Plan Review Details - Permit 05120430
Plan Review Stops For Permit 05120430
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-02-14 Cont ID  
Sent By dpalmer Date 2006-03-08 Time 07:36 Rev Time 0.50
Received By alange Date 2006-02-14 Time 07:49 Sent To  
Notes
2006-02-10 00:00:00NEW SHEETS

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-01-20 Cont ID  
Sent By alange Date 2006-01-20 Time 13:24 Rev Time 0.50
Received By alange Date 2006-01-20 Time 13:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-03-31 Cont ID  
Sent By dpalmer Date 2006-03-31 Time 17:55 Rev Time 0.00
Received By dpalmer Date 2006-03-31 Time 17:55 Sent To PC
Notes
2006-03-31 00:00:00LOAD FOR AHU HEAT SHOULD HAVE BEEN
 FIGURED AT 100%, HOWEVER SHOWN AT 65%.
 EVEN IF FIGURED AT 100%, THE LOAD ON
 GENERATOR WOULD STILL BE IN DESIGNED
 LOAD.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-03-08 Cont ID  
Sent By dpalmer Date 2006-03-08 Time 07:36 Rev Time 0.00
Received By dpalmer Date 2006-03-08 Time 07:05 Sent To B
Notes
2006-03-08 00:00:00********** UNSAT 3RD REVIEW ************
  
 ** PLEASE SEE THAT THE PREVIOUS DEINED
 PLANS WERE NOT PICKED UP AND MADE INTO
 TWO COMPLETE SETS BEFORE RESUBMITTING
 PLANS.
 PLEASE KNOW, MUST PICK UP ALL OLD PLANS
 AND MAKE NEW SETS AND THEN RESUBMIT.
 THIS WILL HELP TO ALLEAVIATE ANY
 CONFUSION OF WHICH PLANS PASSED AND
 WHERE THOSE PLANS ARE/WERE.
 PLEASE SEE COMMENTS FROM OTHER REVIEW
 WHICH IS NOW FAILED AS ORIGINAL PLANS
 WERE NOT PICKED UP AND SUBMITTED BACK.
  
 ** PLEASE SEE NOTES BELOW AS MANY NOTES
 ARE THE SAME AS NOTES ON PREVIOUS REVIEW
 AND NEW NOTES AS RISER DIAGRAM HAS NOW
 CHANGED.PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
  
  
 1)NOTE: NOTE #1 NO, PLEASE SEE SHEETS
 WHICH STILL CONTAIN TITLE BLOCK,SIGNED
 AND DATED, HOWEVER THESE DO NOT CONTAIN
 THE REQUIRED RAISED SEAL.
  
 **PLEASE SEE ANY PLANS CONTAINING
 A TITLE BLOCK AND SIGNATURE OF AN
 ENGINEER SHALL BEAR THE RAISED SEAL, AND
 DATE BY THE SAID ENGINEER. FS471.025
  
 2)NOTE: NOTE #2 NO, PLEASE SEE SAME
 SPECS WHICH DO NOT INDICATE A MCB.
  
 **PLEASE SEE SPECS SUBMITTED DO
 NOT INDICATE THE USE OF AN ATS WITH A
 MCB . PLEASE SEE MAINS ARE NOT GROUPED
 PER 230.72,225.34
  
 3)NOTE: NOTE #3 NO, PLEAS SEE AN
 EQUIPMENT GRND IS BEING SHOWN FROM METER
 TO WHAT MAY BE THE FIRST MEANS OF
 DISCONNECT ?(IF ATS CONTAINS A MCB??
  
 ** PLEASE SEE 250.6,250.24 THE
 "EQUIPMENT GROUNDING CONDUCTORS" ARE
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE RISER SHOWS FROM METER ETC.
 215.5
  
 4)NOTE: NOTE #4 NO, PLEASE SEE NEW SITE
 PLANS IS NOT CLEAR AND VISABLE FOR
 LOCATIONS OF EXISTING PANEL ETC.
 PLEASE SEE NOW RISER HAS BEEN REVISED
 REMOVING THE REQUIRED DISCONNECT??
 ONCE AGAIN, PLEASE KNOW, A DISCONNECT
 WILL BE REQUIRED, GROUPED WITH OTHER
 MAINS,AT THE HOUSE.
 PLEASE CLARIFY RISER AS SHOWN. EXISTING
 PANEL DOES NOT INDICATE A MCB AND
 WHETHER OR NOT THS EXISTING PANEL(MCB?)
 IS GROUPED WITH NEW ATS?
 IT IS SUGGESTED TO CALL THIS OFFICE TO
 GO OVER PLANS AND SCENERIO AS SHOWN TO
 HELP ALLEAVIATE FURTHER REVIEWS.
  
 ** PLEASE SEE SITE PLANS DOES NOT
 INDICATE THE NEW GEN DISCONNECT.
 PLEASE SEE THE RISER SEEMS TO INDICATE
 THE MEANS OF DISCONNECT REQUIRED IN
 225.31 AT GENERATOR?
 PLEASE SEE IF GEN CONTAINS A CB , THEN
 ONLY A DISCONNECTING MEANS IS REQUIRED
 AT MAIN HOUSE AND NOT OCP, ALTHOUGH OCP
 IS PERMITTED.
  
 5)NOTE:NOTE #5, NO, PLEASE SEE NOTE
 ABOVE BEFORE REVIEW NOTES AS TO PICKING
 UP OF ANY OLD PLANS.
  
 **PLEASE SUBMIT TWO COMPLETE SETS
 OF PLANS AND SPECS FOR REVIEW AND
 STAMPING.
 PLEASE SEE ALL SHEETS WERE SUBMITTED
 LOOSELY AND NEED TO ATTACHED TOGETHER.
  
 6)NOTE: NOTE #6 NO, COULD NOT LOCATE A
 NEW RECORDED NOC? PLEASE KNOW, THIS NEED
 ONLY BE SUBMITTED WHEN PICKING UP PERMIT
 ONCE IT IS ISSUED.
  
 ** PLEASE SEE THE NOTICE OF
 COMMENCMENT HAS SINCE EXPIRED PER FS
 713.13(2). IF WORK HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING NOC, THE NOC
 SHALL BECOME VOID.
  
 NEW COMMENT;
  
 7)NOTE: PLEASE SEE FLORIDA STATUES
 553.80(2))B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR
 PLANS REVIEW. PLEASE KNOW, IF PLANS COME
 BACK WITH ANY OF THE SAME CODE COMPLIANT
 COMMENTS STILL NOT ADDRESSED, THIS
 OFFICE SHALL ACCESSED A 4X FEE FOR THE
 PLAN REVIEW PORTION OF THE PERMIT FEE.
 SEEATTACHED COPY OF THIS FS.
  
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-02-10 Cont ID  
Sent By dpalmer Date 2006-02-10 Time 16:42 Rev Time 0.00
Received By dpalmer Date 2006-02-10 Time 14:05 Sent To M
Notes
2006-02-10 00:00:00********** UNSAT************
  
  
 1)NOTE: PLEASE SEE ANY PLANS CONTAINING
 A TITLE BLOCK AND SIGNATURE OF AN
 ENGINEER SHALL BEAR THE RAISED SEAL, AND
 DATE BY THE SAID ENGINEER. FS471.025
  
 2)NOTE: PLEASE SEE SPECS SUBMITTED DO
 NOT INDICATE THE USE OF AN ATS WITH A
 MCB . PLEASE SEE MAINS ARE NOT GROUPED
 PER 230.72,225.34
  
 3)NOTE: PLEASE SEE 250.6,250.24 THE
 "EQUIPMENT GROUNDING CONDUCTORS" ARE
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE RISER SHOWS FROM METER ETC.
 215.5
  
 4)NOTE: PLEASE SEE SITE PLANS DOES NOT
 INDOCATE THE NEW GEN DISCONNECT.
 PLEASE SEE THE RISER SEEMS TO INDICATE
 THE MEANS OF DISCONNECT REQUIRED IN
 225.31 AT GENERATOR?
 PLEASE SEE IF GEN CONTAINS A CB , THEN
 ONLY A DISCONNECTING MEANS IS REQUIRED
 AT MAIN HOUSE AND NOT OCP, ALTHOUGH OCP
 IS PERMITTED.
  
 5)NOTE: PLEASE SUBMIT TWO COMPLETE SETS
 OF PLANS AND SPECS FOR REVIEW AND
 STAMPING.
 PLEASE SEE ALL SHEETS WERE SUBMITTED
 LOOSELY AND NEED TO ATTACHED TOGETHER.
  
 6)NOTE: PLEASE SEE THE NOTICE OF
 COMMENCMENT HAS SINCE EXPIRED PER FS
 713.13(2). IF WORK HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING NOC, THE NOC
 SHALL BECOME VOID.
  
  
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2005-12-28 Cont ID  
Sent By dpalmer Date 2005-12-28 Time 15:48 Rev Time 0.00
Received By dpalmer Date 2005-12-28 Time 15:44 Sent To Z
Notes
2005-12-28 00:00:00************UNSAT ************
  
  
 1)NOTE: PLEASE SEE FBC ADMINISTRATIVE
 CODE 108.3, VALUTAION IS TO BE BASED ON
 ALL LABOR AND MATERIALS, WHETHER OR NOT
 ANY MATERIALS/ EQUIPMENT IS OWNER
 SUPPLIED.
 THE $3680, IS WAY TOO LOW.
  
 2)NOTE: PLEASE PROVIDE A MEANS OF
 DISCONNECT GROUPED WITH OTHER MAINS AS
 REQUIRED PER 225.31-225.39
 PLEASE SEE NEW TRANSFER SWITCH AS
 SUBMITTED WILL ONLY DISCONNECT POWER
 FROM UITILITY AND NOT GENERATOR. PLEASE
 SEE THE REQUIRED DISC SHALL BE RATED FOR
 THE LOAD TO BE SERVED. (A TOGGLE SWITCH
 IS NOT ACCEPTABLE).
  
  
 3)NOTE: PLEASE ALSO SEE THAT ONLY THE
 NORMAL GENERAL LT, RECEPTS LOADS MAY BE
 DE-RATED. ALL OTHER MOTOR, HEAT,
 SPECIFIC APPLIANCE LOADS SHALL BE
 FIGURED AT 100%, INCLUDING HEAT LOADS IN
 A/C UNITS, UNLESS A MEANS OF SHEDDING
 THESE LOADS IS PROVIDED.
 220, 702.5,90.4
  
 4)NOTE: PLEASE VERIFY THE EXISTING
 METER/MAIN IS SHOWN AS 150A, YET ALL NEW
 EQUIPEMNT IS 200A AND EXISTING PANEL IN
 GARAGE DOES NOT INDICATE ANY SIZE??
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2006-01-11 Cont ID  
Sent By jleech Date 2006-01-11 Time 13:00 Rev Time 0.25
Received By jleech Date 2006-01-11 Time 13:00 Sent To B
Notes
2006-01-11 00:00:00GAS PERMIT OK #05121214

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-03-31 Cont ID  
Sent By adarroug Date 2006-03-31 Time 10:25 Rev Time 0.00
Received By adarroug Date 2006-03-31 Time 10:25 Sent To E
Notes
2006-03-31 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-03-17 Cont ID  
Sent By adarroug Date 2006-03-17 Time 09:35 Rev Time 0.00
Received By adarroug Date 2006-03-17 Time 09:06 Sent To Z
Notes
2006-03-17 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-03-07 Cont ID  
Sent By adarroug Date 2006-03-07 Time 08:34 Rev Time 0.00
Received By adarroug Date 2006-03-07 Time 08:34 Sent To E
Notes
2006-03-07 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-02-22 Cont ID  
Sent By adarroug Date 2006-02-22 Time 14:33 Rev Time 0.00
Received By adarroug Date 2006-02-22 Time 14:33 Sent To Z
Notes
2006-02-22 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-02-08 Cont ID  
Sent By adarroug Date 2006-02-08 Time 09:52 Rev Time 0.00
Received By adarroug Date 2006-02-08 Time 09:52 Sent To E
Notes
2006-02-08 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-02-03 Cont ID  
Sent By adarroug Date 2006-02-03 Time 11:31 Rev Time 0.00
Received By adarroug Date 2006-02-03 Time 11:31 Sent To Z
Notes
2006-02-03 00:00:00TO "Z" BOX/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-06 Cont ID  
Sent By adarroug Date 2006-01-06 Time 08:30 Rev Time 0.00
Received By adarroug Date 2006-01-06 Time 08:30 Sent To M
Notes
2006-01-06 00:00:00TO "GEN-RES" BOX "M"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-20 Cont ID  
Sent By alange Date 2006-01-20 Time 13:25 Rev Time 0.00
Received By alange Date 2005-12-13 Time 18:14 Sent To  
Notes
2005-12-13 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-01-06 Cont ID  
Sent By tgordon Date 2006-01-06 Time 16:28 Rev Time 0.15
Received By tgordon Date 2006-01-06 Time 16:28 Sent To G
Notes
2006-01-06 00:00:00*** PROVISO ***
 1) GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-01-11 Cont ID  
Sent By jleech Date 2006-01-11 Time 13:00 Rev Time 0.00
Received By jleech Date 2006-01-11 Time 13:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2006-03-31 Cont ID  
Sent By dpalmer Date 2006-03-31 Time 17:56 Rev Time 0.00
Received By dpalmer Date 2006-03-31 Time 17:56 Sent To I
Notes
2006-03-31 00:00:00PASSED AND STAMPED BY MICHELLE MCLEAN
 ON 3/30/06 AND SENT TO INCOMING. DID NOT
 GET ENTERED IN COMPUTER.BOTH SETS OF
 SURVEY'S, AND RESUB COVER SHEET IN
 PACKAGE WERE SIGNED.

Review Stop Z ZONING
Rev No 3 Status F Date 2006-03-06 Cont ID  
Sent By mmclean Date 2006-03-06 Time 17:30 Rev Time 0.00
Received By mmclean Date 2006-03-06 Time 17:29 Sent To I
Notes
2006-03-06 00:00:00DENIED,
 1. NEED2 COPY A CLEAR SURVEY SHOWING
 THE SETBACK OF THE STRUCTURE.
 2. NEED TO SHOW THE GENERATOR ON THE TWO
 COPY OF SURVEY WITH SETBACKS. (DIMENSION
 OF GENERATOR).
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status N Date 2006-02-07 Cont ID  
Sent By mmclean Date 2006-02-07 Time 13:46 Rev Time 0.00
Received By mmclean Date 2006-02-07 Time 13:46 Sent To I
Notes
2006-02-07 00:00:00ALREADY APPROVED ON 1/5/06

Review Stop Z ZONING
Rev No 1 Status P Date 2006-01-05 Cont ID  
Sent By mmclean Date 2006-01-05 Time 14:01 Rev Time 0.00
Received By mmclean Date 2006-01-05 Time 14:01 Sent To I
Notes
2006-01-05 00:00:00GENERATOR CAN ONLY ENCROACH 4FT INTO A
 SETBACK.