| Plan Review Stops For Permit 05120462 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2006-01-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2006-01-11 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2006-01-11 |
Time |
13:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2005-12-09 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2005-12-09 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2005-12-09 |
Time |
14:26 |
Sent To |
|
|
| Notes |
| 2005-12-09 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | | TO THE FBC2004 | | | | | | 1.)THE APPROVED ASSEMBLYHAS A DESIGN | | | PRESSURE LIMITATION OF -45 PSF, GENERAL | | | LIMITATION #9.YOU MUST SELECT AN | | | APPROVED ASSEMBLY EITHER COMPLIANT FOR | | | ZONE 3 (-89) OR WITH GENERAL LIMITATION | | | #7 WHICH ALLOWS ENHANCED FASTENING IN | | | CORNER AND PERIMETER ZONES. | | | | | | 2.)THE STATE APPROVAL SUBMITTED HAS | | | "RECOVER" HIGHLIGHTED.TO AVOID | | | CONFUSION, THE STATE APPROVAL SHOULD BE | | | CONSISTENT WITH THE NOA SUBMITTED. | | | | | | 3.)THE APPLICATION STATES THAT THIS IS | | | A CONCRETE DECK, BUT THE NOA IS FOR A | | | CEMENTITIOUS WOOD FIBER DECK.PLEASE | | | ADDRESS. |
|
|
|