| 2005-12-13 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- CONTRACTOR'S DECLARED VALUE ON THE |
| | APPLICATION IS EXTEMELY LOW. PROVIDE |
| | CORRECT VALUATION OR VALUATION MAY BE |
| | ESTIMATED USING THE MARSHALL-SWIFT OR |
| | MEANS CONSTRUCTION ESTIMATING BOOK. SEC. |
| | 108.3 CITY AMENDMENTS TO THE FBC 2004. |
| | |
| | 2- SPECIFY: A) MEAN ROOF HEIGHT, B) TYPE |
| | OF DECK, C) PROPOSED ROOF SYSTEM AND D) |
| | SPECIFY IF NEW ROOF, TEAR-OFF OR RECOVER |
| | ROOF AS REQUIRED BY THE CITY POLICY AND |
| | PROCEDURE FOR SUBMITTING PRODUCT |
| | APPROVALS FOR ROOFING/RE-ROOFING |
| | PERMITS. SEE ATTACHED COPY. |
| | |
| | 3- PRODUCT APPROVAL SUBMITTED |
| | LIMITATIONS/CONDITIONS OF USE NOTE #10 |
| | IN PAGE 4 OF 5 REQUIRES MEMBRANE |
| | FASTENERS WITHDRAWAL TESTING AND A |
| | QUALIFIED DESIGN PROFESSIONAL. SEE NOTE |
| | #10 FOR COMPLETE LIMITATION INFORMATION |
| | AND ADDRESS ISSUE AS REQUIRED. |
| | |
| | 4- SEE FOOTNOTES FOR TYPE OF DECK TO |
| | HAVE ROOF INSTALLED TO DETERMINE THE |
| | MAXIMUM DESIGN PRESSURES. THEN, PROVIDE |
| | THE REQUIRED CALCULATIONS. EG: SEE |
| | FOOTNOTE K FOR CONSTRUCTION IN STEEL |
| | DECKS. |
| | |
| | 5- DADE COUNTY NOA REPORT SUBMITTED IS |
| | NOT PART OF THE INFORMATION SUBMITTED |
| | FOR FLORIDA PRODUCT APPROVAL. |
| | |
| | 6- BUILDING INSPECTOR PRE-INSPECTION IS |
| | RECOMMENDED WHEN ROOF-OVERS ARE |
| | SPECIFIED TO VERIFY COMPLIANCE WITH SEC. |
| | 1510 FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712. |