Plan Review Details - Permit 05120451
Plan Review Stops For Permit 05120451
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-02-16 Cont ID  
Sent By mjacobs Date 2006-02-16 Time 10:30 Rev Time 1.00
Received By mjacobs Date 2006-02-15 Time 14:00 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2005-12-22 Cont ID  
Sent By mjacobs Date 2005-12-22 Time 07:50 Rev Time 1.25
Received By mjacobs Date 2005-12-22 Time 06:06 Sent To PC
Notes
2005-12-22 00:00:00 
 1) (2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OF THE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 3) A PLAN OF THE TOTAL AREA IS REQUIRRED
 FOR PLAN REVIEW,SHOWING THE TYPE OF
 OCCUPANCY AND USE OF EACH ROOM IN THE
 NEW AREA.ALSO THE OCCUPANT LOAD OF THE
 TOTAL AREA.
 WHAT TYPE OF WALL IS THE DEMISING WALL?
 IS IT CONCRETE BLOCK OR METAL STUDS?
 SHOW THE HEADDER DETAIL FOR THE NEW
 OPENINGS.
  
 4) ARE THE NEW OPENINGS OPENING INTO A
 HALL WAY OR AN OPEN AREA.PLEASE SHOW
 THIS INFORMATION ON THE PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
 [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-02-04 Cont ID  
Sent By jleahy Date 2006-02-04 Time 13:24 Rev Time 0.30
Received By jleahy Date 2006-02-04 Time 13:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-16 Cont ID  
Sent By jleahy Date 2005-12-16 Time 19:10 Rev Time 0.30
Received By jleahy Date 2005-12-16 Time 19:09 Sent To  
Notes
2005-12-16 00:00:00NEED TO SHOW PANEL LOCATION
  
 NEED PANEL SCHEDULE SHOWING NEW CIRCUITS
  
 DOES SPACE HAVE A/C, WATER HEATER
 IF SO SHOW LOCATIONS
  
 IS THE ELECTRIC IN THIS SPACE ON A
 SEPARATE PANEL?
  
 JAKE LEAHY644-7291

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-02-07 Cont ID  
Sent By mwennerg Date 2006-02-07 Time 11:10 Rev Time 0.00
Received By mwennerg Date 2006-02-07 Time 11:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2005-12-20 Cont ID  
Sent By mwennerg Date 2005-12-20 Time 14:20 Rev Time 0.00
Received By mwennerg Date 2005-12-20 Time 14:20 Sent To  
Notes
2005-12-20 00:00:00******DENIED******
  
 1) WHERE DO PERSONS EXIT USING THE NEW
 EXITS IN THE EXISTING DEMISING WALL?
  
 2) ARE THERE ANY EXISTING OR NEW
 EMERGENCY LIGHTS IN THIS SPACE?
  
 3) 2A-10B,C RATED FIRE EXTINGUISHER IS
 REQUIRED.
  
 4) SEPARATE SHOP DRAWING AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL IF
 APPLICABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-02-03 Cont ID  
Sent By adarroug Date 2006-02-03 Time 12:31 Rev Time 0.00
Received By adarroug Date 2006-02-03 Time 12:31 Sent To  
Notes
2006-02-03 00:00:00TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-02-03 Cont ID  
Sent By adarroug Date 2005-12-23 Time 12:31 Rev Time 0.00
Received By adarroug Date 2005-12-13 Time 13:15 Sent To  
Notes
2005-12-13 00:00:00TO "BOB"#8

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2005-12-22 Cont ID  
Sent By tgordon Date 2005-12-22 Time 12:55 Rev Time 0.15
Received By tgordon Date 2005-12-22 Time 12:55 Sent To  
Notes
2005-12-22 00:00:00NO MECH. PLANS OR MECH. CONTRACTOR
 SUBMITTED AT THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status N Date 2006-02-08 Cont ID  
Sent By jleech Date 2006-02-08 Time 17:49 Rev Time 0.00
Received By jleech Date 2006-02-15 Time 13:56 Sent To  
Notes
2006-02-08 00:00:00 
  
 PLUMBING CONTRACTOR SHALL SUBMIT
 RISER DIAGRAM WITH PLUMBING PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status F Date 2005-12-23 Cont ID  
Sent By jleech Date 2005-12-23 Time 11:03 Rev Time 0.50
Received By jleech Date 2005-12-23 Time 11:03 Sent To  
Notes
2005-12-23 00:00:00DENIED;
 1. SCOPE OF WORK NOT CLEAR,OCCUPANCY
 TYPE NOT CLEAR.
 2.SHOW COMPLIANCE TO FBC-2004 PLUMBIMNG
 TABLE 403.1. DRINKING FOUNTAIN IS
 REQUIRED.
 3.BATHROOM IS NOT HANDICAP ACCESSIBLE,
 DOOR SWING CANNOT SWING INTO THE CLEAR
 FLOOR SPACE OF THE LAV. SHOW TURNING
 RADIUS IN BATHROOM. NOTE LOCKING
 HARDWARE IS REQUIRED ON BATHROOM DOOR.
 SHOW COMPLIANCE WITH FBC-2004 CHAPTER
 11.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695