| 2006-02-08 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 05120367 |
| | ADD: 314 10TH ST |
| | CONT: KENNEDY CONTRACTORS |
| | TEL: (561)307-1461 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | NOTE ONCE NOC IS RECORDED AT THE CLERK |
| | OF THE COURT, WORK MUST START WITHIN 90 |
| | DAYS OF RECORDING OTHERWISE NOC MUST BE |
| | RE-RECORDED. FL SS 71.13(2) |
| | |
| | 2A) SCOPE OF WORK IS LOW, WE WILL |
| | RE-EVALUATEUSING MARSHALL & SWIFT IF |
| | THE VALUE IS NOT INCREASED. |
| | |
| | 2B) THE PERMIT APPLICATION DESCRIPTION |
| | INDICATES CHANGE OF USE, IT APPEARS THAT |
| | AN ADDITION 918 SQ FT IS ALSO BEING |
| | ADDED. |
| | |
| | 2C) NOTHING IN THIS PERMIT INDICATES |
| | THAT THE REAR BUILDING IS UNDER GOING A |
| | CHANGE OF OCCUPANCY? |
| | |
| | 3) IT APPEARS THAT THE OWNER/ CONTRACTOR |
| | HAS DRAWN UP THE PLANS, FL S S |
| | 481.229(1)(C) WHEN THE SCOPE OF WORK IS |
| | UNDER $25,000.00 AN ARCHITECT IS NOT |
| | REQUIRED TO DRAW PLANS, OTHERWISE A |
| | DESIGN PROFESSIONAL WILL BE REQUIRED.SEE |
| | FL S S |
| | 489.229 EXCEPTIONS, EXEMPTIONS FROM |
| | LICENSURE. |
| | |
| | 4) 2004 EXISTING BUILDINGS CHAPTER 8, |
| | CHANE IN OCCUPANCIES 801.3A CERTIFICATE |
| | OF OCCUPANCY SHALL BE ISSUED WHERE A |
| | CHANGE OF OCCUPANCY OCCURS THAT RESULTS |
| | IN BEING CLASSIFIED AS A DIFFERENT |
| | OCCUPANCY CLASSIFICATION AS DETERMINED |
| | BY THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | PLANS ARE TO COMPLY WITH THE PROVISIONS |
| | OF CHAPTER 8 OF EXISTING BUILDING 2004 |
| | CHAPTER 9 FOR ADDITIONS AND THE 2004 |
| | BUILDING CODE FOR COMMERCIAL AS WELL AS |
| | CHAPTER 11 OF THE 2004 FBC. |
| | |
| | 5)2004 EXISTING BUILDING 806.1, |
| | ACCESSIBILITY IN PORTIONS OF BUILDINGS |
| | UNDER GOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH CHAPTER |
| | 11 OF THE FLORIDA BUILDING CODE. |
| | |
| | 5A) AN ACCESSIBLE ROUTE TO THE RIGHT OF |
| | |
| | WAY. |
| | |
| | 5B) 11-4.6.1 PARKING AND PASSENGER |
| | LOADING ZONES. |
| | |
| | 5C) ACCESSIBLE RAMPS: |
| | 11-4.8.2 SLOPE & RISE. THE LEAST |
| | POSSIBLE SLOPE SHALL BE USED FOR ANY |
| | RAMP. THE MAXIMUM SLOPE FOR A RAMP IN |
| | NEW CONSTRUCTION SHALL BE 1 TO 12. THE |
| | MAXIMUM RISE FOR RUN SHALL BE 30" (SEE |
| | FIGURE 16). |
| | 11-4.8.3. CLEAR WIDTH. THE MINIMUM |
| | CLEAR WIDTH OF A RAMP SHALL BE 36". |
| | EXCEPTION: RAMPS THAT ARE PART OF A |
| | REQUIRED MEANS OF EGRESS SHALL NOT BE |
| | LESS THAN 44 INCHES WIDE. |
| | 11-4.8.4.(2) LANDINGS. ALL LANDINGS |
| | ON RAMPS SHALL NOT BE LESS THAN 60" |
| | CLEAR, & THE BOTTOM OF EACH RAMP SHALL |
| | HAVE NOT LESS THAN 72" OF STRAIGHT & |
| | LEVEL CLEARENCE. |
| | 11-4.8.4(3) IF RAMPS CHANGE DIREC- |
| | TION AT LANDINGS, THE MINIMUM LANDING |
| | SIZE SHALL BE 60" X 60". |
| | 11.4.8.5. HANDRAILS: IF A RAMP HAS |
| | A RISE GREATER THAN 6" OR A HORIZONTAL |
| | PROJECTION GREATER THAN 72", THEN IT |
| | SHALL HAVE HANDRAILS ON BOTH SIDES. |
| | |
| | 5D)11-4.21.1 GENERAL. |
| | ACCESSIBLE SHOWER STALLS SHALL COMPLY |
| | WITH SECTION 11-4.21 . |
| | 11-4.21.2 SIZE AND CLEARANCES. |
| | EXCEPT AS SPECIFIED IN SECTION 11-9.1.2 |
| | , SHOWER STALL SIZE AND CLEAR FLOOR |
| | SPACE SHALL COMPLY WITH FIGURE 11-35 (A) |
| | OR FIGURE 11-35 (B). THE SHOWER STALL IN |
| | FIGURE 11-35 (A) SHALL BE 36 INCHES BY |
| | 36 INCHES (915 MM BY 915 MM). SHOWER |
| | STALLS REQUIRED BY SECTION 11-9.1.2 |
| | SHALL COMPLY WITH FIGURE 11-57 (A) OR |
| | FIGURE 11-57 (B). THE SHOWER STALL IN |
| | FIGURE 11-35 (B) WILL FIT INTO THE SPACE |
| | REQUIRED FOR A BATHTUB. |
| | |
| | 11-4.21.3 SEAT. |
| | A SEAT SHALL BE PROVIDED IN SHOWER |
| | STALLS 36 INCHES BY 36 INCHES (915 MM BY |
| | 915 MM) AND SHALL BE AS SHOWN IN FIGURE |
| | 11-36 . THE SEAT SHALL BE MOUNTED 17 |
| | INCHES TO 19 INCHES (430 MM TO 485 MM) |
| | FROM THE BATHROOM FLOOR AND SHALL EXTEND |
| | THE FULL DEPTH OF THE STALL. IN A |
| | 36-INCH BY 36-INCH (915 MM BY 915 MM) |
| | SHOWER STALL, THE SEAT SHALL BE ON THE |
| | WALL OPPOSITE THE CONTROLS. WHERE A |
| | FIXED SEAT IS PROVIDED IN A 30-INCH BY |
| | 60-INCH MINIMUM (760 MM BY 1525 MM) |
| | SHOWER STALL, IT SHALL BE A FOLDING TYPE |
| | AND SHALL BE MOUNTED ON THE WALL |
| | ADJACENT TO THE CONTROLS AS SHOWN IN |
| | FIGURE 11-57 . THE STRUCTURAL STRENGTH |
| | OF SEATS AND THEIR ATTACHMENTS SHALL |
| | COMPLY WITH SECTION 11-4.26.3 . |
| | 11-4.21.4 GRAB BARS. |
| | GRAB BARS COMPLYING WITH SECTION 11-4.26 |
| | SHALL BE PROVIDED AS SHOWN IN FIGURE |
| | 11-37 . |
| | 11-4.21.5 CONTROLS. |
| | FAUCETS AND OTHER CONTROLS COMPLYING |
| | WITH SECTION 11-4.27.4 SHALL BE LOCATED |
| | AS SHOWN IN FIGURE 11-37 . IN SHOWER |
| | STALLS 36 INCHES BY 36 INCHES (915 MM BY |
| | 915 MM), ALL CONTROLS, FAUCETS, AND THE |
| | SHOWER UNIT SHALL BE MOUNTED ON THE SIDE |
| | WALL OPPOSITE THE SEAT. |
| | 11-4.21.6 SHOWER UNIT. |
| | A SHOWER SPRAY UNIT WITH A HOSE AT LEAST |
| | 60 INCHES (1525 MM) LONG THAT CAN BE |
| | USED BOTH AS A FIXED SHOWER HEAD AND AS |
| | A HAND-HELD SHOWER SHALL BE PROVIDED. |
| | EXCEPTION: IN UNMONITORED FACILITIES |
| | WHERE VANDALISM IS A CONSIDERATION, A |
| | FIXED SHOWER HEAD MOUNTED AT 48 INCHES |
| | (1220 MM) ABOVE THE SHOWER FLOOR MAY BE |
| | USED IN LIEU OF A HAND-HELD SHOWER HEAD. |
| | |
| | 11-4.21.7 CURBS. |
| | IF PROVIDED, CURBS IN SHOWER STALLS 36 |
| | INCHES BY 36 INCHES (915 MM BY 915 MM) |
| | SHALL BE NO HIGHER THAN ? INCH (13 MM). |
| | SHOWER STALLS THAT ARE 30 INCHES BY 60 |
| | INCHES (760 MM BY 1525 MM) MINIMUM SHALL |
| | NOT HAVE CURBS. |
| | |
| | 5D) 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| | BE MOUNTED WITH THE COUNTER NO HIGHER |
| | THAN 34" ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARENCE THAT IS AT |
| | LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| | SHALL BE PROVIDED UNDERNEATH SINKS. |
| | |
| | 6) 2004 ENERGY CODE 13-101.3.2 BUILDINGS |
| | HAVING A CHANGE OF OCCUPANCY THAT WERE |
| | PERMITTED AFTER MARCH 15, 1979, SHALL |
| | COMPLY WITH THE REQUIREMENTS OF |
| | SUBCHAPTER 13-4 FOR COMMERCIAL |
| | APPLICATIONS AND MULTIPLE-FAMILY |
| | RESIDENTIAL BUILDINGS GREATER THAN THREE |
| | STORIES OR SUBCHAPTER 13-6 FOR |
| | RESIDENTIAL APPLICATIONS OF THREE |
| | STORIES OR LESS. WHERE THE EFFICIENCY OF |
| | A BUILDING COMPONENT IS UNKNOWN, IT |
| | SHALL BE DETERMINED IN ACCORDANCE WITH |
| | THE CRITERIA SPECIFIED IN SECTION |
| | 101.4.2.1 . |
| | |
| | 7) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | 8) 2004 EXISTING BUILDING CHANGE OF |
| | OCCUPANCY 812.1 COMPLIANCE WITH CHAPTER |
| | 7 THE OCCUPANCY CLASSIFICATION OF AN |
| | EXISTING BUILDING MAY BE CHANGED, |
| | PROVIDED THAT THE BUILDING MEETS ALL THE |
| | REQUIREMENTS OF CHAPTER7 APPLIED |
| | THROUGHOUT THE BUILDING FOR THE NEW |
| | OCCUPANCY GROUP AND COMPLIES WITH THE |
| | REQUIREMENT S OF SECTION 802 THROUGH |
| | 812.SEE : |
| | 705 MEANS OF EGRESS / FLORIDA BUILDING |
| | CODE |
| | 706 ACCESSIBILITY CHAPTER 11 2004 FBC |
| | 707 STRUCTURAL: |
| | 707.5.1 EVALUATION &ANALYSIS FBC |
| | BUILDING FOR WIND LOADING |
| | 1609.1.4.1 BUILDING WITH OPENINGS. |
| | 1609.1.4.WHERE GLAZING IS ASSUMED TO BE |
| | AN OPENING IN ACCORDANCE WITH SECTION |
| | 1609.1.4 , THE BUILDING SHALL BE |
| | EVALUATED TO DETERMINE IF THE OPENINGS |
| | ARE OF SUFFICIENT AREA TO CONSTITUTE AN |
| | OPEN OR PARTIALLY ENCLOSED BUILDING AS |
| | DEFINED IN SECTION 1609.2 . OPEN AND |
| | PARTIALLY ENCLOSED BUILDINGS SHALL BE |
| | DESIGNED IN ACCORDANCE WITH THE |
| | APPLICABLE PROVISIONS OF ASCE 7. |
| | |
| | 1609.1.4 PROTECTION OF OPENINGS. |
| | IN WIND-BORNE DEBRIS REGIONS, EXTERIOR |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IN THE LOWER 60 FEET (18.3 M) IN |
| | BUILDINGS SHALL BE ASSUMED TO BE |
| | OPENINGS AND THE BALANCE OF GLAZED |
| | OPENINGS IN THE REST OF THE BUILDING |
| | SHALL BE ASSUMED TO BE ZERO UNLESS SUCH |
| | GLAZING THAT RECEIVES POSITIVE PRESSURE |
| | IS IMPACT RESISTANT OR PROTECTED WITH AN |
| | IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF SSTD 12, ASTM E 1886 AND |
| | ASTM E 1996, OR MIAMI-DADE TAS 201, 202 |
| | AND 203 REFERENCED THEREIN AS FOLLOWS: |
| | 1.GLAZED OPENINGS LOCATED WITHIN 30 |
| | FEET (9.1 M) OF GRADE SHALL MEET THE |
| | REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | |
| | 1609.1.3 ANCHORAGE AGAINST OVERTURNING, |
| | UPLIFT AND SLIDING. |
| | STRUCTURAL MEMBERS AND SYSTEMS AND |
| | COMPONENTS AND CLADDING IN A BUILDING OR |
| | STRUCTURE SHALL BE ANCHORED TO RESIST |
| | WIND-INDUCED OVERTURNING, UPLIFT AND |
| | SLIDING AND TO PROVIDE CONTINUOUS LOAD |
| | PATHS FOR THESE FORCES TO THE |
| | FOUNDATION. WHERE A PORTION OF THE |
| | RESISTANCE TO THESE FORCES IS PROVIDED |
| | BY DEAD LOAD, THE DEAD LOAD, INCLUDING |
| | THE WEIGHT OF SOILS AND FOUNDATIONS, |
| | SHALL BE TAKEN AS THE MINIMUM DEAD LOAD |
| | LIKELY TO BE IN PLACE DURING A DESIGN |
| | WIND EVENT. WHERE THE ALTERNATE BASIC |
| | LOAD COMBINATIONS OF SECTION 1605.3.2 |
| | ARE USED, ONLY TWO-THIRDS OF THE MINIMUM |
| | DEAD LOAD LIKELY TO BE IN PLACE DURING A |
| | DESIGN WIND EVENT SHALL BE USED. |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS, |
| | B) DOORS |
| | C) MULLIONS |
| | D) LINTELS |
| | E) ROOFING ASSEMBLIES |
| | |
| | 9) 106.3.3* PRODUCT APPROVALS- 2004 |
| | THOSE PRODUCTS THAT ARE RGULATED BY DCA |
| | RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 10)2004 EXISTING BUILD,707.6 GRAVITY |
| | LOADS IS INCREASED ON THE ROOF OR FLOOR |
| | OF A BUILDING ALL STRUCTURAL MEMBERS |
| | AFFECTED BY SUCH INCREASE SHALL MEET THE |
| | GRAVITY LOAD REQUIREMENTS OF THE 2004 |
| | FBC, BUILDING. |
| | |
| | 11)FL. BLD CODE 1603.1.4 THE FOLLOWING |
| | INFORMATION RELATED TO WIND SHALL BE |
| | SHOWN ON THE CONSTRUCTION DRAWINGS, |
| | 1)- BASIC WIND SPEED, MPH |
| | 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| | CATEGORY |
| | 3)- WIND EXPOSURE |
| | 4)- INTERNAL PRESSURE COEFFICIENT, |
| | 5)- COMPONENTS & CLADDING, THE DESIGN |
| | WIND PRESSURES IN TERMS OF PSF. |
| | |
| | 12) SHEET S-2: |
| | |
| | 12A) PLANS DO NOT IDENTIFY THE STEEL C |
| | JOIST AS PER KNOWN MEMBER DEPTH, TYPE OF |
| | SECTION,( 4 ALPHA CHARACTERS ARE USED |
| | ACCORDING TO SHAPE), FLANGE WIDTH & |
| | MATERIAL THICKNESS. |
| | 1604.3.3 STEEL. |
| | PROVIDE THE ALLOWABLE DEFLECTION LIMITS |
| | AS INDICATED IN FBC BUILDINGTABLE 1604.3 |
| | |
| | THE DEFLECTION OF STEEL STRUCTURAL |
| | MEMBERS SHALL NOT EXCEED THAT PERMITTED |
| | BY AISC LRFD, AISC HSS, AISC 335, AISI |
| | -NASPEC, AISI-GENERAL, AISI-TRUSS, ASCE |
| | 3, ASCE 8-SSD-LRFD/ASD, AND THE STANDARD |
| | SPECIFICATIONS OF SJI STANDARD |
| | SPECIFICATIONS, LOAD TABLES AND WEIGHT |
| | TABLES FOR STEEL JOISTS AND JOIST |
| | GIRDERS AS APPLICABLE. |
| | |
| | 12B) 1603.4 OCCUPANCY PERMITS FOR |
| | CHANGED LOADS. CONSTRUCTION DOCUMENTS |
| | FOR OTHER THAN RESIDENTIAL BUILDINGS |
| | FILED WITH THE BUILDING OFFICIAL WITH |
| | APPLICATIONS FOR PERMITS SHALL SHOW ON |
| | EACH DRAWING THE LIVE LOADS PER SQUARE |
| | FOOT (M 2 ) OF AREA COVERED FOR WHICH |
| | THE BUILDING IS DESIGNED. OCCUPANCY |
| | PERMITS FOR BUILDINGS HEREAFTER ERECTED |
| | SHALL NOT BE ISSUED UNTIL THE FLOOR LOAD |
| | SIGNS, REQUIRED BY SECTION 1603.3 , HAVE |
| | BEEN INSTALLED. |
| | |
| | 12C) STATE DEAD AND LIVE LOADS TO BE |
| | IMPOSED ON BOTH THE FLOOR JOIST AND ROOF |
| | |
| | JOIST WITH ATTACHED CEILING. |
| | |
| | 12D) PLANS INDICATE A DROPED CEILING |
| | ATTACHED TO SELF SURRING HI-HAT CHANNEL |
| | BUT NO INFORMATION AS TO WHAT THE HI-HAT |
| | IS TO BE HUNG FROM, BLCK IRON AND |
| | HANGING WIRE? IS THE HI-HAT TO BE TIED |
| | WITH WIRE OR SCREWED/ |
| | |
| | 12E) BOTH THE FLOOR & CEILING JOIST SHOW |
| | A ANGLE ANCHORED TO THE BLOCK WALL, NO |
| | INFORMATION AS TO HOW THE ANGLE IS TO BE |
| | |
| | ANCHORED? |
| | |
| | 12F) NO INFORMATION ON THE ANGLE, STEEL |
| | OR ALUM? SIZE NOR WEIGHT PER FT? PLANS |
| | ALSO MISS THE CONNECTION BETWEEN THE |
| | ANGLE AND STEEL JOIST, NO BOLT |
| | INFORMATION IF WASHERS WILL BE REQUIRED? |
| | PLANS DO NOT IDENTIFY LOADS TO BE |
| | RESISTED, UPLIFT, GRAVITY, NOR |
| | HORIZONTAL LOADS OR COMBINATION OF |
| | LOADS. |
| | |
| | 12G) PLANS DO NOT PROVIDE A PROFILE OF |
| | WINDOWS BUCKS, NOR ATTACHMENT? |
| | 1714.5.4.2 MASONRY, CONCRETE OR OTHER |
| | STRUCTURAL SUBSTRATE. |
| | WHERE THE WOOD SHIM OR BUCK THICKNESS IS |
| | LESS THAN 1 1 / 2 INCHES (38 MM), WINDOW |
| | AND DOOR ASSEMBLIES SHALL BE ANCHORED |
| | THROUGH THE MAIN FRAME OR BY JAMB CLIP |
| | OR SUBFRAME SYSTEM, IN ACCORDANCE WITH |
| | THE MANUFACTURER?S PUBLISHED |
| | INSTALLATION INSTRUCTIONS. ANCHORS SHALL |
| | BE SECURELY FASTENED DIRECTLY INTO THE |
| | MASONRY, CONCRETE OR OTHER STRUCTURAL |
| | SUBSTRATE MATERIAL. UNLESS OTHERWISE |
| | TESTED, BUCKS SHALL EXTEND BEYOND THE |
| | INTERIOR FACE OF THE WINDOW OR DOOR |
| | FRAME SUCH THAT FULL SUPPORT OF THE |
| | FRAME IS PROVIDED. SHIMS SHALL BE MADE |
| | FROM MATERIALS CAPABLE OF SUSTAINING |
| | APPLICABLE LOADS, LOCATED AND APPLIED IN |
| | A THICKNESS CAPABLE OF SUSTAINING |
| | APPLICABLE LOADS. ANCHORS SHALL BE |
| | PROVIDED TO TRANSFER LOAD FROM THE |
| | WINDOW OR DOOR FRAME TO THE ROUGH |
| | OPENING SUBSTRATE. |
| | WHERE THE WOOD BUCK THICKNESS IS 1 1 / 2 |
| | INCHES (38 MM) OR GREATER, THE BUCK |
| | SHALL BE SECURELY FASTENED TO TRANSFER |
| | LOAD TO THE MASONRY, CONCRETE OR OTHER |
| | STRUCTURAL SUBTRATE AND THE BUCK SHALL |
| | EXTEND BEYOND THE INTERIOR FACE OF THE |
| | WINDOW OR DOOR FRAME. WINDOW AND DOOR |
| | ASSEMBLIES SHALL BE ANCHORED THROUGH THE |
| | MAIN FRAME OR BY JAMB CLIP OR SUBFRAME |
| | SYSTEM OR THROUGH THE FLANGE TO THE |
| | SECURED WOOD BUCK IN ACCORDANCE WITH THE |
| | MANUFACTURER?S PUBLISHED INSTALLATION |
| | INSTRUCTIONS. UNLESS OTHERWISE TESTED, |
| | BUCKS SHALL EXTEND BEYOND THE INTERIOR |
| | FACE OF THE WINDOW OR DOOR FRAME SUCH |
| | THAT FULL SUPPORT OF THE FRAME IS |
| | PROVIDED. SHIMS SHALL BE MADE FROM |
| | MATERIALS CAPABLE OF SUSTAINING |
| | APPLICABLE LOADS, LOCATED AND APPLIED IN |
| | A THICKNESS CAPABLE OF SUSTAINING |
| | APPLICABLE LOADS. ANCHORS SHALL BE |
| | PROVIDED TO TRANSFER LOAD FROM THE |
| | WINDOW OR DOOR FRAME ASSEMBLY TO THE |
| | SECURED WOOD BUCK. |
| | |
| | 13)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |