Plan Review Details - Permit 05120685
Plan Review Stops For Permit 05120685
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-01-05 Cont ID  
Sent By lmartine Date 2007-01-05 Time 17:55 Rev Time 0.00
Received By lmartine Date 2007-01-05 Time 17:55 Sent To  
Notes
2007-01-05 17:58:26 
  
 REVISIONS FOR PRODUCT APPROVALS PASSED, EXCEPT FOR
 CONSTRUCTION GLASS INDUSTRIES CORP., STOREFRONT DOOR
 W/SIDELIGHTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-03-31 Cont ID  
Sent By alange Date 2006-03-31 Time 09:32 Rev Time 2.00
Received By alange Date 2006-03-31 Time 09:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-02-27 Cont ID  
Sent By alange Date 2006-02-27 Time 09:45 Rev Time 2.00
Received By alange Date 2006-02-27 Time 09:45 Sent To  
Notes
2006-02-27 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SHOW CONSTRUCTION TYPE ON PLANS.
 CONSTRUCTION TYPE SHOWN IS NOT CORRECT.
 TYPE 6 NO LONGER EXISTS UNDER THE 2004
 FBC.SHOULD BE 5A OR 5B?
  
 3. W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5.ONCE CONSTRUCTION TYPE HAS BEEN
 SELECTED THE PERMIT VALUATION WILL BE
 ADJUSTED ACCORDING TO ICC BUILDING
 VALUATION DATA.ADDITIONAL PERMIT FEES
 WILL BE DUE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE AND REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-01-23 Cont ID  
Sent By alange Date 2006-01-23 Time 09:20 Rev Time 3.00
Received By alange Date 2006-01-23 Time 09:20 Sent To  
Notes
2006-01-23 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SHOW CONSTRUCTION TYPE ON PLANS.
  
 3. W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 4.ENERGY CALCS SUBMITTED SHALL FOR THE
 2004 FBC.
  
 5.ONCE CONSTRUCTION TYPE HAS BEEN
 SELECTED THE PERMIT VALUATION WILL BE
 ADJUSTED ACCORDING TO ICC BUILDING
 VALUATION DATA.ADDITIONAL PERMIT FEES
 WILL BE DUE.
  
 6. SUBMIT SPECS FOR BBQ AND HOOD.
  
 7. SEPERATE GENERATOR PERMIT REQUIRED.
  
 8.PRODUCT APPROVALS REQUIRED FOR
 LINTELS AND STRAPS.
  
 9.ALL PRODUCT APPROVALS SUBMITTED
 SHALL HAVE THE FOLLOWING STATE PRODUCT
 APPROVAL ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 10.ORIGONAL PERMIT APPLICATION IS
 REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2007-02-07 Cont ID  
Sent By dpalmer Date 2007-02-07 Time 11:56 Rev Time 0.00
Received By dpalmer Date 2007-02-07 Time 11:56 Sent To PC
Notes
2007-02-07 11:56:54REDLINED 210.21B3 FOR OVEN BREAKER.

Review Stop E ELECTRICAL
Rev No 10 Status F Date 2007-02-02 Cont ID  
Sent By dpalmer Date 2007-02-02 Time 13:29 Rev Time 0.00
Received By dpalmer Date 2007-02-02 Time 12:25 Sent To PC
Notes
2007-02-02 13:29:54 
 ** UNSAT **
  
 1) NOTE: PLEASE SEE THE LOAD ON THE POOL PANEL EXCEEDS
 THAT OF THE RATING OF THE BREAKER WHICH FEEDS THE POOL
 PANEL.
 PLEASE SEE PREVIOUS PANEL SCHEDULE AND THIS PANEL
 SCHEDULE SHOWS 10.2 KW ON A 40A BREAKER.
  
 2) NOTE: PLEASE SEE 424.3B FOR THE MINIMUM OVER CURRENT
 PROTECTION FOR HEAT STRIPS/AHU?S AT 125%.
  
 3) NOTE: PLEASE SEE POOL PUMP WHICH SHOWS A 1-POLE
 BREAKER AND A LOAD OF 2300 VA.
 PLEASE VERIFY LOAD AND/OR THE NUMBER OF POLES.
 230.42, 240.4, 310.16 ETC.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2007-01-06 Cont ID  
Sent By dpalmer Date 2007-01-06 Time 17:30 Rev Time 0.00
Received By dpalmer Date 2007-01-06 Time 16:59 Sent To PC
Notes
2007-01-06 17:31:18REDLINED, LIGHTING CONTROLS FOR LUTRONR PANEL TO BE
 INSTALLED AS LISTED AND PER MANUFACTURE SPECS.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2006-08-15 Cont ID  
Sent By dpalmer Date 2006-08-15 Time 10:36 Rev Time 0.00
Received By dpalmer Date 2006-08-15 Time 10:36 Sent To PC
Notes
2006-08-15 00:00:00*** REDLINED
 ALL MAINS AND DISCONNECTS GROUPED PER
 225.34, 230.72

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 08:52 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 08:18 Sent To PC
Notes
2006-08-05 00:00:00******* PROVISO/ REVISION ***********
  
  
 1) NOTE: PLEASE SEE PLANS ARE MISSING
 DISCONNETC "B" FOR GROUPED WITH OTHER
 MAINS "A" AND GEN DISCONNECT.
 ALL MAINS ARE GROUPED PER CONTRACTOR,
 SEE RISER DIAGRAM. 230.72, 225.34
  
 2) NOTE: PLEASE REVISE AND SUBMIT ALL
 PANEL SCHEDULES BEFORE FINAL.
 PLEASE SEE THAT ALL CIRCUITING IS
 SPECFIC TO ROOMS AND AREAS IN WHICH THEY
 SERVE. IE; LIVING RM LTS, BEDRM 32,
 RECEPTS/LTS, KITCGEN LTS, ETC ETC.
 408.4.
 FBC 106.1.2
  
  
 **** PLEASE VERIFY NOTE #1, IF MAINIS
 GROUPED, THEN PLEASE SUBMIT THE REVISED
 PANEL SCHEDULES BEFORE FINAL.
 PLEASE KNOW, IF THERE ARE ANY OTHER
 REVISIONS, THESE ARE REQUIRED BEFORE
 ROUGH ELECTRICAL INSPECTION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2006-08-01 Cont ID  
Sent By dpalmer Date 2006-08-01 Time 07:22 Rev Time 0.00
Received By dpalmer Date 2006-08-01 Time 07:06 Sent To PC
Notes
2006-08-01 00:00:00**** UNSAT ******
  
 1) NOTE: PLEASE PROVIDE ALL SERVICE
 EQUIPMENT ON PLANS AND CORRELATE WITH
 RISER DIAGRAM. PLEASE SEE
 MAINS/DISCONNECTS ARENOT GROUPED,
 PLEASE SEE MISSING MAIN FOR PANEL "B".
 ETC
 230.70, 230.2,230.72,230.34 ETC
  
 2) NOTE: PLEASE PROVIDE COMPLETE PANEL
 SCHEDULES SHOWING ALL OCP , CONDUCTOR
 SIZES AND BRANCH CIRCUITS. NEED TO
 VERIFY OCP WITH WIRE SIZES, LOADS ETC.
 PLEASE BE SURE PANEL SCHEDULES ARE
 SPECIFIC TO THE ROOMS AND AREAS IN
 HOUSE. IE: LIVING RM LTS, DINING
 RECEPTS, MASTER BEDRM LT ETC .
 408.4,240.4,310.16, 215.5
  
  
 3) NOTE: PLEASE SEE 210.8A7 AS THE
 RECEPTS LOCATED WITHIN 6FT OF SINK SHALL
 BE GFI/GFI PROTECTED.
  
 4) NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING ON PLANS IN LIVING RM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2006-04-13 Cont ID  
Sent By dpalmer Date 2006-04-13 Time 08:50 Rev Time 0.00
Received By dpalmer Date 2006-04-10 Time 10:40 Sent To PC
Notes
2006-04-10 00:00:00CALLED CONTRACTOR TO HAVE A CONFERENCE
 CALL TO GO OVER PLANS SUBMITTED FOR
 CORRECTIONS, AND SUBMITTIALS.
 LEFT MESSAGE AT 8:30AM

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2006-03-17 Cont ID  
Sent By dpalmer Date 2006-03-17 Time 21:58 Rev Time 0.00
Received By dpalmer Date 2006-03-17 Time 20:27 Sent To M
Notes
2006-03-17 00:00:00******* UNSAT 3RD REVIEW *********
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW
 AND SOME NEW NOTES DUE TO CHANGES IN
 PLANS FROM PREVIOUS PLANS SUBMITTED.
  
 SEE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PERVIOUS REVIEW.
  
 ********** UNSAT *************
  
  
 1)NOTE:NOTE #1 , OK, HOWEVER PLEASE
 SEE SOME CIRCUITS ARE STILL SHOWN ON
 PLANS. PLEASE ALSO SEE CIRCUIT B-7 IS
 STIL SHOWN FOR GDO , YET THE GDO IS A
 DEDICATED CIRCUIT ON PANEL SCHEDULE.
 MOSTCIRCUITING WAS REMOVED FROM PLANS.
  
 ** PREVIOUS NOTE**
 PLEASE CORRELATE CIRCUTING ON PLANS WITH
 PANEL SCHEDULES SUBMITTED.
  
 2)NOTE: NOTE #2 OK.
  
 3)NOTE:NOTE #3 OK, HOWEVER PLEASE SEE
 LOAD ON PANEL "A" (41.3KW) DOES NOT
 CORRELATE WITH LOAD SHOWN ON
 CALCUALTIONS BELOW PANEL. PLEASE SEE
 TOTAAL LOAD IS SHOWN AS 11,440 VA.
 PLEASE ALSO SEE THE FOLLOWING COMMENT AS
 THIS WILL AFFECT LOAD CALCUALTIONS.
  
  
 ** PREVIOUS REVIEW**
 PLEASE SUBMIT LOAD CALCUALTIONS. PLEASE
 SEE MISSING CIRCUITS IN FORTH COMING
 NOTES WHICH WILL AFFECT LOAD CALCS.
 PLEASE SEE LOADS ON POOL PANEL DO NOT
 CORRELATE WITH THE LOAD ON PANEL "B".
 PLEASE BE SURE TO INDICATE IF CONTINUOUS
 LOADS ARE ALREADY FIGURED AT 125% (POOL
 PUMPS) ANY LOADS FOR 3 OR MORE HRS.
 215.5,220, 215.3,230.42 ETC.
  
 4)NOTE:NOTE #4 NO, PLEASE SEE LOADS
 FOR AHUS' ON PANEL "A" ARE BEING DERATED
 AT 65%. THESE MUST BE SHOWN AT 100%.
 PLEASE KNOW, AS GENERATOR IS SHOWN AS
 45KW, THIS SHOULD BE OK, HOWEVE THIS
 NEEDS TO BE SHOWN. IF PROVIDING LOAD
 SHEDDING, PLEASE PROVIDE DETAIL/
  
 ** PREVIOUS REVIEW**
 PLEASE SEE THAT SEPARATE LOAD
 CALCS ARE NEEDED FOR THE PANEL WHICH
 WILL
 BE FED FROM THE GENERATOR AS ANY HEAT
 AND MOTOR LOADS SHALL BE FIGURED AT
 100%. PLEASE KNOW, AUTOMATIC LOAD
 SHEDDING IS PERMITTED, HOWEVER PLEASE
 PROVIDE THIS DETAIL SINCE THE GEN IS
 UNDER THE HOUSE PERMIT.
 220,702.5,215.5
  
 5)NOTE: NOTE #5 NO, PLEASE SEE THIS IS
 STILL NOT INDICATED ON PLANS AND SIZING
 CONDUCTORS PER 445.13 CAN NOT VERIFIED.
  
 ** PREVIOUS REVIEW**
 PLEASE INDICATE THE OCP AT THE
 GENERATOR ON PLANS/RISER. PLEASE 445.13
 FOR SIZING OF CONDUCTORS.
 215..5
  
 6)NOTE:NOTE #6 NO, PLEASE SEE RISER
 APPEARS TO SHOW MAINS GROUPED, HOWEVER
 PLANS DO NOT CORRELATE WITH THIS OR
 GROUPING OF MEANS OF DISCONNECTS ETC..
 PLEASE SEE PLANS SHOW METER AND ONE MAIN
 AT FRONT OF HOUSE AND ATS , DISCONNECT
 AND GEN DISCONNECT AT REAR OF HOUSE??
 PLEASE REVISE PLANS.
  
  
 ** PREVIOUS REVIEW**
 PLEASE SEE THAT THE MAINS ARE GROUPED AT
 MAIN ELECTRICAL SERVICE.
 PLEASE SEE THERE IS A GEN DISCONNECT
 SHOWN ON PLANS, BUT NOT ON RISER. IN
 EITHER CASE THIS DISCONNECT IS REQUIRD
 TO BE GROUPED WITH OTHER MAINS FOR
 HOUSE.
 230.72,225.34 ETC
 225.31-225.39
  
 7)NOTE:NOTE #7 NO, PLEASE SEE THE SAME
 SPEC SHEET WERE SUBMITTED BACK AND NO
 MCB AS REQUIRED IS SHOWN, DETAILED OR
 NOTED. ATS SPEC ONLYS NOTE THAT THIS
 EQUIPMENT IS "SERVICE ENTRANCE RATED" AS
 SERVICE EQUIPMENT", WHICH DOES NOT MEAN
 IT CONTAINS A MCB/OR MAIN AS SHOWN ON
 ON RISER DIAGRAM.
  
 ** PREVIOUS REVIEW **
 PLEASE SEE RISER SEEMS TO INDICATE THE
 ATS CONTAINS A MCB? THIS CAN NOT BE
 VERIFIED AS THE SPECS SUBMITTED DO NOT
 SEEM TO SHOW THIS.
 PLEASE SEE THAT THE MEANS OF DISCONNECT
 SHALL BE LOCATED ON THE OUTSIDE,(READILY
 ACCESSSIBLE), RATED FOR THE LOAD SERVED,
 AND SHALL BE MANUAL.
 230.76,230.79, 230.70
  
 8)NOTE: OK
  
 9)NOTE: NOTE #9 NO, PLEASE KNOW, IT IS
 STILL THIS AHJ'S INTERPRETATION THAT THE
 AMOUNT OF FIXTURES SHOWN GO EBOVE WHAT
 WOULD BE NORMAL "GENERAL LIGHTING" AS
 MENTIONED IN THE EXCEPTION TO 220.3(A)
 AND 220.3B4 AS NOTED IN HANDBOOK.
 PLEASE INDICATE THE # OF FIXTURES X
 -WATTS PER FIXTURE AND ONLY ADD TO OVER
 ALL LOAD.
  
 ** PREVIOUS REVIEW**
 PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
  
 10)NOTE:NOTE #10 NO, PLEASE SEE PLANS,
 PANEL SCHEDULES AND RISER. PLEASE SEE
 PLANS MISSING THE UN-LABELED SUB-PANEL
 FED FROM PANEL "A"?? PLEASE LABEL ALL
 PANELS.
  
 ** PREVIOUS NOTE**
 PLEASE SEE PLANS SHOWS PANELS
 A, B, C, AND D, PLEASE CORRELATE.
 215.5
  
 11)NOTE: NOTE #11 ? NO, THIS IS UNCLEAR
 AS IT SEEMS A NOTE WAS ADDED TO
 "ELECTRICAL NOTES" #22 WHICH MENTIONS A
 STUB OUT FOR "FUTURE" LANDSCAPE
 LIGHTING, HOWEVER PLEASE SEE NOTES #9
 AND #10 ARE STILL NOTED?? PLEASE REMOVE
 NOTES AS THESE ARE SEPARATE PERMIT
 ITEMS.
  
 ** PREVIOUS NOTE**
 PLEASE SEE NOTES PERTAINING TO
 LV LANDSCAPE LTS AND LV SPRKR WIRING
 THIS WOULD EITHER ALL BE COMPLETE UNDER
 MAIN PLANS, OR SHALL BE UNDER SEPARATE
 PERMITS AND PLANS.
  
 12)NOTE:NOTE #12NO, PLEASE SEE THERE
 ARERECEPTS MISSING WHICH WERE REDLINED
 ON PREVIOUS PLANS, BUT DIDN'T GET PLACED
 ON PLANS. PLEASE SEE REDLINED LOCATIONS.
  
 ** PREVIOUS NOTE**
 PLEASE SEE 210.52 FOR MISSING RECEPTS
 FOR 2',6',12' RULE.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 NO, THESE WERE NOT
 ADDED AS REQUIRED.
  
 ** PREVIOUS NOTE**
 PLEASE SEE MISSING DEDICATED
 BATH(S) CIRCUIT(S), SHALL BE 20A AND
 #12. 210.11C3
  
 16)NOTE: NOTE #16 OK, NOTED ON PLANS.
  
 17)NOTE: NOTE #17 ? UNCLEAR AS GEN SLAB
 DETAIL WAS NOT LOCATE ON PLANS? SEE ANY
 COMMENTS FROM BLDG TRADES.
  
 ** PREVIOUS NOTE**
 PLEASE SEE BLDG REVIEW COMMENTS
 FOR SLAB DETAIL REQUIRED.
  
 18)NOTE: NOTE #18 NO? THIS IS NOT CLEAR
 AS THE POOL PANEL MENTIONS A 2-POLE FEED
 TO ANOTHER "POOL PANEL" ?? IS THIS THE
 "JANDY PANEL"?PLEASE ALSO SEE NEW
 COMMENTS FOR POOL EQUIPMENT ETC.
  
 ** PREVIOUS NOTE**
  
 PLEASE INDICATE WHERE AND HOW
 "JANDY PANEL" IS BEING FED ETC.
 A PANEL AND CIRCUTIING IS SHOWN ON
 PLANS, HOWEVER PANEL SCHEDULES DO NOT
 INDICATE ANY FEEDING OF SAID PANEL.
 215.5
 PLEASE ALSO VERIFY GFI RECEPT IN FRONT
 OF HOUSE BEING FED FROM THIS PANEL?
  
 *********** NEW NOTES ****************
  
 19) NOTE: PLEASE CLARIFY THE POOL PUMP
 BEING FED FROM PANEL "B"?
 PLEASE SEE POOL PANEL(?) DOES NOT
 INDICATE THE "WATER FALL" PUMP? IS THIS
 FED FROM THE "JANDY PANEL" ??
 PLEASE ALSO SEE LOAD ON "POOL PANEL" IS
 SHOWN @ 42.5 AMPS, HOWEVER THE BREAKER?
 OCP FROM PANEL "B" ONLY SHOWS A 40A
 BRKR? PLEASE SEE POOL PANEL SHOWS 60A
 BRKR PANEL?
 PLEASE VERIFY AND INCREASE OCP. PLEASE
 SEE NOTE #3 FROM PREVIOUS REVIEW WHICH
 REQUESTED THE CONTINUOUS LOADS, 3 OR
 MORE HRS TO BE SHOWN AT 125%. 215.3,
 230.42. PLEASE KNOW, THE POOL PUMP WOULD
 BE CONSIDERED , AS THIS RUNS FOR MORE
 THAN 3 HRS.
  
 20) NOTE: PLEASE SEE PANEL "A" DOES NOT
 INDICATE THE OCP AND CONDUCTORS FOR
 LIGHTING SUB-PANEL. PLEASE LABEL, AS
 PLANS INDICATES A PANEL "C" OUTSIDE,
 HOWEVER THIS IS UNCLEAR IF THIS IS THE
 POOL PANEL ? OR GEN LIGHTING PANEL.
 215.5
  
 21)NOTE: PLEASE SEE GEN LIGHTING PANEL
 WHICH SHOWS ALL BRANCH CIRCUITS AS 2POLE
 CIRCUITS? THIS MUST BE A MISPRINT?
 215.5
  
 22)NOTE: PLEASE SEE NOTE WHICH WAS ADDED
 TO PREVIOUS PLAN REVIEW, WHICH REQUIRED
 TOTAL VALUATION OG GEN, ATS ETC TO BE
 ADDED TO MAIN HOUSE VALUATION IF BEING
 PERMITTED UNDER MAIN HOUSE.
 108.3 FBC ADMINISTRATIVE CODE AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 ** PLEASE SUBMIT TWO COMPLETE SETS OF
 PLANS FOR REVIEW. PLEASE BE SURE TO
 INSERT ALL ELECTRICAL/ MECHANICAL PLANS
 INTO HOUSE SETS.
 PLEASE SEE MECHANCIAL PLANS ARE NOT
 ATTACHED TO PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO THE TWO COMPLETED SETS FOR
 REVIEW AND STAMPING. PLEASE SEE ONE SET
 OF OLD/VOIDED SHEETS SHOUDL EB SUBMTTED
 FOR REFERENCE ONLY
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-02-15 Cont ID  
Sent By dpalmer Date 2006-02-15 Time 12:02 Rev Time 0.00
Received By dpalmer Date 2006-02-14 Time 19:22 Sent To M
Notes
2006-02-15 00:00:00********** UNSAT *************
  
  
 1)NOTE: PLEASE CORRELATE CIRCUITING ON
 PLANS WITH PANEL SCHEDULES SUBMITTED.
 PLEASE SEE THERE ARE MANY ITEMS EITHER
 MISSING OE DO NOT MATCH.
 215.5
  
 2)NOTE: PLEASE CORRELATE AHU/HEAT LOADS
 AS ALL THE KW RATINGS ON MECHANICAL
 PLANS DO NOT CORRELATE WITH ELECTRICAL
 PLANS.
 PLEASE ALSO SEE OTHER COMMENTS WITH
 RESPECT TO LOADS.
 215.5
  
 3)NOTE: PLEASE SUBMIT LOAD CALCUALTIONS.
 PLEASE SEE MISSING CIRCUITS IN FORTH
 COMING NOTES WHICH WILL AFFECT LOAD
 CALCS.
 PLEASE SEE LOADS ON POOL PANEL DO NOT
 CORRELATE WITH THE LOAD ON PANEL "B".
 PLEASE BE SURE TO INDICATE IF CONTINUOUS
 LOADS ARE ALREADY FIGURED AT 125% (POOL
 PUMPS) ANY LOADS FOR 3 OR MORE HRS.
 215.5,220, 215.3,230.42 ETC.
  
 4)NOTE: PLEASE SEE THAT SEPARATE LOAD
 CALCS ARE NEED FOR THE PANEL WHICH WILL
 BE FED FROM THE GENERATOR AS ANY HEAT
 AND MOTOR LOADS SHALL BE FIGURED AT
 100%. PLEASE KNOW, AUTOMATIC LOAD
 SHEDDING IS PERMITTED, HOWEVER PLEASE
 PROVIDE THIS DETAIL SINCE THE GEN IS
 UNDER THE HOUSE PERMIT.
 220,702.5,215.5
  
 5)NOTE: PLEASE INDICATE THE OCP AT THE
 GENERATOR ON PLANS/RISER. PLEASE 445.13
 FOR SIZING OF CONDUCTORS.
 215..5
  
 6)NOTE: PLEASE SEE THAT THE MAINS ARE
 GROUPED AT MAIN ELECTRICAL SERVICE.
 PLEASE SEE THERE IS A GEN DISCONNECT
 SHOWN ON PLANS, BUT NOT ON RISER. IN
 EITHER CASE THIS DISCONNECT IS REQUIRD
 TO BE GROUPED WITH OTHER MAINS FOR
 HOUSE.
 230.72,225.34 ETC
 225.31-225.39
  
 7)NOTE: PLEASE SEE RISER SEEMS TO
 INDICAT THE ATS CONTAINS A MCB? THIS CAN
 NOT BE VERIFIED AS THE SPECS SUBMITTED
 DO NOT SEEM TO SHOW THIS.
 PLEASE SEE THAT THE MEANS OF DISCONNECT
 SHALL BE LOCATED ON THE OUTSIDE,(READILY
 ACCESSSIBLE), RATED FOR THE LOAD SERVED,
 AND SHALL BE MANUAL.
 230.76,230.79, 230.70
  
 8)NOTE: PLEASE SEE RISER INDICATES A
 400A SERVICE BEING PROVIDED, THE MIN
 SIZE GROUNDING ELECTRODE CONDUCTOR SHALL
 BE 1/0 AS SIZED PER 310.15B6, 250.66.
  
 9 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 10)NOTE: PLEASE SEE PLANS SHOWS PANELS
 A, B, C, AND D, PLEASE CORRELATE.
 215.5
  
 11)NOTE: PLEASE SEE NOTES PERTAINING TO
 LV LANDSCAPE LTS AND LV SPRKR WIRING
 THIS WOULD EITHER ALL BE COMPLETE UNDER
 MAIN PLANS, OR SHALL BE UNDER SEPARATE
 PERMITS AND PLANS.
  
 12)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS FOR 2',6',12' RULE.
  
 13)NOTE: PLEASE SEE 210.52C1 FOR
 POSSIBLE MISSING GFI RECEPTS ALONG
 KITCHEN COUNTERSPACE.
  
 14)NOTE: PLEASE SEE MISSING TWO MIN
 SMALL APPLIANCE CIRCUITS AS REQUIRED PER
 210.52B1,220.16,210.11B1
  
 15)NOTE: PLEASE SEE MISSING DEDICATED
 BATH(S) CIRCUIT(S), SHALL BE 20A AND
 #12. 210.11C3
  
 16)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT CIRCUITS PER 210.12B, 2002 NEC.
  
 17)NOTE: PLEASE SEE BLDG REVIEW COMMENTS
 FOR SLAB DETAIL REQUIRED.
  
 18)NOTE: PLEASE INDICATE WHERE AND HOW
 "JANDY PANEL" IS BEING FED ETC.
 A PANEL AND CIRCUTIING IS SHOWN ON
 PLANS, HOWEVER PANEL SCHEDULES DO NOT
 INDICATE ANY FEEDING OF SAID PANEL.
 215.5
 PLEASE ALSO VERIFY GFI RECEPT IN FRONT
 OF HOUSE BEING FED FROM THIS PANEL?
  
 ** PLEASE SUBMIT TWO COMPLETE SETS OF
 PLANS FOR REVIEW. PLEASE BE SURE TO
 INSERT ALL ELECTRICAL MECHANICAL PLANS
 INTO HOUSE SETS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT NEW REVISED
 SHEETS INTO THE TWO COMPLETED SETS FOR
 REVIEW AND STAMPING. PLEASE SEE ONE SET
 OF OLD/VOIDED SHEETS SHOUDL EB SUBMTTED
 FOR REFERENCE ONLY
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THEREARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 *** VALUATION FOR COMPLETE SCOPE
 INCLUDING GENERATOR INOT ELECTRICAL
 SHALL BE INCREASED
2006-02-14 00:00:00REVIEW IN PROGRESS, NOTES TO FOLLOW.
 PLANS WILL GO INTO "F" STATUS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-01-20 Cont ID  
Sent By jleahy Date 2006-01-20 Time 22:11 Rev Time 0.30
Received By jleahy Date 2006-01-20 Time 22:05 Sent To  
Notes
2006-01-20 00:00:00PLANS FAIL TO SHOW BRANCH CIRCUITS AS
 LABLED ON DRAWINGS PANEL "B" IS LACKING
 MANY CIRCUITS SHOWN ON DRAWINGS.
  
 NO CUT SHEETS FOR ATS AND OTHER
 EQUIPMENT ASSOCIATED WITH THE GENERATOR
  
 ARE MAINS GROUPED TOGETHER?
  
 LOADS ON PANELS WILL NOT MEET PLANS
 AS SHOWN TO MANY CIRCUITS MISSING.
  
 THIS PERMIT HAS BEEN LINKED TO THE
 MASTER THIS PERMIT IS 06010397
  
 SEE DEWEY PALMERS COMMENTS FROM ORIGINAL
 PLAN REVEIW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-27 Cont ID  
Sent By dpalmer Date 2005-12-27 Time 21:02 Rev Time 0.00
Received By dpalmer Date 2005-12-27 Time 20:52 Sent To M
Notes
2005-12-27 00:00:00IN ELEC FOR REVIEW, REVIEW IN PROGRESS
 *********** UNSAT *************
  
  
 1)NOTE; PLEASE SUBMIT MIN PLANS MEETING
 COMPLETE SCOPE OF WORK FOR NEW
 ELECTRICAL FOR DWELLING MEETING MIN
 CODES FOR 2002 NFPA-70, NFPA-72(2002).
 PLEASE ALSO KNOW, IF GENERATORSHOWN ON
 PLANS IS GOING TO BE PERMITTED UNDER
 BASE BUILDING , PLEASE INCLUDE ON PLANS,
 WIRING DIAGRAM ETC.
 PLEASE INCLUDE ALL MANUFACTURES CUT/SPEC
 SHEETS FOR GEN, ATS, PRIME MOVER, ALL
 SHOWING THE NRTL LISTINGS.
 FBC ADMINISTRATIVE CODE.
 106.3.5.4,106.3.4.3,1.6.3
 NEC 215.5, ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-02-01 Cont ID  
Sent By adarroug Date 2007-02-01 Time 10:26 Rev Time 0.00
Received By adarroug Date 2007-02-01 Time 10:26 Sent To E
Notes
2007-02-01 10:27:20TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-01 Cont ID  
Sent By adarroug Date 2006-11-01 Time 17:49 Rev Time 0.00
Received By adarroug Date 2006-11-01 Time 17:49 Sent To P
Notes
2006-11-01 17:49:33TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 11:39 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 11:39 Sent To E
Notes
2006-08-03 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-04-05 Cont ID  
Sent By adarroug Date 2006-04-05 Time 17:03 Rev Time 0.00
Received By adarroug Date 2006-04-05 Time 17:03 Sent To E
Notes
2006-04-05 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-03-16 Cont ID  
Sent By adarroug Date 2006-03-16 Time 17:27 Rev Time 0.00
Received By adarroug Date 2006-03-16 Time 17:27 Sent To E
Notes
2006-03-16 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-13 Cont ID  
Sent By adarroug Date 2006-02-13 Time 16:50 Rev Time 0.00
Received By adarroug Date 2006-02-13 Time 16:50 Sent To E
Notes
2006-02-13 00:00:00TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2005-12-27 Cont ID  
Sent By adarroug Date 2005-12-27 Time 09:06 Rev Time 0.00
Received By adarroug Date 2005-12-27 Time 09:06 Sent To E
Notes
2005-12-27 00:00:00TO "SFR" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-23 Cont ID  
Sent By alange Date 2006-01-23 Time 09:20 Rev Time 0.00
Received By alange Date 2005-12-14 Time 16:22 Sent To  
Notes
2005-12-14 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-03-20 Cont ID  
Sent By tgordon Date 2006-03-20 Time 11:37 Rev Time 1.00
Received By tgordon Date 2006-03-20 Time 11:36 Sent To P
Notes
2006-03-20 00:00:00*** PROVISO ***
 1) SUPPLY COMBUSTION AIR BOR GAS CLOTHS
 DRYER AND GAS WATER HEATER, PER 2004
 FBC/R CH.17 .
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-02-15 Cont ID  
Sent By tgordon Date 2006-02-15 Time 16:12 Rev Time 1.15
Received By tgordon Date 2006-02-15 Time 16:12 Sent To P
Notes
2006-02-15 00:00:00*** DENIED ***
 1) PLEASE ADD COMBUSTION AIR
 CALCULATIONS TO THE MECHANICAL PLANS FOR
 THE GAS CLOTHS DRYER, AND THE GAS WATER
 HEATER SHOWING THE BTU'S, CUBIC FEET,
 OPENING SIZE, ECT. PER 2004 FBC/R CH. 17
  
 2) NEED TO SUPPLY COMBUSTION AIR FOR GAS
 CLOTHS DRYER, AND GAS WATER HEATER, PER
 2004 FBC/R CH. 17.
  
 3) PLEASE PROVIDE THE PAGE WITH THE U.L.
 APPROVAL FOR THE GAS GRILL.
  
 4) THE INFORMATION YOU PROVIDED FOR THE
 HOOD IS FOR A RANGE NOT A GRILL (SEE
 ATTACHED SAMPLE).
  
 5) PLEASE PROVIDEDETAILED
 MANUFACTURE'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR THE
 VENTLESS FIRE PLACE IN THE LIVING ROOM,
 AND THE COVERED PATIO.
  
 6) PLEASE PROVIDE MANUAL J CALCULATIONS
 TO GO WITH YOUR ENERGY CALCULATIONS
 SUBMITED, PER 2004 FBC 13-607.1.ABC.1 .
  
 7) PLEASE BE INFORMED THAT WHEN
 SUPPLYING AIR CONDITIONING TO A GARAGE
 TO COMPLY WITH 2004 FBC/R 309.1.1 DUCT
 PENETRATIONS AND R 309.2 SEPARATION
 REQUIRED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By tgordon Date 2005-12-28 Time 11:49 Rev Time 0.20
Received By tgordon Date 2005-12-28 Time 11:49 Sent To P
Notes
2005-12-28 00:00:00NO MECHANICAL PLANS SUBMITTED. HAS MECH.
 PERMIT NUMBER.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-01-04 Cont ID  
Sent By jleech Date 2007-01-04 Time 13:37 Rev Time 0.00
Received By jleech Date 2007-01-04 Time 13:37 Sent To  
Notes
2007-01-04 13:38:19REVISED RISER DIAGRAM OK

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-03-30 Cont ID  
Sent By jleech Date 2006-03-30 Time 07:28 Rev Time 0.00
Received By jleech Date 2006-03-30 Time 07:28 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-02-24 Cont ID  
Sent By jleech Date 2006-02-24 Time 07:43 Rev Time 0.50
Received By jleech Date 2006-02-24 Time 07:43 Sent To B
Notes
2006-02-24 00:00:00DENIED;
 1.HORIZONTAL DRY VENTS NOT TO CODE 3
 LOCATIONS. FBC-2004 RESIDENTIAL
 SEC.P3104.3.
 2.TWO BIDETS ARE NOT VENTED. NO VENT
 BETWEEN TOILET AND BIDET.
 ONE SET OF PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-29 Cont ID  
Sent By jleech Date 2005-12-29 Time 10:19 Rev Time 1.00
Received By jleech Date 2005-12-29 Time 10:19 Sent To B
Notes
2005-12-29 00:00:00DENIED;
 1.PLANS REVIEW WITH FBC-2004 PLUMBING
 CODE, CHANGE NOTE.
 2.PERSON RESPONSIBLE FOR DRAWING IS
 REQUIRED TO SIGN DRAWINGS. 104.2.1
 3.AUTOMATIC CLOTHES WASHER SHALL CONNECT
 TO A BRANCH DRAIN OR STACK A MINIMUM OF
 3" IN DIAMETER.
 4.BOTH BIDETS IN MASTER BATHROOM ARE NOT
 VENTED.
 5.SIZE ALL PIPES 3" WET VENT REQUIRED
 AFTER SHOWER DRAIN IN MASTER BATHROOM.
 (5 FUS)
 6.BATH #3 BIDET NOT VENTED.
 7.BBQ SINK TO DISCHARGE DOWN STREAM OF
 THE CABANA BATH GROUP. SEE SEC. 909.1.
 8.INSTALL TRAP PRIMER IN LAUNDRY ROOM
 FLOOR DRAIN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2005-12-23 Cont ID  
Sent By mmclean Date 2005-12-23 Time 17:41 Rev Time 0.00
Received By mmclean Date 2005-12-23 Time 17:41 Sent To I
Notes
2005-12-23 00:00:00NOTE: MUST PULL A SEPERATE PERMIT FOR
 POOL/SPA/DECK/SCREEN ENCLOUSRE/FENCE.
 NOTE: GENERATOR/A/C UNIT/POOL EQUIPMENT
 CAN ONLY ENCROACH 4FT INTO SETBACK.