONS
 WITH U.L. APPROVAL PAGE, FOR KITCHEN
 EXHAUST SYSTEM. AND INDICATE THE MODEL
 BEING INSTALLED.
  
 3) PLEASE SHOW COPPER LINES ON PLANS AND
 SIZES FOR WINE ROOM COOLER.
  
 4) PLEASE SUPPLY THE COMPLETE
 MANUFACTURE'S INSTALLATION INSTRUCTIONS
 WITH U.L. APPROVAL PAGE, FOR WINE ROOM
 COOLER. AND INDICATE THE MODEL BEING
 INSTALLED.
  
 5) PLEASE SHOW JOB LOCATION AND
 CONTRACTOR INFO. ON ALL PLAN PAGES.
  
 6) SUPPLY TWO COPYS OF ALL PAPER WORK
 BEING SUBMITTED.
  
 7) 12" SUPPLY AIR DUCT COMMING FROM
 A.H.U. WILL REDUCE AIR FLOW TO MUCH, AND
 SHOULD BE 14" OR LARGER. IF THIS CAN NOT
 BE DONE THAN PLEASE SUPPLY AMANUAL D
 SHOWING DUCT DESIGN, PER FBC/R M1601.1 .
  
 MECHANICAL PLAN REVIEW BY
 TOM GORDON (561) 805-6729.