Plan Review Details - Permit 05120249
Plan Review Stops For Permit 05120249
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-01-20 Cont ID  
Sent By jleech Date 2006-01-20 Time 14:17 Rev Time 0.00
Received By jleech Date 2006-01-20 Time 14:17 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-01-11 Cont ID  
Sent By mperson Date 2006-01-11 Time 13:40 Rev Time 2.00
Received By mperson Date 2006-01-11 Time 13:40 Sent To  
Notes
2006-01-11 00:00:00DENIED
  
 REFERENCE: FBC-2004 FUEL GAS
 SECTION 301.4.1 , 623
  
 AS PER ORIGINAL DENIAL, A COPY OF THE
 PRODUCT LISTING "CSA" STATING PRODUCT IS
 ACCCEPTABLE FOR RESIDENTIAL
 INSTALLATION.IF ONE CAN'T BE PROVIDED
 THAN PRODUCT CAN'T BE APPROVED FOR
 INSTALLATION AND ANOTHER PRODUCT WILL
 HAVE TO BE USED.
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-01-03 Cont ID  
Sent By mperson Date 2006-01-03 Time 11:39 Rev Time 2.00
Received By mperson Date 2006-01-03 Time 13:42 Sent To  
Notes
2006-01-03 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR A GAS PERMIT.
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. TYPE OF GAS, (LP OR NATURAL)
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 5. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 7. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 506.
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.THE
 PRODUCT SUBMITTAL YOU HAVE PROVIDED
 STATES "PROFESSIONAL SERIES,
 COMMERCIAL-TYPE COOKING
 POWER".COMMERCIAL APPLIANCES ARE NOT
 ALLOWED IN RESIDENTIAL DWELLINGS SEC.
 623.2 AND 623.3.PLEASE PROVIDE A "CSA"
 LISTING STATING THIS PRODUCT IS
 ACCEPTABLE FOR RESIDENTIAL USE.
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-01-10 Cont ID  
Sent By adarroug Date 2006-01-10 Time 14:53 Rev Time 0.00
Received By adarroug Date 2006-01-10 Time 14:53 Sent To B
Notes
2006-01-10 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-01-03 Cont ID  
Sent By mperson Date 2006-01-03 Time 13:45 Rev Time 0.00
Received By mperson Date 2005-12-10 Time 14:52 Sent To  
Notes
2005-12-10 00:00:00TO "G" BOX