Plan Review Details - Permit 05120429
Plan Review Stops For Permit 05120429
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-12-26 Cont ID  
Sent By shill Date 2008-01-07 Time 14:57 Rev Time 0.00
Received By lursu Date 2006-12-26 Time 08:35 Sent To  
Notes
2006-12-26 08:36:52PERMIT WAS ATTACHED TO UNIT #0012 FOR 6600 45TH ST FOR
 THIS FACILITY.
  
 NOTE:
 1) PERMIT WAS ATTACHED TO UNIT #0001 UNDER PCN = 74 42
 43 03 00 000 1000. THIS ADDRESS BELONGS TO THE NEW
 STRUCTURE.
  
 01/02/07
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-07-14 Cont ID  
Sent By lursu Date 2006-07-14 Time 13:53 Rev Time 0.00
Received By lursu Date 2006-07-14 Time 13:53 Sent To  
Notes
2006-07-14 00:00:00EXT #0012 UNDER THE MAIN PCN =
 74424234000001010 CAN BE USED FOR THIS
 ADDRESS : 6600 45TH ST
  
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2009-11-19 Cont ID  
Sent By shill Date 2009-11-19 Time 16:06 Rev Time 0.00
Received By shill Date 2009-11-19 Time 16:06 Sent To  
Notes
2009-11-19 16:07:42STAMPED ROOF HATCH PRODUCT APPROVAL, LETTER FROM
 ARCHITECT REGARDING EXITING FROM SLUDGE STORAGE PIT
 AREA, A001A, A001C,A21 SUBMITTAL #15
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status P Date 2009-11-05 Cont ID  
Sent By shill Date 2009-11-05 Time 08:31 Rev Time 0.00
Received By shill Date 2009-11-05 Time 08:31 Sent To  
Notes
2009-11-05 08:32:18REVISION 16 DATED 10/19/09, SHEET S23
 (INCREASED A/C UNIT SIZE FOR CONTROL ROOM)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status F Date 2009-10-26 Cont ID  
Sent By shill Date 2009-10-26 Time 13:49 Rev Time 0.00
Received By shill Date 2009-10-22 Time 11:43 Sent To  
Notes
2009-10-26 13:50:07****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. ALTHOUGH THE PLAN STATES THAT THE COMMON PATH OF
 TRAVEL IS 0, THIS SHOULD BE MEASURED TO THE POINT AT
 WHICH THE OCCUPANT HAS THE CHOICE OF TWO EXITS. AS
 THERE ARE NO EXITS ON ONE SIDE, THE OCCUPANT WOULD BE
 FORCED TO TRAVEL TOWARDS THE SIDE WITH EXITS, SO THIS
 IS THE DISTANCE WHICH SHOULD BE COUNTED AS COMMON PATH
 OF TRAVEL. PLEASE SEE THE COMMENTARY FOR A MORE
 THOROUGH EXPLANATION OF COMMON PATH OF TRAVEL. THE PLAN
 DECLARES THIS AREA AS F3, SEE FBC1013.3, THE COMMON
 PATH EXCEEDS THE MAXIMUM ALLOWED. PLEASE CLARIFY THE
 USE OF THIS AREA; IS THIS A PROCESSING AREA?
  
 I EMAILED THE CONTRACTOR ON 10/22 BUT HAVE NOT YET
 RECEIVED A RESPONSE. PLEASE CONTACT ME TO DISCUSS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status F Date 2009-09-16 Cont ID  
Sent By shill Date 2009-09-16 Time 16:22 Rev Time 0.00
Received By shill Date 2009-09-16 Time 16:22 Sent To  
Notes
2009-09-16 16:33:30REVISION, SHEET S23 OK
  
 ****CORRECTIONS - REVISION, S20 AND ROOF HATCH PRODUCT
 APPROVAL***
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
  
 1. A DETAIL WAS ADDED TO THE SCRUBBER FOUNDATION WHICH
 IS LABLED "EQUIPMENT ACCESS WALKWAY." IS THIS THE STAIR
 AND WALKWAY WHICH IS TO BE A PART OF THE EXIT PATH TO
 THE PUBLIC WAY? IT IS MY UNDERSTANDING THAT THERE IS AN
 EXIT DOOR WHICH HAS ACCESS TO THE PUBLIC WAY BLOCKED BY
 PIPING, AND A STAIR WAS TO BE PROVIDED TO FACILITATE
 EXITING. PLEASE REVISE DRAWING TO PROPERLY LABEL THIS
 MEANS OF EGRESS STAIR/WALKWAY AND INCORPORATE THE NEW
 MEANS OF EGRESS COMPONENT INTO THE LIFE SAFETY PLAN.
 SEE FBC1002, DEFINITION OF MEANS OF EGRESS. SEE
 FBC1003.6, MEANS OF EGRESS CONTINUITY.
  
 2. FBC1003.5, CHANGES IN LEVEL IN THE MEANS OF EGRESS
 SHALL BE BY EITHER A RAMP OR STAIR. SEE OTHER COMMENTS.
  
 3. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED
 CONSTRUCTION, FBC16. ONLY A PLAN VIEW WITH HORIZONTAL
 DIMENSIONS WAS PROVIDED. A DIMENSIONED SECTION AND
 ELEVATION SHOULD BE PROVIDED TO SHOW COMPLIANCE WITH
 THE REQUIREMENTS OF FBC CHAPTER 10.
  
 4. SHOW THE DOOR AND DOOR SWING FOR THE EXIT WHICH THIS
 WALKWAY SERVICES. DOOR IS NOT TO OBSTRUCT THE PATH OF
 TRAVEL, HAS THE EQUIPMENT AND PIPING AFFECTED THE DOOR
 SWING? SEE C9; IT APPEARS THAT THE PROPOSED STAIR IS
 OBSTRUCTED BY THE EXIT DOOR, AND THE DOOR SWING IS
 OBSTRUCTED BY THE PROPOSED STAIR. PLEASE INCORPORATE
 INTO THE LIFE SAFETY PLAN AND REVERSE DOOR SWING IF
 NECESSARY.
  
 5. IN THE DETAIL, PROVIDE DETAILS WITH DIMENSIONS WHICH
 SHOW COMPLIANCE WITH:
  
 1003.3, PROTUDING OBJECTS
 1005.1, EGRESS WIDTH (MAINTAINING MINIMUM
 HEIGHT/PROTUDING OBJECT REQUIREMENTS)
 1006.1, MEANS OF EGRESS ILLUMINATION
 1006.1.3, SHOW LEVEL OF ILLUMINATION
 1008.1.5, LANDING SIZE
 1009, STAIR DIMENSIONS (RISE AND RUN, CLEARANCE, ETC.)
 1009, HANDRAILS (PROVIDE A DETAIL); NOTE THAT HANDRAILS
 ARE SHOWN ON THE PLAN BUT NO EXTENSIONS SHOWN,
 1009.11.5
 1012, GUARDRAILS - PLAN SHOWS THREE RISERS, BUT A NOTE
 ON THE PLAN STATES THAT THE WALKWAY WILL NOT BE MORE
 THAN 4', SO IT IS NOT CLEAR IF GUARDRAILS ARE REQUIRED
 - ELEVATION OR SECTION SHOULD SHOW HEIGHT ABOVE GRADE
 1009.5, DETAIL STATES THAT WALKWAY IS CONSTRUCTED OF
 P.T. LUMBER; THIS BUILDING IS A TYPE IIB, NON
 COMBUSTIBLE BUILDING. CONSTRUCTION OF MEANS OF EGRESS
 STAIRS TO BE CONSISTENT WITH BUILDING TYPE, NON
 COMBUSTIBLE REQUIRED
  
 6. ONE SET OF A ROOF HATCH PRODUCT APPROVAL WAS
 SUBMITTED. DON'T YOU NEED A SET FOR INSPECTION
 PURPOSES?
  
 7. PLEASE REVISE SHEET A21 WHICH DEPICTS AN ALUMINUM
 ROOF HATCH.
  
 8. A21 SHOWS A 60" ROOF HATCH, BUT THE ATTACHMENT
 CALCULATIONS IN THE PRODUCT APPROVAL ARE FOR A 36" ROOF
 HATCH. THE MANUFACTURER'S SPEC SHEET SUBMITTED DOES NOT
 INCLUDE THE JOB SPECIFIC INFORMATION; WIDTH & LENGTH
 AND PART NUMBER. IS THIS A RHG3630T OR RHG3636T? IF THE
 ROOF HATCH TO BE INSTALLED IS NOT 37X43 FRAME SIZE,
 THEN AN ENGINEERED SPECIFICATION FOR INSTALLATION WILL
 BE REQUIRED (PRODUCT APPROVAL INCLUDES CALCS FOR 37X43
 ROOF HATCH, ATTACHED TO 1/4" STEEL L ANGLE (4X4X1/4)
 ATTACHED TO STEEL JOISTS USING 8 3" FILLET WELDS, HATCH
 BOLTED TO THE LANGLE FRAME WITH 5/8" THROUGH BOLTS AS
 SPECIFIED IN THE PRODUCT APPROVAL). CONFIRM CONSISTENCY
 OF THE PRODUCT INSTALLED WITH THE PRODUCT APPROVAL
 (SIZE, INSTALLATION INSTRUCTIONS).
  
 9. A ZONING REVIEW IS REQUIRED FOR ALL IMPROVEMENTS
 OUTSIDE OF THE BUILDING. PER ERIC SCHNEIDER, PLEASE
 INCORPORATE THIS WALKWAY AND STAIR INTO THE SITE PLAN
 FOR REVIEW.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status F Date 2009-08-19 Cont ID  
Sent By shill Date 2009-08-19 Time 16:32 Rev Time 0.00
Received By shill Date 2009-08-12 Time 15:40 Sent To  
Notes
2009-08-19 16:35:39****CORRECTIONS**** SURVEY, VARIOUS CIVIL SHEETS
 ****CORRECTION LIST REVISED 9/17***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE CLARIFY, IT APPEARS THAT THE ACCESSIBLE ROUTE
 IS BLOCKED BY DOOR SWING AND GUIDE RAILS, EAST SIDE
 ADJACENT TO ACCESSIBLE PARKING SPACE. PLEASE CONTACT ME
 TO DISCUSS OR SEND PHOTOS OF ACTUAL CONDITIONS (THAT
 CLEARLY SHOW THAT REQUIRED CLEARANCE HAS NOT BEEN
 OBSTRUCTED). IT APPEARS THAT DOOR SWING SHOULD BE
 REVERSED AND SOUTH GUIDE RAIL REMOVED.
  
 ON 8/21, CONTRACTOR SENT A PHOTOGRAPH SHOWING THAT THE
 GUIDE RAILS SHOWN ON THE PLAN WERE NOT INSTALLED.
 PLEASE REVISE AFFECTED SHEETS AS PLANS AS DRAWN DO NOT
 COMPLY WITH FBC11, ACCESSIBLE ROUTE, CLEARANCE,
 MANEUVERING CLEARANCE, ETC. ALSO REMOVE THE GUIDE RAIL
 DETAIL FROM THE ARCHITECTURAL SHEETS.
  
 AFTER REVISED CIVIL SHEETS HAVE BEEN APPROVED BY THE
 ENGINEERING DEPARTMENT, PLEASE SUBMIT TO CSD TO BE
 INCORPORATED INTO THE PERMIT SET.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status F Date 2009-04-28 Cont ID  
Sent By shill Date 2009-04-28 Time 15:44 Rev Time 0.00
Received By shill Date 2009-04-28 Time 15:44 Sent To  
Notes
2009-04-28 15:46:32****CORRECTIONS****
 ****REVISED ENERGY CALCS ONLY****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. FBC13-101.1.1.1, ENERGY CALCULATIONS SHALL BE SIGNED
 AND SEALED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status P Date 2009-04-03 Cont ID  
Sent By shill Date 2009-04-03 Time 09:51 Rev Time 0.00
Received By shill Date 2009-04-03 Time 08:43 Sent To  
Notes
2009-04-03 10:07:53***PROVISO***
  
 REVIEWED SHEETS A001A, 001B, 001C, 01, 02,
 03,04,05,06,08,09,14,16,22,23
 S05,07,08,10,11,14,15,16,18.2,18.3,18.4,18.5,18.7,18.12
 ,19,19A,21,22,24
  
 SUBMITTED AND FILED FOR INFORMATIONAL PURPOSES,
 PROCESSING SHEETS
 D03,03A,04,05,06,06A,07,08,09,10,12,14,14A,15,16,17
  
 ANCHORING INFORMATION (FBC1609)/SHOPS TO BE SUBMITTED
 TO INSPECTOR PER BUILDING OFFICIAL FOR PROCESS
 EQUIPMENT LOCATED OUTSIDE OF THE BUILDING
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2009-03-17 Cont ID  
Sent By shill Date 2009-03-17 Time 09:09 Rev Time 0.00
Received By shill Date 2009-03-17 Time 09:09 Sent To  
Notes
2009-03-17 09:10:06LETTER FROM ENGINEER (ELECTRIC) AS NEW DOR
 RON LARSON, PE
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status F Date 2008-12-05 Cont ID  
Sent By shill Date 2008-12-05 Time 10:48 Rev Time 0.00
Received By shill Date 2008-12-05 Time 10:48 Sent To  
Notes
2008-12-05 10:49:09****CORRECTIONS****
 ****REVISION****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE PREVIOUS LISTS REGARDING INFORMATION REQUIRED BY
 FAC61G1-16.004:
  
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 AN EMAIL HAS BEEN SENT TO BROOKE AHRENS SUGGESTING
 POSSIBLE RESOLUTIONS.
  
 2. ADDRESSED 12/4/08
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status F Date 2008-12-02 Cont ID  
Sent By shill Date 2008-12-02 Time 14:56 Rev Time 0.00
Received By shill Date 2008-12-02 Time 14:56 Sent To  
Notes
2008-12-02 15:23:48****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SEE PREVIOUS LISTS REGARDING INFORMATION REQUIRED BY
 FAC61G1-16.004:
  
 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 AN EMAIL HAS BEEN SENT TO BROOKE AHRENS SUGGESTING
 POSSIBLE RESOLUTIONS.
  
 2. THE REQUEST FOR REDUCED OCCUPANT LOAD PER FBC1004.1
 EXCEPTION 1 HAS BEEN SUBMITTED TO THE BUILDING
 OFFICIAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status F Date 2008-09-04 Cont ID  
Sent By shill Date 2008-09-04 Time 18:47 Rev Time 0.00
Received By shill Date 2008-09-04 Time 18:47 Sent To  
Notes
2008-09-04 18:51:40****CORRECTIONS****
 ****REVISION, VARIOUS SHEETS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. COMMENT FROM BUILDING REVIEW 13, DOORS 214.2 AND
 219.1 AT STAIR #1 ARE TO BE FIRE RESISTANCE RATED AS
 THEY ARE BOTH LOCATED IN A 2 HOUR WALL, FBC715.3.
  
 2. SHEET A5, MANY WALL TYPES CHANGED FROM THE RECORD
 SET BUT ARE NOT CLOUDED AS CHANGES. PLEASE CHECK THE
 ENTIRE SHEET FOR CHANGES, AND CLOUD AND NUMBER THOSE
 REVISIONS. OLD REVISIONS (BEFORE REVISION 5) DO NOT
 NEED TO BE CLOUDED AS THEY ARE NOW A PART OF THE RECORD
 SET.
  
 3. SHEET A5 DOES NOT MATCH THE LIFE SAFETY PLAN. THE
 RECORD SET HAS A STATEMENT THAT ONLY ONE EXIT IS
 REQUIRED FROM THE SECOND FLOOR. AFTER FURTHER
 INVESTIGATION, I HAVE DISCOVERED THAT THIS STATEMENT IS
 NOT CORRECT, THEREFORE THE LIFE SAFETY PLAN IN OUR
 RECORD SET IS NOT CODE COMPLIANT. THE NEW ARCHITECT OF
 RECORD AGREED TO CORRECT THIS ERROR. ALTHOUGH WE HAD
 THESE DISCUSSIONS IN FEBRUARY, THAT SHEET HAS STILL NOT
 BEEN REVISED. PLEASE SUBMIT. ALSO REVISE ANY OTHER
 SHEETS AFFECTED BY THE CHANGE TO SHEET A5.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status   Date 2008-09-04 Cont ID  
Sent By shill Date 2008-09-04 Time 18:17 Rev Time 0.00
Received By shill Date 2008-09-04 Time 18:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status F Date 2008-08-18 Cont ID  
Sent By shill Date 2008-08-18 Time 14:09 Rev Time 0.00
Received By shill Date 2008-08-18 Time 14:09 Sent To  
Notes
2008-08-18 14:10:46****CORRECTIONS****
 ***SUBMITTAL 15890-002B***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SOUTH FLORIDA BUILDING CODE IS REFERENCED; THIS IS
 NOT GOVERNING CODE.ANCHORING SHOULD BE SPECIFIC AS TO
 BRAND AND ANCHOR."TO CODE" IS NOT A SPECIFICATION;
 THE CODE DOES NOT INCLUDE PRESCRIPTIVE METHOD OF CURB
 ATTACHMENT.
  
 2.STRUCTURAL ENGINEER HAS REQUIRED THAT OPENINGS BE
 EVALUATED BY THE PRECASTER SPECIALTY (DELEGATED)
 ENGINEER.PLEASE HAVE THIS SUBMITTAL REVIEWED BY THE
 SPECIALTY ENGINEER AS WELL AS THE ENGINEER OF RECORD
 FOR THE STRUCTURE.REVISE STRUCTURAL DRAWINGS AS
 NECESSARY.
  
 3.AN OPENING IS SHOWN IN STAIR 1.SEE FBC1019.1.1,
 OPENINGS IN VERTICAL EXIT ENCLOSURES NOT PERMITTED
 EXCEPT AS NOTED.PLEASE CLARIFY PURPOSE; HAVE REVIEWED
 BY DESIGNER OF RECORD FOR LIFE SAFETY ISSUE.
  
 4.THE SHOP DRAWING REVIEW STAMP AND THE SUBMITTAL ARE
 NOT ENTIRELY LEGIBLE.PLEASE PROVIDE THREE LEGIBLE
 SETS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status F Date 2008-08-18 Cont ID  
Sent By shill Date 2008-08-18 Time 13:42 Rev Time 0.00
Received By shill Date 2008-08-18 Time 13:42 Sent To  
Notes
2008-08-18 13:47:57****CORRECTIONS****
 ***SUBMITTAL 15890-002B***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SOUTH FLORIDA BUILDING CODE IS REFERENCED; THIS IS
 NOT GOVERNING CODE.
  
 2.STRUCTURAL ENGINEER HAS REQUIRED THAT OPENINGS BE
 EVALUATED BY THE PRECASTER SPECIALTY (DELEGATED)
 ENGINEER.PLEASE HAVE THIS SUBMITTAL REVIEWED BY THE
 SPECIALTY ENGINEER AS WELL AS THE ENGINEER OF RECORD
 FOR THE STRUCTURE.
  
 3.AN OPENING IS SHOWN IN STAIR 1.SEE FBC1019.1.1,
 OPENINGS IN VERTICAL EXIT ENCLOSURES NOT PERMITTED
 EXCEPT AS NOTED.PLEASE CLARIFY PURPOSE; HAVE REVIEWED
 BY DESIGNER OF RECORD FOR LIFE SAFETY ISSUE.
  
 4.THE SOP DRAWING REVIEW STAMP AND THE SUBMITTAL ARE
 NOT ENTIRELY LEGIBLE.PLEASE PROVIDE THREE LEGIBLE
 SETS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2008-05-27 Cont ID  
Sent By shill Date 2008-05-27 Time 18:19 Rev Time 0.00
Received By shill Date 2008-05-27 Time 18:19 Sent To  
Notes
2008-05-27 18:20:30REVISION; NEW ROOF NOA
 ALSO ISSUED UNDER ROOFING SUB PERMIT 08020218

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2008-05-05 Cont ID  
Sent By shill Date 2008-05-05 Time 13:26 Rev Time 0.00
Received By shill Date 2008-05-05 Time 13:26 Sent To  
Notes
2008-05-05 14:10:48****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE SHEET S1.THE ROOF COVER IS TO MEET THE
 MINIMUMS SPECIFIED BY THE ENGINEER WHO DESIGNED THE
 BUILDING; IN THIS CASE, -53.33, -89.48, -134.67 FOR
 ZONES 1, 2, AND 3 RESPECTIVELY.EITHER REVISE THE
 ROOFING SUBMITTAL TO COMPLY WITH DESIGN CRITERIA ON S1
 OR REVISE SHEET S1.THE FORM SUBMITTED (HVHZ UNIFORM
 PERMIT APPLICATION FORM) MUST CORRELATE WITH THE PLANS
 IF SUBMITTED.THIS FORM NOW SSPECIFIES DESIGN
 PRESSURES AS -40.6, -73.3, AND -73.1.
  
 2.IF SHEET S1 IS REVISED TO THE PRESSURES SPECIFIED
 ON THE HVHZ FORM (-73.3 FOR ZONES 2 AND 3), PLEASE
 PROVIDE CALCULATIONS.SEE TABLES FBC1609.6.2.1(2) AND
 (4).IF THIS IS EXPOSURE C, 48 FEET, THE DESIGN
 PRESSURE FOR ZONE 2 USING THE TABLE WOULD BE
 APPROXIMATELY -90.58.WHEN DESIGN PRESSURES ARE
 SIGNIFICANTLY LOWER THAN TABLE, SIGNED AND SEALED
 CALCULATIONS ARE REQUIRED.
  
 3.THE HVHZ APPLICATION SHOWS A 3' PARAPET.SEE
 SHEET A 001 AND OTHER SHEETS; THE PLAN DOES APPEAR TO
 SHOW A 3' CONTINUOUS PARAPET WALL.WHEN RESUBMITTING,
 IF USING ZONE 2 PRESSURES FOR ZONE 3, PLEASE ADVISE AS
 TO WHERE THIS CAN BE LOCATED ON THE PLAN.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2008-04-22 Cont ID  
Sent By shill Date 2008-04-22 Time 08:19 Rev Time 0.00
Received By shill Date 2008-04-22 Time 08:19 Sent To  
Notes
2008-04-22 08:20:55****CORRECTIONS****
 ***REVISION, VARIOUS SHEETS***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.A ROOF HATCH IS SHOWN ON S07; PLEASE PROVIDE STATE
 OR LOCAL PRODUCT APPROVAL FAC9B72.THIS MAY BE A
 PROVISO ITEM; HOWEVER, PLEASE BE ADVISED THAT THIS
 ISSUE HAS DELAYED (AND ALMOST PREVENTED) C.O. ON OTHER
 JOBS.TO MY KNOWLEDGE, NO MANUFACTURER HAS YET
 OBTAINED STATE PRODUCT APPROVAL FOR A ROOF HATCH, AND
 ONLY ONE HAS OBTAINED A LOCAL PRODUCT APPROVAL.THERE
 HAS BEEN A DECLARATORY STATEMENT ISSUED BY THE STATE
 CONFIRMING THAT ROOF HATCH FALLS UNDER FAC9B72.
  
 2.SECTION 4 S05, DETAIL INDICATOR 4 S14 IS NO LONGER
 INCORPORATED IN THE DETAIL.IS THERE A NEW DETAIL FOR
 THIS, OR IS IT UNNECESSARY?
  
 3.SHEET S20 DOES NOT MATCH THE S20 WE HAVE ON FILE.
 THE SHEET S20 SUBMITTED IS TITLED SCRUBBER, COOLING
 TOWER & PELLET OIL TANK FOUNDATION PLANS & SECTIONS,
 BUT THE INDEX DOES NOT SHOW A SHEET WITH THIS TITLE IN
 THE ISSUED SET OF PLANS.IT APPEARS TO BE A NEW SHEET,
 AND SHOULD HAVE A UNIQUE SHEET NUMBER.THE SHEET ON
 FILE IS TITLED COOLING TOWER PAD & CHEMICAL STORAGE.
 DOES THE NEW SHEET REPLACE THIS ONE OR SHOULD IT BE
 ADDED?
  
 4. S20, COOLING TOWER FOUNDATION PLAN, SHOWS A CLOUD
 WITH A NOTE THAT STATES HOLD.PLEASE PROVIDE MORE
 INFORMATION.
  
 5. SEE SHEET A001A LIFE SAFETY PLAN OVERALL AND THE
 REVISED A001B.THE TRAVEL DISTANCE FROM STAIR 5 IS TO
 BE MEASURED ALONG THE NATURAL PATH OF TRAVEL.AS
 DRAWN, THE PATH APPEARS TO GO THROUGH EQUIPMENT.
 PLEASE REVISE. FBC1015.1.
  
 6.CLARIFY COMMON PATH OF TRAVEL, SHOWN AS 4FT.SEE
 DEFINITION, FBC1002.
  
 7.SEE PREVIOUS LIST; THE CERTIFICATE OF AUTHORIZATION
 FOR THE ARCHITECTURE FIRM AND NAME OF INDIVIDUAL
 SIGNING THE DOCUMENT IS TO BE PRINTED ON EACH SHEET,
 FAC61G16-23.002, 003.
  
 8.THE CERTIFICATE OF AUTHORIZATION FOR THE
 ENGINEERING FIRM IS TO BE PRINTED ON EACH SHEET,
 FAC6G15-23.002.
  
 9. A05, WALL TYPE B STATES THAT THIS IS 8IN CMU WITH
 6IN 20 GAGE METAL STUDS.WALL CONSTRUCTION IS NOT
 CLEAR, PLEASE REVISE OR PROVIDE A DETAIL.
  
 10. DOORS 214.2 AND 219.1 AT STAIR #1 ARE TO BE FIRE
 RESISTANCE RATED AS THEY ARE BOTH LOCATED IN A 2 HOUR
 WALL, FBC715.3.
  
 11. I WAS UNABLE TO LOCATE HARDWARE SET DESCRIPTIONS TO
 CONFIRM COMPLIANCE WITH FBC715.3.7.PLEASE ADVISE.
  
 12.EXITING FROM THE SECOND FLOOR DOES NOT COMPLY WITH
 MAXIMUM TRAVEL DISTANCE FOR ONE EXIT, SEE FBC TABLE
 1018.2.THE TRAVEL DISTANCE IS TO BE MEASURED FROM THE
 FARTHEST POINT TO THE EXIT DISCHARGE; IN THIS CASE, TO
 THE EXIT DOOR ON THE FIRST FLOOR.AS THE DISTANCE FROM
 THE TOP OF STAIR #5 TO THE EXIT DOOR EXCEEDS 124FT,
 THIS AREA HAS A TRAVEL DISTANCE GREATER THAN THE 75FT
 PERMITTED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2008-01-07 Cont ID  
Sent By shill Date 2008-01-07 Time 14:21 Rev Time  
Received By shill Date 2008-01-03 Time 07:48 Sent To  
Notes
2008-01-03 07:50:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ARCHITECT STATES ON SHEET A001B, "ONLY ONE EXIT IS
 REQUIRED FROM THE SECOND LEVEL."PLEASE CLARIFY THIS
 STATEMENT AND DESIGN, SEE FBC TABLE 1018.2.
  
 2.SEE FBC1013.2, EGRESS THROUGH INTERVENING SPACES.
 THIS IS NOT ALLOWED THROUGH KITCHENS, STORAGE, CLOSETS
 OR SIMILAR SPACES.EXITING FROM THE PROCESSING AREA
 THROUGH THE MECHANICAL ROOM APPEARS TO BE PROHIBITED BY
 THIS CODE SECTION.
  
 3.ALL INFORMATIION REQUIRED BY FAC61G1-15.23 IS
 REQUIRED FOR THE ARCHITECT.IF THE TITLE BLOCK FOR HDR
 ENGINEERING IS THE TITLE BLOCK FOR THE ARCHITECT,
 PROVIDE THE CERTIFICATE OF AUTHORIZATION (ARCHITECT
 BUSINESS) LICENSE NUMBER ON THE PLAN.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2007-12-11 Cont ID  
Sent By shill Date 2007-12-11 Time 15:35 Rev Time 0.00
Received By shill Date 2007-12-11 Time 15:35 Sent To  
Notes
2007-12-11 15:36:18SUBMITTAL (FOUNDATION REPAIR) OK, REVIEWED BY RB
  
 DATED 12/3/7
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2007-11-09 Cont ID  
Sent By shill Date 2007-11-09 Time 11:41 Rev Time 0.00
Received By shill Date 2007-11-09 Time 11:41 Sent To  
Notes
2007-11-09 11:50:51****CORRECTIONS****
 ****REVISIONS***
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.FOR THE STRUCTURAL ENGINEER, PLEASE SUBMIT A LETTER
 SHOWING COMPLIANCE WITH FAC61G15-27.UPON RECEIPT OF
 THIS LETTER, THE REVISED SHEETS NOT AFFECTED BY OTHER
 COMMENTS CAN BE PROCESSED.
  
 2.SEE SHEET D03.REGARDING THE AREA ENCLOSED BY
 CHAIN LINK FENCE, IS THIS AREA REQUIRED TO BE
 ACCESSIBLE?NOTE USE OF AREA AND SHOW COMPLIANCE IF
 REQUIRED, FBC11.FEEL FREE TO CONTACT ME TO DISCUSS IF
 YOU NEED ASSISTANCE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2007-10-17 Cont ID  
Sent By shill Date 2007-10-17 Time 14:02 Rev Time 0.00
Received By shill Date 2007-10-17 Time 14:02 Sent To I
Notes
2007-10-17 14:02:40REVISED C03

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2007-09-26 Cont ID  
Sent By shill Date 2007-09-26 Time 14:49 Rev Time 0.00
Received By shill Date 2007-09-26 Time 14:49 Sent To  
Notes
2007-09-26 15:08:16REVISION (PARTIAL) DATED 3/07, SHEETS A2, A3, A5, D3,
 D6, S2, S4, S5, S12, S16, S17

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2007-09-04 Cont ID  
Sent By shill Date 2007-09-04 Time 15:45 Rev Time 0.00
Received By shill Date 2007-09-04 Time 15:36 Sent To  
Notes
2007-09-04 15:50:52****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)I CANNOT DETERMINE WHAT CHANGED ON SHEETS C-08 AND
 C-09.
  
 2.)DEFICIENCY REPORT (DUNKELBERGER) DATED 8/9, ITEM
 8, REQUIRED C3 TO BE REVISED (ROTATE BUILDING TO NEW
 COORDINATES).PLEASE ADDRESS.
  
 3.)DEFICIENCY REPORT ITEM 2 STATES THAT THE ELEVATOR
 CMU WAS CHANGED TO TILT WALL, BUT THE PLAN STILL SHOWS
 A CMU WALL TYPE.
  
 4.)SUBMIT ALL STRUCTURAL STEEL SHOPS, ANCHOR BOLTS,
 ETC. AS REQUESTED (DEFICIENCY REPORT ITEM 7).THREE
 SETS REVIEWED BY DESIGNER OF RECORD REQUIRED.
  
 5.)DEFICIENCY REPORT ITEM 6 REQUIRED THAT DRAWINGS
 S12.001, .002, .003 AND .004 BE REVISED.WERE ALL
 MODIFICATIONS INCLUDED IN THE PACKAGE SUBMITTED?
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2007-06-11 Cont ID  
Sent By shill Date 2007-06-11 Time 16:49 Rev Time 0.00
Received By shill Date 2007-06-11 Time 16:49 Sent To  
Notes
2007-06-11 16:52:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
  
 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS FAC61G15-23.002.
  
 2.)THREE SETS REQUIRED AS THIS IS A RESIDENT
 INSPECTOR JOB.
  
 3.)RATHER THAN SUBMITTING AN 8 1/2 X 11 FOOTING
 SCHEDULE, PLEASE REVISE THE STRUCTURAL SHEET IN THE
 BUILDING PLAN WHICH HAD THIS INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-03-30 Cont ID  
Sent By shill Date 2007-03-30 Time 06:52 Rev Time 0.00
Received By shill Date 2007-03-30 Time 06:52 Sent To  
Notes
2007-03-30 07:24:12***PROVISO***
  
  
 SHOP DRAWINGS OR ENGINEERING REQUIRED FOR SILO, DUSTROL
 TANK, OTHER ITEMS FOR WHICH SPECS WERE NOT SUBMITTED
 PRIOR TO PERMITTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2007-02-08 Cont ID  
Sent By shill Date 2007-02-08 Time 13:18 Rev Time 0.00
Received By shill Date 2007-02-08 Time 13:17 Sent To  
Notes
2007-02-08 13:36:17SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
 1.)AS DISCUSSED, PLANS ARE REQUIRED TO BE SIGNED,
 SEALED, AND DATED.UPON RECEIPT OF ARCHITECT LICENSE,
 MR. VARGA (OR OTHER QUALIFIED INDIVIDUAL) IS TO SUBMIT
 APPROPRIATE PAPERWORK WITH THE STATE TO REPLACE THE
 PREVIOUS ARCHITECT AS RESPONSIBLE SUPERVISOR AND
 QUALIFYING ARCHITECT.UPON RECEIPT OF HIS SEAL, MR.
 VARGA IS TO SIGN, SEAL, AND DATE ALL SHEETS HE IS TO BE
 RESPONSIBLE FOR.PLANS OTHERWISE APPEAR CODE
 COMPLIANT.
  
  
 ***PROVISO***
  
 2.)SHOP DRAWINGS/ENGINEERING WILL BE REQUIRED FOR
 ITEMS SUCH AS THE SILO, DUSTROL TANK, ETC.THEY ARE TO
 BE SUBMITTED PRIOR TO INSTALLATION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-12-26 Cont ID  
Sent By shill Date 2006-12-26 Time 10:48 Rev Time 0.00
Received By shill Date 2006-12-18 Time 09:53 Sent To  
Notes
2006-12-26 10:48:40****CORRECTIONS****
 ****CONVERTED TO PERMIT; SECOND PERMIT
 PLAN REVIEW ****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER 561-805-6724
 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 COMMENTS FROM PREVIOUS REVIEW, EITHER
 NOT ADDRESSED OR REQUIRING FURTHER
 CLARIFICATION; NUMBERING REMAINING THE
 SAME FOR CONSISTENCY:
  
 1.)REGARDING IMPACT FEES, PLEASE SUBMIT A LETTER
 CONFIRMING THAT THE BUILDING IS OWNED BY SOLID WASTE
 AUTHORITY.NOTE THAT PRIVATELY OWNED COMPANIES
 OPERATING ON GOVERNMENT PROPERTY ARE NOT AUTOMATICALLY
 EXEMPT FROM IMPACT FEES.THE PURPOSE OF THE LETTER IS
 TO DOCUMENT EXEMPTION TO IMPACT FEES FOR THIS PROJECT.
  
  
 2.-3.)ADDRESSED.
  
 4.) FBC* 109.3.7RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 OWNER, RESIDENT INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.
  
 THE RESPONSE THAT THIS WILL BE DONE IS ACKNOWLEDGED.
 THIS IS REQUIRED PRIOR TO
 PERMIT ISSUANCE.NOTE THAT AS OF 12/21, MR. PISKURA
 HAS NOT ADVISED THAT THIS HAS BEEN RESOLVED.PLEASE
 CONTACT HIM AS SOON AS POSSIBLE TO PREVENT PERMITTING
 DELAYS.THE RESPONSE LETTER STATED THAT YOU WOULD
 SCHEDULE THE MEETING PRIOR TO INSPECTIONS.NOTE THAT
 THE REQUIREMENT IS TO HAVE AN INSPECTOR APPROVED BY THE
 CITY PRIOR TO PERMIT ISSUANCE.
  
 5-7.)ADDRESSED WITH EXCEPTION OF H4 OCCUPANCY
 CLASSIFICATION FOR CORROSIVE CHEMICAL USED INSIDE THE
 BUILDING; SEE OTHER COMMENTS.
  
 8.)REGARDING THE CODE SUMMARY, PLEASE NOTE THE
 FOLLOWING:
  
 A.)A01 WAS REVISED BUT STILL REFERS TO A ONE STORY
 BUILDING.AS PER CONVERSATIONS WITH ARCHITECT,
 ARCHITECT?S RESPONSE LETTER, AND COMMENTS FROM PREVIOUS
 REVIEWS, THIS IS A TWO STORY BUILDING (NOT A ONE STORY
 WITH A MEZZANINE AREA).PLEASE REVISE.
  
 B.)THE TABULAR OCCUPANT LOAD STATES THAT SECOND FLOOR
 F ACCESSORY IS 1536 SF, 100 SF PER OCCUPANT, FOR
 OCCUPANT LOAD OF 5.THE MATH IS INCORRECT, PLEASE
 REVISE.THE OCCUPANT LOAD FOR MEANS OF EGRESS CANNOT
 BE LESS THAN FBC TABLE 1004.1.2, SEE FBC1004.1.YOU
 CAN DECLARE AN OCCUPANT LOAD WHICH IS LESS THAN THE
 TABLE FOR PURPOSES OF EXCEPTION FROM VERTICAL
 ACCESSIBILITY REQUIREMENTS, BUT THIS IS NOT APPLICABLE
 FOR MEANS OF EGRESS.
  
 C.)SECOND FLOOR F ACCESSORY, SEE FBC302.2.FIRE
 BARRIER REQUIRED FOR ACCESSORY USE IF THE AREA EXCEEDS
 TEN PERCENT OF THE FLOOR AREA.THIS AREA IS 28%.THE
 CODE SUMMARY INDICATES THAT A 2 HOUR SEPARATION IS
 REQUIRED BUT NONE IS SHOWN BETWEEN THE ACCESSORY AREA
 AND THE CORRIDOR, WHICH THE BUSINESS AND FACTORY AREAS
 BOTH USE AS A MEANS OF EGRESS.
  
 D.)M02, IF PLANS ARE REVISED TO REQUIRE THE WALL
 BETWEEN THE CORRIDOR AND THE ACCESSORY AREA IS TO BE
 FIRE RATED, PENETRATIONS ARE TO BE PROTECTED FBC712.
  
 E.)A001 HAS A NOTE THAT THE SECOND FLOOR OCCUPANT
 LOAD WILL BE LESS THAN 50.NOTE THAT IF YOU USE THE
 SQUARE FOOT PER OCCUPANT DECLARED ON A001, THE OCCUPANT
 LOAD WILL BE GREATER THAN 50.HOWEVER, SEE FBC TABLE
 1004.1.2.ACCESSORY STORAGE AREAS, MECHANICAL
 EQUIPMENT ROOM, CAN BE 300 SF PER OCCUPANT.
  
 F.)IN CALCULATING OCCUPANT LOAD, ALL NUMBERS SHOULD
 BE ROUNDED UP AS THE OCCUPANT LOAD CANNOT BE LESS THAN
 FBC TABLE 1004.1.2.SEE FBC1004.1.
  
 9-12.)ADDRESSED.
  
 13.)THE ACCESSIBLE ROUTE FBC11-4.1.2(1) IS SHOWN.
 PLEASE CLARIFY HOW THE ACCESSIBLE ROUTE IS AFFECTED BY
 THE SLIDING GATE.HOW DOES THIS GATE OPERATE; IS THAT
 FUNCTION DIFFERENT FOR ACCESSIBILITY?THE SLOPE AND
 CROSS SLOPE ARE TO COMPLY WITH FBC11-4.3.7.
  
 14.)PROVIDE FIRE SPRINKLER PLANS, FBC*106.3.5.1.1(5).
 A SHEET SHOWING THE TYPE OF SPRINKLERS WHICH WILL BE
 INSTALLED IN EACH AREA WAS PROVIDED BUT DOES NOT COMPLY
 WITH STATUTORY REQUIREMENTS FS553.79(2).YOUR REQUEST
 THAT THIS BE A PROVISO ITEM IS ACKNOWLEDGED BUT PER
 BUILDING OFFICIAL STATUTORY REQUIREMENTS CANNOT BE
 PROVISO ITEMS.PLEASE SEE ATTACHED LETTER FROM THE
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS (REGULATORY
 AGENCY FOR BUILDING CODE).IT STATES ?PLEASE NOTE THAT
 DESIGN DOCUMENTS, INCLUDING THE FIRE PROTECTION
 SPRINKLER SYSTEM (WHICH IS TO BE REVIEWED BY THE
 APPROPRIATE FIRE SAFETY INSPECTOR) ARE TO BE SUBMITTED
 TO YOU AT THE TIME OF PERMITTING, AND THAT THOSE
 DESIGNS MUST BE REVIEWED FOR COMPLIANCE AT THAT TIME
 BEFORE A PERMIT IS ISSUED.?CALCULATIONS, SPEC
 SHEETS, SHOPS, ETC. ARE NOT REQUIRED AT THIS TIME; THEY
 ARE TO BE SUBMITTED WITH THE FIRE SPRINKLER PERMIT
 APPLICATION.
  
 15.)ADDRESSED.
  
 16.)THE LIFE SAFETY PLAN APPEARS CODE COMPLIANT FOR
 F3 OCCUPANCY WITH THE EXCEPTION OF THE ITEMS NOTED
 BELOW.SEE OTHER COMMENTS REGARDING H4 OCCUPANCY. NOTE
 THAT IF H4 IS DETERMINED FOR A PORTION OF THE BUILDING,
 TRAVEL DISTANCE IS LIMITED TO 100FEET AND THE LIFE
 SAFETY PLAN WOULD NOT BE COMPLIANT FOR THAT OCCUPANCY
 CLASSIFICATION.
  
 A.)SPECIFY THE SLOPE FOR THE SLUDGE RECEIVING AREA.
 THIS AREA IS SHOWN AS A MEANS OF EGRESS.FEE
 FBC1003.5; DOES THIS REQUIRE A RAMP TO COMPLY WITH
 FBC1010?SEE ALSO FBC TABLE 1018.2.
  
 B.)DECLARE OCCUPANT LOAD FOR EACH AREA.OCCUPANT
 LOAD FOR MEANS OF EGRESS CANNOT BE LESS THAN FBC TABLE
 1004.1.2, SEE FBC1004.1.YOU CAN DECLARE AN OCCUPANT
 LOAD WHICH IS LESS THAN THE TABLE FOR PURPOSES OF
 EXCEPTION FROM VERTICAL ACCESSIBILITY REQUIREMENTS, BUT
 THIS IS NOT APPLICABLE FOR MEANS OF EGRESS.
  
 C.)THE BUSINESS AREA EXITS THROUGH THE CORRIDOR WHICH
 IS A PART OF THE F3 OCCUPANCY.SEE PREVIOUS LISTS IN
 REGARDS TO EXITING THROUGH A MORE HAZARDOUS OCCUPANCY.
 NOTE THAT THE CORRIDOR IS NOT FIRE RATED AND IS A PART
 OF THE F3 OCCUPANCY, NOT THE B OCCUPANCY.
  
 17-20.) ADDRESSED.
  
 21.)A MEZZANINE IS TO BE LOCATED IN A ROOM.
 AS THE AREA BELOW AND AREA ABOVE ARE
 BOTH ENCLOSED, THIS PORTION IS TWO
 STORIES.SEE THE DEFININTIONS FOR
 MEZZANINE AND STORY.THIS IS NOT
 LOCATED BETWEEN THE FLOOR BELOW AND THE
 CEILING ABOVE AS THE CEILING ABOVE THE
 SLUDGE STORAGE ROOM (WHICH HAS A WALL)
 IS THE 2ND FLOOR.THIS AREA IS TWO
 STORIES, NOT A MEZZANINE, BY DEFINITION.
  
 PLEASE REVISE A001 TO DECLARE A TWO STORY BUILDING.
  
 22.)ADDRESSED.
  
 23.)PRODUCT APPROVALS:
  
 FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED FOR
 ALL PRODUCTS, INCLUDING FOR PRODUCTS WHICH HAVE AN NOA.
 PLEASE PRINT THE FLORIDA STATE PRODUCT APPROVAL FROM
 THE WEBSITE FOR THE FOLLOWING NOAS:03-1015.05,
 05-0214.02, 03-0422.05, 03-1027.01, 03-0611.01.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT AVAILABLE PLEASE
 ADVISE AND A LOCAL PRODUCT APPROVAL WILL BE ISSUED FOR
 YOU.
  
 DESIGN PRESSURES FOR THE WINDOWS WERE NOT PROVIDED ON
 THE PLAN, SHEET S01.
  
 NOA 05-0729.04 IS SMALL MISSILE IMPACT RATED.LARGE
 MISSILE IMPACT REQUIRED FOR THE FIRST THIRTY FEET ABOVE
 GRADE, FBC1609.1.4.IS THIS PRODUCT BEING INSTALLED
 OVER 30 FEET?PLEASE NOTE ON THE PRODUCT APPROVAL TO
 AVOID CONFUSION IN THE FIELD.OTHERWISE IMPACT
 PROTECTION IS REQUIRED.USE OF REMOVABLE SHUTTERS ON
 COMMERCIAL BUILDINGS MUST BE APPROVED BY THE BUILDING
 OFFICIAL.PLEASE ADVISE.
  
 THE PROPOSAL FROM WILLARD SHUTTER COMPANY IS FOR 120
 MPH WIND LOAD.IS THIS FASTEST MILE OR 3 SECOND GUST?
 CITY OF WEST PALM BEACH IS IN THE 140MPH WIND ZONE. SEE
 FBC1609.3.ENGINEERING AND SHOP DRAWINGS WILL BE
 REQUIRED PRIOR TO INSTALLATION.
  
 NOA 03-0827.11 GAF SELF ADHERING MODIFIED HAS A DESIGN
 PRESSURE LIMITATION OF -72.5, GENERAL LIMITATION #9,
 AND IS NOT COMPLIANT FOR ZONES 2 AND 3.
  
 NOA 02-0515.02, GENERAL LIMITATION #3, INSTALLER SHALL
 BE APPROVED BY GAF MATERIAL CORP.PLEASE ADDRESS.
  
 NOA 02-1018.11, BARRETT RAM-TOUGH PLAZA, INSTALLER
 SHALL BE APPROVED BY BARRETT.PLEASE ADDRESS.
  
 ANY PRODUCT APPROVALS NOT SUBMITTED AND REVIEWED PRIOR
 TO PERMIT ISSUANCE WILL BE REQUIRED TO HAVE SEPARATE
 PERMITS FOR THOSE ITEMS WITH SEPARATE FEES.
  
 24.)YOUR RESPONSE THAT THE SLUDGE RECEIVING AND
 SLUDGE STORAGE AREAS ARE EXEMPT FROM VERTICAL
 ACCESSIBILITY IS ACKNOWLEDGED.PLEASE SHOW A DESIGN
 OCCUPANT LOAD OF LESS THAN 5 FOR BOTH OF THESE AREAS ON
 SHEET A001.NOTE THAT YOUR OCCUPANT LOAD FOR EGRESS
 WILL BE GREATER THAN 5 BASED ON SQUARE FOOT AREA.
  
 25-29.)ADDRESSED.
  
 30.)PROVIDE DETAILS FOR THE UL
 ASSEMBLIES SPECIFIED.A05 STATES ?INDICATE 2-HOUR
 RATED ASSEMBLIES (SEE FBC TABLE 7720.1(2) FOR
 EQUIVALENCE OF FIRE RESISTANCE RATING OF SOLID
 CONCRETE)?.THIS IS NOT A CORRECT CODE REFERENCE.
 PROVIDE A DETAIL.IF YOU ARE USING CALCULATED FIRE
 RESISTANCE, PROVIDE COMPONENTS ALONG WITH TIME ASSIGNED
 TO EACH COMPONENT TO SHOW COMPLIANCE WITH THE SPECIFIED
 2 HOUR RATING.
  
 31.)ADDRESSED.
  
 32.)FROM THE PREVIOUS LISTS:PROVIDE ALL STRUCTURAL
 INFORMATION AT THIS TIME FOR ITEMS SUCH AS THE DUSTROL
 TANK;
 LOADS, CONCRETE, ANCHORING,
 FBC415.7.2.2, TANK PROTECTION), NFPA30
 (STORAGE OF COMBUSTIBLES), FBC1606.1.3
 (ANCHORING TO PREVENT OVERTURNING).SEE
 ALSO FBC415.7.1.1, AND FBC415.7.1.5,
 GRAIN ELEVATORS AND SIMILAR STRUCTURES;
 THIS APPEARS TO APPLY TO THE STORAGE
 SILO (PROVIDE INFORMATION IN REGARDS TO CONSTRUCTION
 TYPE, HEIGHT).
  
 THIS WILL BE A PROVISO ITEM AS REQUESTED.CHANGES TO
 THE PLAN SUCH AS CONCRETE SLABS NOT CURRENTLY SHOWN ON
 THE PLAN WILL REQUIRE A REVISION WITH APPLICABLE FEES.
 OTHER ITEMS SUCH AS SHOP DRAWINGS AND ENGINEERING FOR
 ITEMS SUCH AS THE TANKS AND SILO WILL BE SUBMITTALS (NO
 FEE).
  
 33-36.) ADDRESSED.
  
 37-38, 43, 46)REGARDING OCCUPANCY CLASSIFICATION,
 PLEASE PROVIDE QUANTITY OF CORROSIVE CHEMICALS WHICH
 WILL BE USED IN THE PROCESSING AREA.BASED ON A
 TELEPHONE CONVERSATION WITH MR. DELAFOREST AND THE
 RESPONSE LETTER, THE QUANTITY IS LESS THAN THE EXEMPT
 AMOUNT AND DOES NOT CHANGE THE OCCUPANCY CLASSIFICATION
 FROM F3 TO H4.PLEASE NOTE THE QUANTITY OF CORROSIVE
 CHEMICAL TO BE USED IN THE PROCESSING AREA ON THE PLAN
 OR PROVIDE A SIGNED, SEALED, AND DATED CLARIFICATION
 LETTER.
  
 39-42.) ADDRESSED.
  
 44-45.) ADDRESSED.
  
 47.)ADDRESSED.
  
 48.) C12, ACCESSIBLE PARKING, THE FEE IS
 $250 RATHER THAN $100, CITY OF WEST PALM
 BEACH RESOLUTION #390-03, SECTION 2, #D.
  
 PLEASE REVISE.
  
 49-57.) ADDRESSED.
  
 58.)OCCUPANT LOAD SHOULD ROUND UP RATHER THAN ROUND
 DOWN WHEN CALCULATIONS RESULT IN A FRACTION AS THE LOAD
 CANNOT BE LESS THAN THE TABLE FBC1004.1.2.
  
 59-74.) ADDRESSED.
  
 NEW COMMENTS:
  
 75.)THE FIRE RATED WALLS SHOWN ON A001A AND A04 ARE
 NOT CONSISTENT.THE 2 HOUR WALL WHICH PROTECTS THE
 EXTERIOR STAIR IS SHOWN AS EXTENDING 10FT ON EITHER
 SIDE OF THE STAIR ON A001A, BUT ON A04 THE STAIRWAY
 ONLY IS RATED.IT IS NOT CLEAR WHETHER OR NOT DOOR
 103.1 IS REQUIRED TO BE RATED.THE DOOR SCHEDULE ON
 A22 SPECIFIES A NON RATED DOOR, SHEET A001A SHOWS THIS
 OPENING INCLUDED IN THE 10FT FIRE RATED WALL AREA. FIRE
 RESISTANCE RATING OF 1.5 HOUR REQUIRED FOR 2 HOUR WALL,
 FBC715.3.
  
 76.)A001B SHOWS A WINDOW AT THE BREAK ROOM WHICH IS
 TO BE FIRE RATED.SPECIFY OPENING PROTECTION AND
 PROVIDE A PRODUCT APPROVAL.IMPACT PROTECTION
 REQUIRED.
  
 77.)A001A SHOWS A SECOND EXTERIOR STAIR TO THE EAST
 OF STAIR 1.THIS STAIR DOES NOT APPEAR ON A04 OR ON
 OTHER SHEETS.
  
 78.)PLEASE CONFIRM THAT THEPERMIT APPLICATION TO
 REFERS TO THE CORRECT PARCEL ID 74424234000001000.
  
 79.)S18, TILT UP PANEL NOTES, ITEM 13, WRONG CODE
 REFERENCE FOR IMPACT.DESIGN CRITERIA IS REQUIRED BUT
 CODE REFERENCES ARE NOT REQUIRED ON THE PLANS.YOU MAY
 EITHER REVISE THE CODE REFERENCE OR REMOVE IT.
  
 80.)S01, IT IS NOT CLEAR WHAT ROOF ENCLOSURE
 PRESSURES ARE FOR.IS THIS THE CHEMICAL STORAGE
 ENCLOSURE, WHICH NO LONGER HAS A ROOF?
  
 81.)THE DETAIL FOR THE 2 HOUR FLOOR/CEILING ASSEMBLY
 SPECIFIES A 4" POURED CONCRETE TOPPING; OTHER PAGES ON
 THE PLAN SPECIFY 2".PLEASE ADDRESS.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-03 Cont ID  
Sent By shill Date 2006-08-03 Time 15:17 Rev Time 40.00
Received By shill Date 2006-07-21 Time 09:19 Sent To  
Notes
2006-08-03 00:00:00****CORRECTIONS****
 ****CONVERTED TO PERMIT; FIRST PERMIT
 PLAN REVIEW ****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 NEW COMMENT, 8/24/06
  
 AFTER REVIEW OF THE DRAFT OF THE REVISED
 HAZARD ANALYSIS, OCCUPANCY
 CLASSIFICATION FOR THE PROCESSING AREA
 AND SLUDGE CAKE STORAGE AREA ARE H2.
 PLEASE REVISE PLANS ACCORDINGLY.
  
  
 COMMENTS FROM PREVIOUS REVIEW, EITHER
 NOT ADDRESSED OR REQUIRING FURTHER
 CLARIFICATION; NUMBERING REMAINING THE
 SAME FOR CONSISTENCY:
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION, 561-233-5025, 2300 NORTH
 JOG ROAD, SUITE 2W01.
  
 2.)PROVIDE A SOILS INVESTIGATION
 REPORT FBC1802.2.THE SOILS REPORT
 PROVIDED WAS A PHOTOCOPY.ALL DOCUMENTS
 PREPARED BY AN ENGINEER AND SUBMITTED
 FOR PUBLIC RECORD ARE TO BE SIGNED,
 SEALED, DATED ORIGINALS FAC61G15-23.
 PROVIDE THREE ORIGINALS.HAS THE
 DESIGNER OF RECORD REVIEWED THE SOILS
 REPORT?
  
 3.)THREE COPIES OF ALL PERMIT
 DOCUMENTS REQUIRED, SEE ITEM 4 BELOW.
 THIS IS TO BE DONE ON EVERY SUBMITTAL,
 ALL DOCUMENTS, AS CODE COMPLIANT
 DOCUMENTS ARE STAMPED BY THE INDIVIDUAL
 TRADES.FAILURE TO SUBMIT THREE COPIES
 EVERY SUBMITTAL RESULTS IN REVIEWERS WHO
 MAY HAVE ALREADY PASSED THEIR REVIEWS
 BEING REQUIRED TO REVIEW THE PLANS AGAIN
 TO STAMP THE NEW SHEETS.
  
 4.) FBC* 109.3.7RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 OWNER, RESIDENT INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.
  
 THE RESPONSE THAT THIS WILL BE DONE IS
 ACKNOWLEDGED.THIS IS REQUIRED PRIOR TO
 PERMIT ISSUANCE.
  
 5-6.)ADDRESSED.
  
 7.) FROM PREVIOUS REVIEW; NOT COMPLETELY
 ADDRESSED.ALSO SEE NEW COMMENTS.
  
 NOT ENOUGH INFORMATION HAS BEEN PROVIDED
 ABOUT THE MATERIALS PROCESSED AND THE
 END PRODUCT TO DETERMINE THE CORRECT SUB
 CLASSIFICATION.PROVIDE INFORMATION
 ABOUT THE QUANTITY OF MATERIALS USED IN
 PROCESSING, FLAMMABLE GASES PRODUCED,
 AND THE END PRODUCT AS RELATED TO
 OCCUPANCY CLASSIFICATION.SEE ALSO
 FBC307.8 REGARDING MULTIPLE HAZARDS, AND
 NFPA 820 1.3.5, MATERIALS USED FOR ANTI
 CORROSION WHICH MAY CAUSE ACCELERATED
 BURNING.
  
 IN ORDER TO ASSIST IN DETERMINING
 CORRECT OCCUPANCY CLASSIFICATION, PLEASE
 ADDRESS THIS ITEM IN A SIGNED, SEALED
 AND DATED LETTER FROM ONE OF THE DESIGN
 PROFESSIONALS WITH THE ASSOCIATED
 DOCUMENTATION, INCLUDING MSDS IF
 AVAILABLE.
  
 THE HAZARD ANALYSIS DOES NOT ADDRESS
 QUANTITIES OF HAZARDOUS CHEMICALS USED
 IN THE PROCESSING AREA.SEE ALSO OTHER
 COMMENTS.
  
 8.)REVISE OTHER ITEMS A01, CODE
 SUMMARY WHICH ARE AFFECTED BY THE
 OCCUPANCY CLASSIFICATION AND REVISE
 PLANS ACCORDINGLY (BUILDING HEIGHT AND
 AREA, OCCUPANT LOAD, ETC.).NOTE THAT
 DUE TO A LACK OF A CORRECT OCCUPANCY
 CLASSIFICATION A COMPLETE CHECKLIST
 CANNOT BE PROVIDED AT THIS TIME.
  
 9.)ADDRESSED.
  
 10.)CODE COMPLIANCE WITH FBC TABLE
 503, CANNOT BE DETERMINED WITHOUT THE
 CORRECT OCCUPANCY CLASSIFICATION.IF
 YOU ARE USING AN AREA INCREASE, PROVIDE
 CALCULATIONS FBC506.
  
 2ND REVIEW - PLEASE INCORPORATE THE
 CALCULATIONS INTO THE PLAN AFTER AN
 OCCUPANCY CLASSIFICATION HAS BEEN AGREED
 UPON.
  
 11.)PROVIDE MSDS FOR EACH MATERIAL
 USED FOR PROCESSING AND FOR THE END
 PRODUCT.PLEASE PROVIDE IN A MORE
 ORGANIZED FORMAT; PREFERABLY COLLATED,
 TABBED AND BOUND RATHER THAN OVER A
 HUNDRED LOOSE SHEETS OF PAPER.
  
 12.)ADDRESSED.
  
 13.)SHOW THE ACCESSIBLE ROUTE
 FBC11-4.1.2(1).NOT ADDRESSED."AT
 LEAST ONE ACCESSIBLE ROUTE COMPLYING
 WITH SECTION 11-4.3 SHALL BE PROVIDED
 WITHIN THE BOUNDARY OF THE SITE FROM
 PUBLIC TRANSPORTATION STOPS . . . AND
 PUBLIC STREETS OR SIDEWALKS, TO AN
 ACCESSIBLE BUILDING ENTRANCE."
  
 14.)PROVIDE FIRE SPRINKLER PLANS,
 FBC*106.3.5.1.1(5).YOUR RESPONSE THAT
 DETAILED DRAWINGS WILL BE DEVELOPED BY
 THE CONTRACTOR IS ACKNOWLEDGED.THEY
 WERE NOT INCLUDED IN THIS SUBMITTAL.
 SEE FBC*106.3.5.1.1(5), FS553.79(2), AND
 THE ATTACHED LETTER OF CLARIFICATION
 FROM FLORIDA DCA.FIRE SPRINKLER PLANS
 ARE REQUIRED TO BE A PART OF THE ISSUED
 PERMIT PACKAGE.
  
 15.)ADDRESSED.
  
 16.)THE LIFE SAFETY PLAN PROVIDED
 APPEARS NONCOMPLIANT DUE TO THE
 OCCUPANCY CLASSIFICATION OF F3
 DISCREPANCY WITH THE STATEMENTS IN THE
 HAZARD ANALYSIS REGARDING AMOUNTS OF
 CHEMICALS STORED H4 AND DEFLAGRATION
 HAZARD FBC307.4. WITH AN OCCUPANCY
 CLASSIFICATION OF H, TRAVEL DISTANCES
 SHOWN AND THE COMMON PATH OF TRAVEL
 WOULD BE NONCOMPLIANT.
  
 ALSO, NOTE THE FOLLOWING:
  
 A. INCLUDE THE CATWALKS IN THE LIFE
 SAFETY PLAN, SHOWING TRAVEL DISTANCES
 AND COMMON PATH OF TRAVEL.
  
 B. THERE IS A DISTANCE SHOWN OF 210FT
 FROM STAIR 5.USE THE WORST CASE FOR
 TRAVEL DISTANCE.THE COMMON PATH OF
 TRAVEL APPEARS TO BE OVER 100' WHICH
 WOULD BE THE REQUIREMENT FOR F3.H
 OCCUPANCY COMMON PATH OF TRAVEL IS NOT
 TO EXCEED EITHER 25' OR 75', DEPENDING
 ON SUB CLASSIFICATION. A TRAVEL DISTANCE
 OF 256FT IS SHOWN FOR
 THE SLUDGE STORAGE.IT IS NOT CLEAR WHY
 IT WAS MEASURED THIS WAY; IT APPEARS TO
 BE THE DISTANCE FROM ONE END OF THE AREA
 AND GOING IN AROUND THE PERIMETER TO THE
 OTHER SIDE.
  
 C. THE EGRESS PATH FOR THE SLUDGE
 STORAGE TERMINATES AT A DOOR STAIR 3
 WHICH IS LABELED EXIT.SEE THE
 DEFINITION OF EXIT, FBC1002.THIS DOOR
 LEADS TO THE MAIN PROCESSING AREA.AS
 THERE ARE CURRENTLY NO EXIT COMPONENTS
 OTHER THAN DOORS LEADING TO THE OUTSIDE
 ON THE FIRST FLOOR, THE PATH OF TRAVEL
 SHOULD BE MEASURED FROM THE FARTHEST
 POINT TO THE EXIT DISCHARGE.
  
 D. IT IS NOT CLEAR IF THE TWO EXITS FOR
 THE SLUDGE STORAGE COMPLY WITH
 FBC1014.2.1(2).PROVIDE DIMENSIONS.
  
 E. FROM THE BUSINESS AREA FROM THE 2ND
 FLOOR, ONE EXIT IS SHOWN AS GOING
 THROUGH THE PROCESSING AREA.SEE
 FBC1013.2 REGARDING ADJOINING AREAS AND
 REGARDING H OCCUPANCY.IF THE OCCUPANCY
 IS DETERMINED TO BE F3 RATHER THAN H,
 THIS NOT ACCESSORY TO THE AREA SERVED,
 IT IS A MIXED OCCUPANCY.THE OTHER EXIT
 TRAVEL DISTANCE TERMINATES AT THE DOOR
 AT THE LANDING, BUT THIS IS NOT AN EXIT
 AS THE STAIR IS NOT PROTECTED, SEE
 FBC1002, FBC1015.2, FBC1015.1.
  
 F. EXITING THROUGH THE DEWATERING AREA
 APPEARS TO GO THROUGH EQUIPMENT.
 GENERALLY EGRESS PATH IS SHOWN AROUND
 THE PERIMETER OF A ROOM.PLEASE REVISE
 OR CLARIFY.
  
 G. WILL THE MECHANICAL ROOM HAVE LOCKS?
 SEE FBC1013.2 AND NOTE ON THE PLAN.
  
 H. UPPER LEVEL PLAN 47 & 50'6" SHOWS A
 MEZZANINE ON THE RIGHT.PROVIDE SQUARE
 FOOT OF THIS AREA.
  
 I.PROVIDE MORE INFORMATION IN REGARDS
 TO EGRESS FROM THE PROCESSING AREA.IT
 IS NOT CLEAR WHERE THE PATH OF TRAVEL
 WILL BE; WHAT EQUIPMENT IS AT GROUND
 LEVEL AND WHAT EQUIPMENT IS RAISED,
 ALLOWING AN EGRESS PATH BELOW?COMMON
 PATH OF TRAVEL AND PATH OF TRAVEL CANNOT
 BE DETERMINED FROM THE INFORMATION
 PROVIDED.
  
 17.)IT APPEARS THAT THE SLUDGE STORAGE
 AREAS TRAVEL DISTANCES EXCEED THE COMMON
 PATH OF TRAVEL FBC1013.3, TRAVEL
 DISTANCE FBC TABLE 1015.ON THE LIFE
 SAFETY PLAN, CLEARLY SHOW EXITING FOR
 EACH AREA.
  
 2ND REVIEW - NOT ADDRESSED; SEE ATTACHED
 COMMENTARY IN REGARDS TO COMMON PATH OF
 TRAVEL.SHOW COMMON PATH OF TRAVEL FOR
 ALL AREAS AS WELL AS THE TRAVEL
 DISTANCE.CODE COMPLIANCE CANNOT BE
 DETERMINED UNTIL CORRECT OCCUPANCY
 CLASSIFICATION IS ESTABLISHED.
  
 18-19.) ADDRESSED.
  
 20.)IT IS NOT CLEAR WHAT THE USE OF
 THE AREA WITH EQUIPMENT BS302, BS302,
 F301, F302 IS FOR.PLEASE CLARIFY.IT
 DOES NOT APPEAR ON THE MATERIAL FLOW
 SHEETS OR ON OTHER SECTIONS.
  
 2ND REVIEW - YOUR RESPONSE IN THE
 RESPONSE LETTER IS ACKNOWLEDGED.PLEASE
 INCORPORATE INTO THE PLAN AS THE
 RESPONSE LETTER WILL NOT BE A PART OF
 THE PERMIT PACKAGE.
  
 21.)2ND REVIEW, RESPONSE LETTER STATES
 THAT THE MEZZANINE COMPLIES WITH
 FBC505.4(2).SEE ABOVE COMMENT IN
 REGARDS TO THE TWO MEANS OF EGRESS.ONE
 GOES THROUGH AN ADJOINING SPACE, AND THE
 OTHER IS NOT AN EXIT TO THE OUTSIDE AS
 IT GOES THROUGH A STAIRCASE WHICH IS NOT
 PROTECTED.SEE ALSO THE ATTACHED
 COMMENTARY.
  
 A MEZZANINE IS TO BE LOCATED IN A ROOM.
 AS THE AREA BELOW AND AREA ABOVE ARE
 BOTH ENCLOSED, THIS PORTION IS TWO
 STORIES.SEE THE DEFININTIONS FOR
 MEZZANINE AND STORY.THIS IS NOT
 LOCATED BETWEEN THE FLOOR BELOW AND THE
 CEILING ABOVE AS THE CEILING ABOVE THE
 SLUDGE STORAGE ROOM (WHICH HAS A WALL)
 IS THE 2ND FLOOR.THIS AREA IS TWO
 STORIES, NOT A MEZZANINE, BY DEFINITION.
  
 22.)PROVIDE DESIGN CRITERIA FOR
 INTERIOR FINISH CLASSIFICATION, FBC
 TABLE 803.5.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT
 THIS IS FOUND IN THE CODE INVESTIGATION
 REPORT.PLEASE INCORPORATE INTO THE
 PLAN.
  
 23.)PROVIDE PRODUCT APPROVALS FOR
 COMPONENTS AND CLADDING.ALL PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD FBC*106.3.3.
  
 2ND REVIEW - ONLY ONE SET SUBMITTED,
 THREE REQUIRED.HAVE THEM REVIEWED BY
 DESIGNER OF RECORD FBC*106.3.3.THIS
 MAY BE DONE WITH A LETTER REFERRING TO
 EACH PRODUCT APPROVAL OR WITH A SHOP
 DRAWING STAMP.
  
 ALSO, PLEASE CORRECT THE FOLLOWING:
  
 A. FL3011-R1, SELECT THE APPROVED
 ASSEMBLY YOU WILL USE.
 THIS WILL BE ISSUED WITH A PROVISO THAT
 IT WILL BE INSTALLED BY A CONTRACTOR
 APPROVED BY BARRETT AS PER NOA
 LIMITATIONS (INFORMATIONAL ONLY).
  
 B. FL4911, SELECT THE APPROVED ASSEMBLY
 YOU WILL USE.
  
 C. FL617-R1 OR FL206, SELECT THE
 APPROVED ASSEMBLY YOU WILL USE.BOTH
 NUMBERS HAVE BEEN INCLUDED FOR THE
 MODIFIED SYSTEMS; BOTH ARE FOR GAF BUT
 ONLY ONE NUMBER SHOULD BE FOR NOA
 03-0430.13.
  
 D. NOA 01-0129.17, TRI-PLY MODIFIED, NOA
 IS EXPIRED.NO FLORIDA STATE PRODUCT
 APPROVAL WAS PROVIDED, BUT TWO DIFFERENT
 NUMBERS WERE PROVIDED FOR GAF.
  
 E. VALUEGUARD ALUMINUM SOFFIT, IS THIS
 INTERIOR?IF THIS IS EXTERIOR, PROVIDE
 FLORIDA STATE PRODUCT APPROVAL, INDICATE
 WHERE THIS WILL BE INSTALLED AT IT
 APPEARS THAT THE BUILDING DOES NOT HAVE
 A SOFFIT, AND SPECIFY DESIGN PRESSURES.
  
 F. THE PRODUCT APPROVALS PROVIDED ARE
 FOR DOOR SKINS, NONIMPACT RATED, RATHER
 THAN DOOR ASSEMBLIES.
  
 G. THE INDEX SHEET TITLED "FLORIDA
 (MIAMI-DADE) PRODUCT APPROVAL DATA
 SHEETS" HAS OTHER DOORS LISTED BUT NO
 PRODUCT APPROVALS WERE SUBMITTED.NO
 COMPLIANT PRODUCT APPROVALS WERE
 SUBMITTED FOR EXTERIOR DOORS.PRODUCT
 APPROVALS FOR INTERIOR DOORS ARE NOT
 REQUIRED; IF ANY DOORS LISTED ARE
 INTERIOR, PLEASE REMOVE FROM THE LIST.
  
 H. NOA 03-1015.03, OVERHEAD DOOR, 10'
 ROLLING STEEL DOOR, THE NOA PROVIDED IS
 INCOMPLETE.THE SHEET WITH THE DESIGN
 PRESSURES DID NOT PRINT PROPERLY.I
 HAVE PRINTED A NEW ONE FROM
 WWW.MIAMIDADE.GOV (FIND A DEPARTMENT,
 BUILDING CODE COMPLIANCE, PRODUCT
 CONTROL SEARCH).WHEN RESUBMITTING,
 PLEASE PROVIDE ONLY COMPLETE PRODUCT
 APPROVALS.TWO DIFFERENT FLORIDA STATE
 PRODUCT APPROVALS WERE REFERENCED; WHICH
 IS THE CORRECT ONE FOR THIS PRODUCT?
  
 I. NOA 03-0929.05, JANUS INTERNATIONAL,
 OVERHEAD DOOR, PRODUCT APPROVAL IS NOT
 COMPLETE AND THE DESIGN PRESSURES ARE
 NOT COMPLIANT FOR ZONE 5 FOR THE DESIGN
 PRESSURES SPECIFIED BY THE ENGINEER ON
 SHEET S01.WHERE WILL THIS DOOR BE
 INSTALLED?
  
 J. NOA 03-0325.03, COOKSON, OVERHEAD
 DOOR, PRODUCT APPROVAL IS NOT COMPLETE.
 NO FLORIDA STATE PRODUCT APPROVAL NUMBER
 WAS PROVIDED.
  
 K. NOA 02-1231.02, CORNELL IRON WORKS,
 20FT ROLLING DOOR, THE PRODUCT APPROVAL
 IS EXPIRED.NO FLORIDA STATE PRODUCT
 APPROVAL NUMBER WAS PROVIDED.THE
 PRODUCT APPROVAL IS NOT COMPLETE.
  
 L. FOUR DIFFERENT NOAS FOR OVERHEAD
 DOORS WERE SUBMITTED.ARE YOU
 INSTALLING ALL OF THEM OR ARE THEY
 OPTIONS?
  
 M. NOA 02-0124.02, TRACO WINDOW, TWO
 DIFFERENT FLORIDA STATE PRODUCT
 APPROVALS WERE PROVIDED.WHICH ONE IS
 FOR THIS PRODUCT?
  
 N. FL2670, PEERLESS, FIXED WINDOW,
 PROVIDE THE INSTALLATION INSTRUCTIONS
 AND INDICATE WHICH PRODUCT YOU ARE
 USING.PROVIDE OTHER DOCUMENTATION
 (SUCH AS EVALUATION REPORT) FROM THE
 STATE WEBSITE IF AVAILABLE.THE FLORIDA
 STATE PRODUCT APPROVAL IS EXPIRED, 2001
 CODE RATHER THAN 2004 CODE.NOTE THAT
 AS THIS IS BY CERTIFICATION MARK OR
 LISTING NO DESIGN PRESSURES WERE
 REVIEWED.
  
 O. GREENHECK NOAS (00-0929.13,
 02-0415.09, 03-0422.05) FOR THE WALL
 LOUVERS, ALL ARE INCOMPLETE.SOME PAGES
 DID NOT PRINT PROPERLY.
  
 P. NOA 03-1001.01, THE PRODUCT APPROVAL
 IS INCOMPLETE.THE DRAWING IS MISSING.
 THE DESIGN PRESSURE IS USUALLY ON THIS
 PAGE AS WELL AS SIZE LIMITATIONS.THE
 ELEVATIONS REFER TO A LOUVER SYSTEM
 ONLY, NO STRUCTURAL INFORMATION GIVEN
 FOR THE LOUVER WALL ABOVE THE ROOF.
  
 Q. APPENDIX I AND II, PRODUCT APPROVAL
 LISTS WERE SUBMITTED.PLEASE REMOVE AS
 NOT ALL PRODUCTS ARE TO BE INSTALLED ON
 THIS JOB.
  
 R. PRODUCT APPROVALS WERE NOT PROVIDED
 FOR THE WALL PANELS AND ROOF PANELS FOR
 THE CHEMICAL STORAGE STRUCTURE.
  
 24.)ACCESSIBLE ROUTE REQUIRED
 CONNECTING ALL ACCESSIBLE SPACES,
 FBC11-4.1.3(1).NOTE THAT THERE IS NO
 ACCESSIBLE ROUTE FROM THE SLUDGE
 RECEIVING AREA 109 TO THE SLUDGE
 RECEIVING 108, TO THE MAIN PROCESSING
 AREA 107, ELEVATOR AT LANDING 101.SEE
 ALSO FBC11-4.1.1(1)(3) REGARDING WORK
 AREAS.
  
 2ND REVIEW ? YOUR RESPONSE THAT IT WOULD
 BE IMPRACTICABLE TO MAKE THE REFERENCED
 AREAS ACCESSIBLE IS NOTED.THE
 REQUIREMENT OF VERTICAL ACCESSIBILITY
 FBC11-4.1.2 (HIGHLIGHTED IN GREY IN THE
 CODE BOOK) IS A FLORIDA SPECIFIC CODE
 REQUIREMENT.WAIVERS FROM THE CODE CAN
 BE GRANTED THROUGH APPLICATION TO THE
 STATE OF FLORIDA.SEE FBC11, SECTION C.
  
  
 ALSO SEE
 HTTP://WWW.DCA.STATE.FL.US/FBC/
 /COMMITTEES/ACCESSIBILITY/AAC/1_AAC.HTM
  
 25.)ADDRESSED.
  
 26 - 29.)ADDRESSED.
  
 30.)PROVIDE DETAILS FOR THE UL
 ASSEMBLIES SPECIFIED.
  
 31.)ADDRESSED.
  
 32.)YOUR RESPONSE THAT NO SEPARATE
 PERMITS WILL BE REQUIRED IS
 ACKNOWLEDGED.PROVIDE ALL STRUCTURAL
 INFORMATION AT THIS TIME FOR THESE
 ITEMS, INCLUDING THE DUSTROL TANK;
 LOADS, CONCRETE, ANCHORING,
 FBC415.7.2.2, TANK PROTECTION), NFPA30
 (STORAGE OF COMBUSTIBLES), FBC1606.1.3
 (ANCHORING TO PREVENT OVERTURNING).SEE
 ALSO FBC415.7.1.1, AND FBC415.7.1.5,
 GRAIN ELEVATORS AND SIMILAR STRUCTURES;
 THIS APPEARS TO APPLY TO THE STORAGE
 SILO (PROVIDE INFORMATION IN REGARDS TO
 CONSTRUCTION TYPE, HEIGHT).
  
 33.)E01 STATES THAT CALCULATIONS FOR
 THE LIGHT POLE WILL BE REQUIRED.NOTE
 THAT CALCULATIONS FOR THE LIGHT FIXTURE
 ARE REQUIRED ALSO.
  
 34.)THE SIGNATURES ON THE ELECTRICAL
 SHEETS APPEAR TO BE A PHOTOCOPY OF A
 STAMP.WET SIGNATURE REQUIRED PER FBPE.
  
 2ND REVIEW-? NOT ADDRESSED; ONE COPY OF
 PLANS RETAINED BY ELECTRIC REVIEWER FOR
 POSSIBLE SUBMITTAL TO FBPE.
  
 35-36.) ADDRESSED.
  
 NEW COMMENTS:
  
 37.) SEE FBC307.3 THROUGH 307.5.THE
 HAZARD ANALYSIS CLASSIFIED THREE OF THE
 MATERIALS USED IN PROCESSING AND STORED
 IN THE PROPOSED BUILDING AS H4.THE
 REPORT DID NOT ADDRESS THE CHEMICALS AS
 RELATED TO THE REQUIREMENTS OF FBC307.3
 THROUGH 307.5.FBC307.3 "BUILDINGS AND
 STRUCTURES CONTAINING MATERIALS THAT
 POSE A DEFLAGRATION HAZARD . . ."
 CLASSIFIES THE BUILDING AS H2.THE
 HAZARD REPORT ADDRESSED THE DEFLAGRATION
 RISK AND EXPLAINED THAT HAZARDS ARE
 PREVENTED; BUT DOESN?T THE RISK ITSELF
 PUT THIS BUILDING IN H2 CLASSIFICATION?
  
 38.) SEE FBC414.1.3.IT APPEARS THAT
 PORTIONS OF THE BUILDING MAY HAVE H4
 OCCUPANCY, AND MAY ALSO HAVE A
 CLASSIFICATION OF H2 OR H3.INCORPORATE
 THE REQUIRED INFORMATION (SOME OF WHICH
 IS IN THE HAZARDS ANALYSIS) INTO THE
 PLAN.ADDRESS QUANTITIES OF HAZARDOUS
 MATERIALS WHICH WILL BE USED DURING
 PROCESSING.
  
 39.) IN THE RESPONSE LETTER, YOU
 REFERRED TO MEETINGS WITH FIRE AND THE
 HAZARDS ANALYSIS REPORT AND TO PREVIOUS
 MEETINGS AND DISCUSSIONS WITH MIKE
 CARSILLO AND JAKE LEAHY.PLEASE NOTE
 THAT COMPLIANCE WITH FBC2004 IS REQUIRED
 IN ADDITION TO THE REQUIREMENTS OF NFPA,
 AND ALSO THAT PAPERWORK SUBMITTED
 SEPARATELY FROM THE PERMIT PACKAGE
 (APPLICATION, PLANS, SPECS, ETC.), MAY
 NOT BE AVAILABLE TO OTHER REVIEWERS.
  
 40.) THREE COPIES OF ALL DOCUMENTS
 REQUIRED.A STACK OF UNCOLLATED PAPERS
 WAS SUBMITTED WHICH INCLUDED COPIES OF
 THE HAZARD ANALYSIS AND MSDS SHEETS.
 PLEASE PROVIDE ALL DOCUMENTS WHICH ARE
 REQUIRED TO SHOW CODE COMPLIANCE IN A
 MORE ORGANIZED FORMAT; THREE DISTINCT
 COPIES, PREFERABLY INDEXED AND TABBED.
  
 THIS MAY BE DONE EITHER WITH A SHOP
 DRAWING REVIEW STAMP OR A COVER LETTER
 REFERRING TO EACH PRODUCT APPROVAL.
  
 41.) THE HAZARD REPORT IS DATED AUGUST,
 2005 AND REFERS TO FLORIDA BUILDING
 CODE.SECTION 2.3 BUILDING
 CLASSIFICATION (HAZARD REPORT) STATES
 "BASED ON SECTION 307 OF THE GROUP H . .
 . BUILDINGS ARE CONSIDERED TO HAVE
 DEFLAGRATION HAZARDS IF COMBUSTIBLE
 DUSTS ARE STORED IN PILES OR WITHIN OPEN
 CONTAINERS . . . "
  
 THE SECTION QUOTED REGARDING COMBUSTIBLE
 DUSTS WAS FROM FBC2001, SECTION 308.
 FBC2004 307.2, H2 OCCUPANCY STATES
 "BUILDINGS AND STRUCTURES CONTAINING
 MATERIALS THAT POSE A DEFLAGRATION
 HAZARD OR A HAZARD FROM ACCELERATED
 BURNING SHALL BE CLASSIFIED AS GROUP
 H2."IT APPEARS FROM THE REPORTS
 PROVIDED THAT A DEFLAGRATION HAZARD DOES
 EXIST IN THE BUILDING.THE HAZARD
 ANALYSIS STATES ". . . THE DRYING
 PROCESS HAS POTENTIAL FOR A FIRE OR
 DEFLAGRATION."IT APPEARS THAT THERE
 ARE TWO HAZARDS WHICH WOULD CLASSIFY THE
 AREAS AS H2; THE STORED SLUDGE,
 COMBUSTIBLE DUSTS.
  
 PLEASE REVISE THE HAZARD ANALYSIS TO
 REFER TO FBC2004.THE HAZARD ANALYSIS
 WAS APPARENTLY PREPARED IN A PRELIMINARY
 DESIGN STAGE.THE DESIGN OF THE
 BUILDING CHANGED AND THE GOVERNING CODE
 CHANGED ON OCTOBER 1, 2005.
  
 42.) THE HAZARD ANALYSIS, PAGE 20, TABLE
 2, SHOWS THAT QUANTITIES OF CHEMICALS
 WHICH WOULD CLASSIFY THE BUILDING (OR
 PORTION OF THE BUILDING) AS H4 WILL BE
 STORED IN EXCESS OF THE AMOUNT EXEMPTED
 IN FBC TABLE 307.2(2).THE REPORT
 STATES THAT THE H4 MATERIALS WILL BE
 STORED IN QUANTITIES IN EXCESS OF THE
 EXEMPT AMOUNT WITH A 2 HOUR WALL WITH AN
 F3 CLASSIFICATION, WHICH WOULD NOT BE
 PERMITTED, BUT THE PLAN SHOWS THESE
 CHEMICALS AS STORED IN ANOTHER
 STRUCTURE.AS THE HAZARD ANALYSIS WAS
 PREPARED PRIOR TO FINALIZATION OF THE
 DESIGN, PLEASE REVISE TO BE CONSISTENT
 WITH THE PLANS SUBMITTED FOR
 APPLICATION.
  
 43.) WHAT QUANTITY OF THE CORROSIVE
 CHEMICALS WILL BE USED IN THE PROCESSING
 AREA?
  
 44.) THE MAXIMUM VOLUME, STORED, OF
 DUSTROL 3010 (OR EQUIVALENT) FIELD WAS
 LEFT BLANK (PAGE 20, TABLE 2).IT
 INDICATES N/A, STORED OUTSIDE, AND THE
 NOTE "STORAGE BELOW EXEMPT AMOUNT".
 PLEASE PROVIDE THE VOLUME.INDICATE
 DISTANCE ON THE SITE PLAN.SHOW
 COMPLIANCE WITH THE DISTANCE
 REQUIREMENTS OF NFPA 30, 4.3.2 AND NFPA
 430.NOTE THAT IT APPEARS CLOSE TO THE
 CHEMICAL STORAGE STRUCTURE.NO
 INFORMATION WAS PROVIDED IN REGARDS TO
 THE STORAGE TANK.
  
 45.)SEE FBC307.1 THROUGH 307.5.THE
 HAZARD ANALYSIS DID NOT ADDRESS
 OXIDIZERS BUT THE SHEET PREPARED BY
 CRAWFORD INDUSTRIAL GROUP IS AN OXIDIZER
 PROCESS FLOW DIAGRAM.ARE ALL OXIDIZERS
 USED OUTSIDE?WHAT DISTANCE FROM THE
 BUILDING?
  
 46.) AS YOU HAVE DECLARED F3 OCCUPANCY
 ON THE PLAN, IN THE RESPONSE LETTER, AND
 IN THE HAZARD REPORT, BUT SHOW USE AND
 STORAGE OF CHEMICALS WHICH MAY CLASSIFY
 THE BUILDING OR PORTION OF BUILDING AS
 H4, AND SHOW 2 HOUR FIRE SEPARATIONS, IT
 APPEARS THAT YOU ARE CLASSIFYING THESE
 AREAS AS INCIDENTAL OR ACCESSORY USE.
 PLEASE CLARIFY YOUR CLASSIFICATION AS F3
 AS IT APPEARS TO BE H4 OR AN OCCUPANCY
 WITH MULTIPLE HAZARDS FBC307.8.THE
 PRELIMINARY CODE INVESTIGATION PREPARED
 BY RCT DATED APRIL 19, 2006 REFERS TO
 BOTH INCIDENTAL AND ACCESSORY USE.HOW
 THE CODE REFERENCES IN THE REPORT APPLY
 TO THE DIFFERENT AREAS OF YOUR PROJECT
 IS NOT CLEAR.IF YOUR INTENTION IS TO
 RESUBMIT THE PLANS WITH AN F3 OCCUPANCY
 A THIRD TIME (RATHER THAN H), PLEASE
 CONTACT ME TO RESOLVE THIS ISSUE PRIOR
 TO RESUBMITTAL.
  
 47.) THE RESPONSE LETTER AND CODE
 INVESTIGATION REPORT ARE USEFUL IN
 EXPEDITING PLAN REVIEW.HOWEVER, THEY
 WILL NOT BE A PART OF THE ISSUED PERMIT
 PACKAGE UNLESS SIGNED, SEALED, AND
 DATED.ALL RESPONSES WHICH SHOW CODE
 COMPLIANCE ARE TO BE INCORPORATED INTO
 THE PLAN.THE HAZARD ANALYSIS WILL BE A
 PART OF THE PERMIT PACKAGE, AND IS TO BE
 SIGNED, SEALED, AND DATED.
  
 48.) C12, ACCESSIBLE PARKING, THE FEE IS
 $250 RATHER THAN $100, CITY OF WEST PALM
 BEACH RESOLUTION #390-03, SECTION 2, #D.
  
 49.) OLD SHEETS WERE NOT SUBMITTED.NO
 CHANGES WERE CLOUDED, AND EVERY SHEET
 WAS CHANGED.IN THE FUTURE, PLEASE
 CLEARLY INDICATE CHANGES WITH CLOUDS AND
 REVISION NUMBERS, REPLACE ONLY SHEETS
 WHICH HAVE BEEN REVISED, AND SUBMIT THE
 OLD VOIDED SHEETS SEPARATELY FOR
 REFERENCE.
  
 50.) COMBUSTIBLES IN CONCEALED SPACES
 NOT ALLOWED IN TYPE II CONSTRUCTION,
 PLYWOOD ABOVE ALUMINUM SOFFIT, A09,
 FBC707.1.
  
 51.) THE CHEMICAL STORAGE STRUCTURE IS
 TO COMPLY WITH FBC TABLE 601.PROVIDE
 INFORMATION IN REGARDS TO THE STRUCTURE
 (CONSTRUCTION TYPE, AREA, THE DISTANCE
 TO ASSUMED PROPERTY LINE) AND SHOW
 COMPLIANCE.IF THIS IS A SEPARATE
 STRUCTURE, BOTH STRUCTURES (MAIN
 PROCESSING BUILDING AND THE CHEMICAL
 STORAGE STRUCTURE) ARE TO COMPLY WITH
 THE FIRE RESISTANCE REQUIREMENTS OF
 TABLE 601.IF THIS IS A PART OF THE
 MAIN PROCESSING BUILDING, THIS AREA IS H
 OCCUPANCY, SHOULD BE SHOWN ON THE PLAN
 AS MIXED OCCUPANCY, AND THIS AREA
 INCLUDED IN THE AREA CALCULATIONS.
  
 52.) THE STAIRWAY, ELEVATOR AND LANDING
 IS A PART OF THE BUSINESS OCCUPANCY.NO
 FIRE PROTECTION IS SHOWN ON THE FIRST
 FLOOR.SEE ALSO FBC1018.3, EXIT
 CONTINUITY.IT IS NOT CLEAR IF THIS IS
 INTENDED TO BE A VERTICAL EXIT, FBC1019,
 OR AN EXTERIOR STAIR, FBC1022.
  
 53.) A15 STATES THAT THE TILT WALL
 CONSTRUCTION IS TO COMPLY WITH PALM
 BEACH COUNTY REQUIREMENTS.CORRECT AHJ
 IS CITY OF WEST PALM BEACH.
  
 54.) INCLUDE THE CATWALKS IN THE AREA
 CALCULATIONS.THEY ARE TO COMPLY WITH
 FBC505.5.
  
 55.) S01, PRESSURES ARE GIVEN FOR THE
 ROOF ENCLOSURE.THEY ARE ALL WALL
 PRESSURES.WHAT ARE THE ROOF PRESSURES?
  
  
 56.) S01, CONCRETE CAST PERMANENTLY
 AGAINST THE EARTH IS TO HAVE 3IN MINIMUM
 COVER, FBC TABLE 1907.7.1.THIS
 DIMENSION IS NOT PROVIDED IN THE
 SPECIFICATION.IT IS SHOWN ON SOME BUT
 NOT ALL OF THE DETAILS.
  
 57.) WOULD THIS BE CONSIDERED A
 CORROSIVE ENVIRONMENT?CONCRETE
 COVERAGE IS TO COMPLY WITH FBC1907.7.5,
 ACI 381 7.7.5.
  
 58.)THE OCCUPANT LOAD FOR THE BUSINESS
 AREA SHOULD BE 48 RATHER THAN 47 (ROUND
 UP), FBC1004.1.2.
  
 59.)SEE FBC414.1.3.A FLOOR PLAN IS
 TO BE PROVIDED IDENTIFYING THE LOCATIONS
 OF ANTICIPATED CONTENTS AND PROCESSES TO
 REFLECT THE NATURE OF EACH OCCUPIED
 PORTION OF THE BUILDING.INCLUDE
 AMOUNTS OF EACH OF THE THREE CHEMICALS,
 THE END PRODUCT, METHANE GAS IN THE
 SLUDGE STORAGE AREA, ANY OTHER PERTINENT
 INFORMATION.SEE ALSO FBC307.1,
 DEFINITION OF CONTROL AREAS, AND FBC
 TABLES 307.7(1) AND (2).THERE IS
 CONFLICT BETWEEN THE HAZARD ANALYSIS AND
 PRELIMINARY DESIGN REPORT AND THE PLAN.
 ALSO SHOW ANY DOUBLE CONTAINMENT
 REQUIRED FOR HAZARDOUS MATERIALS.
  
 60.)I HAVE RETAINED ONE COPY OF THE
 HAZARD ANALYSIS.NOTE THAT THIS BOUND
 REPORT IS 19 PAGES; THE LOOSE ONE (WHICH
 I HAVE STAPLED) IS 20.IT APPEARS TO BE
 A PRINTING ISSUE.PLEASE CONFIRM THAT
 THE REPORTS ARE THE SAME AND WHEN
 RESUBMITTING, ALL THREE COPIES ARE TO BE
 IDENTICAL.NOTE THAT I HAVE ALSO
 RETAINED ONE COPY OF EACH OF THE MSDS.
 THIS IS SO THAT I MAY HAVE THEM FOR
 REFERENCE IF THE DESIGNER OF RECORD
 CONTACTS ME TO DISCUSS.
  
 61.)THE HAZARD ANALYSIS STATES THAT IT
 IS TO BE SUBMITTED IN CONJUNCTION WITH
 THE PRELIMINARY DESIGN REPORT.ONLY ONE
 COPY OF THE PRELIMINARY DESIGN REPORT
 WAS SUBMITTED.PROVIDE THREE ORIGINALS
 OF ALL DOCUMENTS REQUIRED TO SHOW CODE
 COMPLIANCE.
  
 62.)WILL THE CHEMICAL STORAGE AND SILO
 BE SPRINKLED?IF NOT, WILL THEY HAVE
 OTHER FIRE SUPPRESSION SYSTEMS?
  
 63.)THE MSDS STATES THAT SULFURIC ACID
 IS INCOMPATIBLE WITH SODIUM HYDROXIDE.
 PROVIDE INFORMATION IN REGARDS TO HOW
 THIS WILL BE ADDRESSED.THEY ARE STORED
 IN THE SAME OUTDOOR STRUCTURE WITH A
 WALL IN BETWEEN.PROVIDE INFORMATION IN
 REGARDS TO THE WALL.HOW WILL YOU
 PREVENT ACCIDENTAL EXPOSURE OF ONE
 CHEMICAL TO THE OTHER, SUCH AS DURING
 THE EVENT OF A WINDSTORM?
  
 64.)THE MSDS STATES THAT SODIUM
 HYDROXIDE SOLUTION IS INCOMPATIBLE WITH
 CHLORO ORGANIC COMPOUNDS.DO ANY OF THE
 OTHER CHEMICALS FALL INTO THIS CATEGORY
 OF CHEMICALS?
  
 65.)THE MSDS STATE THAT SULFURIC ACID
 IS INCOMPATIBLE WITH METALS, AND SODIUM
 HYDROXIDE CAN REACT WITH METALS TO FORM
 FLAMMABLE HYDROGEN GAS.THE PLAN A25
 STATES THAT THE METAL WILL BE COATED IN
 ACCORDANCE WITH THE SPECIFICATIONS.
 NOTE COATINGS ON THE PLAN, AND ALSO SEE
 COMMENT ABOVE IN PREVENTING ACCIDENTAL
 EXPOSURE OF THE CHEMICALS TO THE STEEL
 STRUCTURE.
  
 66.)IS THERE A MOISTURE MONITORING
 SYSTEM FOR THE SILO?WILL SYSTEMS BE
 MONITORED BY ALARMS?
  
 67.)SEE FBC414.3, HAZARD OCCUPANCY,
 MANUAL SHUTOFF FOR VENTILATION EQUIPMENT
 REQUIRED.
  
 68.)IT IS NOT CLEAR IF THERE IS A
 HAZARD FROM METHANE GASES FOR THE SLUDGE
 STORAGE AREA.IF THIS PORTION OF THE
 BUILDING IS F3, OCCUPANCY SEPARATION IS
 REQUIRED BETWEEN THIS TWO STORY AREA AND
 THE PROCESSING AREA.IF THIS IS H2, ONE
 STORY ALLOWED FBC TABLE 503.THE
 REDUCED HAZARD (SLUDGE CAKE COMPARED TO
 SLUDGE) WAS ADDRESSED IN THE LETTER
 DATED MAY 2, 2005 PREPARED BY HDR AND
 ADDRESSED TO CAPTAIN MIKE CARSILLO.THE
 PLANS ARE MARKED SLUDGE STORAGE; IS THIS
 SLUDGE OR SLUDGE CAKE?THE REPORT
 MENTIONS SLUDGE CAKE GOING THROUGH THE
 DRYING PROCESS, BUT DOES NOT MENTION THE
 DEWATERING AREA FUNCTION.
  
 69.)THE LETTER ALSO STATES THAT FUEL
 WILL BE STORED ON SITE FOR THE EMERGENCY
 GENERATOR.WHERE WILL THE FUEL BE
 STORED, AND IN WHAT QUANTITY?
  
 70.)FBC414.5.4, STANDBY POWER
 REQUIRED.PLEASE PROVIDE ALL
 INFORMATION REQUIRED FOR THE GENERATOR
 WHICH IS SHOWN ON THE SITE PLAN.
  
 71.)SEE PLUMBING COMMENTS REGARDING
 ACCESSIBLE BATHROOM STALL.
  
 72.)SEE PLUMBING COMMENTS REGARDING
 THE ROOF DRAINS.
  
 73.)SEE ALSO FBC414.6.1 REGARDING
 OUTSIDE STORAGE SHELTERS FOR HAZARDOUS
 CHEMICALS.
  
 74.)SEE FBC415.7.1.2 REGARDING
 OPERATIONS THAT PRODUCE COMBUSTIBLE
 DUSTS.HOW DOES THIS REQUIREMENT AFFECT
 THE CYCLONE SEPARATOR AND THE SCREENING
 PROCESS?IT APPEARS THAT THESE TWO
 PROCESSES GENERATE COMBUSTIBLE DUSTS.
2006-03-28 00:00:00 

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-04-03 Cont ID  
Sent By jleahy Date 2006-04-03 Time 11:39 Rev Time  
Received By shill Date 2006-03-28 Time 12:56 Sent To  
Notes
2006-03-28 00:00:00****CORRECTIONS****
 ****PLAN REVIEW ONLY****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION (PERMIT ONLY).
  
 2.)PROVIDE A SOILS INVESTIGATION
 REPORT FBC1802.2.
  
 3.)THREE COPIES OF ALL PERMIT
 DOCUMENTS REQUIRED, SEE ITEM 4 BELOW.
  
 4.) FBC* 109.3.7RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 OWNER, RESIDENT INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.
  
 5.)PROVIDE A FLOOD ZONE DESIGNATION
 FOR THIS PARCEL.CITY OF WEST PALM
 BEACH MUNICIPAL CODE 94-546(B) REQUIRES
 FFE TO BE 6IN ABOVE BASE FLOOD ELEVATION
 FOR IMPROVEMENTS IN THE HIGH HAZARD
 FLOOD ZONE AREAS.NOTE MINIMUM
 ELEVATION ON THE PLAN IF APPLICABLE.
  
 6.)PARKING SPACE STRIPING IS TO COMPLY
 WITH CITY OF WEST PALM BEACH STANDARDS,
 C12, SEE ATTACHED DETAIL.
  
 7.) A01 DECLARES F3 OCCUPANCY.SEE NFPA
 820 REGARDING THE FIRE HAZARD ASSOCIATED
 WITH THIS TYPE OF FACILITY.THE CORRECT
 OCCUPANCY WOULD BE H.NOT ENOUGH
 INFORMATION HAS BEEN PROVIDED ABOUT THE
 MATERIALS PROCESSED AND THE END PRODUCT
 TO DETERMINE THE CORRECT SUB
 CLASSIFICATION.PROVIDE INFORMATION
 ABOUT THE MATERIALS STORED IN THE
 BUILDING, MATERIALS USED IN PROCESSING,
 FLAMMABLE GASES PRODUCED, AND THE END
 PRODUCT AS RELATED TO OCCUPANCY
 CLASSIFICATION.DECLARE OCCUPANCY
 CLASSIFICATION, FBC307, SEE ALSO
 FBC307.8 REGARDING MULTIPLE HAZARDS, AND
 NFPA 820 1.3.5, MATERIALS USED FOR ANTI
 CORROSION WHICH MAY CAUSE ACCELERATED
 BURNING.
  
 IN ORDER TO ASSIST IN DETERMINING
 CORRECT OCCUPANCY CLASSIFICATION, PLEASE
 ADDRESS THIS ITEM IN A SIGNED, SEALED
 AND DATED LETTER FROM ONE OF THE DESIGN
 PROFESSIONALS WITH THE ASSOCIATED
 DOCUMENTATION, INCLUDING MSDS IF
 AVAILABLE.
  
 8.)REVISE OTHER ITEMS A01, CODE
 SUMMARY WHICH ARE AFFECTED BY THE
 OCCUPANCY CLASSIFICATION AND REVISE
 PLANS ACCORDINGLY (BUILDING HEIGHT AND
 AREA, OCCUPANT LOAD, ETC.).NOTE THAT
 DUE TO A LACK OF A CORRECT OCCUPANCY
 CLASSIFICATION A COMPLETE CHECKLIST
 CANNOT BE PROVIDED AT THIS TIME.
  
 9.)REVISE OCCUPANT LOAD FBC1004.A01
 PROVIDES AN OCCUPANT LOAD BUT IS NOT
 CLEAR AS TO THE OCCUPANCY OF THE
 DIFFERENT AREAS.PROVIDE SQUARE FOOT
 BUSINESS AREA, AND OCCUPANT LOAD.
  
 10.)CODE COMPLIANCE WITH FBC TABLE
 503, CANNOT BE DETERMINED WITHOUT THE
 CORRECT OCCUPANCY CLASSIFICATION.IF
 YOU ARE USING AN AREA INCREASE, PROVIDE
 CALCULATIONS FBC506.
  
 11.)PROVIDE MSDS FOR EACH MATERIAL
 USED FOR PROCESSING AND FOR THE END
 PRODUCT.
  
 12.)E12 SHOWS SULFURIC ACID STORAGE AT
 THE STAIR AND CHEMICAL STORAGE IN THE
 CONTROL ROOM.THIS APPEARS TO BE IN
 CONFLICT WITH OTHER DETAILS WHICH SHOW
 THIS OUTSIDE.CLARIFY.
  
 13.)PROVIDE AN ARCHITECTURAL SITE
 PLAN.SHOW DIMENSIONS TO THE LOT LINES
 OR OTHER STRUCTURES, FBC TABLE 602.
 SHOW THE ACCESSIBLE ROUTE
 FBC11-4.1.2(1).
  
 14.)PROVIDE FIRE SPRINKLER PLANS,
 FBC*106.3.5.1.1(5)
  
 15.)S01 DECLARES THIS BUILDING AS A
 TYPE II ESSENTIAL FACILITY, IMPORTANCE
 FACTOR 1.0.SEE FBC TABLE 1604.5.
 ESSENTIAL FACILITIES ARE TO BE A TYPE
 IV, 1.15 WIND FACTOR.REVISE TO MAKE
 THE LANGUAGE CONSISTENT WITH THE TYPE
 AND FACTOR DECLARED.IF THIS IS NOT
 DECLARED TYPE IV, PLEASE PROVIDE
 RATIONALE.
  
 16.)PROVIDE A LIFE SAFETY PLAN, FBC10.
  
 17.)IT APPEARS THAT THE SLUDGE STORAGE
 AREAS TRAVEL DISTANCES EXCEED THE COMMON
 PATH OF TRAVEL FBC1013.3, TRAVEL
 DISTANCE FBC TABLE 1015.ON THE LIFE
 SAFETY PLAN, CLEARLY SHOW EXITING FOR
 EACH AREA.
  
 18.)PROVIDE MINIMUM DIMENSION FOR ALL
 EGRESS COMPONENTS ON THE FLOOR PLAN.
 FOR INSTANCE, ON THE MEZZANINE LEVEL,
 THE WALKWAY LEADING TO STAIR 5, ALL
 EGRESS STAIRS.
  
 19.)PROVIDE FIRE RATING IN TIME RATHER
 THAN (OR IN ADDITION TO) LETTER RATING,
 FBC TABLE 715.3, A22.
  
 20.)IT IS NOT CLEAR WHAT THE USE OF
 THE AREA WITH EQUIPMENT BS302, BS302,
 F301, F302 IS FOR.PLEASE CLARIFY.IT
 DOES NOT APPEAR ON THE MATERIAL FLOW
 SHEETS OR ON OTHER SECTIONS.
  
 21.)IT IS NOT CLEAR UNDER WHICH
 EXCEPTION TO THE OPENNESS REQUIREMENT
 FOR MEZZANINES APPLIES TO THIS PROJECT,
 FBC505.4, IF ANY.IF THIS IS NOT A
 MEZZANINE IT MUST BE DECLARED AS A TWO
 STORY BUILDING.PLEASE SHOW CODE
 COMPLIANCE ON THE PLAN.
  
 22.)PROVIDE DESIGN CRITERIA FOR
 INTERIOR FINISH CLASSIFICATION, FBC
 TABLE 803.5.
  
 23.)PROVIDE PRODUCT APPROVALS FOR
 COMPONENTS AND CLADDING.ALL PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD FBC*106.3.3.
  
 PLEASE NOTE THAT FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO
 THE EVALUATION REPORT, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 IF FLORIDA STATE PRODUCT APPROVAL IS NOT
 AVAILABLE FOR ANY OF THE COMPONENTS AND
 CLADDING CHOSEN FOR THIS PROJECT, PLEASE
 CONTACT ME FOR ASSISTANCE.
  
 24.)ACCESSIBLE ROUTE REQUIRED
 CONNECTING ALL ACCESSIBLE SPACES,
 FBC11-4.1.3(1).NOTE THAT THERE IS NO
 ACCESSIBLE ROUTE FROM THE SLUDGE
 RECEIVING AREA 109 TO THE SLUDGE
 RECEIVING 108, TO THE MAIN PROCESSING
 AREA 107, ELEVATOR AT LANDING 101.SEE
 ALSO FBC11-4.1.1(1)(3) REGARDING WORK
 AREAS.
  
 25.)THE SLUDGE STORAGE AREA SHOWS
 EQUIPMENT.IS THIS A STORAGE AREA OR A
 WORK AREA?
  
 26.)THE STAIR SECTIONS A07HANDRAIL
 DETAILS DO NOT COMPLY WITH
 FBC11-4.9.4(2) AND (6), BOTTOM.SEE
 ALSO FBC FIGURE 11-19.
  
 27.)NO STAIR TREAD AND RISER
 DIMENSIONS SHOWN (REQUIRES
 CALCULATIONS).PROVIDE DIMENSIONS SO
 THAT DESIGN CRITERIA AND CODE COMPLIANCE
 ARE CLEARLY SHOWN, FBC1009.3.
  
 28.)IT APPEARS THAT THE SECTION FOR
 THE BREAK ROOM HAS AN INCORRECT
 REFERENCE ON A05 (4-A19 RATHER THAN
 DA19).
  
 29.)D-A19, BREAK ROOM SINK IS TO
 COMPLY WITH FBC11-4.24.SHOW ALL
 DETAILS.NOTE THAT CABINET DOORS NOT
 ALLOWED AS IT PREVENTS COMPLIANCE WITH
 FBC11-4.24.3, KNEE CLEARANCE.
  
 30.)PROVIDE DETAILS FOR THE UL
 ASSEMBLIES SPECIFIED.
  
 31.)PROVIDE DESIGN LOAD CRITERIA FOR
 THE VARIOUS AREAS OF THE MEZZANINE AREA,
 FBC16, ROOF.
  
 32.)SEPARATE PERMITS REQUIRED FOR THE
 OTHER STRUCTURES SHOWN ON THE PLAN (FOR
 INSTANCE, THE STORAGE SILOS AND THE
 STEEL STRUCTURE).NO PLANS OR OTHER
 INFORMATION PROVIDED.
  
 33.)E01 STATES THAT CALCULATIONS FOR
 THE LIGHT POLE WILL BE REQUIRED.NOTE
 THAT CALCULATIONS FOR THE LIGHT FIXTURE
 ARE REQUIRED ALSO.
  
 34.)THE SIGNATURES ON THE ELECTRICAL
 SHEETS APPEAR TO BE A PHOTOCOPY OF A
 STAMP.WET SIGNATURE REQUIRED PER FBPE.
  
 35.)THE IR SHEETS ARE NOT SIGNED,
 SEALED AND DATED.
  
 36.)THIS PLAN IS NOTED AS 90% REVIEW.
 NOTE THAT ADDITIONAL INFORMATION MAY
 ALSO TRIGGER NEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 13 Status P Date 2009-11-23 Cont ID  
Sent By btrobaug Date 2009-11-23 Time 12:18 Rev Time 0.00
Received By btrobaug Date 2009-11-23 Time 12:18 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 12 Status P Date 2009-10-15 Cont ID  
Sent By btrobaug Date 2009-10-15 Time 14:30 Rev Time 0.00
Received By btrobaug Date 2009-10-15 Time 13:20 Sent To  
Notes
2009-10-15 14:31:22REVISED SHEET E-10, ADED ONE LIGHT FIXTURE./WRT

Review Stop E ELECTRICAL
Rev No 11 Status P Date 2009-07-27 Cont ID  
Sent By btrobaug Date 2009-07-27 Time 09:46 Rev Time 0.00
Received By btrobaug Date 2009-07-27 Time 09:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2009-04-16 Cont ID  
Sent By btrobaug Date 2009-04-16 Time 13:52 Rev Time 0.00
Received By btrobaug Date 2009-04-16 Time 10:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 9 Status F Date 2009-01-14 Cont ID  
Sent By btrobaug Date 2009-01-14 Time 14:44 Rev Time 0.00
Received By btrobaug Date 2009-01-14 Time 06:59 Sent To  
Notes
2009-01-14 14:44:26 
  
  
 REVISION DENIED
  
 SAME COMMENTS AS THE PREVIOUS REVIEW:
  
 1} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEAL ACCEPTABLE TO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
  
 2} SHEET E-14 HAS A NOTE REGARDING ENCASING THE SERVICE
 CONDUIT AND INDICATES A DETAIL ON SHEET "20". IT IS NOT
 INDICATED WHICH SHEET "20", E, A, S, ETC. PLEASE
 INDICATE THE SHEET THIS DETAIL IS ON.
  
 NOTE: SEE 61G15-27.001, AND PRODUCE A LETTER FROM
 RONALD LARSON TO THIS DEPARTMENT , SIGNED, DATED AND
 SEALED BY HIM, NOT MR. DELAFOREST, OF HIS INTENT TO BE
 THE SUCCESSOR ENGINEER. IF MR. LARSON WILL NOT TAKE
 THAT RESPONSIBILITY THEN THE DESIGNER OF RECORD MUST
 SIGN, DATE AND SEAL ALL REVISIONS TO THE PLAN HE
 DESIGNED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2008-09-19 Cont ID  
Sent By btrobaug Date 2008-09-19 Time 14:08 Rev Time 0.00
Received By btrobaug Date 2008-09-19 Time 13:08 Sent To PC
Notes
2008-09-19 14:08:35 
  
 REVISION DENIED
  
 1} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEAL ACCEPTABLE TO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
  
 2} SHEET E-14 HAS A NOTE REGARDING ENCASING THE SERVICE
 CONDUIT AND INDICATES A DETAIL ON SHEET "20". IT IS NOT
 INDICATED WHICH SHEET "20", E, A, S, ETC. PLEASE
 INDICATE THE SHEET THIS DETAIL IS ON.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-04-14 Cont ID  
Sent By jleahy Date 2008-04-14 Time 16:33 Rev Time 4.00
Received By jleahy Date 2008-04-14 Time 16:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2007-09-07 Cont ID  
Sent By jleahy Date 2007-09-07 Time 07:27 Rev Time 2.00
Received By jleahy Date 2007-09-07 Time 07:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-06-20 Cont ID  
Sent By jleahy Date 2007-06-20 Time 17:21 Rev Time 2.30
Received By jleahy Date 2007-06-20 Time 17:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-03-21 Cont ID  
Sent By jleahy Date 2007-03-14 Time 07:54 Rev Time 4.00
Received By jleahy Date 2007-03-14 Time 07:54 Sent To  
Notes
2007-03-14 14:29:01 
 PROVISO!!!THESE COMMENTS TO BE ADDRESSED BY 5/1/07
 JLEAHY
  
 PAGE E-02RISER NOTES, MISSED ON THE PAST REVIEW.
  
 THE MAIN FEEDERS COMMING INTO THE BUILDING SHOW A 2/0
 GND?????
  
 IF THIS GROUND IS THE NEUTRAL THEN YOU NEED TO IDENTIFY
 IT AS SUCH.
  
 250.24(B) (1) STATES THE MINIMUM IS BASED ON NOT
 SMALLER THAN THE REQUIRED
 GROUNDING ELECTRODE WHICH WOULD BE A 3/0 BASED ON
 250.66???
  
 YOUR MAIN SERVICE ENTRANCE CONDUCTORS SHOW GND. AND
 YOUR SUBFEEDS SHOW GND
 WHICH ONES ARE NEUTRALS AND WHICH ARE EQUIPMENT
 GROUNDING CONDUCTORS?
 NEED TO REIDENTIFY ALL NEUTRAL CONDUCTORS AS SUCH, AND
 NOT AS A GROUND
  
 I DID NOT NOTICE THE NOTE FOR EM1, AND EM2 UNTIL YOU
 CHANGED THEM.
 LIGHTS IDENTIFIED AS EM1 AND EM2HAVE NO CIRCUIT
 NUMBERS SHOWN FOR THE BRANCH CIRCUITS.
 THE NOTE TO CONNECT TO THE NEAREST CIRCUIT DOES NOT
 WORK FOR LOADING OF THE BRANCH CIRCUITS.
 PLEASE DESIGNATE CIRCUIT NUMBERS ON PLANS.ADJUST
 LOADS ON PANEL SCHEDULES.
  
 NEED GENERATOR SPECS AND TRANSFER SWITCH SPECS FOR
 REVIEW
  
 QUESTIONS CALL JAKE 805-6740

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-11-29 Cont ID  
Sent By jleahy Date 2006-11-29 Time 08:10 Rev Time 4.00
Received By jleahy Date 2006-11-28 Time 18:07 Sent To  
Notes
2006-11-28 18:11:45PAGE E-02,E-03, AND E-04 LOAD CALCULATIONS ARE NOT
 DETAILED ENOUGH
  
 PLEASE SHOW HOW LOADS ARE CALCULATED.
  
 WHEN I DID THE MCC'S PG. E-02,03,I CAME OUT WITH MORE
 THAN 1200 AMPS FOR EACH?
  
 THIS WOULD MAKE THE BUSS TOO SMALL.
  
 THE CALCULATION WAS DONE PER 430.24.
  
 PLEASE SHOW HOW LOADS WHERE CALCULATED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-06-20 Cont ID  
Sent By jleahy Date 2006-06-20 Time 20:00 Rev Time 7.00
Received By jleahy Date 2006-06-20 Time 20:00 Sent To  
Notes
2006-06-20 00:00:001) THE LOAD CALCULATIONS SHOWN ON
 DRAWINGS ARE STILL VERY VAGUE.YOU
 INDICATE AN 80% DIVERSITY?IN ARTICLE
 430 FOR FEEDERS THERE IS NO 80%
 DIVERSITY THAT I CAN FIND, PLEASE
 INDICATE WHICH SECTION APPLIES. SHOW HOW
 LOADS WHERE CALCULATED FOR SERVICE
 ENTRANCE. DESCRIBE OTHER LOADS, PER
 ARTICLE 220
  
 2) THE MAIN SWITCH GEAR ROOM IS ON THE
 MEZZ.LEVEL MAINS SHALL BE READILY
 ACCESSIBLE.THE SHUNT TRIPS ARE OK BUT
 YOU STILL HAVE TO HAVE READILY
 ACCESSIBLE MAINS WHICH ARE 50' UP OF THE
 GROUND.230.70 A1, A3
  
 3) THE SERVICE ENTRANCE CONDUCTORS ARE
 NOT ALLOWED TO TRAVEL THROUGH THE
 BUILDING. NO MORE THAN 8' OF CONDUCTOR
 IS ALLOWED IN THE BUILDING.
  
 4) CUT SHEETS FOR THE CRUSHER, SCREENER
 ARE THESE TOTALY ENCLOSED???????
  
 5) LIGHTING CONTROL IS TO BE DONE PER
 FBC CHAPTER 13 SECTION 415.
  
 6) GENERATOR MAIN IS TO BE INSTALLED PER
 700.12 B(6).
  
 7) IF A DUST COLECTOR IS NEEDED FOR THE
 SILOS, WHAT HAPPENS IF IT DOES NOT WORK?
  
 8) ON PAGE E-14 THERE IS A JUNCTION BOX
 ON THE OUTSIDE WALL, IT HAS FPL AND BELL
 SOUTH INSTALLEDIN IT?????????????
  
 9) THE AREAS AROUND THE SCREENER AND
 CRUSHER ARE STILL IN QUESTION AS A
 CLASSIFIED AREA. IF EQUIPMENT IS NOT
 TOTALY ENCLOSED THEY SHALL BE CLASSIFIED
 AS A CLASS II AREA. PLEASE SHOW THE
 EXTENT OF THE CLASSIFIED AREA.
  
 10) SIGNATURE ON THE DRAWINGS IS A STAMP
 AND NOT A SIGNED SIGNATURE, THIS OFFICE
 MAY RETAIN A COPY OF THESE DRAWING TO
 SEND TO THE STATE FOR NON-COMPLIANCE
 WITH THE FLORIDA STATUTES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-20 Cont ID  
Sent By jleahy Date 2006-03-04 Time 09:18 Rev Time 6.00
Received By jleahy Date 2006-03-03 Time 07:19 Sent To  
Notes
2006-03-03 00:00:001.PLEASE DOCUMENT THE CLASS LOCATIONS
 PER 500.4(A).
  
 2.HAVING READ YOUR BOOK ON THE LOCATION
 IT DOES NOT PROVIDE ENOUGH INFORMATION
 TO THE CITY TO NOT CLASSIFY THESE
 LOCATIONS.
  
 3.IF YOU READ 500.8 IT CALLS FOR THE
 PROPER MAINTENANCE OF THE EQUIPMENT,
 THAT WAS ONE OF THE POINTS IN YOUR
 PRESENTATION THAT YOU WOULD PROVIDE GOOD
 HOUSEKEEPING, NOT ONLY DO YOU HAVE
 TO,IT'S A REQUIREMENT.
  
 4.SHUNT TRIPS ARE SHOWN, WHERE ARE THEY
 GOING TO BE LOCATED AND WHY/
  
 5.SERVICE SHOWS TWO 4000A AMPERE MAINS
 NO GFI PROTECTION PLEASE INDICATE WHY
 NONE IS PROVIDED. SEE 230.95
  
 6.GENERATOR DISCONNECT SHALL BE READILY
 ACCESSIBLE AND WITHIN 50' OF THE
 BUILDING OR ANOTHER MEANS OF DISCONNECT
 WILL BE REQUIRED.225.32
  
 7.LOAD CALCULATION IS VAGUE PLESE SHOW
 HOW LOAD CALCULATION WAS DONE IN
 ACCORDANCE WITH ARTICLE 220, NEED
 CALCULATION FOR SWB1,2 MCC 1-4,
 GENERATOR.
  
 8.MCCS SHOW HOW BRANCH CIRCUIT
 PROTECTION WAS DONE AND THE MULTIPLIER
 USED FOR THE PROTECTION. 430.52, 430.6A1
  
 9.WHAT TYPE OF PROTECTION IS BEING USED
 FOR THE BRANCH CIRCUITS IN THE MCCS.
  
 10.SEE 500.5B2 FOR TYPES OF LOCATIONS
 CONSIDERED HAZARDOUS SEE 1,2,3. THIS
 LOOKS TO BE THE TYPE OF SYSTEM BEING
 INSTALLED. THROUGH GOOD HOUSEKEEPING AND
 YOUR DESIGN YOU CAN NOT SHOW THAT AN
 ACCIDENT OR FAILURE OF THE SYSTEM WILL
 NEVERIT WILL BE THE RECOMENDATION OF
 THIS PLAN REVIEWER THAT THE AREA BE
 CLASSIFIED CLASS 1 DIVISION 2.
  
 QUESTIONS CALL JAKE LEAHY
 561-644-7291
  

Review Stop ENG ENGINEERING CSD
Rev No 8 Status N Date 2009-08-21 Cont ID  
Sent By dlauderm Date 2009-08-21 Time 10:11 Rev Time 0.25
Received By dlauderm Date 2009-08-21 Time 10:11 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 7 Status F Date 2009-04-20 Cont ID  
Sent By dlauderm Date 2009-04-20 Time 12:50 Rev Time 0.00
Received By dlauderm Date 2009-04-20 Time 12:34 Sent To  
Notes
2009-04-20 12:49:47PLAN FAILED.
 PLAN REVIEWER: DEAN LAUDERMILK, ENG. SRVC. #
 561-494-1083, CONSTR. SRVC. # 561-805-6716
 1. CIVIL PLAN HAS NOT BEEN RESUBMITTED TO ENGINEERING
 SERVICES SINCE THE PLANS WERE APPROVED ON MARCH 3,
 2006. CIVIL PLAN IS ONLY APPROVED FOR A PERIOD OF 1
 YEAR AND THAT IS ONLY IF NO REVISIONS HAVE BEEN MADE.
 SOME SHEETS HAVE OVER 10 REVISIONS MADE FROM 04-21-06
 TO 01-14-09. PLUMBING PLAN SHOWS TWO SUMP PUMPS SERVING
 THE TRUCK SCALES ARE TIED TO THE BUILDINGS SANITARY
 SEWER SYSTEM, WHILE THE CIVIL SHEETS (5' OUTSIDE THE
 BUILDING) SHOW NO CHANGES TO THE SANITARY. RESUBMIT A
 MINIMUM OF FOUR FULL SETS OF CIVIL DRAWINGS TO
 ENGINEERING SERVICES FOR REVIEW. TWO OF THE SETS WILL
 BE RETURNED. IF MORE ARE REQUIRED (FOR PERMITTING) THEN
 SUPPLY MORE THAN 4 SETS. SEE ITEM 2 WHICH NEEDS TO BE
 SHOWN ON THE CIVIL PLANS.
  
 2. P-10 HAS A REVISION TO ALLOW TWO SUMP PUMPS TO BE
 INSTALLED TO PUMP (WHAT?) INTO THE BUILDINGS INTERIOR
 GRAVITY SYSTEM AND OUT INTO THE CITY'S SYSTEM. THERE IS
 NOT ENOUGH DETAIL IN THE PLANS TO SHOW PROOF THAT THE
 BUILDING IS WATER TIGHT AND NO RAIN WATER WILL GET INTO
 THE SYSTEM. THE ONLY WAY THIS SYSTEM CAN BE TIED TO THE
 CITY SYSTEM IS IF THE AREA IS ROOFED AND NO RAIN WATER
 CAN BE TRANSPORTED INTO THE SANITARY SEWER. THEN THE
 LIQUID WILL NEED TO GO VIA A WATER/OIL SEPARATOR
 (GREASE TRAP) AND THEN IT CAN BE DIRECTED TO THE CITY
 SYSTEM. THIS NEEDS TO BE SHOWN ON THE CIVIL PLAN SHEET
 SINCE IT IS OUTSIDE THE BUILDING FOOT PRINT.

Review Stop ENG ENGINEERING CSD
Rev No 6 Status N Date 2009-01-13 Cont ID  
Sent By efabian Date 2009-01-13 Time 10:45 Rev Time 0.00
Received By efabian Date 2009-01-13 Time 10:40 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 5 Status N Date 2007-11-20 Cont ID  
Sent By rchokshi Date 2007-11-20 Time 15:29 Rev Time 0.00
Received By rchokshi Date 2007-11-20 Time 15:29 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2007-10-12 Cont ID  
Sent By rchokshi Date 2007-10-12 Time 13:43 Rev Time 0.00
Received By rchokshi Date 2007-10-12 Time 13:43 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2007-08-30 Cont ID  
Sent By rchokshi Date 2007-08-30 Time 08:20 Rev Time 0.00
Received By rchokshi Date 2007-08-30 Time 08:19 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2006-07-21 Cont ID  
Sent By rchokshi Date 2006-07-21 Time 15:41 Rev Time 0.00
Received By rchokshi Date 2006-07-21 Time 15:41 Sent To  
Notes
2006-07-21 00:00:00PASSED 7-21-06

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By mamini Date 2006-02-24 Time 14:27 Rev Time 0.00
Received By rchokshi Date 2006-02-24 Time 15:40 Sent To  
Notes
2006-07-20 00:00:00PASSED-ENG 7-20-06
2006-02-24 00:00:00FAILED:
  
 1. PLEASE NOTE THAT PRIOR TO GETTING
 APPROVAL FOR CIVIL PLANS FROM
 CONSTRUCTION SERVICES, ALL THE ISSUES
 WITH PUBLIC UTILITIES MUST BE ADDRESSED
 AND IMPLEMENTED.
 2. PLEASE SUBMIT A COPY OF THE MODIFIED
 SFWMD PERMIT.
 3. PLEASE SUBMIT STORM WATER CALCULATION
 FOR OUR REVIEW AND APPROVAL.
 4. CIVIL PLANS, SHHET C-10 REFER TO FDOT
 SPEC. FOR ROAD & BRIDGE, 2000. PLEASE
 VERIFY.
 5. SHHET C-12 DETAIL, TYP. PARKING
 SPACES, IS NOT THE LATEST PER ADA,
 PLEASE REVISE.
 6 NOTE THAT ALL REGULAR PARKING STALLS
 MUST BE PAINTED WITH DOUBLE 4" WIDE.
  
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG-M ENGINEERING MODIFICATION REV
Rev No 1 Status N Date 2009-04-09 Cont ID  
Sent By mgonzale Date 2009-04-09 Time 12:55 Rev Time 1.00
Received By mgonzale Date 2009-04-09 Time 12:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 13 Status   Date 2009-11-10 Cont ID  
Sent By mawillia Date 2009-11-10 Time 09:39 Rev Time 0.00
Received By mawillia Date 2009-11-10 Time 09:28 Sent To  
Notes
2009-11-10 09:39:43*****APPROVED*****
  
  
 REVISED PLAN SHEETS (M-03, M-08, S-23, E-11, E-18) WERE
 REVIEWED, HOWEVER NO FIRE-STAMPING REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 12 Status P Date 2009-10-19 Cont ID  
Sent By mawillia Date 2009-10-19 Time 15:06 Rev Time 0.00
Received By mawillia Date 2009-10-19 Time 14:42 Sent To  
Notes
2009-10-19 15:06:05*****REVISION, DATED 9/15/09, APPROVED*****
  
  
 REVISED PLAN SHEETS A-001A, A-001C, AND E-10 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 11 Status P Date 2009-04-02 Cont ID  
Sent By mawillia Date 2009-04-02 Time 13:01 Rev Time 0.00
Received By mawillia Date 2009-04-02 Time 12:39 Sent To  
Notes
2009-04-02 13:01:48*****REVISION APPROVED*****
  
  
 REVISED PLAN SHEETS A-001A, A-001B, A-001C, A-22, A-23,
 AND E-12 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 10 Status F Date 2009-01-05 Cont ID  
Sent By mawillia Date 2009-01-05 Time 11:13 Rev Time 0.00
Received By mawillia Date 2009-01-05 Time 11:00 Sent To  
Notes
2009-01-05 11:13:48*****UNSAT*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-SAMPED WHEN THE
 BUILDING EXAMINER'S (12/02/2008) COMMENTS HAVE BEEN
 ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 9 Status F Date 2008-09-09 Cont ID  
Sent By mwennerg Date 2008-09-09 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2008-09-09 Time 13:58 Sent To  
Notes
2008-09-09 14:04:10***DENIED***
  
 1) PLEASE SEE BUILDING REVIEW COMMENTS REGARDING FIRE
 RATING ISSUES AND INFORMATION DISREPENCY ON LIFE SAFETY
 SHEET. NO CHANGES TO FIRE PROTECTION SYSTEMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 8 Status P Date 2008-04-10 Cont ID  
Sent By mwennerg Date 2008-04-10 Time 10:55 Rev Time 0.00
Received By mwennerg Date 2008-04-10 Time 10:55 Sent To  
Notes
2008-04-10 10:56:33REVISION #7 TO ARCHITECTURAL, STRUCTURAL AND ELECTRICAL
 SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status F Date 2008-01-09 Cont ID  
Sent By mwennerg Date 2008-01-09 Time 09:27 Rev Time 0.00
Received By mwennerg Date 2008-01-09 Time 09:27 Sent To  
Notes
2008-01-09 09:30:06***DENIED***
  
 1) PLEASE SEE BUILDING REVIEW COMMENTS #1&2. PLEASE
 REFER TO NFPA 101, SEC. 38.2.4.4.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2008-01-04 Cont ID  
Sent By shill Date 2008-01-07 Time 13:32 Rev Time 0.00
Received By mwennerg Date 2008-01-04 Time 14:48 Sent To  
Notes
2008-01-04 14:49:05REVISED A001B, A02, A09, A22 REVISION DATED 12/17/07

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-12-12 Cont ID  
Sent By mawillia Date 2007-12-12 Time 18:31 Rev Time 0.00
Received By mawillia Date 2007-12-12 Time 18:02 Sent To  
Notes
2007-12-12 18:30:54*****REVISION (10/15/07) APPROVED*****
  
  
 REVIEWED REVISED PLAN SHEETS A-02 THRU A-5, A-10, A-14,
 A-19, AND A-22;STAMPED, INITIALED, AND DATEDA-02,
 A-03, A-05, AND A-14.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status F Date 2007-09-26 Cont ID  
Sent By mwennerg Date 2007-09-26 Time 14:23 Rev Time 0.00
Received By mwennerg Date 2007-09-26 Time 14:23 Sent To  
Notes
2007-09-26 14:25:42***DENIED***
  
 1) FIRE PLAN REVIEW PASSED WITH A PROVISO AT LAST
 REVIEW, HOWEVER COMMENTS WERE NOT ADDRESSED AT THIS
 TIME.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-01-10 Cont ID  
Sent By mwennerg Date 2007-01-10 Time 10:38 Rev Time 0.00
Received By mwennerg Date 2007-01-10 Time 10:38 Sent To  
Notes
2007-01-10 10:45:05***PROVISO***
  
 1) COMMENT #2 NOT ADDRESSED. PLEASE ADD TO CODE
 SUMMARY. SHT A-001
  
 2) COMMENT #3 NOT FOUND. PLEASE ADD TO CODE SUMMARY.
 SHT E-02
  
 3) IT IS UNDERSTOOD THAT SHOP DRAWINGS WILL BE
 SUBMITTED AT A LATER TIME, HOWEVER IN ACCORDANCE WITH
 FBC A FIRE SPRINKLER LAYOUT IS REQUIRED WITH THIS
 SUBMITTAL.
  
 4) COMMENT #18 TO INCLUDE WORDING, " SHALL INITIATE A
 GENERAL FIRE ALARM" IN ADDITION TO FAN SHUT DOWN.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-08-08 Cont ID  
Sent By mwennerg Date 2006-08-08 Time 09:52 Rev Time 0.00
Received By mwennerg Date 2006-08-08 Time 09:52 Sent To  
Notes
2006-08-08 00:00:00***DENIED***
  
 PLEASE SEE LAST FIRE REVIEW AND PROVIDE
 ALL NECESSARY RESPONSES.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
 PLEASE SEE SOME COMMENTS FROM FIRST FIRE
 REVIEW AND NEW COMMENTS:
  
 COMMENT
 1) PLEASE ADD NFPA STANDARD WITH ADOPTED
 EDITION TO SHT A-01 CODE SUMMARY.
  
 2) PLEASE ADD NFPA STANDARDS WITH
 ADOPTED ADDITIONS TO SHT A-01 CODE
 SUMMARY.
  
 3) PLEASE ADD NFPA STANDARD WITH ADOPTED
 EDITION TO PLANS.
  
 4) PLEASE ADD NFPA STANDARD WITH ADOPTED
 EDITION TO PLANS.
  
 5) OK
  
 6) OK
  
 7) OK
  
 NEW COMMENTS
  
 8) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE FOR ALL NEW
 BUILDINGS PROTECTED BY AN AUTOMATIC FIRE
 SPRINKLER SYSTEM. M-07 NOTE (7) IS NOT
 THE SAME.
  
 9) MSDS SHEETS REQUIRED IN APPROVED
 LOCATION AT FACILITY.
  
 10) ACCESS FOR EMERGENCY VEHICLES AND
 WATER SUPPLY TO COMPLY WITH NFPA 1, 2003
 EDITION.
  
 11) MANUFACTURER SPEC SHEETS REQUIRED
 FOR GENERATOR AND FUEL EQUIPMENT.
  
 12) ADDRESS REQUIRED ON BUILDING THAT
 SHALL BE A MINIMUM OF 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND.
  
 13) PLEASE CLEARLY IDENTIFY THE
 LOCATIONS OF NEW AND EXISTING FIRE
 HYDRANTS ON CIVIL PLANS.
  
 14) PLEASE PROVIDE ADDITION INFORMATION
 AND SPEC SHEETS FOR ACCESS GATES. PLEASE
 INDICATE FAILSAFE MEASURES IN THE EVENT
 OF POWER FAILURE.
  
 15) SHT M-07 INDICATES FIRE PROTECTION
 PLAN, BUT DOES NOT SHOW FIRE SPRINKLER
 LAYOUT. THAT INFORMATION SHALL BE
 INCLUDED IN ACCORDANCE WITH FBC.
  
 16) SOME RATED DOORS ARE CALLED OUT ON
 DOOR SCHEDULE, HOWEVER NO MENTION OF UL
 LISTED CLOSERS AS DOORS ARE REQUIRED TO
 POSITIVELY LATCH.
  
 17) ALL REQUIRED HAZARDOUS MATERIAL
 IDENTIFICATION SHALL BE DISPLAYED IN
 ACCORDANCE WITH NFPA 704.
  
 18) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 19) EXIT SIGNS ARE DISPLAYED AT EXIT
 DOORS, HOWEVER IT WOULD APPEAR THAT MORE
 EXIT SIGNS MAY BE REQUIRED TO ILLUSTRATE
 OBVIOUS TRAVEL DIRECTION WITHIN AREAS OF
 THE MEANS OF EGRESS.
  
 20) A KNOX BOX WILL BE REQUIRED FOR THE
 BUILDING. APPLICATIONS CAN BE OBTAINED
 AT THE BUREAU OF FIRE PREVENTION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-02-15 Cont ID  
Sent By nmccray Date 2006-02-15 Time 10:45 Rev Time 0.00
Received By nmccray Date 2006-02-14 Time 15:43 Sent To  
Notes
2006-03-14 00:00:00DENIED:
  
 1) THE NFPA STANDARD ON SHEET #G-04
 GENERAL NOTES #1 IS INCORRECT. THE
 CORRECT STANDARD IS NFPA 820 STANDARD
 FOR FIRE PROTECTION IN WASTEWATER
 TREATMENT AND COLLECTION FACILITIES.(
 ALSO INDICATE ON SHEET #A-01 UNDER CODE
 SUMMARY.
  
 2) SHALL COMPLY WITH NFPA 101 LIFE
 SAFETY CODE, 2003 EDITION AND NFPA 1
 UNIFORM FIRE CODE, 2003 EDITION. (
 PLEASE INDICATE ON SHEET # A-01 UNDER
 CODE SUMMARY )
  
 3) THE EMERGENCY GENERATOR SHALL COMPLY
 WITH NFPA 110 STANDARD FOR EMERGENCY AND
 STANDBY POWER SYSTEMS, 2002 EDITION.
  
 4) FIRE PROTECTION MEASURES DURING
 CONSTRUCTION AT BOTH NEW AND EXISTING
 WASTEWATER FACILITIES SHALL BE PROVIDED
 IN ACCORDANCE WITH NFPA 241.
  
 5) THIS FACILITIE IS REQUIRED TO HAVE A
 FIRE RISK EVALUATION, FIRE PREVENTION
 PROGRAM, AND FIRE EMERGENCY PLAN.
  
 6) SEPARATE PLANS AND PERMIT
 APPLICATIONS ARE REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS
 INSTALLATION.
  
 7) WHERE UNDERGROUND WATER MAINS AND
 HYDRANTS ARE TO BE PROVIDED, THEY SHALL
 BE INSTALLED, COMPLETED, AND IN SERVICE
 PRIOR TO CONSTRUCTION WORK.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL
 561-804-4754

Review Stop G GAS REVIEW
Rev No 6 Status   Date   Cont ID  
Sent By kstevens Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2009-04-13 Cont ID  
Sent By kstevens Date 2009-04-13 Time 13:25 Rev Time 0.00
Received By kstevens Date 2009-04-10 Time 16:57 Sent To  
Notes
2009-04-16 14:18:06REVISION OK -- SHT P-13. THE SHUT OFF VALVES SHALL BE
 INSTALLED UPSTREAM OF THE DRIP LEGS AND THE CHECK
 VALVES.

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-03-30 Cont ID  
Sent By kstevens Date 2007-03-30 Time 07:18 Rev Time 0.00
Received By kstevens Date 2007-03-30 Time 07:18 Sent To  
Notes
2007-03-30 07:20:21PASSED/PROVISO
 GAS EQUIPMENT SHALL BE LISTED. PLEASE SHOW LISTING AT
 THE TIME OF FINAL GAS INSPECTION FOR ALL GAS EQUIPMENT.

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-03-09 Cont ID  
Sent By kstevens Date 2007-03-09 Time 16:31 Rev Time 0.00
Received By kstevens Date 2007-03-09 Time 16:31 Sent To  
Notes
2007-03-09 16:32:36GAS PLANS APPROVED, BUT WILL STAY IN FAILED STATUS
 UNTIL ALL SHEETS FOR NEW ARCHITECT OF RECORD ARE
 SIGNED/SEALED/DATED.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-12-30 Cont ID  
Sent By kstevens Date 2006-12-30 Time 07:41 Rev Time 0.00
Received By kstevens Date 2006-12-30 Time 19:37 Sent To  
Notes
2007-03-09 07:42:42DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 G. OK
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE NOTED.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR
 THE INDUSTRIAL FURNACE/DRYER IS REQUIRED SHOWING THE
 LISTING AND BTU LOAD.
  
 21. OK
  
 **************NEW COMMENTS**************
  
 1B. OK
  
 2B. FOR THE GAS SYSTEM: SUBMIT MANUF. SPECIFICATIONS
 FOR THE REGULATORS USED.
 INDICATE IF THE REGULATOR WILL BE VENTED
 AND IF SO INDICATE THE MATERIAL USED FOR
 THE VENT. ALSO SHOW VENTING ROUTE FOR
 REGULATOR. SECTION 106.1.1.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATION
 SHEETS FOR THE REGULATORS ARE REQUIRED. PLEASE INDICATE
 MODEL NUMBER BEING USED FOR EACH REGULATOR.
  
 3B. OK
 4B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-01 Cont ID  
Sent By kstevens Date 2006-07-01 Time 15:45 Rev Time 0.00
Received By kstevens Date 2006-06-29 Time 18:39 Sent To  
Notes
2006-07-01 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PREVIOUS REVIEW:
  
 19. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT SOME SECTION DO
 NOT INDICATE THE LENGHTS.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ***RESPONSE NOTED, BUT INDICATE IF ALL
 PIPE IS WELDED. (NATURAL GAS PIPE NOT
 INDICATED). WELDING CERTIFICATE AND
 WELDING PROCEDURE REQUIRED AT TIME OF
 APPLICATION.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE ON PLANS TABLE
 BEING USED OF ALL GAS PIPING.
 ***RESPONSE NOTED, BUT THE TABLE USED
 FOR SIZING THE PIPE SHALL BE SUBMITTED
 WITH PLANS.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ***RESPONSE NOTED, BUT TOTAL DEVELOPED
 LENGTH IS NOT SHOWN, AND CAN NOT BE
 VERIFIED UNTIL ALL CUT SECTION
 MEASUREMENTS ARE SHOWN.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***NO RESPONSE TO THIS COMMENT FOUND.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ***NO RESPONSE NOTED.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE NOTED.
  
 **************NEW COMMENTS**************
  
 2B. FOR THE GAS SYSTEM: SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS USED.
 INDICATE IF THE REGULATOR WILL BE VENTED
 AND IF SO INDICATE THE MATERIAL USED FOR
 THE VENT. ALSO SHOW VENTING ROUTE FOR
 REGULATOR. SECTION 106.1.1.
  
 3B. FOR THE GAS SYSTEM: SLEEVES ARE
 REQUIRED WHERE THE GAS ENTERS THE
 BUILDING. SECTION 404.7.
  
 4B. FOR THE GAS SYSTEM: SHT P-12 SHOW
 THE PIPING TO FU101 & FU201. SHOW SHUT
 OFF VALVES AND DRIP LINES FOR ALL UNITS.
 SECTIONS 408.2, 408.4, 409.4 & 409.5.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2009-12-15 Cont ID  
Sent By btrobaug Date 2009-12-15 Time 09:16 Rev Time 0.00
Received By btrobaug Date 2009-12-15 Time 08:49 Sent To  
Notes
2009-12-15 09:16:37REVISION #9120302 IN C9

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2009-10-28 Cont ID  
Sent By jwitmer Date 2009-10-28 Time 16:38 Rev Time 0.00
Received By jwitmer Date 2009-10-28 Time 16:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2009-10-01 Cont ID  
Sent By rmcdouga Date 2009-09-29 Time 08:29 Rev Time 0.00
Received By rmcdouga Date 2009-09-29 Time 08:29 Sent To  
Notes
2009-10-01 08:30:10TO C-39

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2009-09-02 Cont ID  
Sent By kstevens Date 2009-09-02 Time 10:42 Rev Time 0.00
Received By kstevens Date 2009-09-02 Time 10:42 Sent To  
Notes
2009-09-02 10:50:06SENT TO C-18.

Review Stop I INCOMING/PROCESSING
Rev No 21 Status   Date 2009-07-27 Cont ID  
Sent By btrobaug Date 2009-07-27 Time 09:35 Rev Time 0.00
Received By btrobaug Date 2009-07-27 Time 09:35 Sent To  
Notes
2009-07-27 09:36:29 
  
 C-9

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2009-06-16 Cont ID  
Sent By lmartine Date 2009-06-16 Time 14:05 Rev Time 0.00
Received By lmartine Date 2009-06-12 Time 14:05 Sent To  
Notes
2009-06-16 14:05:36GAVE TO TROBAUGH

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2009-03-09 Cont ID  
Sent By adarroug Date 2009-03-09 Time 10:08 Rev Time 0.00
Received By adarroug Date 2009-03-09 Time 10:08 Sent To M
Notes
2009-03-09 10:09:07TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2009-02-24 Cont ID  
Sent By adarroug Date 2009-02-24 Time 15:25 Rev Time 0.00
Received By adarroug Date 2009-02-24 Time 15:25 Sent To  
Notes
2009-03-25 09:48:563/25/09--MOVED TO "COMM" BD#25
2009-02-24 15:40:26TO "COMM" BD#21/PLANS ON RACK/3 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-11-25 Cont ID  
Sent By adarroug Date 2008-11-25 Time 11:48 Rev Time 0.00
Received By adarroug Date 2008-11-25 Time 11:48 Sent To  
Notes
2008-11-25 11:48:54TO "COMM" BD#31

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-08-08 Cont ID  
Sent By adarroug Date 2008-08-08 Time 11:37 Rev Time 0.00
Received By adarroug Date 2008-08-08 Time 11:37 Sent To  
Notes
2008-08-08 11:42:37TO "COMM" BD#26

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-07-31 Cont ID  
Sent By adarroug Date 2008-07-31 Time 11:57 Rev Time 0.00
Received By adarroug Date 2008-07-31 Time 11:57 Sent To M
Notes
2008-07-31 11:58:25TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-07-29 Cont ID  
Sent By adarroug Date 2008-07-29 Time 09:21 Rev Time 0.00
Received By adarroug Date 2008-07-29 Time 09:21 Sent To M
Notes
2008-07-29 09:21:56TO "M" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-05-01 Cont ID  
Sent By adarroug Date 2008-05-01 Time 10:54 Rev Time 0.00
Received By adarroug Date 2008-05-01 Time 10:54 Sent To B
Notes
2008-05-01 10:54:51TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-03-25 Cont ID  
Sent By adarroug Date 2008-03-25 Time 11:44 Rev Time 0.00
Received By adarroug Date 2008-03-25 Time 11:44 Sent To  
Notes
2008-03-25 11:44:54TO "COMM" BD#39

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-12-21 Cont ID  
Sent By spalmer Date 2007-12-21 Time 16:15 Rev Time 0.00
Received By spalmer Date 2007-12-21 Time 16:15 Sent To B
Notes
2007-12-21 16:16:12TO SAMANTHA HILL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-10-24 Cont ID  
Sent By adarroug Date 2007-10-24 Time 15:22 Rev Time 0.00
Received By adarroug Date 2007-10-24 Time 15:22 Sent To  
Notes
2007-11-09 16:32:36TO "COMM" BD#39
2007-10-24 15:23:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2007-10-17 Cont ID  
Sent By adarroug Date 2007-10-17 Time 14:08 Rev Time 0.00
Received By adarroug Date 2007-10-17 Time 14:08 Sent To Z
Notes
2007-10-17 14:09:02TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2007-10-10 Cont ID  
Sent By adarroug Date 2007-10-10 Time 10:08 Rev Time 0.00
Received By adarroug Date 2007-10-10 Time 10:08 Sent To ENG
Notes
2007-10-10 10:08:34TO "ENG" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-08-02 Cont ID  
Sent By adarroug Date 2007-08-02 Time 11:02 Rev Time 0.00
Received By adarroug Date 2007-08-02 Time 11:02 Sent To  
Notes
2007-08-21 11:07:33TO "COMM" BD#4
2007-08-02 11:03:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-12 Cont ID  
Sent By adarroug Date 2007-06-12 Time 10:35 Rev Time 0.00
Received By adarroug Date 2007-06-12 Time 10:35 Sent To E
Notes
2007-06-12 10:35:58TO "JLEAHY" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-05-25 Cont ID  
Sent By adarroug Date 2007-05-25 Time 11:30 Rev Time 0.00
Received By adarroug Date 2007-05-25 Time 11:30 Sent To B
Notes
2007-05-25 11:31:11TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-22 Cont ID  
Sent By adarroug Date 2007-02-22 Time 16:06 Rev Time 0.00
Received By adarroug Date 2007-02-22 Time 16:06 Sent To  
Notes
2007-02-22 16:10:39TO "COMM" BD#7/PLANS ON RACK 4 ROLLS AND BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-14 Cont ID  
Sent By adarroug Date 2006-11-14 Time 08:53 Rev Time 0.00
Received By adarroug Date 2006-11-14 Time 08:53 Sent To  
Notes
2006-11-15 10:43:15TO "COMM" BD#35/4 ROLLS AND 1 BOX BY INCOMING
2006-11-14 08:53:28WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-05-24 Cont ID  
Sent By adarroug Date 2006-05-10 Time 14:32 Rev Time 0.00
Received By adarroug Date 2006-05-10 Time 14:32 Sent To  
Notes
2006-06-02 00:00:00TO "COMM" BD#40
2006-05-24 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-04-03 Cont ID  
Sent By shill Date 2006-04-03 Time 11:49 Rev Time 0.00
Received By shill Date 2005-12-12 Time 09:09 Sent To  
Notes
2006-01-30 00:00:00TO "COMM" BD#38
2005-12-15 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2009-11-04 Cont ID  
Sent By rregueir Date 2009-11-04 Time 11:43 Rev Time 0.00
Received By rregueir Date 2009-11-04 Time 11:01 Sent To  
Notes
2009-11-04 11:43:29REVISED M-3 DELTA 2, M-8 DELTA 1

Review Stop M MECHANICAL (A/C)
Rev No 12 Status N Date   Cont ID  
Sent By   Date 2009-04-21 Time   Rev Time  
Received By rregueir Date 2009-04-21 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2009-03-27 Cont ID  
Sent By rregueir Date 2009-03-27 Time 15:29 Rev Time 0.00
Received By rregueir Date 2009-03-27 Time 14:56 Sent To  
Notes
2009-03-27 15:27:02AN ENERGY INPUT DATA REPORT WITH LOAD CALCULATIONS WAS
 SUBMITTED. HOWEVER, THE INPUT DATA REPORT MUST BE
 ACCOMPANIED WITH THE ENERGY CODE COMPLIANCE FORM. THE
 INPUT DATA REPORT WAS NOT REVIEWED WITH THIS REVISION.
  
 THE FOLLOWING PAGES WERE REVIEWED AND INCORPORATED INTO
 THE PERMIT RECORD:
  
 REVISED M-01 DELTA 2
 REVISED M-02 DELTA 8
 REVISED M-03 DELTA 3
 REVISED M-04 DELTA 7
 REVISED M-06 DELTA 4
 REVISED M-08 DELTA 9
  

Review Stop M MECHANICAL (A/C)
Rev No 10 Status N Date 2009-03-16 Cont ID  
Sent By rregueir Date 2009-03-16 Time 10:54 Rev Time 0.00
Received By rregueir Date 2009-03-16 Time 10:54 Sent To PC
Notes
2009-03-16 10:54:55REVISED PROCESS INSTRUMENTATION PAGES Y-04 THROUGH Y-11

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-08-22 Cont ID  
Sent By rregueir Date 2008-08-22 Time 11:39 Rev Time 0.00
Received By rregueir Date 2008-08-22 Time 08:44 Sent To  
Notes
2008-08-22 11:39:03M-2 REV.6, M-4 REV.5, M-8 REV.8

Review Stop M MECHANICAL (A/C)
Rev No 8 Status F Date 2008-08-08 Cont ID  
Sent By rregueir Date 2008-08-08 Time 14:31 Rev Time 0.00
Received By rregueir Date 2008-08-08 Time 14:29 Sent To B
Notes
2008-08-08 14:31:18SEE PREVIOUS REVIEW COMMENTS DATED 8/8/08. SAME ISSUES.
 THIS SUBMITTALWAS FOR THE PURPOSE OF PROVIDING
 ORIGINAL SIGNATURES ON THE SHOP DRAWING REVIEW STAMPS.
 HOWEVER, THE STRUCTURL STAMP AND SIGNATURES ARE STILL
 PHOTOCOPIES. OTHERWISE, THE SAME CODE ISSUES AS
 PREVIOUS REIVEW APPLY TO TIS SUBMITTAL. SEE ATTACHED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2008-08-08 Cont ID  
Sent By rregueir Date 2008-08-08 Time 14:07 Rev Time 0.00
Received By rregueir Date 2008-08-08 Time 13:15 Sent To B
Notes
2008-08-08 14:07:11REVIEW #: SHOP DRAWINGS
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SHOP DRAWINGS HAVE BEEN SUBMITTED SHOWING
 MODIFICATIONS TO THE HVAC SECTION DETAIL C/M-02 AS
 SHOWN ON PAGE M-06. THE SIZES OF THE DUCTS SHOWN ON THE
 PLANS DO NOT CORRESPOND WITH THE SIZES SHOWN ON THE
 SHOP DRAWINGS. MODIFICATIONS TO SIGNED AND SEALED PLANS
 SHALL BE SUBMITTED AS REVISIONS TO THE PERMIT DRAWINGS
 AND SHALL BE SIGNED AND SEALED BY THE DESIGNER OF
 RECORD IN ACCORDANCE WITH FBCB 106.4
  
 2. SHOP DRAWINGS CONTAIN A NOTE STATING "PER SOUTH
 FLORIDA BUILDING CODE." THE SOUTH FLORIDA BUILDING CODE
 IS NO LONGER IN EXISTANCE AND HAS NEVER BEEN IN FORCE
 WITHIN THIS JURISDICTION. ALL WORK SHALL BE DESIGNED
 AND CONSTRUCTED IN ACCORDANCE WITH THE 2004 FLORIDA
 BUILDING CODE WITH 2005 AMENDMENTS.
  
 NOTE: SHOP DRAWINGS MAY BE USED TO PROVIDE ADDITIONAL
 INSTALLATION DETAILS BUT MAY NOT BE USED TO MODIFY THE
 OFFICIAL CONSTRUCTION DOCUMENTS. PLEASE ADDRESS THE
 ABOVE COMMENTS AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2007-11-26 Cont ID  
Sent By rregueir Date 2007-11-26 Time 14:19 Rev Time 0.00
Received By rregueir Date 2007-11-24 Time 16:26 Sent To  
Notes
2007-11-26 14:19:30REVISED M-2, M-4 AND M-8.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2007-08-21 Cont ID  
Sent By rregueir Date 2007-08-21 Time 18:37 Rev Time 0.00
Received By rregueir Date 2007-08-21 Time 17:17 Sent To  
Notes
2007-08-21 18:37:56REVISED PAGE M08

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-03-17 Cont ID  
Sent By rregueir Date 2007-03-17 Time 13:47 Rev Time 0.00
Received By rregueir Date 2007-03-17 Time 12:14 Sent To PC
Notes
2007-03-17 12:16:15ALL PREVIOUS REVIEW COMMENTS AND PROVISOS HAVE BEEN
 SATISFIED.
 NEW SHEETS M2 AND M8 REVIEWED: OK
  
 RONALD J REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-11-29 Cont ID  
Sent By pkrauss Date 2006-11-17 Time 10:33 Rev Time 0.00
Received By pkrauss Date 2006-11-16 Time 09:31 Sent To  
Notes
2006-11-17 10:46:36PROVISO:
  
 PLAN SHEET M-06,DETAIL F & G, DETAIL DOES NOT
 INDICATE HEIGHT OF THE ROOF CURB.PER 2004 FBC 1509.7,
 ROOF MOUNTED MECHANICAL EQUIPMENT SHALL BE MOUNTED ON
 CURBS RAISED A MINIMUM OF 8 INCHES ABOVE THE ROOF
 SURFACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-18 Cont ID  
Sent By pkrauss Date 2006-07-18 Time 09:15 Rev Time 0.00
Received By pkrauss Date 2006-07-18 Time 09:15 Sent To  
Notes
2006-07-18 00:00:00DENIED:
 ALL COMMENTS FROM REVIEW DATED 2-16-06
 WERE ADDRESSED WITH THE EXCEPTION OF THE
 FOLLOWING:
  
 COMMENT 4: NARRATIVE PROVIDED, BUT
 MANFACTURER SUBMITTAL DATA NOT PROVIDED.
  
 **************NEW COMMENTS*************
 1.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE GENERATOR.
 PLEASE INDICATE FUEL SOURCE (NATURAL
 GAS, DIESEL, LP GAS, ETC).PLEASE NOTE,
 ADDITIONAL PERMIT REQUIRED FOR
 GENERATOR.
  
 2.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE FUME HOOD
 INDICATED ON PLAN SHEET M-03.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-02-16 Cont ID  
Sent By pkrauss Date 2006-02-16 Time 10:57 Rev Time 0.00
Received By pkrauss Date 2006-02-16 Time 10:57 Sent To  
Notes
2006-02-16 00:00:00DENIED: **** PLAN REVIEW ONLY ***
  
 INDEX PLAN SHEET & COVER SHEET FOR THE
 SPEC BOOK INDICATES 90% REVIEW.PLEASE
 NOTE, INCOMPLETE SUBMITTAL MAY GENERATE
 ADDITIONAL COMMENTS UPON COMPLETION OF
 PLANS & SPECIFICATIONS AS WELL AS
 RESPONSES TO REVIEW COMMENTS.
  
 1.PLEASE CLARIFY THE RATING OF THE
 WALL BETWEEN THE MAIN PROCESSING (107) &
 SLUDGE STORAGE (103).48" X 48" DUCT
 PENETRATING THIS WALL IS THIS TRANSFER
 DUCT?
  
 2.PLAN SHEET M-03 MAKE-UP AIR FROM
 STAIR INTO ROOM (NOT IDENTIFIED ON THE
 PARTIAL LOWER LEVEL HVAC PLAN). PLEASE
 ALSO INDICATE WHERE EF-04 TERMINATES &
 AT WHAT ELEVATION.PLEASE IDENTIFY THIS
 ROOM.IS THIS A RATED WALL?
  
 3.PLAN SHEET M-03 PROVIDE ELEVATION &
 TERMINATION POINT OF EF-05.
  
 4.PLEASE PROVIDE COMBUSTION AIR
 CALCULATIONS PER 2004 FMC CHAPTER 7.
 PLEASE PROVIDE ADDITIONAL INFORMATION ON
 THE 2 "FURNANCES" INDICATED ON PLAN
 SHEET E-11.THESE ARE NOT INDICATED ON
 AN EQUIPMENT SCHEDULE.
  
 5.PLEASE PROVIDE MSDS SHEETS FOR ALL
 CHEMICALS THAT WILL BE UTILIZED OR
 STORED AT THE SITE.PLEASE PROVIDE
 INFORMATION ON STORAGE OF CHEMICALS.
  
 6.PLAN SHEET D-04 INDICATES AN
 EMERGENCY GENERATOR.NOTE 1 REFERS TO
 CIVIL DRAWINGS FOR LOCATION.CIVIL
 DRAWINGS TO NOT INDICATE LOCATION.
 PLEASE PROVIDE DISTANCES FROM BUILDING,
 PROPERTY LINES AND FRESH AIR INTAKES.
  
 7.PLEASE PROVIDE A OUTSIDE AIR
 CALCULATIONS & AIR BALANCE SCHEDULE.
  
 8.PLUMBING PLANS INDICATE GAS WATER
 HEATER.PLEASE PROVIDE GAS PLANS.
  
 9.FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS.2004 FMC
 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop P PLUMBING
Rev No 12 Status P Date 2009-09-09 Cont ID  
Sent By kstevens Date 2009-09-09 Time 11:10 Rev Time 0.00
Received By kstevens Date 2009-09-08 Time 16:59 Sent To  
Notes
2009-09-09 11:11:04REVISIONS OK -- SHTS P-1, P-2, P-4, P-6, P-8 , P-10 &
 P-12.

Review Stop P PLUMBING
Rev No 11 Status F Date 2009-04-13 Cont ID  
Sent By kstevens Date 2009-04-13 Time 13:27 Rev Time 0.00
Received By kstevens Date 2009-04-10 Time 16:58 Sent To  
Notes
2009-04-13 13:53:21REVISION DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 CITY WPB MUNICIPAL CODE
  
 1. SHTS P-02 & P-10 SHOWS TWO SUMP PUMPS AT THE SILOS.
 PLEASE INDICATE WHAT WILL BE DRAINING INTO THE SUMPS.
 SECTION 106.1.2 (MORE INFORMATION REQUIRED). IF IT IS
 STORM WATER DRAINING INTO THE SUMP, THEN IT CAN NOT BE
 CONNECTED TO THE SANITARY SYSTEM PER ARTICLE III
 SECTION 90-125(5). IF ITS WASTE WATER THEN EXPLAINATION
 IS REQUIRED ON HOW TO KEEP THE STORM WATER FROM THE
 SUMP. IF THERE ARE CHEMICALS DRAINING INTO THE SUMPS,
 THEN A NEUTRALIZER TANK MAY BE REQUIRED AND THE UTILITY
 DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE
 SHALL BE CONTACTED. (HOLLY MCGRATH LABORATORY
 SUPERVISOR - (561) 822-2271) PLEASE CLARIFY.
  
 2. SHTS P-02 & P-10 THE SUMPS SHALL BE VENTED. PLEASE
 INDICATE HOW THIS WILL BE ACCOMPLISHED. THIS IS NOT
 SHOWN ON THE FLAT PLAN, NOR ON THE ISOMETRIC RISER
 DIAGRAM. SECTION 916.5.
  
 3. SHT P-07 DETAIL 2 SHOWS THE DRIP LEG FOR THE GAS
 LINE EXTENDING TO A DRIP PAN. PLEASE CALRIFY. THE
 DRIP/SEDIMENT TRAP SHALL BE A CAPPED NIPPLE. AS
 INDICATED THIS NOT INDICATED. SECTION 408.4.
  
 4. SHT P-07 DETAIL 4 SHOWS THE HOT WATER SUPPLY LINE
 DIRECTIONAL ARROW AGAINST THE FLOW TO THE TEMPERING
 VALVE. PLEASE CLARIFY. SECTION 106.1.1.
  
 5. SHT P-08 MAIN LEVEL PLUMBING ISOMETRIC DOES NOT
 REFLECT THE CHANGES INDICATED ON SHEET P-01 NOR MANY
 OTHER WATER LINES IN THE SYSTEM. FOR EXAMPLE MANY
 BYPASSES, REDUCERS, LINES, THE 2" PWC TO MECH ROOM, THE
 2" WM TO 2ND FLOOR OFFICE AREA, P1 ON LINES TO P303 &
 P304, SOLENOID VALVES & SHUT OFF VALVES TO BS 301 & BS
 302. THESE ARE JUST SOME EXAMPLES. PLEASE CORRELATE THE
 ISOMETRIC RISER DIAGRAM WITH THE POTABLE & INDUSTRIAL
 WATER FLOW SCHEMATIC SO THE PLANS REFLECT EACH OTHER.
 SECTION 106.1.1
  
 6. SHT P-11 FD-3 AT THE TOP OF THE 4" RISER (SANITARY
 DOWN TO RECEIVING) IS NOT VENTED. SECTION 901.2.1. ALSO
 SHOW THE VENT TERMINATION FOR THE FD-3 FIXTURES AT THE
 END OF THE SAME STACK FOR THE FLOOR DRAINS. SECTION
 903.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 10 Status P Date 2009-04-13 Cont ID  
Sent By kstevens Date 2009-04-13 Time 13:26 Rev Time 0.00
Received By kstevens Date 2009-04-10 Time 16:57 Sent To  
Notes
2009-04-13 13:27:24REVISIONS OK -- SHTS P-01, P-03, P-05, P-06, P-09,
 P-12.

Review Stop P PLUMBING
Rev No 9 Status P Date 2008-08-11 Cont ID  
Sent By kstevens Date 2008-08-11 Time 11:35 Rev Time 0.00
Received By kstevens Date 2008-08-11 Time 11:35 Sent To  
Notes
2008-08-11 11:35:56REVISIONS OK--SHTS P-05 & P-11

Review Stop P PLUMBING
Rev No 8 Status P Date 2007-12-05 Cont ID  
Sent By kstevens Date 2007-12-05 Time 07:26 Rev Time 0.00
Received By kstevens Date 2007-12-04 Time 18:49 Sent To  
Notes
2007-12-05 07:26:55REVISION OK - SHTS P-02 & P-10

Review Stop P PLUMBING
Rev No 7 Status F Date 2007-09-15 Cont ID  
Sent By kstevens Date 2007-09-15 Time 15:38 Rev Time 0.00
Received By kstevens Date 2007-09-15 Time 15:38 Sent To  
Notes
2007-09-15 15:45:50DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P-01 FLOW SCHEMATIC SHOWS NO WATER SUPPLY TO THE
 TWO ESEW, THE LS-1 AND THE DWH-201. PLEASE CLARIFY.
 SECTION 106.1.1.
  
 2. SHT P-08 PLUMBING ISOMETRIC WATER RISER DIAGRAM DOES
 NOT REFLECT THE PIPING SHOWN ON THE FLOW SCHEMATIC. THE
 2" PWC IS NOT SHOWN CONNECTING TO THE DWH-201 RISER
 DIAGRAM.--ONE ESEW IS SHOWN WITH HOT WATER SUPPLY
 ONLY. PLEASE CLARIFY. CORRELATE RISER AND FLOW
 SCHEMATIC.--PLEASE INDICATE IS THERE IS A TEMPERING
 VALVE FOR THE EMERGENCY SHOWERS OR DO THEY HAVE A
 TEMPERING/ANTI-SCALD VALVE AT THE SHOWER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 6 Status P Date 2007-09-15 Cont ID  
Sent By kstevens Date 2007-09-15 Time 15:36 Rev Time 0.00
Received By kstevens Date 2007-09-15 Time 15:36 Sent To  
Notes
2007-09-15 15:38:12REVISION OK - SHTS P-09, P-10, P-11, P-12 & Y-11--
 REVISIONS DMO25, DM011, DM023, & DM008

Review Stop P PLUMBING
Rev No 5 Status P Date 2007-03-30 Cont ID  
Sent By kstevens Date 2007-03-30 Time 07:15 Rev Time 0.00
Received By kstevens Date 2007-03-30 Time 07:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2007-03-09 Cont ID  
Sent By kstevens Date 2007-03-09 Time 16:29 Rev Time 0.00
Received By kstevens Date 2007-03-09 Time 13:08 Sent To  
Notes
2007-03-09 16:30:57PLUMBING PLANS OK - NEED SHEETS SIGNED/SEALED/DATED BY
 NEW ARCHITECT OF RECORD THEN WILL CHANGE TO PASSED

Review Stop P PLUMBING
Rev No 3 Status F Date 2007-01-05 Cont ID  
Sent By kstevens Date 2007-01-05 Time 18:41 Rev Time 0.00
Received By kstevens Date 2006-12-30 Time 19:37 Sent To  
Notes
2007-01-05 18:58:24DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW. COMMENT NUMBER
 SHALL REMAIN THE SAME FOR CLARITY:
  
 4. OK
 8. OK
  
 9. SHT A-10 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FOOTAGE BEING DRAINED BY EACH
 PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS IN
 CALCULATIONS. - SHOW THE LOCATION OF ALL
 OVERFLOW SCUPPERS, AND SIZE OF O/F
 SCUPPERS PER SECTIONS 1101.7, 1107.3 AND
 TABLE 1106.7. THE SIZING OF THE SCUPPERS
 CAN NOT BE DETERMINED WITHOUT REFERENCE
 TO THE DEFLECTION OF THE ROOF. PLEASE
 SHOW O/F SCUPPER CALCULATION ON PLANS
 INDICATING SIZE OF SCUPPERS AND PROVIDE
 DETAIL OF O/F SCUPPERS SHOWING HEIGHT
 AND WIDTH.
 ***RESPONSE NOTED, BUT THE EMERGENCY
 OVERFLOW SCUPPERS ARE REQUIRED PER
 SECTION 1107.1. PLEASE SIZE SCUPPERS PER
 SECTIONS AND TABLE REFERENCED ABOVE AND
 SHOW THE LOCATION OF ALL SCUPPERS. ALSO
 SEE SECTION 1503.4.3. SUBMIT A DETAIL
 FOR EMERGENCY OVER FLOW SCUPPERS. SHOW
 SCUPPERS ON EXTERIOR ELEVATIONS FOR
 BUILDING.
 ******RESPONSE NOTED, BUTSEPARATE SYSTEMS ARE
 REQUIRED. THE PRIMARY SCUPPERS ARE INDICATED AS 2 -
 12"X24"OPENINGS, AND THE OVERFLOWSCUPPERS ARE
 INDICATED AS THE SAME. PLEASE CLARIFY. PLEASE SUBMIT A
 DETAIL OF THE LEADER BOX. SHOW THE ELEVATIONS FROM THE
 FRONT AND THE SIDE TO INDICATE WHERE THE SECONDARY
 SCUPPER DRAINS.-DOWNSPOUTS (2) ARE INDICATED IN THE
 CALCULATIONS, BUT (4) ARE SHOWN ON THE ROOF PLAN. SHT
 A-21, DETAIL 12 PLEASE INDICATE THE SIZE OF THE
 DOWNSPOUT.
  
 11. OK
 13. OK
 15. OK
 16. OK
 17. OK
 18. OK
  
 19. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 G. OK
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE NOTED.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR
 THE INDUSTRIAL FURNACE/DRYER IS REQUIRED SHOWING THE
 LISTING AND BTU LOAD.
  
 21. OK
  
 **************NEW COMMENTS**************
  
 1B. OK
  
 2B. FOR THE GAS SYSTEM: SUBMIT MANUF. SPECIFICATIONS
 FOR THE REGULATORS USED.
 INDICATE IF THE REGULATOR WILL BE VENTED
 AND IF SO INDICATE THE MATERIAL USED FOR
 THE VENT. ALSO SHOW VENTING ROUTE FOR
 REGULATOR. SECTION 106.1.1.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATION
 SHEETS FOR THE REGULATORS ARE REQUIRED. PLEASE INDICATE
 MODEL NUMBER BEING USED FOR EACH REGULATOR.
  
 3B. OK
 4B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-06-30 Cont ID  
Sent By kstevens Date 2006-06-30 Time 17:29 Rev Time 0.00
Received By kstevens Date 2006-06-29 Time 18:39 Sent To  
Notes
2006-06-30 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW. COMMENT NUMBER
 SHALL REMAIN THE SAME FOR CLARITY:
  
 4. SHT A-01 WATER CLOSETS REQUIRED PER
 TABLE 403.1 ARE 2 FOR FACTORY AND 2 FOR
 BUSINESS. SECTION 403.3 STATES THE
 REQUIRED WATER CLOSETS, LAVATORIES, ETC.
 SHALL BE DISTRIBUTED EVENLY BETWEEN THE
 SEXES. FLOOR PLAN INDICATES ONE WATER
 CLOSET IN THE WOMEN'S TOILET ROOM AND
 ONE WATER CLOSET AND TWO URINALS IN THE
 MEN'S TOILET ROOM. PLEASE CLARIFY.
 ***RESPONSE NOTED, BUT DRINKING FOUNTAIN
 ADDED TO THE FACTORY AREA ON THE MAIN
 FLOOR HAS NOT BEEN FOUND. PLEASE
 CLARIFY.
  
 8. SHT A-08 SHOW THE CLEAR FLOOR SPACE
 AND TURNING AREA IN BOTH TOILET ROOMS
 AND FOR ALL ACCESSIBLE FIXTURES IN BOTH
 TOILET ROOMS.
 ***RESPONSE NOTED, BUT THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSETS, URINAL AND
 SHOWERS ARE NOT SHOWN. - TURNING AREA
 SHALL BE LOCATED IN THE TOILET ROOM, NOT
 THE STALL.
  
 9. SHT A-10 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FOOTAGE BEING DRAINED BY EACH
 PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS IN
 CALCULATIONS. - SHOW THE LOCATION OF ALL
 OVERFLOW SCUPPERS, AND SIZE OF O/F
 SCUPPERS PER SECTIONS 1101.7, 1107.3 AND
 TABLE 1106.7. THE SIZING OF THE SCUPPERS
 CAN NOT BE DETERMINED WITHOUT REFERENCE
 TO THE DEFLECTION OF THE ROOF. PLEASE
 SHOW O/F SCUPPER CALCULATION ON PLANS
 INDICATING SIZE OF SCUPPERS AND PROVIDE
 DETAIL OF O/F SCUPPERS SHOWING HEIGHT
 AND WIDTH.
 ***RESPONSE NOTED, BUT THE EMERGENCY
 OVERFLOW SCUPPERS ARE REQUIRED PER
 SECTION 1107.1. PLEASE SIZE SCUPPERS PER
 SECTIONS AND TABLE REFERENCED ABOVE AND
 SHOW THE LOCATION OF ALL SCUPPERS. ALSO
 SEE SECTION 1503.4.3. SUBMIT A DETAIL
 FOR EMERGENCY OVER FLOW SCUPPERS. SHOW
 SCUPPERS ON EXTERIOR ELEVATIONS FOR
 BUILDING.
  
 11. SHT A-18 THE FOLLOWING SHALL BE
 SHOWN ON THE TOILET ROOMS ELEVATIONS:
 FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE (NOT
 SHOWN).
 B. 11-4.16.5 FLUSH CONTROLS (MEN'S OK -
 WOMEN'S NOT CORRECT).
 FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE (NOT
 SHOWN)
 B. 11-4.19.5 FAUCETS (NO RESPONSE)
 FOR URINALS:
 B. 11-4.18.3 CLEAR FLOOR SPACE (NOT
 SHOWN).
 C. 11-4.18.4 FLUSH CONTROLS (NOT
 SHOWN).
 FOR SHOWERS
 B. 11-4.21.3 SEAT (IF INSTALLED) NOT
 SHOWN).
 E. 11-4.21.6 SHOWER UNIT (NOT SHOWN).
 F. 11-4.21.7 CURBS (NOT ADDRESSED)
 ***SUBMIT ALL ELEVATIONS FOR SHOWER.
  
 13. PLEASE CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER FOR
 POSSIBLE INTERCEPTORS AND/OR NUTRALIZER
 TANKS. CONTACT HER AT (561) 822-2271,
 (561) 822-2279 (FAX), OR [email protected] (E-MAIL).
 ***RESPONSE NOTED, WAITING FOR A
 RESPONSE FROM LYNN.
  
 15. SHT P-07 DETAIL 2 WATER HEATER,
 THERMAL EXPANSION CONTROL REQUIRED PER
 SECTION 607.3.2. PLEASE INDICATE MENTOD. DIELECTRIC
 "UNIONS" NOT APPROVED FOR
 WATER USAGE. PLEASE CHANGE TO
 "COUPLINGS".
 ***RESPONSE NOTED, BUT THE THERMAL
 EXPANSION CONTROL WAS NOT ADDRESSED.
  
 16. SHT P-08 WATER ISOMETRIC FOR THE
 MAIN LEVEL DOES NOT REFLECT THE PIPING
 SHOWN ON SHT P-01 FLOW SCHEMATIC. PLEASE
 CORRELATE ISOMETRIC AND FLOW SCHEMATIC.
 SECTION 106.1.1.
 ***RESPONSE NOTED, BUT THE RISER DIAGRAM
 STILL DOES NOT REFLECT THE FLOOR PLAN.
 AN EXTRA URINAL IS SHOWN, W/C MISSING,
 AND THE WATER PIPING CAN NOT BE
 INSTALLED AS SHOWN. (SEE EXAMPLE ON SHT
 P-09. IF OVERHEAD SHOW ALL DROPS.
  
 17. SHT P-10 DRAINAGE PLUMBING ISOMETRIC
 DOES NOT MEET CODE REQUIREMENTS, NOR
 DOES IT REFLECT THE FLOOR PLAN SHT P-02.
 TRAPS ARE REQUIRED ON ALL FIXTURES
 EXCEPT THE CLEANOUTS AND THE WATER
 CLOSETS AS THE W/C'S HAVE AN INTEGRAL
 TRAP IN THE FIXTURES. SECTION 1002.1. -
 NO HORIZONTAL DRY VENTS PER SECTIONS
 905.3 & 905.4. - PIPING DOES NOT REFLECT
 THE FLOOR PLAN AT ESEW. NO PIPING SHOWN
 ON THE FLOOR PLAN. SHOW ALL PIPE SIZES
 ON ISOMETRIC. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT RISER DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS. 1 FLOOR DRAIN AND ONE
 4" VTR IS MISSING, AND THERE ARE
 NUMEROUS HORIZONTAL DRY VENTS STILL
 SHOWN. (SEE EXAMPLE IN RED ON SHEET FOR SOLUTION).
  
 18. SHT P-11 DRAINAGE PLUMBING ISOMETRIC
 DOES NOT MEET CODE REQUIREMENTS. TRAPS
 ARE REQUIRED ON ALL FIXTURES EXCEPT
 CLEANOUTS AND WATER CLOSETS AS THE W/C'S
 HAVE INTEGRAL TRAPS IN THE FIXTURES. -
 DRY HORIZONTAL VENTS ARE NOT APPROVED
 PER SECTIONS 905.3 & 905.4.- MANY
 FIXTURES ARE NOT VENTED PROPERLY AS
 REQUIRED IN SECTION 901.2.1. (SEE
 EXAMPLE ON THIS SHEET ONE SET OF PLANS)
 - SHOW ALL PIPE SIZES ON THE ISOMETRICS. ***RESPONSE
 NOTED, BUT HORIZONTAL DRY
 VENTS STILL SHOWN. SOME PIPE SIZES NOT
 SHOWN.
  
 19. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT SOME SECTION DO
 NOT INDICATE THE LENGHTS.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ***RESPONSE
 NOTED, BUT INDICATE IF ALL
 PIPE IS WELDED. (NATURAL GAS PIPE NOT
 INDICATED). WELDING CERTIFICATE AND
 WELDING PROCEDURE REQUIRED AT TIME OF APPLICATION.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE ON PLANS TABLE
 BEING USED OF ALL GAS PIPING.
 ***RESPONSE NOTED, BUT THE TABLE USED
 FOR SIZING THE PIPE SHALL BE SUBMITTED
 WITH PLANS.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ***RESPONSE NOTED, BUT TOTAL DEVELOPED
 LENGTH IS NOT SHOWN, AND CAN NOT BE
 VERIFIED UNTIL ALL CUT SECTION
 MEASUREMENTS ARE SHOWN.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***NO RESPONSE TO THIS COMMENT FOUND.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ***NO RESPONSE NOTED.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE NOTED.
  
 21. SHTS IR-1 THRU IR-5 IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT OR ENGINEER
 THEN PLANS SHALL BE SIGNED, SEALED, AND
 DATED BY THE DESIGN PROFESSIONAL.
 SECTION 106.1.1.
 ***RESPONSE NOTED, BUT TITLE BLOCKS
 SHALL BE REMOVED IF THE DESIGN
 PROFESSIONAL DID NOT DESIGN THE SYSTEM.
 THE PERSON WHO DESIGNED THE SYSTEM MUST
 PRINT HIS/HER NAME AND PLACE HIS/HER
 SIGNATURE ON EACH SHEET. SECTIONS
 106.1.2 AND 106.1.3.
  
 **************NEW COMMENTS**************
  
 1B. THE ACCESSIBLE STALLS IN THE TOILET
 ROOMS ARE NOT LARGE ENOUGH. MINIMUM SIZE
 FOR A AN ACCESSIBLE STALL IS 7'1". ONE
 STALL IS 6'0" AND THE OTHER IS 5'6". SEE
 ATTACHED SHEET FOR NEW CONSTRUCTION
 TOILET STALL FIGURE 30E.
  
 2B. FOR THE GAS SYSTEM: SUBMIT MANUF. SPECIFICATIONS
 FOR THE REGULATORS USED.
 INDICATE IF THE REGULATOR WILL BE VENTED
 AND IF SO INDICATE THE MATERIAL USED FOR
 THE VENT. ALSO SHOW VENTING ROUTE FOR
 REGULATOR. SECTION 106.1.1.
  
 3B. FOR THE GAS SYSTEM: SLEEVES ARE
 REQUIRED WHERE THE GAS ENTERS THE
 BUILDING. SECTION 404.7.
  
 4B. FOR THE GAS SYSTEM: SHT P-12 SHOW
 THE PIPING TO FU101 & FU201. SHOW SHUT
 OFF VALVES AND DRIP LINES FOR ALL UNITS.
 SECTIONS 408.2, 408.4, 409.4 & 409.5.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-03-07 Cont ID  
Sent By kstevens Date 2006-03-07 Time 07:15 Rev Time 0.00
Received By kstevens Date 2006-03-06 Time 09:30 Sent To  
Notes
2006-03-07 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 PLAN REVIEW ONLY
 1. PLANS INDICATED DOCUMENT 90% COMPLETE
 AND AS SUCH MORE COMMENTS MAY BE
 FORTHCOMING DEPENDING ON COMMENT
 RESPONSES AND NEW INFORMATION SUBMITTED
 AS COMPLETE PLANS ARE SUBMITTED. SECTION
 106.1.1.
 2. TITLE BLOCKS FOR HDR ENGINEERING INC. CERTIFICATE OF
 AUTHORIZATION NUMBER ON
 THE STATE WEBSITE INDICATES THE ADDRESS
 AS 8404 INDIAN HILLS DR. OMAHA NEBRASKA.
 PLEASE INCLUDE THIS ADDRESS ON THE TITLE
 BLOCK OF EACH SHEET AS REQUIRED. (SEE
 ATTACHED SHEET FROM FLORIDA DBPR).
 3. SHT C-09 DDCVA ON 8" DIP WM NOT
 APPROVED FOR THE TYPE OF HIGH HAZARD FOR
 THE INDUSTRIAL SUPPLY WATER MAIN. RPZV
 BACKFLOW REQUIRED. SECTION 608.13.2. -
 ALSO 6" ISWM LINE THAT IS CAPPED OFF
 SHALL HAVE AN RPZV BACKFLOW ON THAT LINE
 AS WELL. PLEASE INDICATE THE LOCATION OF
 THE BACKFLOW FOR THAT LINE. SECTIONS
 608.13.2 AND 106.1.1.
 4. SHT A-01 WATER CLOSETS REQUIRED PER
 TABLE 403.1 ARE 2 FOR FACTORY AND 2 FOR
 BUSINESS. SECTION 403.3 STATES THE
 REQUIRED WATER CLOSETS, LAVATORIES, ETC.
 SHALL BE DISTRIBUTED EVENLY BETWEEN THE
 SEXES. FLOOR PLAN INDICATES ONE WATER
 CLOSET IN THE WOMEN'S TOILET ROOM AND
 ONE WATER CLOSET AND TWO URINALS IN THE
 MEN'S TOILET ROOM. PLEASE CLARIFY.
 5. SHT A-05 BREAK ROOM SINK (214) SHALL
 BE ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 6. SHT A-05 BREAKROOM ELEVATION
 INDICATOR SHOWS 4/A-19. NO ELEVATION #4
 SHOWN. PLEASE CLARIFY. SECTION 106.1.1.
 7. SHT A-05 DRINKING FOUNTAIN. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS AS WELL AS
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 8. SHT A-08 SHOW THE CLEAR FLOOR SPACE
 AND TURNING AREA IN BOTH TOILET ROOMS
 AND FOR ALL ACCESSIBLE FIXTURES IN BOTH
 TOILET ROOMS.
 9. SHT A-10 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FOOTAGE BEING DRAINED BY EACH
 PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS IN
 CALCULATIONS. - SHOW THE LOCATION OF ALL
 OVERFLOW SCUPPERS, AND SIZE OF O/F
 SCUPPERS PER SECTIONS 1101.7, 1107.3 AND
 TABLE 1106.7. THE SIZING OF THE SCUPPERS
 CAN NOT BE DETERMINED WITHOUT REFERENCE
 TO THE DEFLECTION OF THE ROOF. PLEASE
 SHOW O/F SCUPPER CALCULATION ON PLANS
 INDICATING SIZE OF SCUPPERS AND PROVIDE
 DETAIL OF O/F SCUPPERS SHOWING HEIGHT
 AND WIDTH.
 10. SUBMIT MSDS SHEETS FOR ALL HAZARDOUS
 MATERIALS USED AND/OR STORED AT THE
 FACILITY. THIS SHOULD INCLUDE AND
 PRODUCTS PRODUCED AND STORED.
 11. SHT A-18 THE FOLLOWING SHALL BE
 SHOWN ON THE TOILET ROOMS ELEVATIONS:
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
 FOR URINALS
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 FOR SHOWERS
 A. 11-4.21.2 SIZE AND CLEARANCES
 B. 11-4.21.3 SEAT (IF INSTALLED)
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
 12. SHT A-23 ROOM FINISH SCHEDULE, ROOM
 213 INDICATED AS MEN'S RESTROOM, FLOOR
 PLAN SHOW IT AS WOMEN'S RESTROOM. PLEASE CORRELATE.
 SECTION 106.1.1.
 13. PLEASE CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER FOR
 POSSIBLE INTERCEPTORS AND/OR NUTRALIZER
 TANKS. CONTACT HER AT (561) 822-2271,
 (561) 822-2279 (FAX), OR [email protected] (E-MAIL).
 14. P-07 DETAIL NUMBER 3 INDIRECT WASTE,
 AIR GAP BETWEEN THE INDIRECT WASTE PIPE
 AND THE FLOOD LEVEL RIM OF THE WASTE
 RECEPTOR SHALL BE A MINIMUM OF TWICE THE
 EFFECTIVE OPENING OF THE INDIRECT WASTE
 PIPE. SECTION 802.2.1. INDICATE THE PIPE
 SIZE OF ALL INDIRECT WASTE PIPES.
 15. SHT P-07 DETAIL 2 WATER HEATER,
 THERMAL EXPANSION CONTROL REQUIRED PER
 SECTION 607.3.2. PLEASE INDICATE MENTOD. DIELECTRIC
 "UNIONS" NOT APPROVED FOR
 WATER USAGE. PLEASE CHANGE TO
 "COUPLINGS".
 16. SHT P-08 WATER ISOMETRIC FOR THE
 MAIN LEVEL DOES NOT REFLECT THE PIPING
 SHOWN ON SHT P-01 FLOW SCHEMATIC. PLEASE
 CORRELATE ISOMETRIC AND FLOW SCHEMATIC.
 SECTION 106.1.1.
 17. SHT P-10 DRAINAGE PLUMBING ISOMETRIC
 DOES NOT MEET CODE REQUIREMENTS, NOR
 DOES IT REFLECT THE FLOOR PLAN SHT P-02.
 TRAPS ARE REQUIRED ON ALL FIXTURES
 EXCEPT THE CLEANOUTS AND THE WATER
 CLOSETS AS THE W/C'S HAVE AN INTEGRAL
 TRAP IN THE FIXTURES. SECTION 1002.1. -
 NO HORIZONTAL DRY VENTS PER SECTIONS
 905.3 & 905.4. - PIPING DOES NOT REFLECT
 THE FLOOR PLAN AT ESEW. NO PIPING SHOWN
 ON THE FLOOR PLAN. SHOW ALL PIPE SIZES
 ON ISOMETRIC. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 106.1.1.
 18. SHT P-11 DRAINAGE PLUMBING ISOMETRIC
 DOES NOT MEET CODE REQUIREMENTS. TRAPS
 ARE REQUIRED ON ALL FIXTURES EXCEPT
 CLEANOUTS AND WATER CLOSETS AS THE W/C'S
 HAVE INTEGRAL TRAPS IN THE FIXTURES. -
 DRY HORIZONTAL VENTS ARE NOT APPROVED
 PER SECTIONS 905.3 & 905.4.- MANY
 FIXTURES ARE NOT VENTED PROPERLY AS
 REQUIRED IN SECTION 901.2.1. (SEE
 EXAMPLE ON THIS SHEET ONE SET OF PLANS)
 - SHOW ALL PIPE SIZES ON THE ISOMETRICS.
 19. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE ON PLANS TABLE
 BEING USED OF ALL GAS PIPING.
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 I. SUBMIT GAS PIPING ON THE FLOOR PLANS
 TO CONFIRM ROUTING OF PLANS SHOWN ON THE ISOMETRIC.
 SECTION 106.1.1.
 20. SUBMIT PLANS FOR THE COMPRESSED AIR
 SYSTEM. SHOW A FLAT DRAWING AND AN
 ISOMETRIC DRAWING WITH ALL PIPE SIZES,
 VALVES, TYPE OF MATERIAL ETC. SECTION 106.3.1.5.3.
 21. SHTS IR-1 THRU IR-5 IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT OR ENGINEER
 THEN PLANS SHALL BE SIGNED, SEALED, AND
 DATED BY THE DESIGN PROFESSIONAL.
 SECTION 106.1.
 22. ALL DOMESTIC PUMPS AND OR BOOSTER
 PUMPS SHALL BE LISTED. SUBMIT MANUF. SPECIFICATIONS
 SHEETS. SECTION 303.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 9 Status F Date 2009-07-28 Cont ID  
Sent By eschneid Date 2009-07-28 Time 11:54 Rev Time 0.50
Received By eschneid Date 2009-07-28 Time 11:54 Sent To  
Notes
2009-07-28 11:58:13REVISION FAILED
  
 1) THE CIVIL PLANS INCLUDED IN THE PACKET ARE NOT
 SIGNED AND SEALED BY THE ENGINEER OF RECORD.
  
 2) THE CIVIL PLANS AND THE SURVEY SUBMITTED AS PART OF
 THIS REVISION DO NOT MATCH.
  
 3) NOTE - AS OF TODAY, NO REVISED LANDSCAPE AND
 IRRIGATION PLANS HAVE BEEN SUBMITTED TO MATCH EITHER
 THE SURVEY OR THE CIVIL PLANS.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.

Review Stop Z ZONING
Rev No 8 Status P Date 2009-04-21 Cont ID  
Sent By eschneid Date 2009-03-10 Time 10:06 Rev Time 0.50
Received By eschneid Date 2009-03-10 Time 10:06 Sent To  
Notes
2009-03-10 10:11:23PASSED AS-BUILT REVISON, SUBJECT TO THE FOLLOWING:
  
 NO UPDATED LANDSCAPE AND IRRIGATION PLANS WERE
 SUBMITTED TO REFLECT THE CHANGES THAT ARE PART OF THE
 "AS-BUILT" PLANS. LOCATIONS OF EQUIPMENT AND CONCRETE
 PADS HAVE CHANGED THAT AFFECT THE LOCATION OF TREES,
 SOD AND THE REQUIRED IRRIGATION. THESE SHALL BE
 SUBMITTED AS A SEPARATE REVISION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.

Review Stop Z ZONING
Rev No 7 Status N Date 2009-02-24 Cont ID  
Sent By adarroug Date 2009-02-24 Time 15:25 Rev Time 0.00
Received By adarroug Date 2008-12-02 Time 17:48 Sent To  
Notes
2008-12-03 08:58:06REVISIONS DO NOT AFFECT ZONING APPROVAL.

Review Stop Z ZONING
Rev No 6 Status P Date 2007-11-19 Cont ID  
Sent By eschneid Date 2007-11-19 Time 16:56 Rev Time 0.00
Received By eschneid Date 2007-11-19 Time 16:56 Sent To  
Notes
2007-11-19 16:56:58STAMP REVISIONS ON SHEET C-05.

Review Stop Z ZONING
Rev No 5 Status P Date 2007-10-19 Cont ID  
Sent By eschneid Date 2007-10-19 Time 18:24 Rev Time 0.00
Received By eschneid Date 2007-10-19 Time 18:24 Sent To B
Notes
2007-10-19 18:25:25PROVISO
  
 LANDSCAPE SHALL BE ADJUSTED ACCORDINGLY.

Review Stop Z ZONING
Rev No 4 Status P Date 2007-03-01 Cont ID  
Sent By eschneid Date 2007-03-01 Time 12:06 Rev Time 0.00
Received By eschneid Date 2007-03-01 Time 12:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2006-12-05 Cont ID  
Sent By eschneid Date 2006-12-05 Time 13:09 Rev Time 0.00
Received By eschneid Date 2006-12-05 Time 13:09 Sent To  
Notes
2006-12-08 15:17:51FAILED
  
 CONDITION OF CERTIFICATION PROVIDED.FOLLOWING COMMENT
 STILL APPLIES:
  
 1) A SHADE OR FLOWERING TREE IS REQUIRED AT EACH END OF
 THE PARKING ROW.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.
2006-12-08 08:52:37FAILED
  
 PLANS REDLINED ON 12/8/06 TO ADDRESS 3 OF THE PREVIOUS
 COMMENTS.FOLLOWING COMMENTS STILL APPLY:
  
 1) PLEASE PROVIDE A COPY OF THE CONDITIONS OF
 CERTIFICATION PREPARED BY THE CITY OF WEST PALM BEACH.
 THE PLANS WILL BE REVIEWED AGAIN TO VERIFY THAT THEY
 COMPLY WITH THE CONDITIONS OF CERTIFICATION.
  
 2) A SHADE OR FLOWERING TREE IS REQUIRED AT EACH END OF
 THE PARKING ROW.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.
2006-12-05 13:27:49FAILED
  
 1) PLEASE PROVIDE A COPY OF THE CONDITIONS OF
 CERTIFICATION PREPARED BY THE CITY OF WEST PALM BEACH.
 THE PLANS WILL BE REVIEWED AGAIN TO VERIFY THAT THEY
 COMPLY WITH THE CONDITIONS OF CERTIFICATION.
  
 2) THE PARKING DETAIL PROVIDED ON SHEET C-12 SHALL SHOW
 THE WHEEL STOP LOCATED 2 FEET FROM THE END OF THE
 PARKING SPACE.
  
 3) THE PARKING STRIPING IN SHEET C-06 CALLS OUT 4 INCH
 WIDE SINGLE STRIPED STALLS.THE PARKING SPACES SHALL
 MEET THE DETAIL FROM SHEET C-12.
  
 4) A BICYCLE RACK IS REQUIRED FOR THE BIO-SOLIDS
 FACILITY.
  
 5) A SHADE OR FLOWERING TREE IS REQUIRED AT EACH END OF
 THE PARKING ROW.
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-13 Cont ID  
Sent By eschneid Date 2006-07-13 Time 12:56 Rev Time 0.00
Received By eschneid Date 2006-07-13 Time 12:56 Sent To  
Notes
2006-07-13 00:00:00THE FACILITY REQUIRES CLASS A SPECIAL
 USE PERMIT APPROVAL BY THE CITY
 COMMISSION. (SAME COMMENT AS 3/31/2006
 REVIEW).CONTACT THE PLANNING
 DEPARTMENT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-03-31 Cont ID  
Sent By eschneid Date 2006-03-31 Time 17:22 Rev Time 0.00
Received By eschneid Date 2006-03-31 Time 17:22 Sent To  
Notes
2006-03-31 00:00:00THE FACILITY REQUIRES THE APPROVAL OF A
 CLASS A SPECIAL USE PERMIT BY THE CITY
 COMMISSION.