Plan Review Details - Permit 05120487
Plan Review Stops For Permit 05120487
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2006-11-13 Cont ID  
Sent By shill Date 2006-11-13 Time 13:50 Rev Time 0.00
Received By shill Date 2006-11-13 Time 13:50 Sent To  
Notes
2006-11-13 13:54:00REVISION DATED 10/30, REPAIR DETAIL WALLS @ MECHANICAL
 SHAFTS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-11-05 Cont ID  
Sent By shill Date 2006-11-05 Time 15:59 Rev Time 0.00
Received By shill Date 2006-11-05 Time 15:59 Sent To  
Notes
2006-11-05 15:59:47REVISION A8 DATED 10-20-06

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-01 Cont ID  
Sent By shill Date 2006-09-01 Time 14:03 Rev Time 0.00
Received By shill Date 2006-09-01 Time 13:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-18 Cont ID  
Sent By shill Date 2006-07-18 Time 13:47 Rev Time 0.00
Received By shill Date 2006-07-18 Time 13:47 Sent To  
Notes
2006-07-18 00:00:00***CORRECTIONS***
 ***MAJOR WORKING DRAWING REVIEW***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 NOTE - NO PLANS SUBMITTED ON FIRST
 REVIEW, REPORT ONLY.
  
 1.)THE PRODUCT APPROVAL SUBMITTED
 FL6872 IS PENDING.CURRENT PRODUCT
 APPROVAL REQUIRED, FAC9B72.IF THE
 PRODUCT APPROVAL IS STILL PENDING AT THE
 TIME OF RESUBMITTAL, PLEASE ADVISE AND A
 LOCAL PRODUCT APPROVAL WILL BE ISSUED
 USING THE NOA.
  
 2.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING - MINIMUM BUILDING
 TYPE FBC6 (INCLUDE A OR B), AREA,
 OCCUPANCY FBC3.
  
 3.)RELATED TO COMMENT #2 ABOVE,
 SEVERAL DETAILS A7 SHOW COMBUSTIBLE
 FRAMING.IS THIS ALLOWED?
  
 4.)DECLARE GOVERNING CODE, INCLUDING
 FBC 2004 EXISTING BUILDING CODE.
  
 5.)DECLARE LEVEL OF ALTERATION, FBC EB
 3.
  
 6.)FS SHEETS ARE NOT SIGNED, SEALED
 AND DATED FAC61G15-23.002.THE
 INFORMATION REQUIRED TO BE ON THE TITLE
 BLOCK IS ILLEGIBLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-03-27 Cont ID  
Sent By shill Date 2006-03-27 Time 13:12 Rev Time 0.00
Received By shill Date 2006-03-27 Time 13:12 Sent To  
Notes
2006-03-27 00:00:00 
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
  
  
 1.)NO BUILDING PLANS SUBMITTED.
  
 2.)FOR PERMITTING PURPOSES, SUBMIT A
 DETAIL OF THE 1 HOUR INFILL IN THE
 CORRIDOR.PROVIDE A UL ASSEMBLY OR
 CALCULATED FIRE RESISTANCE FBC7.
  
 3.)THE ENGINEER'S REPORT IS TO COMPLY
 WITH FAC61G15-23.002.THE COFA NUMBER,
 PRINTED LICENSE NUMBER OF THE PERSON
 SEALING THE DOCUMENT ARE TO BE ON THE
 PLAN.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-12-31 Cont ID  
Sent By dpalmer Date 2006-12-31 Time 08:21 Rev Time 0.00
Received By dpalmer Date 2006-12-30 Time 16:04 Sent To PC
Notes
2006-12-31 08:22:19REV FOR ADDING ONE HOUSE PANEL AND HALLWAY PHOTOMETRICS

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-12-20 Cont ID  
Sent By dpalmer Date 2006-12-20 Time 19:38 Rev Time 0.00
Received By dpalmer Date 2006-12-20 Time 19:10 Sent To PC
Notes
2006-12-20 19:39:07** UNSAT **
  
 1) NOTE:NOTE OK, AS THE ELECTRICAL PERMIT WAS NOT
 AATCHED IN COMPUTER SYSTEM, PREVIOUS NOTE FOR 4X FEE
 AND HOLD REMOVED.
  
  
 2) NOTE: PLEASE COMPLETE PHOTO-METRICS AS PARTIALLY
 SHOWN FOR HALLWAYS/EGRESS PATHS.
 PLEASE SEE MINIMUM LIGHTING LEVELS UNDER NORMAL AND
 EMERGENCY ARE REQUIRED.
 PLEASE SEE NFPA-101 2003 7.8, 7.9
 PLEASE SEE ONLY A PARTIAL HALLWAY IS SHOWN FOR LIGHTING
 LEVELS WHICH ARE ONLY JUST OVER MINIMUM AND OTHER AREAS
 OF HALLWAYS NOT SHOWN CONTAIN LESS LIGHTING FIXTURES IS
 OF CONCERN TO THIS OFFICE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-25 Cont ID  
Sent By dpalmer Date 2006-08-25 Time 18:15 Rev Time 0.00
Received By dpalmer Date 2006-08-25 Time 08:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-30 Cont ID  
Sent By dpalmer Date 2006-06-30 Time 18:58 Rev Time 0.00
Received By dpalmer Date 2006-06-30 Time 18:02 Sent To  
Notes
2006-06-30 00:00:00*****UNSAT *****
 1ST REVIEW, ELECTRICAL PLANS NOW
 SUBMITTED.
  
  
 ** PLEASE KNOW, PLANS ARE STILL ONLY
 BEING SUBMITTED FOR "PLAN REVIEW" AND
 HAVE NOT SUBMITTED FOR PERMIT.
  
  
 1) NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCK FOR THE
 ARCHITECTURAL FIRM. FAC 61G1-16.004.
 PLEASE SEE MISSING THE PRINTED NAME AND
 LICENSE NUMBER OF ARCHITECT, AND MISSING
 THE CERTIFICATE OF AUTHORIZATION NUMBER
 FOR ARCHITECTURAL FIRM.
 THIS IS REQUIRED ON ALL SHEETS
 CONTAINING A TITLE BLOCK FOR SADI FIRM.
 ** THIS IS REQUIRED FOR ALL TRADES AND
 FOR REVIEW WHETHER OR NOT COMMENT IS
 MADE BY OTHER TRADES.
  
 2) NOTE: PLEASE SEE FS SHEETS SUBMITTED
 ARE NOT SIGNED,DATED, OR SEALED??
 PLEASE KNOW, IF THESE ARE SUBMITTED AS
 PART OF THIS SETS FOR RECORD, EVEN IF
 THE FS ARE UNDER SEPARATE PERMIT, THE
 SHEETS SHALL BE SIGNED, DATED, AND
 SEALED.
 FS 471.025, FAC 61G15-23.002
  
 3) NOTE: PLEASE KNOW, WHEN THIS IS BEING
 SUBMITTED FOR PERMIT, THE COMPLETE VALUE
 FOR SCOPE OF WORK SHALL INCLUDE ALL
 LABOUR AND MATERIALS, WHETHER OR NOT ANY
 MATERIALS ARE OWNER SUPPLIED.
 FBC 108.3 ADMIN SECT.
  
 4) NOTE: PLEASE SEE THAT CONDUCTOR TYPE
 SHALL BE INDICATED.
 215.5,
 106.1.2 FBC ADMIN SECT.
  
 5) NOTE: PLEASE PROVIDE PHOTO-METRICS
 FOR HALL WAYS. THIS CAN BE A TYPICAL
 DETAIL AND SECTION AS EACH FLR SEEMS
 TYPICAL.
 NFPA-101 7.8, 7.9 PLEASE SEE A MIN OF
 1FT CANDLE SHALL BE PROVIDED UNDER
 NORMAL AND EMCONDITIONS.
  
 6) NOTE: PLEASE SEE THAT NOW, EACH OF
 THESE UNITS HAVE BECOME "CONDOS", THE
 WASHER AND DRYER RECEPT CIRCUIT WIRING
 SHALL NOT BE INCLUDE ON THESE PLANS FOR
 SCOPE OF WORK.
 THE CALCULATIONS FOR THE ADDED LOAD TO
 EACH METER BACNK AND MAIN SERVICE SHOUDL
 REMAIN IN SETS.
 215.5
  
 7) NOTE: PLEASE SEE PANEL LOCATIONS.
 UNABLE TO VERIFY WHICH SIDE OF THE
 PANELS SHOWN ARE THE ACCESSIBLE/OPENING
 SIDE. THE OPEING SIDE SHOULD ALL MEET
 110.26 AND CORRELATE.
 215.5
  
 8) NOTE: PLEASE SEE THAT THE ADDRESS FOR
 PROJECT SHALL BE INDICATED ON ALL
 SHEETS.
 FAC 61G1-16.004, FAC 61G15-23.002
 PLEASE SEE ONLY THE "A" SHEETS CONTAINS
 AN ADDRESS OF 1830 EMBASSY DR.
  
 9) NOTE: PLEASE SEE LOAD CALCULATIONS
 WHICH REFLECT NEC 220.84??
 UNABLE TO LOCATED THIS REFERENCE IN THE
 CURRENT WE ARE UNDER IN THE STATE OF
 FLORIDA.
 NEC 2002
  
 10) NOTE: PLEASE SEE THAT PLANS REFLECT
 THE FOLLOWING CODES.
 2004 FBC, 2002 NFPA-70(NEC), 2002
 NFPA-72, 2003 NFPA-101
  
 11) NOTE: PLEASE CLARIFY WHERE MAIN 1OF6
 IS?? RISER SHOWS 2OF6, THRU 6OF6.
 215.5
  
 12) NOTE: PLEASE SEE WHEN RESUBMITTING
 PLANS TO BE SURE AN MAKE TWO COMPLETE
 SETS FOR REVIEW AND STAMPING. PLEASE SEE
 SOME ELECTRICAL SHEETS WERE IN SEPARATE
 SETS.
 106.1.3
  
 13) NOTE: PLEASE BE SURE TO ADJUST SCOPE
 OF WORK ON APPLICATION AS THIS DOES NOT
 INCLUDE ALL THE REFEEDS TO HOUSE PANELS,
 "CONDO"PANELS AND METER BANKS.
 PLEASE SEE APPL MENTIONS INSTALLATION OF
 GFI RECEPTS, YET THESE COULD NOT BE
 LOCATED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-01 Cont ID  
Sent By nmccray Date 2006-08-01 Time 12:09 Rev Time 0.00
Received By nmccray Date 2006-07-26 Time 13:59 Sent To  
Notes
2006-08-01 00:00:00PROVISO:
  
 THE PREVIOUS COMMENTS FROM THE FIRST
 REVIEW BY FIRE MARSHAL MIKE CARSILLO
 STILL REQUIRED.
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-01-23 Cont ID  
Sent By mcarsill Date 2006-01-23 Time 13:36 Rev Time 0.00
Received By mcarsill Date 2006-01-23 Time 13:36 Sent To  
Notes
2006-01-23 00:00:00THIS OFFICE HAS REVIEWED THE SCHIRMER
 ENGINEERING REPORT, FIRE SAFETY
 EVALUATION REPORT PREPARED FOR BH
 CONDOMINIUM SERVICES, LLC. THE FOLLOWING
 COMMENTS ARE PROVIDED.
  
 1. PLANS AND PERMITS REQUIRED FOR THE
 REMOVAL OF THE EXISTING TRANSFER GRILLS
 AND TO REPAIR THESE LOCATIONS TO THE ONE
 HOUR FIRE RATING. (CORRIDORS)
  
 2. THE REPLACEMENT OF DOORS AND EXIT
 HARDWARE IN THE STAIRWELLS SHOULD ALSO
 BE INCLUDED ON PLANS WITH AN APPROVED
 DOOR SCHEDULE ILLUSTRATING THE NEW 1 1/2
 HOUR RATED DOORS.
  
 3. STAIR IDENTIFICATION SIGNS WILL
 CERTAINLY HELP TO IMPROVE THE OVERALL
 FIRE AND LIFE SAFETY CONDITIONS AT THE
 BUILDING.
  
 4. THE PROPOSED NEW FIRE ALARM SYSTEM
 SHALL MEET ALL OF THE REQUIREMENTS OF
 NFPA 72, 2002 EDITION. PLANS AND PERMITS
 WILL BE REQUIRED PRIOR TO INSTALLATION.
 SINCE A NEW SYSTEM IS EXPECTED, THE
 SYSTEM SHALL BE MONITORED BY A LICENSED
 UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
  
 5. THIS OFFICE HAS REVIEWED THE
 INFORMATION REGARDING THE PARTIAL FIRE
 SPRINKLER PROTECTION.THIS OFFICE WOULD
 RECOMMEND THAT THE ENTIRE BUILDING BE
 FIRE SPRINKLER PROTECTED.AS YOU ARE
 AWARE, THE MOST SEVERE RISK OF FIRE IS
 LOCATED WITHIN THE RESIDENTIAL UNITS OF
 THE BUILDING. SINCE THE PLAN IS TO
 SPRINKLER ONLY THE CORRIDORS AND THE
 STAIRS, THE REQUIRED INFRASTRUCTURE WILL
 HAVE TO BE INSTALLED.WITH THE ADDITION
 OF FIRE SPRINKLER PIPING AND SPRINKLER
 HEADS THE ENTIRE BUILDING COULD BE
 PROTECTED WITH SPRINKLERS. FIRE
 SPRINKLER HEADS SELECTED SHOULD BE QUICK
 RESPONSE OR LISTED RESIDENTIAL TYPE.
 SEPERATE PLANS AND PERMITS REQUIRED FOR
 THE INSTALLATION OF ANY FIRE SPRINKLER
 SYSTEM.
  
 6. THE REPORT INDICATES THAT A NEW FIRE
 PUMP AND JOCKEY PUMP IS PLANNED. THIS
 OFFICE SUPPORTS THE INSTALLATION OF A
 NEW FIRE PUMP AND JOCKEY PUMP AS THE
 EXISTING FIRE PUMP HAS BEEN UTILIZED FOR
 MANY YEARS AND HAS OUTLIVED ITS
 USEFULNESS. THE NEW FIRE PUMP SHOULD BE
 AS LEAST A 750 GPM FIRE PUMP SINCE THERE
 ARE TWO REQUIRED STAIRWELLS FOR THE
 BUILDING. AGAIN, PLANS AND PERMITS ARE
 REQUIRED PRIOR TO INSTALLATION. ALSO
 PRIMARY AND EMERGENCY POWER SUPPLIES ARE
 TO BE DETERMINED FOR ADEQUACY.
  
 7. ALTHOUGH NOT NOTED IN THE REPORT, ANY
 MULTI-LEVEL APARTMENTS SHALL HAVE
 ELECTRIC POWERED SMOKE DETECTORS PRESENT
 ON EVERY LEVEL.
  
 8. ANY OTHER FIRE AND LIFE SAFETY
 SYSTEMS OR DEVICES THAT NEED TO BE
 REPAIRED SHOULD BE CORRECTED AT THIS
 TIME.
  
 IF YOU SHOULD HAVE ANY QUESTIONS, PLEASE
 FEEL FREE TO CONTACT THIS OFFICE AT
 804-4709.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-12-27 Cont ID  
Sent By adarroug Date 2006-12-27 Time 15:47 Rev Time 0.00
Received By adarroug Date 2006-12-27 Time 15:47 Sent To E
Notes
2006-12-27 15:48:34TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 13:05 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 13:05 Sent To E
Notes
2006-12-17 13:05:46TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-11-13 Cont ID  
Sent By adarroug Date 2006-11-13 Time 11:22 Rev Time 0.00
Received By adarroug Date 2006-11-13 Time 11:22 Sent To B
Notes
2006-11-13 11:24:00TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 15:51 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 15:51 Sent To B
Notes
2006-10-27 15:52:18TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 17:28 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 17:28 Sent To  
Notes
2006-08-23 00:00:00TO "COMM" BD#33
2006-08-16 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-21 Cont ID  
Sent By adarroug Date 2006-06-21 Time 15:29 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 15:29 Sent To  
Notes
2006-06-29 00:00:00TO "COMM" BD#57
2006-06-21 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-18 Cont ID  
Sent By jleech Date 2006-04-07 Time 08:24 Rev Time 0.00
Received By jleech Date 2005-12-13 Time 13:44 Sent To  
Notes
2006-01-13 00:00:00TO "COMM" BD#42
2005-12-13 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-24 Cont ID  
Sent By tgordon Date 2006-08-24 Time 13:36 Rev Time 0.30
Received By tgordon Date 2006-08-24 Time 13:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By tgordon Date 2006-07-18 Time 15:32 Rev Time 0.25
Received By tgordon Date 2006-07-18 Time 15:32 Sent To  
Notes
2006-07-18 00:00:00*** DENIED ***
 1) BATHROOM EXHAUST FANS MAY NOT
 DISCHARGE INTO AN INCLOSED HALLWAY, OR
 ON TO A WALKWAY, AND MUST DISCHARGE TO
 THE OUTDOORS ,PER 2004 FBC/M 501.2, AND
 401.5.2 .
  
 2) PLEASE PROVIDE INFORMATION AND
 INSTALLATION DETAILS ON THE FIRE DAMPERS
 FOR THE BATHROOM EXHAUST FANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-20 Cont ID  
Sent By lfranco Date 2006-07-20 Time 20:05 Rev Time 0.00
Received By lfranco Date 2006-07-20 Time 20:05 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2006-04-07 Cont ID  
Sent By lfranco Date 2006-04-07 Time 20:07 Rev Time 0.00
Received By lfranco Date 2006-04-07 Time 20:07 Sent To I
Notes
2006-04-07 00:00:00PLANNING AND ZONING:FAILED
  
 1.PROVIDE A COPY OF THE ZONING
 CONFIRMATION LETTER FROM THE CITY
 VERYING THE INTENT TO CONVERT THESE
 APARTMENTS TO CONDOS. IF SUCH LETTER WAS
 NOT PREVIOUSLY ASKED FOR, YOU WILL NEED
 TO CONTACT THE PLANNING DEPARTMENT OR GO
 TO OUR WEBSITE: WWW.CITYOFWPB.ORG
 UNDER ZONING REQUESTS TO DOWNLOAD A
 ZONING CONFIRMATION LETTER REQUEST AND
 INSTRUCTIONS.
  
 2.THE PACKET SUBMITTED IS NOT SUFFICIENT
 TO PROVIDE INFORMATION SUCH AS, WHAT
 TYPE OF IMPROVEMENTS ARE BEING PROPOSED.
 PROVIDE AN EXISTING SURVEY OF THE SITE
 AND A WRITTEN EXPLANATION OF THE EXTENT
 OF THE WORK TO BE PERFORMED.
  
 3. DO YOU HAVE A COPY OF THE
 DOCUMENTATION TO MEET THECONDO
 CONVERTION REQUIREMENTS FROM THE STATE
 OF FLORIDA? IF SO, PLEASE PROVIDE A COPY
 IN THE RE-SUBMITTAL PACKET.
  
  
 IF YOU HAVE ANY QUESTIONS IN REGARDS TO
 THESE COMMENTS, PLEASE CONTACT LINDA MIA
 FRANCO, SENIOR PLANNER AT (561)822-1435.
  
  
  